0 ratings0% found this document useful (0 votes) 138 views22 pagesNhom 8
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, 
claim it here.
Available Formats
Download as PDF or read online on Scribd
Evaporators and
the Refrigeration System
OBJECTIVES
Aer studying this unt you should be able
define high, medium, and low-temperature refrigeration,
+ determine the boling tempecatute in an evaporator.
+ identify diferent types of evaporators
+ descrivea paraliel-low, plate-anc-fn evaporator.
+ describe multple- and single-crcult evaporators
CEE eee
SAFETY CHECKLIST
[14 ear goggles and gloves when attaching arremaving gauges to
transfer eigerant oto check pressures,
a veaesrarm clothing when working ina wallcincooleror freezer
  
 
21.1 REFRIGERATION
Refrigeration is the process of removing heat from a place
where itis nor wanted and transferring thar heat roa place
where it makes litle or no difference. Commercial refrigera-
tion is similar to the refrigeration thar occurs in your house-
hold refrigerator. The food that you keep in the refrigerator
is stored ata temperature lower than the room temperature.
Typically, the fresh-food compartment temperature is about
35°K Heat trom the room (typically noves through
the walls of the refrigerator to the cooler temperature in
the refrigerator. Heat travels normally and naturally from a
‘warm t0 a cool medium.
If the heat that is transferred into the refrigerator re-
mains in the refrigeratos, it will warm the food products
and spoilage will occur. This heat may be removed from the
refrigerator by mechanical means using the refrigerator’
refrigeration equipment, which requires energy, or work
Figure 21.1 shows how heat is removed with the com-
pression eyele, Because itis 35°F in the box and 75°F in
the room, the mechanical energy in the compression cycle
 
 
 
 
 
  
 
    
MoToR DRIVEN
‘COMPRESSOR
  
\
at ere
oom a 756) tal Conta
fexrraow
INSIDE THE Box
   
 
ier to na
sorin the rel
  
that forces the
ots ate nosmaly driven by elect
 
 
actually pumps the heat to & warmer environment from the
box to the room,
The heat is transferred into a cold refrigerant coil and
pumped by the system compressor to the condenser, where it
 
Js released into the room. This is much like using. sponge to
move water from one place to another. When a dry sponge
is allowed to absorh water in a puddle and you take the wet
sponge to a container and squeeze t, you exert energy, much
like a compressor in the refrigeration system, Figure 21.2.
Another example of refrigeration is a central air-
conditioning system in a
residence. It absorbs heat from thev2
Figure 21.2 A sponge absorbs wate. The water can then be carted in
the sponge to another place. When the sponge i squeeze the water
Isrejected to another place. The squeezing ofthe sponge may be con-
Sdeted the energy that it akesto pump the watec
  
  
 
 
  
oom supty
AIR (55°F)
OUTSIDE (95°6
COIL TEMPERATURE
Gor)
<== ROOM RETURN
AIR (75°F)
 
 
Figure21.3 An aiccondiloning example of etigeaton,
home by passing indoor air at about 75°F over a coil that
1s cooled to about 40°E. Heat will transter from the room
air to the coil cooling the air. This cooled air may be mixed
with the room air, lowering its temperature, Figure 21.3.
‘This process is called air-conditioning, but itis also refrig-
eration at a higher temperacure level than that of the house
hold refrigerator, so itis frequently called high-temperacure
refrigeration.
‘Commercial refrigeration is used in commercial busi-
ness locations. The food store, fast-ood restaurant, drug
store, flower shop, and food processing plant are only a few
of the applications. Some of the commercial systems are
plug-in appliances, such as a small, reach-in ice storage bin
at the local convenience store. The system is entirely located
within the one unit. Some systems consist of individual
boxes with single remore condensing units, and some are
complex systems with several compressors in a rack serving
several reach-in display cases, as in a supermarket. Most
commercial refrigeration is installed and serviced by a spe
cial group of technicians who work only with commercial
refrigeration and the food-service business.
 
 
‘aa nthe tigen Str
21.2 TEMPERATURE RANGES,
OF REFRIGERATION
‘The temperature ranges for commercial retrigeration may
refer to the temperature of the refrigerated box or the boil-
ing temperature of the refrigerant in the coil. The following,
temperatures illustrate some of the guidelines used in the
industry when discussing box temperacures.
HIGH-TEMPERATURE APPLICATIONS. High-temperature
refrigeration applications will normally involve box tem-
peratures of 47°F to 60°F. Storing such products as flowers
and candy may require these temperatures.
MEDIUM-TEMPERATURE APPLICATIONS. The household
relrigerator fresh-food compartment is a good example of
‘medium-temperature refrigeration, which typically ranges
from 28°F co 40°F. Many different products are stored at
the medium-temperacure range, For most products, the
‘medium-temperature refrigeration range is above freezings
few products are stored below 32°F. Items such as eggs,
lettuce, and tomatoes lose their appeal if they freeze in a
refrigerator
LOW-TEMPERATURE APPLICATIONS. Low-temperature re-
{rigeration produces temperaturce below the freezing point
of water, 32°F One of the higher low-temperature applica-
tions is the making of ice.
Low-temperature food storage applications generally
start at O°F and go as low as ~20°F. Ar this temperature
ice eream would be frozen hard. Frozen meats, vegetables,
and dairy products are ony a few of the foods preserved by
freezing, Some foods may be kept for long periods of time
and are appetizing when thawed for cooking, provided they
are frozen correctly and kept frozen.
  
21.3 THE EVAPORATOR
‘The evaporator in a refrigeration system is responsible for
absorbing heat into the system from whatever medium is
to be cooled. This heat-absorbing process is accomplished
bby maintaining the evaporator coil ata lower temperature
than the meditim to be cooled. For example, if a walk-in
cooler is to be maintained at 35°F to preserve food prod-
ucts, the col in the cooler must be maintained at a lower
temperature than the 35°F air that will be passing over it
Irigure 21.4 shows the refrigerant in the evaporator boiling
at 20°F, which is 15°F lower than the entering ar. The evap-
‘orator operating at these low temperatures removes latent
and sensible heat from the cooler. Operating at 20°F, as in
the preceding example, the evaporator will collect moisture
from the air in the cooler, latent heat: The removal of sen-
sible heat reduces the food temperature
 
 
 
 
am.8
sects
RETURN AIR (25°F)
HAS PASSED
‘OVER FOOD.
PRODUCTS.
‘TEMPERATURE
DIFFERENCE (15°F)
‘COIL TEMPERATURE
(20°F)
  
FAN AND MOTOR
THE COMPRESSOR IS RUNNING —
THIS LOWERS COIL TEMPERATURE.
Figure 21.4 The relationship ofthe ails bling temperature tothe ai
passing over the col while it operating inthe design range,
 
21.4 BOILING AND CONDENSING
‘Two important factors in understanding refrigeration are
the (1) boiling temperature and (2) condensing tempera
ture. The boiling temperatuee and its relationship to the
system involve the evaporator. The condensing tempera-
ture involves the condenser and will be discussed in the
next unit. These temperatures can be followed by using the
temperatirelpressure chat in conjunction with a set of re-
frigeration pressure gauges, Figure 21.5 and Figure 21.6.
21.5 THE EVAPORATOR
AND BOILING TEMPERATURE
‘The boiling temperature of the liquid refrigerant deter-
‘mines the coil operating temperature In an air-conditioning,
system a 40°F evaporator coil with 75°F air passing over
ir produces conditions used for airconditioning or high-
temperature refrigeration. Boiling is normally associated
with high temperatures and water. Unit 3, “Refrigeration
and. Kefrigerants,” discussed. the fact that water boils at
2I2PF at atmospheric pressure. It also discussed the fact
that water boils at other temperatures, depending on the
pressure. When the pressure is reduced, warer will boil at
40°E. This is still boiling—changing a liquid to a vapor. In
a refeigeration system, the refrigerant may boil at 20°F by
absorbing heat from the 35°F food.
‘The service technician must be able to determine what
‘operating pressures and temperatures are correct for the
various systems being serviced under different load con-
ditions. Much of this knowledge comes from experience.
‘When taking readings from thermometers and gauges, the
 
 
Commer Retgertn
readings must be evaluated. There can be as many differ
ent readings as there are changing conditions. Guidelines
‘can help the technician know the pressure and temperature
anges at which the equipment should operate. There are
relationships between the entering ai temperature and the
evaporator for each system, These relationships are similar
from installation to installation.
21.6 REMOVING MOISTURE
Dehumidifying the air means to remove the moisture, and
this is frequently desirable in refrigeration systems, Moisture
removal is similar from one refrigeration system to another.
Knowing what the coibto-air relationship is can help the
technician know what conditions to look for. The load on.
the coil would rise or fall accordingly as the return-air tem-
perature rises or falls. Warmer return aie in the box will also
have more moisture content, which imposes further load on
the ail, the cooler is warm die ro food added ta it the col
would have more heat to remove because it has more load
on it Iewould be much like boiling water in an open pan on.
the stove, The warer boils atone rate with the burner on me-
dium and at an inereased rate with the burner on high. The
boiling pressure stays the same in the boiling water in a pan
because the pan is open to the atmosphere. When this same
boiling process occurs in an enclosed coil, the pressures will
rise when the boiling occurs at a faster rate. This causes the
operating pressure of the whole system to rise, Figure 21.7.
When the evaporator removes heat from air and lowers
the temperature of the aig, sensible heat is removed. When
moisture is removed from the air latent heat is removed
“The moisture is piped to a drain, Figure 21.8, Latent heat
is called hidden heat because it does not register on a ther-
rmometer, but it is heat, like sensible heat, and it must be
removed, which takes energy.
‘The refrigeration evaporator is a component that ab-
sorbs heat from the conditioned space into the refrigeration
system. The evaporator ean be thought of as the sponge of
the system. Iris responsible fora heat exchange between the
conditioned space or product and the refrigerant inside the
system. Some evaporators absorb heat more efficiently than |
others. Figure 21.9 illustrates the heat exchange between air
and refrigerant.
 
  
 
21.7 HEAT EXCHANGE
CHARACTERISTICS
OF THE EVAPORATOR
‘The following are conditions that govern the rate of heat
exchange:
1, The evaporator material theough which the heat has
to be exchanged. Evaporators may be manufactured
from copper, steel, brass, stainless steel, of aluminum,a9,
Unt 21- ana andthe eigen Sse
 
idsoden pue 774 erase vEare YOU PUE VCS
 
sunssaua 2919sects
 
 
Figure 21.6 Many pressure gauges have temperatue/pressure rel
‘Nonships printed onthe gauge.
  
 
   
 
 
AIR RETURNING.
TOCOIL
50°F DUE TO WARM
FOOD BEING
ADDED TO BOX
© sv4 psi '
eicea i
CORRESPONDS
Soastcon
TewPeRATURE &
Figure 21.7 The colHo-air temperature relationship under increased
oo
Corrosion is one factor that determines what material
is used. For instance, when acidic materials need to be
cooled, copper or aluminum evils would be eaten away.
Stainless steel may be used instead, bur stainless steel
does not conduct heat as well as copper. Some evapo-
rators are even coated with a plastic-hke substance to
protect the metal underneath fom rust or oxidation.
“This application is often seen in restaurants with smaller
commercial, medium-temperature coolers that store
salad preparation materials, which are acidic because
they often have a vinegar base for added flavor and for
‘extended shelf life
Commer Retgertn
    
MOISTURE
DRIPPING.
 
a
‘LOR DRAIN 3
Figure 21.8 The cooing collcondenses masture tam the a
FINS
  
   
RETURN AIR (95°F) WITH
HEAT FROM FOOD PRODUCTS
REFRIGERANT BOILING.
‘AT 20°F ABSORBS HEAT
THROUGH THE WALL OF
‘THE COPPER TUBING.
TUBING
THE FINS GIVE THE COPPER TUBING MORE
SURFACE AREA FOR GREATER HEAT EXCHANGE,
Figure21.9 The hestcichange lstionchip betwicen stand rekigeant
2. The medium to which the heat is exchanged. Giving
heat up from air to refrigerant is an example. The best
heat exchange oceurs between two liquids, such as wa-
ter to liquid refrigerant. This is because liquids are more
dense than vapors and usually have a higher specific
heat. However, this isnot always practical because heat
frequently has to be exchanged between air and vapor
refrigerant. The vapor‘to-vapor exchange is slower than
the liguid-to-liquid exchange, Figure 21.10.
3. The film factor. This isa relationship between the me-
dium gig up heat and the heat exchange surface.
‘The film factor relates to the velocity of the medium
passing over the exchange surface. When the velocity is
too slows; the film berween the medium and the surface
becomes an insulator and slows the heat exchange,
‘The velocity keeps the film to a minimum, Figure 21.11.
‘The correct velocity is chosen by the manufacturer.v2
WATER (65°F)
—
 
  
 
  
 
   
      
VAPOR
REFRIGERANT
100% VAPOR
APPROXIMATELY
25% VAPOR
79% UQUIO
CHILLED WATER
7
LIQUID
REFRIGERANT
 
 
  
WATER (45°F)
METERING’
DEVICE
Figure 21.10 The heat exchange relationship between a liquid in a
Theaverahange axlersingeant fsa te wa
 
 
Figure 21.11. One of the deterring factors in anormal heat exchange.
“Tre fm factors the fy of ai oF guid next to the tube inthe heat
‘aa nthe tigen Str
4. The temperature difference between the two mediums
in which the heat exchange is taking place. The greater
the temperature difference between the evaporator coil
and the medium giving up the heat, ehe faster the heat
exchange will occur,
21.8 TYPES OF EVAPORATORS
Numerous types of evaporators are available, and each
hhas its purpose. The first evaporators for cooling air were
of the natural-convection type. They were actually bare
pe evaporators with refrigerant circulating through them,
Figure 21.12. This evaporator was used in carly walk-in cool=
crs and was mounted high in the ceiling. Ie relied on the air
being cooled, falling to the floor, and setting up a natural ir
current. The evaporator had to be quite lage forthe particu-
lar application because the velocity ofthe air passing over the
coil was 30 slow. Natural convection evaporators are stil oc
casionally used today. The use ofa blower co force or induce
air over the coil improved the efficiency of the heat exchange.
‘This meant that smaller evaporators could be used to do the
same job, Design trends in the industry have always been to-
‘ward smaller, more efficient equipment, Figure 21.13.
‘The expansion of the evaporator surface to a surface
larger than the pipe itself produces a more efficient heat
exchange. The stumped etuporstor was one of the Brae de
signs to create a large pipe surface. It consisted of two pieces
‘of metal stamped with the impression of a pipe passage
through it, Figure 21.
‘A pipe with fins attached, called a fnned-tube evapo-
zator,is today used more than any other type of heat ex
changer between air and refrigerant. This hear exchanger is
 
 
 
 
  
exchanger efficient because the fins are in good contact with the pi
nay ficient by the fi good h the pipe
ACONVECTION CURRENT INSULATED BARE PIPES WITH
IS SET UP WHEN THE COLDER, CEILING REFRIGERANT
HEAVIER AIN DISPLACE THE CIRCULATING
WARMER AIR NEAR THE FLOOR.
CONDENSATE
CONDENSATE
=—_ ——
wee )F
Figure 21.12 A bare-pipe evaporator
 
 
\s AIR2
 
Figure 21.13 forced cia evaporator cunmyl
 
carrying the refrigerant. Figure 21.15 shows an example of
a finned-tube evaporator, Figure 21.15(B) shows a finned-
tube evaporator used in a low-temperature, commercial,
well-type freezer. The leading fins come in contact with the
aur first and must have wider spacing between the fins. Its
these leading fins that are more prone to frost accumula:
tion. The wider fin spacing can accumulate more frost be-
fore becoming plugged and impeding the airflow. The fins
toward the back of the evaporator then encounter drier air
‘with less frost and so are more closely spaced.
Multiple circuits improve evaporator performance and
efficiency by reducing pressure drop inside the evaporator.
Even though the pipes inside the evaporator might be pol
ished smooth, they still offer resistance to the flow of both
liguid and vapor refrigerants. The shorter the evaporator
is, the less resistance there is to this flow. The “U" bends
at the ends of the evaporator also offer a great deal of re-
sistance to the flow of refrigerant. As evaporators hecome
longer, they have more and more pressure drop associated
 
  
Commer Regen
 
®)
Figure 21.15 (AIA
commerell reng
 
evaporator for a medi
Cate W) rinned tube vapor
  
     
with refrigerant flowing through them. The manufacturer
will design the evaporator so thatthe tubing bundles are in
parallel ro one another, Figure 21.16
The evaporator for cooling liquids of making ice oper
ates under the same principles a¢ one for cooling air but
is designed differenely. It may be strapped on the side of
a cylinder with liquid inside, submerged inside the liquid
container, or be a double-pipe system with the refrigeranc
inside one pipe and the liquid to be cooled circulated inside
fn enter pipe, Fig 21.17,
Every central splir-cooling system manufaerured in
the United States today must have a Seasonal Energy
Efficiency Ratio (SEER) of atleast 13. This energy require-
‘ment was mandated by federal law as of January 23, 2006
Also, with the phascoue of R-22 just around the comner,
‘manufacturers of HVACIR equipmcat have been looking
for energy-efficient methods to apply to their equipment
to meet these new energy requirements, The timeline for
R22 is as follows:
 
© 2010—R-22 use is banned at the original equipment
manufacturer (OEM) level with a 75% reduction of
HEC production.
+ 2015—90% reduction of HCFC production,
© 2020—Total ban of R-22 productionUne2t asain tigen Stem 6
Z suchow
EXPANSION LINE TO
2 VALVE COMPRESSOR
“ : r
 
| ‘
EVAPORATOR PIPING F
AROUND CYLINDER 2
Oy)
PLATE-TYPE
EVAPORATORS
Liguip LeveL
uaUID
REFRIGERANT
TO EXPANSION
VALVE |
  
  
 
Oy
‘GUCTION
LINE TO «
‘COMPRESSOR ©
 
e)
 
©
Figure 21.16 (4) A
duce pressure cr
evaporator. Thes in paral to reduce BeS- Figure 21.17 Liquid heat exchangers. (A) A drum-type evaporator
sure drop Couey Spoon Compu ard) Cues Fer Ste rier (8) A plate type evaporator na tank {C) A ppe-in pine evaporstor
Sy Prtos by hee (Ccouner/ nora Met ates re
    
©sects
The equipment covered by this federal mandate includes
*# unitary equipment from 1.5 to 5 tons,
+ splitipackaged air conditioners and heat pumps.
Equipment not covered includes
+ commercial equipment greater than 6 tons,
* spaceeonstrained units smaller than 3 t0ns (room air
conditioners),
SEER is caleulated on the basis of the total amount of
cooling {in Bru} the system will provide over the entire sea-
son, divided by the total number of wart-hours it will con-
swine, Higher SEERS reflow « snore efficient cooling system
TThe federal mandate impacts 95% of che unitary market in
the United States, which is about $ million units manufac
tured at the time of this writing. Because of the new federal
‘mandate of 13 SEER, most airconditioning and heat pump
manufacturers are looking for more efficient evaporator
and condenser designs, more efficient compressors and fan
‘motors, and more sophisticated control systems in order to
reer the new energy efficiency requirement
‘One such evaporator design incorporates an aluminum
parallel-flow, flat-plate-and-fin configuration with small
parallel channels inside the flat plate. The plates are flat-
tened, streamlined tubes each one of which is split into
smalls, parallel ports, Viguse 24.18. % Refigerant willphase
‘change or evaporate from a liquid toa vapor inside the channels
in the plate, while strategically shaped fins (extended surfaces)
will enhance heat transfer fromthe air into the evoporator, The
plates and fins are bonded or soldered to increase heat transfer
‘and to eliminate any contact resistance (air gaps) that will reduce
heat transfer Headers at the inlet and outlet of the heat
texchanger are also bonded to the plates through soldering,
Heat is transferred from the air to the evaporating re-
Irigerane in three steps, as follows:
 
 
  
 
1. Air side—hetween the fins and the air to be cooled
2. Heat conduetion—berween the fins and the tubes
3. Refrigerant side—hetween the tubes and the evaporat-
 
ing refrigerant
{The air side of the heat exchange can be enhanced through
fin geometry. Louvres, lances, and ippled edges all increase heat
transfer Figure 21.19, The conduction between the fins andthe
tubes is enhanced through the application of a metalic bond
(soldering) that eliminates any airgaps.%9 The refrigerant side
of the heat transfer deals with how much surface area of the
incide n the bes will eame intr enmact with the phace
changing refrigerant. This intemal surface area is often re-
ferced to as a wetted perimeter. As the internal surface area
of the tubes increases, the heat transfer increases. Internal
surface area can be increased by:
 
 
* increasing the number of parallel channels inside the flat
plates,
Commer Regen
 
 
©)
Figure 21.18 An aluminum paralle-Tow, fat plate-and fin heat ex
AMEE cure Meine Manacting Ca are
+ increasing the number of fae plates (decreasing the spac
ing between chem)
Te capacity (tonnage) of the heat exchanger ean vary
with its height and length. The plaes can be oriented vert
eally for an evaporator application oF horizontally for con
denser applications. The Vertical orientation of the flar platesv2
 
©
Figure 21.19 Fin geometry fer increasing heat wansie.
sy ene Natt Co, aie
allows condensate removal to occur naturally, alleviating any
water drainage issues from the evaporator Figure 21.20. This
technology is being used with condensers as well as evapora-
tors, Figire 21.21. Applications in the HVACR fed inclnde
residential airconditioning, rooftop airconditioning, chillers,
geothermal heat pumps, electronic cooling, packaged termi-
nal air conditioners (PTAC), ice machines, beverage dispens-
cr, refrigerated display cases, and foodservice refrigeration,
Some of the benefits of this parallelflow; plate-and-fin heat
‘exchanger technology are as follows:
‘+ Reduces static pressure through the coil—which means
fewer fan watts and less horsepower
‘+ Reduces coil depth for the evaporator and condenser,
which leads to easier cleaning and less airside static
pressure
‘+ Reduced internal volume reduces refrigerant charge
‘+ Reduced face area of condenser and evaporator
‘+ Smaller foorprin forthe condensing unit
 
‘aa nthe tigen Str
MOUNTING WITH VERTICAL HEADERS.
HEADER i
MA GAEnen TUBE SIDE += FIN SIDE
    
   
‘TuBe sive view
LRAT
 
  
  
 
“FIN ORIENTATION IS NOT + CONDENSATE
‘CRITICAL ‘WILL MOVE
“AIRFLOWMUST ENTERTUBE ——_-WITHAIRFLOW
SIDE OF EVAPORATOR AND DRAIN
Down Fit SIDE
“
MOUNTING WITH HORIZONTAL HEADERS
FIN ORIENTATION MUST BE FLOW DIRECTION
CONCAVE SHEY FACE). SNOT CRITICAL
=. =,
l
FINORIENTATION
OAS
‘CONDENSATE WILL ORAIN THROUGH FIN LOUVERS
©
Figure 21.20 Condensate removal for vertical and horzontal header
‘configuration, Coun Medre trating Co. Rate Mt
‘+ 4.30% reduction in coil weight and size
‘+ A reduction in packing costs, sizes, and weights
‘+ The allaluminum coil, header, and fins enhance corro-
*+ Lower system costs
‘+ Higher system efficiencies than a round, copper-tube heat
exchanger with aluminum fins, Figure 21.16(C)
‘+ Lower operating costs
+ Quieter operations
 
Field repair of leaking heat exchangers, Figure 21.22, can
bbe accomplished by
 
recovering the refrigerant,
cleaning the leaking area with a solution,
‘brushing the area with a wire brush,
using a utility knife blade to remove any fins that may be
in the local area,6 Sexton Commer Reign
 
Oy) ®
Figure 21.21 (A) Condenser (8) Evaporator Couns
 
 
 
 
 
Figure 21.22 Feld repair of aleaking heat exchanv2
+ palling  wacunm with a vacuses pomp,
+ applying a two-part epoxy that will be sucked into the
fla plate where the leak exists,
‘+ applying heat with an clecri blow dice wntl the epoxy
is cured,
1» evacuating ro 2 500-micron vacuum,
‘charging with the appropriate refrigerant.
Field cleaning heat exchangers can be accomplished using.
the same methods as for a standard round copper-tube heat
exchanger with aluminum fins:
‘+ Elevate the temperature of the mixed cleaner t0 120°
‘© Use a power washer with a broad spray pattern.
‘+ Use nonacidic cleaners (pH < 10.5).
= When che heat exelianger is el
clean water.
ringe ule coil with
 
21.9 EVAPORATOR EVALUATION
Knowing the design considerations helps in evaporator
evaluation. When the service technician arrives atthe job,
iemay be necessary 3 evaluate whether a parscular evapo
ator is performing properly. This can be considered one
of the starting points in organized teoubleshooting. The
evaporator absorbs heat, the compressor pumps it, and the
condenser rejects it. The following example pertains to a
fumicmperalace walk-in bos, Lloweves the procede
‘would be about the same for any typical application,
 
SUCTION LINE
TO COMPRESSOR,
     
  
  
 
   
  
170 psig
100% PURE
LiguiD)
35% VAPOR
155% LIQUID
PERE oe rev ersrune arruicanon, yorwas oreninion
tad psig
‘aa nthe tigen Str
Evaporator Specifications
Copper pipe coil
Aluminum fins attached to the copper-pipe coil
Forced draft with a prop-type fan
One continual refrigerant circuit
Re134a
Evaporator to maintain space temperature at 35°F
Evaporator clean and in good working condition
 
First we describe how the evaporator functions when itis
working correctly
Entering the evaporator isa partial liquid-partal vapor
mixture at 20°F and 18.4 psig; it is approximately 65%
liquid and 35% vapor. Approximately 35% of the liquid
cenvering the expansion devive at che evaporavor is changed
to a vapor and cools the remaining 65% of the liquid to
the evaporator's boiling temperature (20°F). This is accom
plished by the pressure drop across the expansion device.
‘When the warm liquid passes through the small opening
in the expansion device into the low pressure (184 psig)
of the evaporator side, some of the liquid flashes to a gas,
Figure 21.23.
‘As the parcial liguidepartial vapor mixture moves
through the evaporator, more of the liquid changes to a va-
pot. This is called boiling and is a result of heat absorbed
into the col from whatever medium the evaporator is cool
ing, Finally, near the end of the evaporator the liquid is
all boiled away wo a vapos. At this point the teftigerant is
known as saturated vapor. This means that the refrigerant
184 psi
EVAPORATOR COIL.
 
i
Flqure 21.23 When the | 1Fliquid passes through the eansion vale rice, some ofthe liquid Rashes toa vanor and cools the remainina ligld
tothe evaparator temperature a 20°
 
aaSexton Commer Reign
vapor is saturated with heat. Ifany more heat is added to
it, it will rise in temperature. If any heat is taken away from
it, it will stare changing back to aliquid. This vapor is satu-
rated with heat, but i is still atthe evaporating temperature
corresponding to the boiling point, 20°F. 9 This isa most
important point in the function of an evoporator becouse all of
the quid must be boiled away as close to the end ofthe col as
possible. This s necessary to (1) keep the coil efficiency up and
(2) ensure that liquid refrigerant doesnot leave the evaporator
{and move into the compressor: For efficient operation, the
evaporator must be as full of liquid as possible without al-
lowing liquid to reach the outlet of the coil, because the bese
heat exchange is between the liquid refrigerant and the air
passing over the col
‘The pressurefemblpy chart in Figure 21.24 shows
sraphically what happens inside the evaporator of the pre-
ceding walk in cooler example. The refrigerant enters the
evaporator at point A (after leaving the expansion valve)
‘The liquid pressure is 18.4 psig and contains 48.7 Beu/lb of
heat at this point. Approximately 33% of the liquid flashed
 
to a vapor when passing through the expansion valve. As
the liquid proceeds through the evaporator, it is changing
to a vapor. All of it has changed to a vapor at point B, but
the vapor temperature is still 20°F and capable of absorbing,
heat; in the form of superheat. The vapor temperature starts
‘orice while iis ll n the evaporator until the temperature
is 30°F (containing 10°F of superheat). The vapor leaves the
evaporator at point C with a heat content of 108.1 Btuflb,
‘The usable refrigeration in the evaporator is from points
A to CG, where the refrigerant absorbed 59.4. Bra/lb
(108.1 Bru/lb ~ 48.7 Bro/Ib) of the circulating refrigerant.
You only need roknow how many Brufh capacity is needed %6
determine the amount of refrigerant that needs to be circu-
lated. For example, ifthe evaporator needs to have a capacity
of 33,000 Buu, it must have 389.2 Ib of refsiges
‘culate through it per hour (35,000 Brwh + 59.4 Bru/lb
5389.2 lbh). This sounds like a lot of refrigerant, bue it is
only 9.82 Ihvmin (589.2 Ibvh + 60 minfh = 9.82 lbvmin).
“The siz of the compressor and the system operating condi-
tions determine how much refrigerant can be pumped.
 
 
 
 
 
 
 
 
 
 
 
 
 
g
 
 
Pressure (psia)
5888
3
 
 
 
 
 
 
 
 
 
 
 
EFFECT
 
 
Figure 21.24 The refgeration effect inthe evaporator. outer | Dont
 
 
 
NET REFRIGERATION
108.1
=487
504 Blus NET REFRIGERATION EFFECT
°
 
soav2
21,10 LATENT HEAT
IN THE EVAPORATOR
‘The latent heat absorbed during the change of state is much
‘more concentrated than the sensible heat that would be
added to the vapor leaving the coil. Refer to the example
in Unie 1, Section 1.3, that showed how it takes 1 Bru to
change the temperature of 1 Ib of 68°F water to 69°F water.
Section 1.8 also showed that itrakes 9/0 btu to change 1 1D
(of 212°F water to 212°F steam, The change of state is where
the greatest amount of heat is absorbed into the system.
The preceding example showed that 59.4 Bru of heat were
absorbed for every 1 Ib of refrigerant that was circulated
{59.4 Bru/lb). This happened at a boiling temperature of
20°F, without a change in pressure.
21.11 THE FLOODED EVAPORATOR
“To get the maximum effcieney from the evaporator heat
exchange, some evaporators are operated full of liquid, oF
flooded, and are equipped with a device to keep the liquid
refrigerant from passing to the compressor. These flooded
evaporators are specially made and normally use a float me-
tering device to keep the liquid evel as igh as possible inthe
evaporator This text will not go into detail about ths system
Ihecause itis not a device often encountered, The manufactur
ers literature should be consulted for any special application.
RETURN
AIR
es
2F
35°F ——>
37
so}
39°F ——>
39°F
METERING
DEVICES
100% LIQUIDS
184 psig Liou.
REFRIGERANT
UNE
  
t
f  (sucTion une)
Figure 21.25 The evaporator operating under normal load.
 
         
    
   
  
|-—VAPOR REFRIGERANT LINE.
‘aa nthe tigen Str
When an evaporator is flooded, it would operate much
like water boiling in a pot with a compressor taking the
vapor off the top of the liquid. There would always be a lig
uid level. Ifthe evaporator is not flooded, that is, when the
refrigerane starts out as a partial liquid and boils away toa
vapor in the heat exchange pipes; it ix known as a dry-type,
‘or direct-expansion, evaporator,
21.12 DRY-TYPE EVAPORATORS,
PERFORMANCE
‘To check the performance of a dry-type evaporator, the ser-
vice technician would first make sure that the refrigerant
col is operating with enough liquid inside the eoil. To de-
termine this, the technician must calculate the evaporator
superheat. This is generally done by comparing the boiling
temperature of the refrigerant inside the coil with the line
temperature leaving the coil. The difference in temperatures
is usually 8°F to 12°F For example, in the coil pictured in
Figure 21.25, the superheat in the coil was arrived at by
converting the coil pressure (suction pressure) to tempera-
ture, In this example, the pressure is 18.4 psig, which eor-
responds to 20°F. The suction pressure reading is important
to the technician because the boiling temperature must be
known to arrive at the superheat reading for the coil. In
the following example, the evaporator supetheat reading is
10°F (30°F = 20°F),
[HIS HEFHIGEHAN CONIAINS
LAST POINT
‘OF LIQUID
REFRIGERATED
— _AR
— Spy
ones
 
   
CONDENEATE DRAIN
‘APPROXIMATELY 35% VAPOR,
165% LIQUID
\
 
 
 
 
8sects
21,13 EVAPORATOR SUPERHEAT
‘The difference in temperature between the boiling relriger-
ant temperature and the evaporator outlet tempcrature is
known as evaporator superheat. Superheat is the sensible
heat added to the vapor refrigerant ater the change of state
hhas occurred. Supetheat is the best method of checking to
see when a refrigerant coil has a proper level of refrigerant.
When a metering device is not feeding enough refrigerant ta
the coil the col is said to be a starved coil, and the super-
hreat is greater, Figure 21.26. Itcan be seen from the exam-
ple that all of the refrigeration takes place at che beginning
of the col. The suction pressure is very low; below freezing,
but only a portion of the coil is being used effectively. This
coil would freeze solid and no air would pass through
‘The freeze line would creep upward until the whole coil
was a block of ice, and the refrigeration would do no good.
‘The refrigerated box temperature would rise because ice is
 
 
21.14 HOT PULLDOWN (EXCESSIVELY
LOADED EVAPORATOR)
‘When the refrigerated space has been allowed ro warm up
considerably, the system must go through a hot pulldown.
On a hot pulldown the evaporator and metering device
are not expected to act exactly as they would in a typical
design condition, For instance, if a walk-in cooler supposed
~.
AB AUF
    
   
    
 
AIR 40°F
FAN AND MOTOR
  
Commer Retgertn
to maintain 35°F were allowed to warm up to 60°F and had
some food or beverages inside, it would take an extended
time to pull the air and product temperacure down. The coil
‘may be boiling the refrigerant 3 fast thatthe supetheat may:
not come down to §°F to 12°F until the box has cooled
dlown closer to the design temperature.
‘A superheat reading on a hot pulldown should be in-
terpreted with caution, Figure 21.27. The reading will be
 
   
ETHAN AIR
(65°F)
Figure 21.27 1lot pulldown witha coll Thisis@ medium temperature
evaporator that should be operating at 18a psig 38a, 20°F The e-
turn airs 55 instead of 35° This causes the pressure in the colo a,
The warm box balls the refrigerant a faster Fate. The thermostatic exe
pansion vaive isnat abl to ee the evaporator quickly enough ta keep
the supatheat at 10% The evaporator has 15 of superhoat
 
THIS
30°F
GAS CONTAINS,
-F SUPENHEAT,
f= OF LIQUID
gy ase
FEFHIGEHATED AIH
   
  
104 \, NAPPRONATELY G5 VAPOR, 65% LOUID =
| t \ \wererine ovce 4
100% LIQUID i
HIGH PRESSURE m LOW TEMPERATURE coo, tow §
(WARM LIQUID LOW-PRESSURE LIQUIDNAPOR PRESSUREVAPOR
Figure 21.26 A starved evaporator col showing 38°F (40°F ~ 27) of evanoratarsuperheat,v2
  
AIR (95°F) FAN
Figure 21.28 The evanorator is Fading because the thermostatic
fearsion device s nat conteing religeant flow propery
correct only when the coil is at or near design conditions
However, many modern thermostatic expansion valves
(TXVs) have wide temperature control ranges. Some ean
control evaporator superheat from +20*F to ~20°F, and
they are advertised to do this effectively even when un-
der heavy or light heat loadings of the evaporaror. TXVs
should control superheat under most normal conditions
However, when a system is under a hot pulldown, the
technician should let the system get past this heavy load
period and reach a somewhat stabilized condition before
trying to calculate an evaporator superheat reading. Hot
pulldowns are not considered normal conditions, and the
technician must be patient when calculating evaporator
supetheat. Ir eakes time for a TXY to fill aut the evapora
tor with refrigerant even when itis wide open during a
hot pulldown.
When a dey.cype col is fed too much sofigerant, not all
the refrigerant changes to a vapor. This coils thought of asa
flooded coil—flooded with liquid refrigerants, Figure 21.28
Do not confuse this with a coil flooded by design. This is
rmptom that can cause real trouble because unless the
Tiquid fn the snction line hails tr a vaper before it reaches
the compressor, compressor damage may occur. Remember,
the evaporator is supposed to boil al ofthe liquid to a vapor.
‘Therefore, a thermostatic expansion devies that is not oper-
ating correctly can cause compressor failure,
  
 
 
   
   
21,15 PRESSURE DROP
IN EVAPORATORS
“Mulkicircuie evaporators are used when the coil would be-
come t00 long for a single circuit, Figure 21.29, The same
evaluating procedures hold true for a multicircut evapora-
tor as fora singlecireuit evaporator.
‘aa nthe tigen Str
cameras
   
JCONDENSEA VALVE REWOTE BULB
Figure 21.29 A mulcicuit evaporator counry “pink Company
A dry-type evaporator has to be as full as possible
with refrigerant to be efficient. Each circuit should be
feeding che same amount of refrigerant. If this needs to
be checked, the service technician can check the common
pressure tap for the boiling pressure, which can be con-
verted ra temperature. Then the temperature will have
to be checked at the outlet of each circuit to see whether
circuit is overfeeding or starving, Figure 21.30 and
Figure 21.31.
Some reasons for uneven feeding of a mulkicireuit evap-
orator are the following:
 
Blocked distribution system
Direy coil
Uneven air distribution
Coil circuits of different lengths
In larger commercial and industrial-type evaporators,
an associated pressure drop usualy is caused from friction
as the refrigerant eravels the length of the evaporator and
down a long suction line to the compressor. This causes the
pressure at the compressor to be a bit lower than the pres-
sure at the evaporator outlet. With larger evaporators and
longer suction lines, itis importanc to measure the refriger-
ant’s pressure atthe evaporator outlet—not at the compres-
sor service valves—when measuring evaporator superheat,
Figure 21.29 and Figure 21.30, It is best to measure the
refrigerant pressure at the same location that che evapora-
tor outlet temperature is taken when measuring evaporator
supecheat. This will give the service technician a more ac-
curate evaporator superheat reading and, therefore, better
evaporator efficiencies. Schrader taps are often provided at
the outlet of larger evaporators for this reason. Line taps
also can be used to gain access to evaporator outler pres-
sure. This method also will protect the compressor from
flooding or slugging problems caused by inaccurate evapo-
rator superheat readings.2 Secon Comme ei
 
ecHnapen
VALVE AND
GAGE
THERMOSTATIC
EXPANSION VALVE
REFRIGERANT SENSING ELEMEN
DISTRIBUTOR
  
    
 
  
  
FIN. EXTERNAL EQUALIZER TUBE —~
      
   
 
   
 
 
   
SLOPE DOWN — CoMPRESSOR
|-—REFRIGERANT VAPOR
  
 
{oF SUBEANEAT
UST PONT OF TOUD NEROTEOIL
Liquip f
tne] A
[
{_EQUAL-LENGTH DISTRIBUTOR TUBES FOR EXACT COIL FEEDING $
THERMOSTATIC EXPANSION VALVE j
Figure 21.30 The 2pcaarcec amultdicut oapactr onthe sie when ted comet reels soxtleapnctr plpedin pal
 
    
  
TO
COMPRESSOR
SUPERHEAT IN THIS
CIRCUIT IS 20°F AND
THE OTHER CIRCUITS:
ARE 10°F THIS IS A
STARVED CIRCUIT.
    
CRIMP IN LINE CAUSING THIS CIRCUIT TO
SLIGHTLY STARVE FOR REFRIGERANT
LIQUID LINE
THERMOSTATIC
t EXPANSION VALVE
 
 
Figure 21.31 The appearance ofa mulicicuit evaporator onthe inside wien itis nt fetne21 fa
2
 
-16 LIQUID COOLING
EVAPORATORS (CHILLERS)
A ditferent type of evaporator is required for liquid cooling.
Ir functions much like the one for cooling air and is nor-
‘mally a dry-type expansion evaporator in smaller systems,
Figure 21,32(A). Evaporators for larger-tonnage chiller are
usually the flooded type. They have sarurated liquidivapor
refrigerant in the shell and the water to be chilled flows in
the tube bundles, Figure 21.32(B). They use a low side float
to meter the refrigerant into the shell of the evaporator to
maintain the proper refrigerant level,
Liquid cooling evaporators have more than one refrigerant
circuit to prevent pressure drop. These evaporators sometimes
have to be checked to see whether they are absorbing heat as
THERMOMETER —
Vv
WATER
our,
er
THERMOSTATIC
EXPANSION VALVE —
LQUID-LINE
REFRIGERANT IN
Figure 21.3218) Adi
 
OPERATING THERMOSTAT \,
/
 
‘or cooing liquids
sand the ageraton Sse 2
they should. Using refrigeration gauges and some accurate
method for checking the temperature of the suction line are
very important. These evaporators have anormal superheat
range similar to airtype evaporators (8°F to 12°F). When the
superheat is within this range and all circuits in a mulicircuit
evaporator are performing alike, the evaporator is doing its job
‘on the refrigerant side, However, this does not mean that it will
cool properis. The liquid side of the evaporator must be clean so
that the guid will come in proper contact withthe evaporator,
“The following problems are typical on the liquid side of
the evaporators
 
Mineral deposits may build up on the liquid side and cause
‘a poor heat exchange. They would act like an insulator
2. Poor circulation of the liguid to be cooled where a cir
culating pump is involved,
THERMOMETER,
     
    
       
 
 
 
 
 
 
PRESSURE
  
TAPS
;-FREEZE ae
* STAT WATER,
IN
REFRIGERANT OUT =
SUCTION LINE
TO COMPRESSOR
HARDWARE AND CONTROL
BOARD COMPARTMENT
CHILLED WATER
RETURN
100-tn F134) flooded type evaporator Use
 
 
 
chil water for cooling al
CONTROLLER
WATER,
INSULATED EVAPORATOR
(OF CHILLER BARREL
CHILLING WATERsects
51.3 psig OH 55° 15°F SUPERHEAT. |
     
 
 
 
 
‘SUCTION LINE
LIQUID LINE
Commer Retgertn
CHILLED WATER CHILLED WATER OUT
(75°F) INTO THE (esr)
EVAPORATOR CONTAINS
HEAT FROM BUILDING.
 
Figure 21.33 Ahot pulldown on aliquid evaporator aving up its heat to refrigerant This evaporator notmaly has 55°F water in and 45°F weer out
Tre hot plldowin th 75 ner inated of $5 ater bo the efigeront ata fate rae The expansion valve ry not beable to feed the evapo
 
ter quichlyenaugh to maintan 10"
 
‘When the supetheat is correct and the coil is feeding cor
rectly in a multicireuit system, the echnician should con-
sider the temperature ofthe hquid. the superheat may not
be within the prescribed limits ifthe liquid to be cooled is
not close to the design temperature. On a hot pulldown of a
liquid product, the heat exchange can be such that the coil
appears t0 be starved for refrigerant because itis so loaded
up that itis boiling the refrigerant faster than normal. The
technician must be patient because a pulldown cannot be
rushed, Figure 21.33. Airto-refrigerant evaporators do not
have quite the pronounced difference in pulldown that lig-
uid heat exchange evaporators do because of the excellent
heat exchange properties ofthe liquid to the refrigerant.
 
21,17 EVAPORATORS FOR
LOW-TEMPERATURE
APPLICATIONS
Low-temperature evaporators used for cooling space or
product to below freezing are designed differently because
they require the coil to operate below freezing.
In an airflow application, the water that accumulates on
the coil will freeze and will have to be removed, The design
of the fn spacing must be carefully chosen, because a very
small amount of ice accumulated on the fins will restriet
the airflow. Low-temperature coils have fin spacings that
are wider than medium-temperature coils, Figure 21.34.
Other than the airflow blockage due to ice buildup, these
low-temperature evaporators perform much the same as
:medium-temperature evaporators. They are normally dry-
type evaporators and have one or more fans to circulate the
air across the coil. The defrosting of the coil has to be done:
by raising the coil temperature above freezing to melt the ice.
 
 
Superheat. No conclusions should be made untl the system aparoaches design cantons,
 
@
Figure 21.4 Fin scacng, (8) Law-tempertue evaccat (8) Mediu:
temperature evaporate Peasy Bereanv2
“Then the condensate water has to be drained aff and kept
from freezing. Defrost is sometimes accomplished with heat
from outside the system. Electric heat can be added to the
evaporator to melt the ie but this heat adds to che load of
the system and needs to be pumped out after defrost.
21.18 DEFROST OF
ACCUMULATED MOISTURE
Defrost can be accomplished with heat from inside the sys-
tem using the hot gas from the discharge lin of the compres
sor by routing a hot gas lin from the compressor discharge
line to the outlet of the expansion valve and insalling a
solenoid valve to control the flow. When defrost is needed,
hot gas is released inside the evaporator, which will quickly
smelt any ice, Figure 21.35
‘When the hor gas enters the evaporator, tis likely chat
liquid refrigerane will be pushed out of the suction line to-
ward the compeessoe. In fact, when hor gas enters an evapo-
rator and starts to cool. as it melts ice or frst, it wll soon lose
all of its supesheat and turn to liquid or condense. This ig-
uid will goto the aecumolator and fall to ts hortom. Dense
saturated vapors will be drawn into the compressor’ suction
stroke. The compressor will see an increased load from these
dense vapors and may draw a highce amp than during the
normal running cycle. Ifthe system does not have an accu
‘mulator, this condensed liquid may flood the compressors
crankcase and foaming of the oil in the crankcase may occu,
Figure 21.36. This can lower the oil level in the crankease
 
SOLENOID VALVE ~
TO CONTROL
‘SUCTION-LINE HOT GAS,
ACCUMULATOR
RECEIVER, 7
DRIER SIGHT
GLASS
Figure 21.35 Using hot gas to defrost an evaporator
 
 
  
‘aa nthe tigen Str
and cause scoring of bearing surfaces in the compresion. This
condition is often referred to as bearing washout
Flooding the compressor’ crankcase with liquid refi
«rant ean also cause the foaming refrigerant and oil mixtare
to pressurize the crankcase, which causes the mixture of lig
vid and vapor refrigerant and ol foam to be forced through
any crevice available, including the compressor’s piston
rings. The mixture is often pumped into the high side of the
system by the compressor. The compressor’ discharge tem
perature will decrease from the wet compression of the rich
mixture of refrigerant and oil foam, As soon as this mixture
is compressed, it will vaporize and absorb heat away from
the cylinder walls. This is what causes a lower-than-normal
discharge temperature on the compressor's discharge line.
Some manufaciurers of systems incorporating hoc yas de
frost place a thermistor on the discharge line of the compres-
sof f0 sense this cooler than normal discharge temperacure
 
) e
 
Figure 21.36 (A) A compressors clear cl sight glass. (6 A sight lass
from loading crankcase foams with Iquidreigeant.
   
   
     
EVAPORATOR
REFRIGERATED
‘SPACE
+ CONDENSATE
DAAIN LINE
 
 
eSsects
while in the defrost mode. The thermistor relays a mescage
t0 a control circuit ro deenergize the hot gas solenoid; clos-
ing the hor gas solenoid temporarily prevents any more hot
1 from entering the evaporator and dus turning to liquid
[As the compressor’ discharge temperature rises again, the
thermistor rensct the dae in temperature and relays a mes:
sage to the control circuit to continue with hot gas defrost
by energizing the hot gas solenoid again.
This sequence of events may continue until defrost is com
plete. The sequence simply protects the compressor from bear-
ing washout and wet compression while in defrost I may also
protect the compressor during the refrigeration eycle by shut
ting down the compressor if the discharge temperature gets
100 low indicating wer compression. To prevent this liquid
from eter the Compressor, ofcn a sui line wecunulstor
will be added to the suction piping, Figure 21.35.
‘The hot gos defost system is economical because power
does not have to be purchased for defost using external
heat, such as electric heaters that will heat the evaporator.
The heat is aready in thesystem
Electric defrost is accomplished using electric heat-
ing elements located at the evaporator. The compressor is
stopped and the heaters are energized on a call for defrost
and allowed to operate until the frost is melted from the
coil Figure 21.37. These heaters are often embeded in the
actual evaporator fins and cannot be removed if they burn
‘out. Peequently, in uhe event that the heaters do bun out,
hhot gas defrost can be added to the system and the electric
heat defrost procedures discontinued.
‘When either system is used for defrost, the evaporator
fan is often turned off during defrost; if iti not, wwo things
will happens
 
 
1. ‘The heat from defrost will be transferred directly to the
‘conditioned space.
2. The cold, conditioned air will slaw down the defrost
process,
Commer Retgertn
 
:
3
 
Figure 21.37 A heater used for electric defiost of low-temperature
evaporators
However, some manufacturers design their open frozen-
food cases so that the evaporator fans are left on during
defrost. Ths allows the supply-air and return-air ducts t0
be defrosted along, with the coil. The warm defrost airs dis
‘charged from the supply duct and rises out ofthe case, hav-
ing litte effect on the product temperature. Fans are always
shut off on closed, glass-door cases because of the problem
of fogging on glass or mirrored surfaces.
Evaporators in some ice-making processes have similar
defrost methods. They must have some method of applying,
heat to the evaporator to free the ice. Sometimes the heat
is electric or hot gas. When the evaporator is being used t0
make ice, the makeup water for the ive maker is sometimes
used for defrost. Evaporator defrosting is covered in more
detail in Section 22, (Defrost Cycle) oF Unit 25, “Special
Refrigeration System Components.”
In summary, when checking an evaporator remember
that its job isto absorb heat into the refrigeration system.
SUMMARY
‘+ Heat travels normally from a warm substance to a cool
‘+ For heat to travel from a cool substance to a warm sub-
stance, work must be performed. The motor that drives
the compressor in the refrigetation eyele does this work.
‘+ The evaporator is the component that absorbs the heat
into che refrigeration system.
‘+ The evaporator must be cooler than the medium to be
cooled to have a heat exchange.
++ The refrigerant boils to a vapor in the evaporator and
absorbs heat because it is boiling at a low pressure and
low temperature.
 
+ The boiling temperature of the refrigerant in the evapo-
savor determines the evaporator (low side) pressure
‘+ Medium-temperature systems can use offcycle defrost.
‘The product is above freezing, and the heat from it can
be used to initiate the defrost.
‘+ Low-temperature refrigeration must have heat added to
the evaporator to mele the ice.
‘+ For the same types of installations, evaporators have the
same characteristies regardless of location,
‘+ Most refrigeration coils ace copper with aluminum fins,
‘© The starting point in organized troubleshooting is to
decermine whether the evaporator is operating elv2
Checking the superheat is the hese mthod the service
technician has for evaluating evaporator performance.
‘+ Some evaporators are called dry-type because they use a
sninimam of refrigecant.
‘* Dry-type evaporators ae also called direct expansion
evaporators.
‘+ Some evaporators are flooded and use a float to meter
the refrigerant. Supetheat checks on these evaporators
should be interpreted with caution,
 
‘aa nthe tigen Str
Some evaporators have a single cireuit, and some have
multiple circuits.
Mulicircuit evaporators keep excessive pressure drop
from occurring in the evaporator
‘There is a relationship between the boiling temperature
of the refrigerant in the evaporator and the temperature
of the medium being cooled.
‘The coil normally operates at temperatures from 10°F to
20°F eolder than the temperature of the air pasting over it
REVIEW QUESTIONS
1. What is the function of the evaporator in the refrigera-
sion system?
2. Refrigerant in the evaporator
A. changes from vapor to liquid
B, changes from liquid to vapor.
C.stays in the vapor state,
D. stays in che liquid state.
3. The sensible heat that is added to a saturated vapor af-
ter all of the liguid has boiled away is referred to as
 
4, What determines the pressure on the low-pressure side
of the system?
5. A refrigerant systems evaporator typically runs about
‘degrees of superheat
6. What docs a high evaporator superheat indicate?
7. A low evaporator supetheat indicates
‘A. undercharge,
B, system restriction
C. overcharge.
D. dirt buildup.
8. Why is a molticircuit evaporator used?
 
10.
"
13,
4,
9. Flooded evaporators use a
device.
An evaporator that is wo« flooded is thought of xs what
type of evaporator?
‘When an evaporator experiences a heat-load increase,
the suction pressure
A. remains constant.
B. decreases.
C. varies up and down,
D. increases,
. What is commonly used to defrost the ice from a low-
temperature evaporator?
A medium-temperature refrigeration box operates
‘within whae remperature range?
A. 28°F t0 40°F
B. 40°F to 60°F
C.0°F to 20°F
D. O°F to 50°F
List seven advantages that an aluminum paralle-flow,
platen evaporator has over a standard round, copper
tube platefin evaporator.
type of expansion
 
 
 
 
a