Main PLC
Catalogue No:              1756-A4
CONTROLLOGIX CHASSIS 4 SLOTS
Automation Systems > Modular Programmable Controllers > Large PLC Systems > Allen-Bradley ControlLogix® >
ControlLogix® Chassis
                                                                        ControlLogix Chassis 4 Slot
                                                                                   ·   Distributes power to each of the modules in the
                                                                                       chassis via the backplane
                                                                                   ·   Slot guides and snap-in retention for easy and secure
                                                                                       fit for any type of 1756 module
                                                                                   ·   Slot fillers specifically designed for the standard or
                                                                                       extreme environment chassis (optional)
                                                                                   ·   Accommodates direct mounting for any 1756 power
                                                                                       supply
                                                                                   ·   Conformal coated options are available - contact NHP
                                                                                       for further information
Representative Photo Only
(actual product may vary based on configuration selections)
 SPECIFICATIONS
 Product Series                                                         ControlLogix (Bul. 1756 / 1757)
 Component Type PLC & I/O                                               Chassis
 Number of Slots                                                        4
 Module Specific Functions                                              The chassis backplane provides a high-
                                                                        speed communication path between
                                                                        modules and distributes power to each
                                                                        of the modules within the chassis.
 Operating Temperature, Max                                             60 °C max
 Operating Temperature, Min                                             0 °C min
 Storage Temperature, Max                                               85 °C max
 Storage Temperature, Min                                               -40 °C min
 Relative Humidity, Max                                                 95 %RH
 Vibration Acceleration (Max.)                                          2 m/s²
 Vibration Frequency, Operational (Max.)                                500 Hz
 Standards Compliance                                                   IEC 60068-2-27
                                                                        IEC 60068-2-30
                                                                        IEC 60068-2-6
                                                                        IEC 60068-2-1
                                                                        IEC 60068-2-14
                                                                        IEC 60068-2-2
                                                                        IEC 61000-4-2
                                                                        IEC 61000-4-3
                                                                        IEC 61000-6-4
 Certifications                                                         CSA
                                                                        CE
                                                                        C-Tick
                                                                        KC (KCC)
                                                                 NHP Electrical Engineering Products                           1756A4 Datasheet
                                                      1300 NHP NHP | nhp.com.au | 0800 NHP NHP | nhp-nz.com            5 March 2021, Page 1 of 2
ControlLogix System
Logix Controllers Comparison
Characteristic           1756 ControlLogix®                        CompactLogix™                     CompactLogix                      CompactLogix
                         1756-L71, 1756-L72, 1756-L73,             1769-L30ER, 1769-L30ER-NSE,       1769-L24ER-BB1B,                  1769-L16ER-BB1B,
                         1756-L73XT, 1756-L74, 1756-L75            1769-L30ERM, 1769-L33ER,          1769-L24ER-QBFC1B,                1769-L18ER-BB1B,
                                                                   1769-L33ERM, 1769-L36ERM          1769-L27ERM-QBFC1B                1769-L18ERM-BB1B
                         1756 GuardLogix®
                         1756-L71S, 1756-L72S, 1756-L73S
Controller tasks:        • 32;                                     • 32;                             • 32;                             • 32;
• Continuous             • 100 programs/task                       • 100 programs/task               • 100 programs/task               • 100 programs/task
• Periodic
• Event
Event tasks              Consumed tag, EVENT instruction           Consumed tag, EVENT instruction   Consumed tag, EVENT instruction   Consumed tag, EVENT
                         triggers, Module Input Data changes,      triggers and motion events        triggers and motion events        instruction triggers and
                         and motion events                                                                                             motion events
User memory              • 1756-L71: 2 MB                          • 1769-L30ER,                     • 1769-L24ER: 750 KB              • 1769-L16ER: 384 KB
                         • 1756-L72: 4 MB                            1769-L30ER-NSE,                 • 1769-L27ERM: 1 MB               • 1769-L18ER,
                         • 1756-L73: 8 MB                            1769-L30ERM: 1MB                                                    1769-L18ERM: 512 KB
                           1756-L73XT: 8 MB                        • 1769-L33ER, 1769-L33ERM:
                         • 1756-L74: 16 MB                           2 MB
                         • 1756-L75: 32 MB                         • 1769-L36ERM: 3 MB
                         • 1756-L71S: 2 MB + 1 MB safety
                         • 1756-L72S: 4 MB +2 MB safety
                         • 1756-L73S: 8 MB +4 MB safety
Memory card              Secure Digital                            Secure Digital                    Secure Digital                    Secure Digital
Built-in ports           1 port USB Client                         • Dual-port EtherNet/IP           • Dual-port EtherNet/IP           • Dual-port EtherNet/IP
                                                                   • 1 port USB Client               • 1 port USB Client               • 1 port USB Client
Communication options    •     EtherNet/IP                         • EtherNet/IP                     • EtherNet/IP                     • EtherNet/IP
                         •     ControlNet                            – Embedded switch                 – Embedded switch                 – Embedded switch
                         •     DeviceNet                             – Single IP address               – Single IP address               – Single IP address
                         •     Data Highway Plus                   • DeviceNet                       • DeviceNet                       • USB Client
                         •     Remote I/O                          • USB Client                      • USB Client
                         •     SynchLink
                         •     USB Client
Controller connections   500                                       256                               256                               256
Network connections      Per network module:                       • 1769-L30ER,                     • 1769-L24ER-QB1B:                • 1769-L16ER-BB1B
                         • 40 ControlNet (CNB)                       1769-L30ER-NSE,                   8 EtherNet/IP; 120 TCP            4 EtherNet/IP; 120 TCP
                         • 100 ControlNet (CN2/A)                    1769-L30ERM: 16 EtherNet/IP;    • 1769-24ER-BFC1B: 8              • 1769-L18ER-BB1B: 8
                         • 128 ControlNet (CN2/B)                    120 TCP                           EtherNet/IP; 120 TCP              EtherNet/IP; 120 TCP
                         • 128 EtherNet/IP; 64 TCP (ENBT)          • 1769-L33ER, 1769-L33ERM:        • 1769-L27ERM-QBFC1B:             • 1769-L18ERM-BB1B:
                         • 256 EtherNet/IP; 128 TCP (EN2x)           32 EtherNet/IP; 120 TCP           16 EtherNet/IP; 120 TCP           8 EtherNet/IP; 120 TCP
                         • 256 Ethernet (ENxT(R))                  • 1769-L36ERM: 48 EtherNet/IP;
                                                                     120 TCP
Controller redundancy    Full support                              Backup via DeviceNet              Backup via DeviceNet              None
Simple motion            • Stepper                                 • Servo via DeviceNet             • Servo via DeviceNet             Analog or Networked AC drive
                         • Servo via DeviceNet                     • Analog or Networked AC drive    • Analog or Networked AC drive
                         • Analog or networked AC drive
Integrated motion        • EtherNet/IP                             EtherNet/IP:                      EtherNet/IP:                      EtherNet/IP:
                         • SERCOS interface                        1769-L30ERM, 1769-L33ERM,         1769-L27-ERM-QBFC1B               1769-L18ERM-BB1B
                         • Analog options:                         1769-L36ERM
                           – Encoder input
                           – LDT input
                           – SSI input
Programming languages    •     Relay ladder                        •     Relay ladder                •     Relay ladder                •     Relay ladder
                         •     Structured text                     •     Structured text             •     Structured text             •     Structured text
                         •     Function block                      •     Function block              •     Function block              •     Function block
                         •     Sequential function chart           •     Sequential function chart   •     Sequential function chart   •     Sequential function chart
                         •     Safety task: relay ladder, safety
                               application instructions
          Allen-Bradley 1756-L71
2                                                           Rockwell Automation Publication 1756-SG001S-EN-P - August 2014
Select a ControlLogix System
ControlLogix Controllers
The ControlLogix controller provides a scalable controller solution capable of addressing a large number of I/O points.
The controller can be placed into any slot of a ControlLogix chassis and multiple controllers can be installed in the same chassis.
Multiple controllers in the same chassis communicate with each other over the backplane (just as controllers can communicate
over networks) but operate independently.
ControlLogix controllers can monitor and control I/O across the ControlLogix backplane, and over I/O links. ControlLogix
controllers can communicate over EtherNet/IP, ControlNet, DeviceNet, DH+, Remote I/O, and RS-232-C (DF1/DH-485 protocol)
networks and many third-party process and device networks. To provide communication for a ControlLogix controller, install
the appropriate communication interface module into the chassis.
 Cat. No.                          Description                                                                                                                          User Memory
 1756-L71                          ControlLogix controller, 1 built-in USB port(1)                                                                                      2 MB
 1756-L72                                                                                                                                                               4 MB
 1756-L73                                                                                                                                                               8 MB
 1756-L74                                                                                                                                                               16 MB
 1756-L75                                                                                                                                                               32 MB
 1756-L73XT                        ControlLogix-XT controller, extreme environment                                                                                      8 MB
 1756-L71S                         GuardLogix safety controllers                                                                                                        2 MB standard
                                                                                                                                                                        1 MB safety
 1756-L72S                                                                                                                                                              4 MB standard
                                                                                                                                                                        2 MB safety
 1756-L73S                                                                                                                                                              8 MB standard
                                                                                                                                                                        4 MB safety
 1756-L7SP                         GuardLogix safety partner (one is required for each GuardLogix L7 controller)                                                        —
(1) The USB port is intended only for temporary local programming purposes and not intended for permanent connection. Do not use the USB port in hazardous locations.
For detailed specifications, see the 1756 ControlLogix Controllers Specifications Technical Data, publication 1756-TD001.
28                                                          Rockwell Automation Publication 1756-SG001S-EN-P - August 2014
                                                                                                             Select a ControlLogix System
Standard ControlLogix Controllers
The ControlLogix controller is part of the Logix5000 family of controllers. A ControlLogix system
includes the following:
    • The ControlLogix controller, available in different combinations of user memory
    • Studio 5000 environment
    • 1756 ControlLogix I/O modules that reside in a 1756 chassis
    • Separate communication modules for network communication
 Feature                                            1756-L71, 1756-L72, 1756-L73, 1756-L74, 1756-L75
 Controller tasks                                   • 32 tasks
                                                    • 100 programs/task
                                                    • Event tasks: all event triggers
 Built-in communication ports                       1 port USB Client
 Communication options                              •   EtherNet/IP
                                                    •   ControlNet
                                                    •   DeviceNet
                                                    •   Data Highway Plus
                                                    •   Remote I/O
                                                    •   SynchLink
                                                    •   Third-party process and device networks
 Built-in port                                      USB Client
 Controller connections supported, max              500
 Network connections, per network module            •   256 EtherNet/IP; 128 TCP (1756-EN2x, 1756-EN3x)
                                                    •   128 EtherNet/IP; 64 TCP (1756-ENBT)
                                                    •   128 ControlNet (1756-CN2/B, 1756-CN2R/B)
                                                    •   64 DeviceNet (1756-DNB)
 Controller redundancy                              Full support
 Integrated motion                                  • EtherNet/IP connection
                                                    • SERCOS interface
                                                    • Analog options (encoder input, LDT input, SSI input)
 Programming languages                              •   Relay ladder
                                                    •   Structured text
                                                    •   Function block
                                                    •   Sequential function chart (SFC)
         Allen-Bradley 1756-L71
                                           Rockwell Automation Publication 1756-SG001S-EN-P - August 2014                             29
Technical Data
1756 ControlLogix Power Supplies Specifications
Standard Chassis Catalog Numbers 1756-A4, 1756-A10, 1756-A13, 1756-A17
ControlLogix-XT Chassis Catalog Numbers 1756-A4LXT, 1756-A5XT, 1756-A7XLT, 1756-A7XT
Standard Power Supplies Catalog Numbers 1756-PA72, 1756-PA75, 1756-PB72, 1756-PB75, 1756-PC75, 1756-PH75
ControlLogix-XT Power Supplies Catalog Numbers 1756-PAXT, 1756-PBXT
Redundant Power Supplies Catalog Numbers 1756-PA75R, 1756-PB75R
Redundant Power Supplies Chassis Adapter Module Catalog Number 1756-PSCA2
ControlLogix-XT Redundant Power Supplies Catalog Numbers 1756-PAXTR, 1756-PBXTR
ControlLogix-XT Redundant Power Supplies Chassis Adapter Module Catalog Number 1756-PSCA2XT
Topic                                                   Page
Standard AC power supplies                              2
Standard DC Power Supplies                              5
1756 ControlLogix-XT Power Supplies                     8
Redundant Power Supplies                                11
ControlLogix® power supplies are used with the 1756 chassis to provide 1.2V, 3.3V, 5V, and 24V DC power directly to the
chassis backplane. Standard, ControlLogix-XT™, and redundant power supplies are available.
1756 ControlLogix Power Supplies Specifications
Summary of Changes
This manual contains new and updated information. Changes throughout this revision are marked by change bars, as
shown to the left of this paragraph.
    Topic                                                                                                       Page
    Added Technical Specifications, Environmental Specifications, and Certifications tables for of Tables for   15, 17
    ControlLogix-XT Redundant Power Supplies
    Updated the tables to include the ControlLogix-XT Redundant Power Supply Chassis Adapter                    17
The following components were added to this technical data:
  • ControlLogix-XT Redundant Power Supply (catalog number1756-PAXTR)
  • ControlLogix-XT Redundant Power Supply (catalog number 1756-PBXTR)
  • ControlLogix-XT Redundant Power Supply Chassis Adapter Module (catalog number1756-PSCA2XT)
  • Standard AC power supplies
Standard AC Power Supplies
1756-PA72 and 1756-PB75 Mounting Dimensions
                                                14.0
                                                (5.51)
                         11.2
                         (4.41)
                                                         42669
Dimensions are in cm (in.).
Table 1 - Technical Specifications - Standard AC Power Supplies
    Attribute                                                           1756-PA72/C                                              1756-PA75/B
                         (1)
    Input voltage range                                                 85…265V AC
    Input voltage, nom                                                  120V/240V AC
    Input frequency range                                               47…63 Hz
    Input power, max                                                    100VA/100 W
    Output power, max                                                   75 W @ 0…60 °C (32…140 °F)(3)
    Power consumption                                                   25 W @ 0…60 °C (32…140 °F)
    Power dissipation                                                   85.3 BTU/hr
2                                                                Rockwell Automation Publication 1756-TD005E-EN-E - April 2014
                                                                                                                                                       1756 ControlLogix Power Supplies Specifications
Table 1 - Technical Specifications - Standard AC Power Supplies
 Attribute                                                                 1756-PA72/C                                                      1756-PA75/B
 Hold-up time(2)                                                           5 cycles @ 85V AC, 50/60 Hz
                                                                           6 cycles @ 120V AC, 50/60 Hz
                                                                           6 cycles @ 200V AC, 50/60 Hz
                                                                           6 cycles @ 240V AC, 50/60 Hz
 Inrush current, max                                                       20 A
 Current capacity at 1.2V DC                                               1.5 A
 Current capacity at 3.3V DC                                               4A
 Current capacity at 5.1V DC                                               10 A                                                             13 A
 Current capacity at 24V DC                                                2.8 A
 Overcurrent protection, max                                               User-supplied 15 A(4)
 Fusing                                                                    Non-replaceable fuse is soldered in place(5)
 Transformer load, max                                                     100VA
 Isolation voltage                                                         250V (continuous), reinforced insulation type
                                                                           Type tested @ 3500V DC for 60 s, power input-to-backplaneapprox
 Weight, approx                                                            0.95 kg (2.10 lb)
 Dimensions                                                                14.0 x 11.2 x 14.5 cm (5.51 x 4.41 x 5.71 in.)
 Module location                                                           Left side of 1756 chassis
 Chassis                                                                   1756-A4, 1756-A7, 1756-A10, 1756-A13, 1756-A17
 Chassis compatibility                                                     Series A                                                         Series B
                                                                           Series B
 Wire size                                                                 2.5 mm2 (14 AWG) solid or stranded copper wire rated at
                                                                           90 °C (194 °F), or greater, 1.2 mm (3/64 in.) insulation max
 Wire category                                                             1 - on power ports(6)
 Conductor screw torque                                                    0.8 N•m (7 lb•in)
 North American temperature code                                           T4
 Enclosure type rating                                                     None (open-style)
(1)   UL certification for 120/240V AC, 50/60 Hz nominal. Rockwell Automation specified 85…265V AC, 47…63 Hz.
(2)   The hold-up time is the time between input voltage removal and DC power failure.
(3)   The combination of all output power (5.1V backplane, 24V backplane, 3.3V backplane, and 1.2V backplane) cannot exceed 75 W.
(4)   Use time-delay type overcurrent protection in all ungrounded conductors.
(5)   This fuse is intended to guard against fire hazard due to short circuit conditions.
(6)   Use this conductor category information for planning conductor routing as described in the system level installation manual. See the Industrial Automation Wiring and Grounding Guidelines,
      publication 1770-4.1.
Table 2 - Environmental Specifications - Standard AC Power Supplies
 Attribute                                                                1756-PA72/C, 1756-PA75/B
 Temperature, operating                                                   0…60 °C (32…140 °F)
 IEC 60068-2-1 (Test Ad, Operating Cold),
 IEC 60068-2-2 (Test Bd, Operating Dry Heat),
 IEC 60068-2-14 (Test Nb, Operating Thermal Shock)
 Temperature, surrounding air, max                                        60 °C (140 °F)
 Temperature, non-operating                                               -40…85 °C (-40…185 °F)
 IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold),
 IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat),
 IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock)
 Relative humidity                                                        5…95% noncondensing
 IEC 60068-2-30 (Test Db, Unpackaged Damp Heat)
 Vibration                                                                2 g @ 10…500 Hz
 IEC 60068-2-6 (Test Fc, Operating)
 Shock, operating                                                         30 g
 IEC 60068-2-27 (Test Ea, Unpackaged Shock)
                                                                  Rockwell Automation Publication 1756-TD005E-EN-E - April 2014                                                                     3
1756 ControlLogix Power Supplies Specifications
Table 2 - Environmental Specifications - Standard AC Power Supplies
    Attribute                                                              1756-PA72/C, 1756-PA75/B
    Shock, nonoperating                                                    50 g
    IEC 60068-2-27 (Test Ea, Unpackaged Shock)
    Emissions                                                              Class A
    CISPR 11 (IEC 61000-6-4)
    ESD immunity                                                           6 kV contact discharges
    IEC 61000-4-2                                                          8 kV air discharges
    Radiated RF immunity                                                   10V/m with 1 kHz sine-wave 80% AM from 80…2000 MHz
    IEC 61000-4-3                                                          10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz
                                                                           10V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz
                                                                           3V/m with 1kHz sine-wave 80% AM from 2000…2700 MHz
    EFT/B immunity                                                         ±4 kV at 5 kHz on power ports
    IEC 61000-4-4
    Surge transient immunity                                               ±1 kV line-line (DM) and ±2 kV line-earth (CM) on power ports
    IEC 61000-4-5
    Conducted RF immunity                                                  10V rms with 1 kHz sine-wave 80% AM from 150 kHz…80 MHz
    IEC 61000-4-6
    Oscillatory surge withstand                                            3 kV
    IEEE C37.90.1
    Voltage variation                                                      30% dips for 1 period at 0° and 180° on AC supply ports
    IEC 61000-4-11                                                         60% dips for 5 and 50 periods on AC supply ports
                                                                           ±10% fluctuations for 15 min on AC supply ports
                                                                           >95% interruptions for 250 periods on AC supply ports
Table 3 - Certifications - Standard AC Power Supplies
    Certification(1)                                                       1756-PA72/C, 1756-PA75/B
    UL                                                                     UL Listed Industrial Control Equipment. See UL File E65584.
    CSA                                                                    CSA Certified Process Control Equipment. See CSA File LR54689C.
                                                                           CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous Locations. See CSA File LR69960C.
    FM                                                                     FM Approved Equipment for use in Class I Division 2 Group A,B,C,D Hazardous Locations
    CE                                                                     European Union 2004/108/EC EMC Directive, compliant with:
                                                                           • EN 61326-1; Meas./Control/Lab., Industrial Requirements
                                                                           • EN 61000-6-2; Industrial Immunity
                                                                           • EN 61000-6-4; Industrial Emissions
                                                                           • EN 61131-2; Programmable Controllers (Clause 8, Zone A & B)
                                                                           European Union 2006/95/EC LVD, compliant with:
                                                                           • EN 61131-2; Programmable Controllers (Clause 11)
    C-Tick                                                                 Australian Radiocommunications Act, compliant with:
                                                                           • AS/NZS CISPR 11; Industrial Emissions
    KC                                                                     Korean Registration of Broadcasting and Communications Equipment, compliant with:
                                                                           • Article 58-2 of Radio Waves Act, Clause 3
(1) When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.
4                                                                 Rockwell Automation Publication 1756-TD005E-EN-E - April 2014
                                                                                                                                     1756 ControlLogix Power Supplies Specifications
Standard DC Power Supplies
1756-PB72, 1756-PB75, 1756-PC75, and 1756-PH75 Mounting Dimensions
                                   14.0
                                   (5.51)
                     11.2
                     (4.41)
                                            42669
Dimensions are in cm (in.).
Table 4 - Technical Specifications - Standard DC Power Supplies
 Attribute                                                 1756-PB72/C                             1756-PB75/B                1756-PC75/B                 1756-PH75/B
 Input voltage range                                       18…32V DC(2)                                                       30…60V DC(7)                90…143V DC(8)
 Input voltage, nom                                        24V DC                                                             48V DC                      125V DC
 Input power, max                                          95 W
 Output power, max                                         75 W @ 0…60 °C (32…140 °F)(3)
 Power consumption                                         20 W @ 0…60 °C (32…140 °F)
 Power dissipation                                         68.2 BTU/hr
              (1)
 Hold-up time                                              35 ms @ 18V DC                                                     50 ms @ 30…60V DC nom       50 ms @ 90…143V DC nom
                                                           40 ms @ 24V DC
                                                           40 ms @ 32V DC
 Inrush current, max                                       30 A                                                               20 A
 Current capacity at 1.2V                                  1.5 A
 Current capacity at 3.3V                                  4A
 Current capacity at 5.1V                                  10 A                                    13 A
 Current capacity at 24V                                   2.8 A
 Overcurrent protection, max                               User-supplied 15 A(4)
 Fusing                                                    Non-replaceable fuse is soldered in place(5)
 Isolation voltage                                         250V (continuous), reinforced insulation type, power input-to-backplane
                                                           Type tested @ 3500V DC for 60 s
 Weight, approx                                            0.95 kg (2.10 lb)
 Dimensions                                                14.0 x 11.2 x 14.5 cm (5.51 x 4.41 x 5.71 in.)
 Module location                                           Left side of 1756 chassis
 Chassis                                                   1756-A4, 1756-A7, 1756-A10, 1756-A13, 1756-A17
 Chassis compatibility                                     Series A                                Series B
                                                           Series B
 Wire size                                                 2.5 mm2 (14 AWG) solid or stranded copper wire rated at
                                                           90 °C (194 °F), or greater, 1.2 mm (3/64 in.) insulation max
 Wire category                                             1 - on power ports(6)
                                                    Rockwell Automation Publication 1756-TD005E-EN-E - April 2014                                                                 5
1756 ControlLogix Power Supplies Specifications
Table 4 - Technical Specifications - Standard DC Power Supplies
    Attribute                                                             1756-PB72/C                          1756-PB75/B                    1756-PC75/B                    1756-PH75/B
    Conductor screw torque                                                0.8 N•m (7 lb•in)
    North American temperature code                                       T4
    IEC temperature code                                                  T4                                                                  N/A
    Enclosure type rating                                                 None (open-style)
(1) The hold-up time is the time between input voltage removal and DC power failure.
(2) UL certification for 24V DC nominal. Rockwell Automation specified 18…32V DC.
(3) The combination of all output power (5.1V backplane, 24V backplane, 3.3V backplane, and 1.2V backplane) cannot exceed 75 W.
(4) Use time-delay type overcurrent protection in all ungrounded conductors.
(5) This fuse is intended to guard against fire hazard due to short circuit conditions.
(6) Use this conductor category information for planning conductor routing as described in the system level installation manual. See the Industrial Automation Wiring and Grounding Guidelines,
    publication 1770-4.1.
(7) UL Certification for 48V DC nominal. Rockwell Automation specified 30…60V DC.
(8) UL certification for 125V DC nominal. Rockwell Automation specified 90…143V DC.
Table 5 - Environmental Specifications - Standard DC Power Supplies
    Attribute                                                            1756-PB72/C, 1756-PB75/B                                          1756-PC75/B, 1756-PH75/B
    Temperature, operating                                               0…60 °C (32…140 °F)
    IEC 60068-2-1 (Test Ad, Operating Cold),
    IEC 60068-2-2 (Test Bd, Operating Dry Heat),
    IEC 60068-2-14 (Test Nb, Operating Thermal Shock)
    Temperature, surrounding air, max                                    60 °C (140 °F)
    Temperature, nonoperating                                            -40…85 °C (-40…185 °F)
    IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold),
    IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat),
    IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock)
    Relative humidity                                                    5…95% noncondensing
    IEC 60068-2-30 (Test Db, Unpackaged Damp Heat)
    Vibration                                                            2 g @ 10…500 Hz
    IEC 60068-2-6 (Test Fc, Operating)
    Shock, operating                                                     30 g
    IEC 60068-2-27 (Test Ea, Unpackaged Shock)
    Shock, nonoperating                                                  50 g
    IEC 60068-2-27 (Test Ea, Unpackaged Shock)
    Emissions                                                            Class A
    CISPR 11 (IEC 61000-6-4)
    ESD immunity                                                         6 kV contact discharges
    IEC 61000-4-2                                                        8 kV air discharges
    Radiated RF immunity                                                 10V/m with 1 kHz sine-wave 80% AM from 80…2000 MHz
    IEC 61000-4-3                                                        10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz
                                                                         10V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz
                                                                         3V/m with 1 kHz sine-wave 80% AM from 2000…2700 MHz
    EFT/B immunity                                                       ±4 kV at 5 kHz on power ports
    IEC 61000-4-4
    Surge transient immunity                                             ±1 kV line-line (DM) and ±2 kV line-earth (CM) on power ports
    IEC 61000-4-5
    Conducted RF immunity                                                10V rms with 1 kHz sine-wave 80% AM from 150 kHz…80 MHz
    IEC 61000-4-6
    Oscillatory surge withstand                                          N/A                                                               3 kV
    IEEE C37.90.1
    Voltage variation                                                    60% dips for 100 ms on DC supply ports
    IEC 61000-4-29                                                       100% dips for 50 ms on DC supply ports
                                                                         ±20% fluctuations for 15 min on DC supply ports
                                                                         5 s interruptions on DC supply ports
                                                                         10 ms interruption on DC supply ports
6                                                                Rockwell Automation Publication 1756-TD005E-EN-E - April 2014
                                                                                                                                                          1756 ControlLogix Power Supplies Specifications
Table 6 - Certifications - Standard DC Power Supplies
 Certification(1)                                                          1756-PB72/C, 1756-PB75/B                                           1756-PC75/B, 1756-PH75/B
 UL                                                                        N/A                                                                UL Listed Industrial Control Equipment. See UL File E65584.
 c-UL-us                                                                   UL Listed Industrial Control Equipment, certified for US and       N/A
                                                                           Canada. See UL File E65584.
                                                                           UL Listed for Class I, Division 2 Group A,B,C,D Hazardous
                                                                           Locations, certified for US and Canada. See UL File E194810.
 CSA                                                                       CSA Certified Process Control Equipment. See CSA File LR54689C.
                                                                           CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous Locations. See CSA File LR69960C.
 FM                                                                        FM Approved Equipment for use in Class I Division 2 Group          N/A
                                                                           A,B,C,D Hazardous Locations
 CE                                                                        European Union 2004/108/EC EMC Directive, compliant with:
                                                                           • EN 61326-1; Meas./Control/Lab., Industrial Requirements
                                                                           • EN 61000-6-2; Industrial Immunity
                                                                           • EN 61000-6-4; Industrial Emissions
                                                                           • EN 61131-2; Programmable Controllers (Clause 8, Zone A & B)
                                                                           European Union 2006/95/EC LVD, compliant with:
                                                                           • EN 61131-2; Programmable Controllers (Clause 11)
 C-Tick                                                                    Australian Radiocommunications Act, compliant with:
                                                                           • AS/NZS CISPR 11; Industrial Emissions
 Ex                                                                        European Union 94/9/EC ATEX Directive, compliant with:             N/A
                                                                           • EN 60079-15; Potentially Explosive Atmospheres,
                                                                              Protection "n"
                                                                           • EN 60079-0; General Requirements
                                                                           • II 3 G Ex nA IIC T4 Gc X
 KC                                                                        Korean Registration of Broadcasting and Communications Equipment, compliant with:
                                                                           • Article 58-2 of Radio Waves Act, Clause 3
(1) When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.
                                                                  Rockwell Automation Publication 1756-TD005E-EN-E - April 2014                                                                             7
1756 ControlLogix Power Supplies Specifications
1756 ControlLogix-XT Power Supplies
The ControlLogix-XT products include control and communication system components that, when used with
FLEX I/O-XT™ products, provide a complete control system solution that you can use in environments where
temperatures range from -20…70 °C (-4…158 °F).
When used independently, the ControlLogix-XT system can withstand environments where the temperature ranges
from -25…70 °C (-13…158 °F).
1756-PAXT and 1756-PBXT Mounting Dimensions
                                          14.0
                                          (5.51)
                        11.2
                        (4.41)
                                                   42669
Dimensions are in cm (in.).
Table 7 - Technical Specifications - ControlLogix-XT Power Supplies
    Attribute                                                     1756-PAXT                                                       1756-PBXT
                                                                                (2)
    Input voltage range                                           85…265V AC                                                      18…32V DC
    Input voltage, nom                                            120/240V AC                                                     24V DC
    Input frequency range                                         47…63 Hz                                                        N/A
    Input power, max                                              82VA 64 W                                                       54 W
    Output power, max                                             42 W @ -25…70 °C (-13…158 °F)
    Power consumption                                             22 W                                                            12 W
    Power dissipation                                             75.1 BTU/hr                                                     40.9 BTU/hr
                 (1)
    Hold-up time                                                  6 cycles @ 85V AV, 50/60 Hz                                     35 ms @ 18V DC
                                                                  6 cycles @ 120V AV, 50/60 Hz                                    40 ms @ 24V DC
                                                                  6 cycles @ 200V AV, 50/60 Hz                                    40 ms @ 32V DC
                                                                  6 cycles @ 240V AV, 50/60 Hz
    Inrush current, max                                           20 A                                                            30 A
    Current capacity at 1.2V                                      1.5 A
    Current capacity at 3.3V                                      4A
    Current capacity at 5.1V                                      8A
    Current capacity at 24V                                       1.75 A
    Overcurrent protection, max                                   User-supplied 15 A(3)
    Fusing                                                        Non-replaceable fuse is soldered in place(4)
    Isolation voltage                                             250V (continuous), reinforced insulation type, power input-to-backplane
                                                                  Type tested @ 3260V DC for 60 s
8                                                          Rockwell Automation Publication 1756-TD005E-EN-E - April 2014
                                                                                                                                                       1756 ControlLogix Power Supplies Specifications
Table 7 - Technical Specifications - ControlLogix-XT Power Supplies
 Attribute                                                                1756-PAXT                                                          1756-PBXT
 Weight, approx                                                           0.95 kg (2.10 lb)
 Dimensions                                                               14.0 x 11.2 x 14.5 cm (5.51 x 4.41 x 5.71 in.)
 Module location                                                          Left side of 1756 chassis
 Chassis                                                                  1756-A4LXT, 1756-A5XT, 1756-A7LXT, 1756-A7XT
 Wire size                                                                2.5 mm2 (14 AWG) solid or stranded copper wire rated at 90 °C (194 °F), or greater,
                                                                          1.2 mm (3/64 in.) insulation max
 Wire category                                                            1 - on power ports(5)
 Conductor screw torque                                                   0.8 N•m (7 lb•in)
 North American temperature code                                          T4                                                                 T4A
 IEC temperature code                                                     T4
 Enclosure type rating                                                    None (open-style)
(1)   The hold-up time is the time between input voltage removal and DC power failure.
(2)   UL certification for 120/240V AC, 50/60 Hz nominal. Rockwell Automation specified 85…265V AC, 47…63 Hz.
(3)   Use time-delay type overcurrent protection in all ungrounded conductors.
(4)   This fuse is intended to guard against fire hazard due to short circuit conditions.
(5)   Use this conductor category information for planning conductor routing as described in the system level installation manual. See the Industrial Automation Wiring and Grounding Guidelines,
      publication 1770-4.1.
Table 8 - Environmental Specifications - ControlLogix-XTPower Supplies
 Attribute                                                                 1756-PAXT                                                         1756-PBXT
 Temperature, operating                                                    -25…70 °C (-13…158 °F)
 IEC 60068-2-1 (Test Ad, Operating Cold),
 IEC 60068-2-2 (Test Bd, Operating Dry Heat),
 IEC 60068-2-14 (Test Nb, Operating Thermal Shock)
 Temperature, surrounding air, max                                         70 °C 158 °F)
 Temperature, nonoperating                                                 -40…85 °C (-40…185 °F)
 IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold),
 IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat),
 IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock)
 Relative humidity                                                         5…95% noncondensing
 IEC 60068-2-30 (Test Db, Unpackaged Damp Heat)
 Vibration                                                                 2 g @ 10…500 Hz
 IEC 60068-2-6 (Test Fc, Operating)
 Shock, operating                                                          30 g
 IEC 60068-2-27 (Test Ea, Unpackaged Shock)
 Shock, nonoperating                                                       50 g
 IEC 60068-2-27 (Test Ea, Unpackaged Shock)
 Emissions                                                                 Class A
 CISPR 11 (IEC 61000-6-4)
 ESD immunity                                                              6 kV contact discharges
 IEC 61000-4-2                                                             8 kV air discharges
 Radiated RF immunity                                                      10V/m with 1 kHz sine-wave 80% AM from 80…2000 MHz
 IEC 61000-4-3                                                             10V/m with 200 Hz 50% Pulse 100% AM at 900 MHz
                                                                           10V/m with 200 Hz 50% Pulse 100% AM at 1890 MHz
                                                                           3V/m with 1 kHz sine-wave 80% AM from 2000…2700 MHz
 EFT/B immunity                                                            ±4 kV at 5 kHz on power ports
 IEC 61000-4-4
 Surge transient immunity                                                  ±1 kV line-line (DM) and ±2 kV line-earth (CM) on power ports
 IEC 61000-4-5
 Conducted RF immunity                                                     10V rms with 1 kHz sine-wave 80% AM from 150 kHz…80 MHz
 IEC 61000-4-6
                                                                  Rockwell Automation Publication 1756-TD005E-EN-E - April 2014                                                                     9
1756 ControlLogix Power Supplies Specifications
Table 8 - Environmental Specifications - ControlLogix-XTPower Supplies
 Attribute                                                                  1756-PAXT                                                          1756-PBXT
 Oscillatory surge withstand                                                3 kV                                                               N/A
 IEEE C37.90.1
 Voltage variation                                                          30% dips for 1 period at 0° and 180° on AC supply ports            N/A
 IEC 61000-4-11                                                             60% dips for 5 and 50 periods on AC supply ports
                                                                            ±10% fluctuations for 15 min on AC supply ports
                                                                            >95% interruptions for 250 periods on AC supply ports
 Voltage variation                                                          N/A                                                                60% dips for 100 ms on DC supply ports
 IEC 61000-4-29                                                                                                                                100% dips for 50 ms on DC supply ports
                                                                                                                                               ±20% fluctuations for 15 min on DC supply ports
                                                                                                                                               5 s interruptions on DC supply ports
                                                                                                                                               10 ms interruption on DC supply ports
Table 9 - Certifications - ControlLogix-XPowerT Supplies
 Certification(1)                                                          1756-PAXT, 1756-PBXT
 c-UL-us                                                                   UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584.
                                                                           UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations, certified for US and Canada. See UL File E194810.
 CE                                                                        European Union 2004/108/EC EMC Directive, compliant with:
                                                                           • EN 61326-1; Meas./Control/Lab., Industrial Requirements
                                                                           • EN 61000-6-2; Industrial Immunity
                                                                           • EN 61000-6-4; Industrial Emissions
                                                                           • EN 61131-2; Programmable Controllers (Clause 8, Zone A & B)
                                                                           European Union 2006/95/EC LVD, compliant with:
                                                                           • EN 61131-2; Programmable Controllers (Clause 11)
 C-Tick                                                                    Australian Radiocommunications Act, compliant with:
                                                                           • AS/NZS CISPR 11; Industrial Emissions
 Ex                                                                        European Union 94/9/EC ATEX Directive, compliant with:
                                                                           • EN 60079-15; Potentially Explosive Atmospheres, Protection "n"
                                                                           • EN 60079-0; General Requirements
                                                                           • II 3 G Ex nA IIC T4 Gc X
 KC                                                                        Korean Registration of Broadcasting and Communications Equipment, compliant with:
                                                                           • Article 58-2 of Radio Waves Act, Clause 3
(1) When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.
10                                                                Rockwell Automation Publication 1756-TD005E-EN-E - April 2014
                                                                                                                                             1756 ControlLogix Power Supplies Specifications
Redundant Power Supplies
To build a redundant power supply system, you need the following.
 Cat. No.                                           Description                                                                 Amount
 1756-PA75R/A , 1756-PAXTR,                         Redundant power supply                                                      2
 1756-PB75R/A, or 1756-PBXTR
 1756-CPR2(1)                                       Redundant power supply cable (Length = 0.9 1m [3 ft])                       2
                                                                                                        (2)
 1756-PSCA2 or 1756-PSCA2XT                         Redundant power supply chassis adapter module                               1
                                                                        (3)
 User-supplied                                      Annunciator wiring (Max. length = 10 m [32.8 ft])                           2
(1) Cable bend radius is 12.7 cm (5.0 in.).
(2) The 1756-PSCA2 or 1756-PSCA-2XT chassis adapter module is a passive device that funnels power from the redundant power supplies to the
    single power connector on the ControlLogix series B chassis backplane.
(3) Optional user-provided annunciator wiring can be connected to the solid-state relay for status and troubleshooting purposes.
                                                               Rockwell Automation Publication 1756-TD005E-EN-E - April 2014                                                             11
1756 ControlLogix Power Supplies Specifications
System Configuration Recommendations
We recommend that you use one of these methods to configure your redundant power supply system.
               Recommended Configurations for a System That Uses One Chassis
                                      42655                                                        42657
              Recommended Configurations for a System That Uses Two Chassis
                                              42658                                              42655
12                                                     Rockwell Automation Publication 1756-TD005E-EN-E - April 2014
                                                                                                                                   1756 ControlLogix Power Supplies Specifications
1756-PA75R, 1756-PAXTR, 1756-PB75R, and 1756-PBXTR Mounting Dimensions
                            7.0
                            (2.76)
                                                                            Top Mounting                         Bottom Mounting
                                                                            Hole Diameter                         Hole Diameter
                                                                                                       0.55
                                                                                                       (0.217)
                                                                                                       1.1
                                                                                                       (0.433)
  15.8                                 17.5                                                                                     45829
  (6.22)                               (6.88)
                            14.4
                                                42668
                            (5.66)
Dimensions are in cm (in.).
Redundant Power Supply Features
The redundant power supplies offer the same features as the standard power supplies, in addition to the following:
  • Automatic chassis load sharing between the redundant power supplies
  • Status indicators for visual operating status of the pair
  • Solid-state relay for system recognition of supply status when wired to an input module
Table 10 - Technical Specifications - ControlLogix Redundant Power Supplies
 Attribute                                              1756-PA75R                                                      1756-PB75R
                                                                      (1)
 Input voltage range                                    85…265V AC                                                      18…32V DC(2)
 Input voltage                                          120V/240V AC, 50/60 Hz                                          24V DC
 Input frequency range                                  47…63 Hz                                                        DC
 Input power, max                                       120VA 115 W                                                     110 W
 Output power, max                                      75 W @ 0…60 °C (32…140 °F)
              (3)
 Hold-up time                                           2 cycles @ 60 Hz                                                20 ms
                                                        2 cycles @ 50 Hz
 Inrush current, max                                    20 A                                                            30 A
 Current capacity at 1.2V                               1.5 A
 Current capacity at 3.3V                               4A
 Current capacity at 5.1V                               13 A
 Current capacity at 24V                                2.8 A
 Annunciator power                                      240V AC 50/60 Hz, 240V DC, 50 mA, resistive only
 Overcurrent protection, max                            User-supplied 15 A(4)
 Fusing                                                 Non-replaceable fuse is soldered in place(5)
 Isolation voltage                                      250V (continuous), Reinforced Insulation Type, Power Input to Backplane, Power Input to Annunciator, Annunciator to Backplane
                                                        Type tested at 3250V DC for 60 s
                                                Rockwell Automation Publication 1756-TD005E-EN-E - April 2014                                                                           13
1756 ControlLogix Power Supplies Specifications
Table 10 - Technical Specifications - ControlLogix Redundant Power Supplies
 Attribute                                                                1756-PA75R                                                       1756-PB75R
 Dimensions (HxWxD), approx                                               17.5 x 14.5 x 13.7 cm (6.9 x 5.7 x 5.4 in.)
 Weight, approx                                                           1.45 kg (3.2 lb)
 Chassis                                                                  1756-A4, 1756-A7, 1756-A10, 1756-A13, 1756-A17
 Wire size                                                                Power - 2.5 mm2 (14 AWG) solid or stranded copper wire rated at 90 °C (194 °F), or greater, 1.2 mm (3/64 in.) insulation max
                                                                          Annunciator - 0.25…2.5 mm2 (22…14 AWG) solid or stranded copper wire rated at 90 °C (194 °F), or greater, 1.2 mm (3/64 in.)
                                                                          insulation max
 Wire category (6)                                                        3 - on annunciator ports
                                                                          1 - on power ports
                                                                          3 - on 1756-CPR2 connections
 Pilot duty rating                                                        Annunciator - not rated
 Conductor screw torque                                                   0.79 N•m (7 lb•in)
 Solid-state relay contact                                                240V AC/DC(7)
 North American temperature code                                          T3C                                                              T4
 IEC temperature code                                                     T3                                                               T4
 Enclosure type rating                                                    None (open-style)
(1)   UL certification for 120/240V AC, 50/60 Hz nominal. Rockwell Automation specified 85…265V AC, 47…63 Hz.
(2)   UL certification for 24V DC nominal. Rockwell Automation specified 18…32V DC.
(3)   The hold-up time is the time between input voltage removal and DC power failure.
(4)   Use time-delay type overcurrent protection in all ungrounded conductors.
(5)   This fuse is intended to guard against fire hazard due to short circuit conditions.
(6)   Use this conductor category information for planning conductor routing. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.
(7)   Do not exceed 50 mA; resistive only.
Table 11 - Environmental Specifications - Redundant Power Supplies
 Attribute                                                                 1756-PA75R                                                       1756-PB75R
 Temperature, operating                                                    0…60 °C (32…140 °F)
 IEC 60068-2-1 (Test Ad, Operating Cold),
 IEC 60068-2-2 (Test Bd, Operating Dry Heat),
 IEC 60068-2-14 (Test Nb, Operating Thermal Shock)
 Temperature, surrounding air, max                                         60 °C 140 °F)
 Temperature, nonoperating                                                 -40…85 °C (-40…185 °F)
 IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold),
 IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat),
 IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock)
 Relative humidity                                                         5…95% noncondensing
 IEC 60068-2-30 (Test Db, Unpackaged Damp Heat)
 Vibration                                                                 2 g @ 10…500 Hz
 IEC 60068-2-6 (Test Fc, Operating)
 Shock, operating                                                          30 g
 IEC 60068-2-27 (Test Ea, Unpackaged Shock)
 Shock, nonoperating                                                       50 g
 IEC 60068-2-27 (Test Ea, Unpackaged Shock)
 Emissions                                                                 Class A
 CISPR 11 (IEC 61000-6-4)
 ESD immunity                                                              6 kV contact discharges
 IEC 61000-4-2                                                             8 kV air discharges
 Radiated RF immunity                                                      10V/m with 1 kHz sine-wave 80% AM from 80…2000 MHz
 IEC 61000-4-3                                                             10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz
                                                                           10V/m with 200 Hz 50% Pulse 100% AM at 1890 MHz
                                                                           3V/m with 1 kHz sine-wave 80% AM from 2000…2700 MHz
 EFT/B immunity                                                            ±4 kV at 5 kHz on power ports
 IEC 61000-4-4                                                             ±4 kV at 5 kHz on annunciator ports
14                                                               Rockwell Automation Publication 1756-TD005E-EN-E - April 2014
                                                                                                                                                          1756 ControlLogix Power Supplies Specifications
Table 11 - Environmental Specifications - Redundant Power Supplies
 Attribute                                                                  1756-PA75R                                                          1756-PB75R
 Surge transient immunity                                                   ±1 kV line-line (DM) and ±2 kV line-earth (CM) on power ports
 IEC 61000-4-5
 Conducted RF immunity                                                      15V rms with 1 kHz sine-wave 80% AM from 150 kHz…80 MHz
 IEC 61000-4-6
 Voltage variation                                                          30% dips for 1 period at 0° and 180° on AC supply ports             N/A
 IEC 61000-4-11                                                             60% dips for 5 and 50 periods on AC supply ports
                                                                            ±10% fluctuations for 15 min on AC supply ports
                                                                            >95% interruptions for 250 periods on AC supply ports
 Voltage variation                                                          N/A                                                                 10 ms interruption on DC supply ports
 IEC 61000-4-29                                                                                                                                 60% dips for 100 ms on DC supply ports
                                                                                                                                                100% dips for 50 ms on DC supply ports
                                                                                                                                                ±20% fluctuations for 15 min on DC supply ports
                                                                                                                                                5 s interruptions on DC supply ports
Table 12 - Certifications - Redundant Power Supplies
 Certification(1)                                                           1756-PA75R                                                         1756-PB75R
 c-UL-us                                                                    UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584.
                                                                            UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations, certified for U.S. and Canada. See UL File E194810.
 CSA                                                                        CSA Certified Process Control Equipment. See CSA File LR54689C.
                                                                            CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous Locations. See CSA File LR69960C.
 FM                                                                         FM Approved Equipment for use in Class I Division 2 Group A,B,C,D Hazardous Locations
 CE                                                                         European Union 2004/108/EC EMC Directive, compliant with:
                                                                            • EN 61326-1; Meas./Control/Lab., Industrial Requirements
                                                                            • EN 61000-6-2; Industrial Immunity
                                                                            • EN 61000-6-4; Industrial Emissions
                                                                            • EN 61131-2; Programmable Controllers (Clause 8, Zone A & B)
                                                                            European Union 2006/95/EC LVD, compliant with:
                                                                            • EN 61131-2; Programmable Controllers (Clause 11)
 RCM                                                                        Australian Radiocommunications Act, compliant with:
                                                                            • EN 61000-6-4; Industrial Emissions
 Ex                                                                         European Union 94/9/EC ATEX Directive, compliant with:
                                                                            • EN 60079-15; Potentially Explosive Atmospheres, Protection "n"
                                                                            • EN 60079-0; General Requirements
                                                                            • II 3 G Ex nA IIC T4 Gc
 KC                                                                         Korean Registration of Broadcasting and Communications Equipment, compliant with:
                                                                            • Article 58-2 of Radio Waves Act, Clause 3
(1) When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.
Table 13 - Technical Specifications - ControlLogix-XT Redundant Power Supplies
 Attribute                                                                 1756-PAXTR                                                          1756-PBXTR
                                                                                         (1)
 Input voltage range                                                       85…265V AC                                                          18…32V DC
 Input voltage                                                             120V/240V AC                                                        24V DC
 Input frequency range                                                     47…63 Hz                                                            DC
 Input power, max                                                          75VA 65 W                                                           75W
 Output power, max                                                         42 W @ 0…60 °C (32…140 °F)
               (2)
 Hold-up time                                                              2 cycles @ 60 Hz                                                    20 ms
                                                                           2 cycles @ 50 Hz
 Inrush current, max                                                       20 A                                                                30 A
 Current capacity at 1.2V                                                  1.5 A
 Current capacity at 3.3V                                                  4A
 Current capacity at 5.1V                                                  8A
                                                                  Rockwell Automation Publication 1756-TD005E-EN-E - April 2014                                                                         15
1756 ControlLogix Power Supplies Specifications
Table 13 - Technical Specifications - ControlLogix-XT Redundant Power Supplies
 Attribute                                                                1756-PAXTR                                                       1756-PBXTR
 Current capacity at 24V                                                  1.75 A
 Annunciator power                                                        240V AC 50/60 Hz, 240V DC, 50 mA, resistive only
 Overcurrent protection, max                                              User-supplied 15 A(3)
 Fusing                                                                   Non-replaceable fuse is soldered in place(4)
 Isolation voltage                                                        250V (continuous), Reinforced Insulation Type, Power Input to Backplane, Power Input to Annunciator, Annunciator to Backplane
                                                                          Type tested at 3250V DC for 60 s
 Dimensions (HxWxD), approx                                               17.5 x 14.5 x 13.7 cm (6.9 x 5.7 x 5.4 in.)
 Weight, approx                                                           1.45 kg (3.2 lb)
 Chassis                                                                  1756-A4, 1756-A7, 1756-A10, 1756-A13, 1756-A17
 Wire size                                                                Power - 2.5 mm2 (14 AWG) solid or stranded copper wire rated at 90 °C (194 °F), or greater, 1.2 mm (3/64 in.) insulation max
                                                                          Annunciator - 0.25…2.5 mm2 (22…14 AWG) solid or stranded copper wire rated at 90 °C (194 °F), or greater, 1.2 mm (3/64 in.)
                                                                          insulation max
 Wire category (5)                                                        1 - on power ports
                                                                          3 - on annunciator ports
                                                                          3 - on 1756-CPR2 connections
 Pilot duty rating                                                        Annunciator - not rated
 Conductor screw torque                                                   0.79 N•m (7 lb•in)
 Solid-state relay contact                                                240V AC/DC(6)
 North American temperature code                                          T4A
 IEC temperature code                                                     T4
 Enclosure type rating                                                    None (open-style)
(1)   UL certification for 120/240V AC, 50/60 Hz nominal. Rockwell Automation specified 85…265V AC, 47…63 Hz.
(2)   The hold-up time is the time between input voltage removal and DC power failure.
(3)   Use time-delay type overcurrent protection in all ungrounded conductors.
(4)   This fuse is intended to guard against fire hazard due to short circuit conditions.
(5)   Use this conductor category information for planning conductor routing. See Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.
(6)   Do not exceed 50 mA; resistive only.
Table 14 - Environmental Specifications - XT Redundant Power Supplies
 Attribute                                                                 1756-PAXTR                                                      1756-PBXTR
 Temperature, operating                                                    -25…70 °C (13…158 °F)
 IEC 60068-2-1 (Test Ad, Operating Cold),
 IEC 60068-2-2 (Test Bd, Operating Dry Heat),
 IEC 60068-2-14 (Test Nb, Operating Thermal Shock)
 Temperature, surrounding air, max                                         70 °C (158 °F)
 Temperature, nonoperating                                                 -40…85 °C (-40…185 °F)
 IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold),
 IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat),
 IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock)
 Relative humidity                                                         5…95% noncondensing
 IEC 60068-2-30 (Test Db, Unpackaged Damp Heat)
 Vibration                                                                 2 g @ 10…500 Hz
 IEC 60068-2-6 (Test Fc, Operating)
 Shock, operating                                                          30 g
 IEC 60068-2-27 (Test Ea, Unpackaged Shock)
 Shock, nonoperating                                                       50 g
 IEC 60068-2-27 (Test Ea, Unpackaged Shock)
 Emissions                                                                 Class A
 CISPR 11 (IEC 61000-6-4)
 ESD immunity                                                              6 kV contact discharges
 IEC 61000-4-2                                                             8 kV air discharges
16                                                               Rockwell Automation Publication 1756-TD005E-EN-E - April 2014
                                                                                                                                                          1756 ControlLogix Power Supplies Specifications
Table 14 - Environmental Specifications - XT Redundant Power Supplies
 Attribute                                                                  1756-PAXTR                                                          1756-PBXTR
 Radiated RF immunity                                                       10V/m with 1 kHz sine-wave 80% AM from 80…1000 MHz
 IEC 61000-4-3                                                              10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz
                                                                            10V/m with 200 Hz 50% Pulse 100% AM at 1890 MHz
                                                                            3V/m with 1 kHz sine-wave 80% AM from 2000…2700 MHz
 EFT/B immunity                                                             ±4 kV at 5 kHz on power ports
 IEC 61000-4-4                                                              ±4 kV at 5 kHz on annunciator ports
 Surge transient immunity                                                   ±1 kV line-line (DM) and ±2 kV line-earth (CM) on power ports
 IEC 61000-4-5
 Conducted RF immunity                                                      15V rms with 1 kHz sine-wave 80% AM from 150 kHz…80 MHz
 IEC 61000-4-6
 Voltage variation                                                          30% dips for 1 period at 0° and 180° on AC supply ports             N/A
 IEC 61000-4-11                                                             60% dips for 5 and 50 periods on AC supply ports
                                                                            ±10% fluctuations for 15 min on AC supply ports
                                                                            >95% interruptions for 250 periods on AC supply ports
 Voltage variation                                                          N/A                                                                 10 ms interruption on DC supply ports
 IEC 61000-4-29                                                                                                                                 60% dips for 100 ms on DC supply ports
                                                                                                                                                100% dips for 50 ms on DC supply ports
                                                                                                                                                ±20% fluctuations for 15 min on DC supply ports
                                                                                                                                                5 s interruptions on DC supply ports
Table 15 - Certifications - XT Redundant Power Supplies
 Certification(1)                                                          1756-PAXTR                                                          1756-PBXTR
 c-UL-us                                                                   UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584.
                                                                           UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations, certified for U.S. and Canada. See UL File E194810.
 CE                                                                        European Union 2004/108/EC EMC Directive, compliant with:
                                                                           • EN 61326-1; Meas./Control/Lab., Industrial Requirements
                                                                           • EN 61000-6-2; Industrial Immunity
                                                                           • EN 61000-6-4; Industrial Emissions
                                                                           • EN 61131-2; Programmable Controllers (Clause 8, Zone A & B)
                                                                           European Union 2006/95/EC LVD, compliant with:
                                                                           • EN 61131-2; Programmable Controllers (Clause 11)
 RCM                                                                       Australian Radiocommunications Act, compliant with:
                                                                           • EN 61000-6-4; Industrial Emissions
 Ex                                                                        European Union 94/9/EC ATEX Directive, compliant with:
                                                                           • EN 60079-15; Potentially Explosive Atmospheres, Protection "n"
                                                                           • EN 60079-0; General Requirements
                                                                           • II 3 G Ex nA IIC T4 Gc X
 KC                                                                        Korean Registration of Broadcasting and Communications Equipment, compliant with:
                                                                           • Article 58-2 of Radio Waves Act, Clause 3
(1) When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.
Redundant Power Supply Chassis Adapter Module
Table 16 - Technical Specifications - Redundant Power Supplies Chassis Adapter Module
 Attribute                                                                 1756-PSCA2                                                          1756-PSCA2XT
 Current capacity at 1.2V DC                                               1.5 A
 Current capacity at 3.3V DC                                               4A
 Current capacity at 5.1V DC                                               15 A
 Current capacity at 24V DC                                                2.8 A
 Wire category (1)                                                         3 - on 1756-CPR2 connections
                                                                  Rockwell Automation Publication 1756-TD005E-EN-E - April 2014                                                                       17
1756 ControlLogix Power Supplies Specifications
Table 16 - Technical Specifications - Redundant Power Supplies Chassis Adapter Module
 Attribute                                                               1756-PSCA2                                                         1756-PSCA2XT
 North American temperature code                                         T5                                                                 T4A
 IEC temperature code                                                    T5                                                                 T4
 Enclosure type rating                                                   None (open-style)
(1) Use this conductor category information for planning conductor routing. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.
Table 17 - Environmental Specifications - Redundant Power Supplies Chassis Adapter Module
 Attribute                                                               1756-PSCA2                                                         1756-PSCA2XT
 Temperature, operating                                                  0…60 °C (32…140 °F)                                                -25…70 °C (-13…158 °F)
 IEC 60068-2-1 (Test Ad, Operating Cold),
 IEC 60068-2-2 (Test Bd, Operating Dry Heat),
 IEC 60068-2-14 (Test Nb, Operating Thermal Shock)
 Temperature, surrounding air, max                                       60 °C 140 °F)                                                      70 °C (158 °F)
 Temperature, nonoperating                                               -40…85 °C (-40…185 °F)
 IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold),
 IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat),
 IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock)
 Relative humidity                                                       5…95% noncondensing
 IEC 60068-2-30 (Test Db, Unpackaged Damp Heat)
 Vibration                                                               2 g @ 10…500 Hz
 IEC 60068-2-6 (Test Fc, Operating)
 Shock, operating                                                        30 g
 IEC 60068-2-27 (Test Ea, Unpackaged Shock)
 Shock, nonoperating                                                     50 g
 IEC 60068-2-27 (Test Ea, Unpackaged Shock)
 Emissions                                                               Class A
 CISPR 11 (IEC 61000-6-4)
 ESD immunity                                                            6 kV contact discharges
 IEC 61000-4-2                                                           8 kV air discharges
 Radiated RF immunity                                                    10V/m with 1 kHz sine-wave 80% AM from 80…2000 MHz
 IEC 61000-4-3                                                           10V/m with 200 Hz 50% Pulse 100% AM at 900 MHz
                                                                         10V/m with 200 Hz 50% Pulse 100% AM at 1890 MHz
                                                                         3V/m with 1 kHz sine-wave 80% AM from 2000…2700 MHz
Table 18 - Certifications - Redundant Power Supplies Chassis Adapter Module
 Certification(1)                                                        1756-PSCA2                                                         1756-PSCA2XT
 c-UL-us                                                                 UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584.
                                                                         UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations, certified for U.S. and Canada. See UL File E194810.
 CSA                                                                     CSA Certified Process Control Equipment. See CSA File              N/A
                                                                         LR54689C.
                                                                         CSA Certified Process Control Equipment for Class I, Division 2
                                                                         Group A,B,C,D Hazardous Locations. See CSA File LR69960C.
 FM                                                                      FM Approved Equipment for use in Class I Division 2 Group          N/A
                                                                         A,B,C,D Hazardous Locations
 CE                                                                      European Union 2004/108/EC EMC Directive, compliant with:
                                                                         • EN 61326-1; Meas./Control/Lab., Industrial Requirements
                                                                         • EN 61000-6-2; Industrial Immunity
                                                                         • EN 61000-6-4; Industrial Emissions
                                                                         • EN 61131-2; Programmable Controllers (Clause 8, Zone A & B)
18                                                              Rockwell Automation Publication 1756-TD005E-EN-E - April 2014
                                                                                                                                                          1756 ControlLogix Power Supplies Specifications
Table 18 - Certifications - Redundant Power Supplies Chassis Adapter Module
 RCM                                                                        Australian Radiocommunications Act, compliant with:
                                                                            • EN 61000-6-4; Industrial Emissions
 Ex                                                                         European Union 94/9/EC ATEX Directive, compliant with:
                                                                            • EN 60079-15; Potentially Explosive Atmospheres, Protection "n"
                                                                            • EN 60079-0; General Requirements
                                                                            • II 3 G Ex nA IIC T5 Gc X
 KC                                                                         Korean Registration of Broadcasting and Communications Equipment, compliant with:
                                                                            • Article 58-2 of Radio Waves Act, Clause 3
(1) When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.
                                                                  Rockwell Automation Publication 1756-TD005E-EN-E - April 2014                                                                       19
1756 ControlLogix Power Supplies Specifications
Power Load and Transformer Sizing
The following graphs show the input power requirements for the power supplies, given the power they are providing to the
modules in the chassis.
Follow these steps to determine the power requirements for your chassis.
     1. Calculate the Backplane Power Load by adding the power draw (in Watts) for all of the planned modules.
         For module power draws, refer to the module specification tables in the ControlLogix Selection Guide,
         publication 1756-SG001.
     2. Locate the Backplane Power Load on the graph’s vertical (y) axis and determine the corresponding Real Power
        (input-power) rating on the horizontal (x) axis.
         The Real Power value is the amount of power consumed by the power supply.
20                                                Rockwell Automation Publication 1756-TD005E-EN-E - April 2014
                                                                                                                                                                  1756 ControlLogix Power Supplies Specifications
Power Supply Power Requirements
                                        1756-PA72/C, 1756-PA75/B (AC)                                                                                         1756-PBXT (DC)
                                                                                                                                                                                                    54
                                                                           100                                                        42
                   75
                   60                                                                                                                 35
 Backplane Power   45                                                                                                                 28
 Load (Watts)      30                                                                                                 Backplane Power 21
                   15                                                                                                 Load (Watts)    14
                            6
                   0                                                                                                                  7
                                                                                                                                                 4
                        0               20     40         60        80         100        120                                         0
                                              Real Power (Watts)                                 43895                                       0        10      20           30        40        50         60
                                                                                                                                                                                                                45809
                                                                                                                                                             Real Power (Watts)
                                        1756-PB72/C, 1756-PB75/B (DC)
                 75                                                       95                                                                                 1756-PBXTR (DC)
                                                                                                                                                                                                                   75
                 60                                                                                                                     42
 Backplane Power 45                                                                                                                     35
 Load (Watts)    30                                                                                                                     28
                 15                                                                                                   Backplane Power   21
                 0          4
                                                                                                                      Load (Watts)      14
                      0                 20    40       60           80         100        120                                           7
                                              Real Power (Watts)                                43896                                            6
                                                                                                                                        0
                                                                                                                                             0        10     20       30        40        50        60          70      80
                                        1756-PH75/B, 1756-PC75/B (DC)                                                                                        Real Power (Watts)                                         43898
                                                                               95
                 75
                                                                                                                                                           1756-PA75R/A (AC)
                 60
 Backplane Power 45                                                                                                                                                                             115
                                                                                                                                        75
 Load (Watts) 30                                                                                                                        60
                 15                                                                                                   Backplane Power   45
                            4                                                                                         Load (Watts)      30
                 0
                                                                                                                                        15
                        0               20     40         60        80         100        120                                                    13
                                                                                                43618                                   0
                                              Real Power (Watts)                                                                             0        20      40        60       80        100           120
                                                                                                                                                                                                               43588
                                                                                                                                                             Real Power (Watts)
                                                    1756-PAXT (AC)
                                                                                                 64
                 42                                                                                                                                         1756-PB75R/A (DC)
                 35                                                                                                                                                                            110
                                                                                                                                        75
                 28
                                                                                                                                        60
 Backplane Power 21                                                                                                   Backplane Power   45
 Load (Watts)    14                                                                                                   Load (Watts)      30
                 7                                                                                                                      15
                                    6                                                                                                            7
                 0                                                                                                                      0
                        0               10     20         30        40          50        60          70                                     0        20      40        60       80        100           120
                                                                                                         45808                                                                                                 43589
                                              Real Power (Watts)                                                                                             Real Power (Watts)
                                                      1756-PAXTR (AC)
                                                                                                 75
                   42
                   35
                   28
 Backplane Power   21
 Load (Watts)      14
                   7
                                8
                   0
                        0           10       20      30        40         50         60     70           80
                                                                                                              45897
                                              Real Power (Watts)                                                               Apparent Power (Watts) = Transformer Load (VA) = Real Power (Watts)
                                                                         Rockwell Automation Publication 1756-TD005E-EN-E - April 2014                                                                                       21
1756 ControlLogix Power Supplies Specifications
Additional Resources
These documents contain additional information concerning related products from Rockwell Automation.
 Resource                                                                                    Description
 ControlLogix Selection Guide, publication 1756-SG001                                        Provides overview of the ControlLogix system and its products.
 ControlLogix Chassis Specifications Technical Data, publication 1756-TD006                  Provides technical specifications for ControlLogix chassis.
 ControlLogix Chassis and Power Supplies Installation Instructions, publication 1756-IN005   Provides planning and installation information for the ControlLogix chassis and power
                                                                                             supplies.
 ControlLogix System User Manual, publication 1756-UM001                                     Provides information on how to install, configure, program, and use ControlLogix
                                                                                             systems.
 Industrial Automation Wiring and Grounding Guidelines, publication 1770.4.1                 Provides general guidelines for installing a Rockwell Automation® industrial system.
 Product Certifications website, http://www.ab.com                                           Provides declarations of conformity, certificates, and other certification details.
You can view or download publications at http://www.rockwellautomation.com/literature/. To order paper copies of
technical documentation, contact your local Allen-Bradley distributor or Rockwell Automation sales representative.
22                                                        Rockwell Automation Publication 1756-TD005E-EN-E - April 2014
                                                                         1756 ControlLogix Power Supplies Specifications
Notes:
         Rockwell Automation Publication 1756-TD005E-EN-E - April 2014                                               23
Important User Information
Read this document and the documents listed in the additional resources section about installation, configuration, and
operation of this equipment before you install, configure, operate, or maintain this product. Users are required to
familiarize themselves with installation and wiring instructions in addition to requirements of all applicable codes, laws,
and standards.
Activities including installation, adjustments, putting into service, use, assembly, disassembly, and maintenance are required
to be carried out by suitably trained personnel in accordance with applicable code of practice.
If this equipment is used in a manner not specified by the manufacturer, the protection provided by the equipment may be
impaired.
In no event will Rockwell Automation, Inc. be responsible or liable for indirect or consequential damages resulting from the
use or application of this equipment.
The examples and diagrams in this manual are included solely for illustrative purposes. Because of the many variables and
requirements associated with any particular installation, Rockwell Automation, Inc. cannot assume responsibility or
liability for actual use based on the examples and diagrams.
No patent liability is assumed by Rockwell Automation, Inc. with respect to use of information, circuits, equipment, or
software described in this manual.
Reproduction of the contents of this manual, in whole or in part, without written permission of Rockwell Automation,
Inc., is prohibited.
Documentation Feedback
Your comments will help us serve your documentation needs better. If you have any suggestions on how to improve this
document, complete this form, publication RA-DU002, available at http://www.rockwellautomation.com/literature/.
Allen-Bradley, Rockwell Software, Rockwell Automation, ControlLogix, ControlLogix-XT, FLEX I/O-XT, and LISTEN. THINK. SOLVE are trademarks of Rockwell Automation, Inc.
Trademarks not belonging to Rockwell Automation are property of their respective companies.
Rockwell Otomasyon Ticaret A.Ş., Kar Plaza İş Merkezi E Blok Kat:6 34752 İçerenköy, İstanbul, Tel: +90 (216) 5698400
Publication 1756-TD005E-EN-E - April 2014
Supersedes Publication 1756-TD005D-EN-E - March 2013                                                                                      Copyright © 2014 Rockwell Automation, Inc. All rights reserved. Printed in the U.S.A.
Catalogue No:              1756-RM2
CONTROLLOGIX REDUNDANCY MODULE
Automation Systems > Modular Programmable Controllers > Large PLC Systems > Allen-Bradley ControlLogix® >
ControlLogix® Redundancy
                                                                        ControlLogix Redundancy Enhanced Module
                                                                                     ·   High performance in an easy-to-use environment
                                                                                     ·   Tight integration between the programming software,
                                                                                         controller, and I/O modules reduces development time
                                                                                         and cost at commissioning and during normal
                                                                                         operation
                                                                                     ·   Perform standard and safety control in the same
                                                                                         chassis for a truly integrated system
                                                                                     ·   Leverage the high-availability and extreme
                                                                                         environment capabilities to meet your application
                                                                                         needs
Representative Photo Only
(actual product may vary based on configuration selections)
 SPECIFICATIONS
 Component Type PLC & I/O                                               Controller
 Module Specific Functions                                              Redundancy Module
  REFERENCES
  IECEx Certificate                      -
  Supplier Declaration of
                                         -
  Conformity:
  Installation Guide:                    -
  User Manual:                           -
  Manufacturer Datasheet:                -
  Manufacturer Catalogue
                                         -
  & Product Selection:
                                                                 NHP Electrical Engineering Products                           1756RM2 Datasheet
                                                      1300 NHP NHP | nhp.com.au | 0800 NHP NHP | nhp-nz.com           4 February 2021, Page 1 of 1
Catalogue No:              1756-RMC1
CONTROLLOGIX REDUNDANCY FIBER CABLE 1MT
Automation Systems > Modular Programmable Controllers > Large PLC Systems > Allen-Bradley ControlLogix® >
ControlLogix® Redundancy
                                                                        ControlLogix Fiber Cable For 1756-RM redundancy module, 1
                                                                        Meter
                                                                                    ·   High performance in an easy-to-use environment
                                                                                    ·   Tight integration between the programming software,
                                                                                        controller, and I/O modules reduces development time
                                                                                        and cost at commissioning and during normal
                                                                                        operation
                                                                                    ·   Perform standard and safety control in the same
                                                                                        chassis for a truly integrated system
                                                                                    ·   Leverage the high-availability and extreme
                                                                                        environment capabilities to meet your application
                                                                                        needs
Representative Photo Only
(actual product may vary based on configuration selections)
 SPECIFICATIONS
 Component Type PLC & I/O                                               Accessory
 Module Specific Functions                                              Connector cable to 1756 Redundancy Modules, 1m
  REFERENCES
  IECEx Certificate                      -
  Supplier Declaration of
                                         -
  Conformity:
  Installation Guide:                    -
  User Manual:                           -
  Manufacturer Datasheet:                -
  Manufacturer Catalogue
                                         -
  & Product Selection:
                                                                 NHP Electrical Engineering Products                            1756RMC1 Datasheet
                                                      1300 NHP NHP | nhp.com.au | 0800 NHP NHP | nhp-nz.com              4 February 2021, Page 1 of 1
Catalogue No:              1756-EN2T
CONTROLLOGIX ENET MODULE SINGLE 128 TCP 8 AXES MB
Automation Systems > Modular Programmable Controllers > Large PLC Systems > Allen-Bradley ControlLogix® >
ControlLogix® Communication Modules
                                                                        ControlLogix Ethernet 10-100M Interface Module (Supports 128
                                                                        TCP/IP Connections)
                                                                                     ·   Conformal coated options are available – contact NHP
                                                                                         for further information
Representative Photo Only
(actual product may vary based on configuration selections)
 SPECIFICATIONS
 Product Series                                                         ControlLogix (Bul. 1756 / 1757)
 Component Type PLC & I/O                                               Communications Module
 Communications Ports (On Board)                                        USB (programming only)
                                                                        Ethernet RJ45 Category 5
 Communications Protocols                                               EtherNet/IP
                                                                        EtherNet/OCPP
 Communication Port Speed (Max.)                                        100 Mbit/s
 Operating Temperature, Max                                             60 °C max
 Operating Temperature, Min                                             0 °C min
 Storage Temperature, Max                                               85 °C max
 Storage Temperature, Min                                               -40 °C min
 Relative Humidity, Max                                                 95 %RH
 Vibration Acceleration (Max.)                                          2 m/s²
 Vibration Frequency, Operational (Max.)                                500 Hz
 Standards Compliance                                                   IEC 60068-2-1
                                                                        IEC 60068-2-14
                                                                        IEC 60068-2-2
                                                                        IEC 60068-2-27
                                                                        IEC 60068-2-30
                                                                        IEC 60068-2-6
                                                                        IEC 61000-4-2
                                                                        IEC 61000-4-3
                                                                        IEC 61000-4-4
                                                                        IEC 61000-4-5
                                                                        IEC 61000-4-6
                                                                        IEC 61000-6-4
 Certifications                                                         CE
                                                                        CSA
                                                                        KC (KCC)
                                                                        RCM
                                                                        ODVA - EtherNet/IP
                                                                 NHP Electrical Engineering Products                         1756EN2T Datasheet
                                                      1300 NHP NHP | nhp.com.au | 0800 NHP NHP | nhp-nz.com             5 March 2021, Page 1 of 2
Catalogue No:          1756-EN2T
CONTROLLOGIX ENET MODULE SINGLE 128 TCP 8 AXES MB
Automation Systems > Modular Programmable Controllers > Large PLC Systems > Allen-Bradley ControlLogix® >
ControlLogix® Communication Modules
  REFERENCES
 IECEx Certificate          -
 Supplier Declaration of
                            -
 Conformity:
 Installation Guide:        -
 User Manual:               -
 Manufacturer Datasheet:    -
 Manufacturer Catalogue
                            -
 & Product Selection:
                                                NHP Electrical Engineering Products                              1756EN2T Datasheet
                                     1300 NHP NHP | nhp.com.au | 0800 NHP NHP | nhp-nz.com                  5 March 2021, Page 2 of 2
Catalogue No:              1756-EN2TR
CONTROLLOGIX ENET MODULE DUAL 128 TCP 8 AXES MB
Automation Systems > Modular Programmable Controllers > Large PLC Systems > Allen-Bradley ControlLogix® >
ControlLogix® Communication Modules
                                                                        ControlLogix Ethernet Dual Port 10-100M Interface Module
                                                                        (Supports 128 TCP/IP Connections, Up To 8 Axis ), Ring And
                                                                        Linear Topologies
                                                                                     ·   Conformal coated options are available – contact NHP
                                                                                         for further information
Representative Photo Only
(actual product may vary based on configuration selections)
 SPECIFICATIONS
 Product Series                                                         ControlLogix (Bul. 1756 / 1757)
 Component Type PLC & I/O                                               Communications Module
 Communications Ports (On Board)                                        2 x Ethernet RJ-45
                                                                        USB (programming only)
 Communications Protocols                                               EtherNet/IP
                                                                        EtherNet/OCPP
 Communication Port Speed (Max.)                                        100 Mbit/s
 Operating Temperature, Max                                             60 °C max
 Operating Temperature, Min                                             0 °C min
 Storage Temperature, Max                                               85 °C max
 Storage Temperature, Min                                               -40 °C min
 Relative Humidity, Max                                                 95 %RH
 Vibration Acceleration (Max.)                                          2 m/s²
 Vibration Frequency, Operational (Max.)                                500 Hz
 Standards Compliance                                                   IEC 60068-2-1
                                                                        IEC 60068-2-14
                                                                        IEC 60068-2-2
                                                                        IEC 60068-2-27
                                                                        IEC 60068-2-30
                                                                        IEC 60068-2-6
                                                                        IEC 61000-4-2
                                                                        IEC 61000-4-3
                                                                        IEC 61000-4-4
                                                                        IEC 61000-4-5
                                                                        IEC 61000-4-6
                                                                        IEC 61000-6-4
 Certifications                                                         CE
                                                                        KC (KCC)
                                                                        RCM
                                                                        ODVA - EtherNet/IP
                                                                 NHP Electrical Engineering Products                       1756EN2TR Datasheet
                                                      1300 NHP NHP | nhp.com.au | 0800 NHP NHP | nhp-nz.com             5 March 2021, Page 1 of 2
Catalogue No:          1756-EN2TR
CONTROLLOGIX ENET MODULE DUAL 128 TCP 8 AXES MB
Automation Systems > Modular Programmable Controllers > Large PLC Systems > Allen-Bradley ControlLogix® >
ControlLogix® Communication Modules
  REFERENCES
 IECEx Certificate          -
 Supplier Declaration of
                            -
 Conformity:
 Installation Guide:        -
 User Manual:               -
 Manufacturer Datasheet:    -
 Manufacturer Catalogue
                            -
 & Product Selection:
                                                NHP Electrical Engineering Products                            1756EN2TR Datasheet
                                     1300 NHP NHP | nhp.com.au | 0800 NHP NHP | nhp-nz.com                  5 March 2021, Page 2 of 2