Datasheet S7-300
Datasheet S7-300
4
                                       4/2    Introduction
www.DataSheet4U.com
                                       4/4    Central processing units
4/101 Communication
4/123 Accessories
■ Overview
 4
www.DataSheet4U.com
        ■ Technical specifications
          General technical specifications S7-300, S7-300F                             General technical specifications S7-300 Outdoor
          Degree of protection                     IP 20 to IEC 529                    Climatic operating conditions
          Ambient temperature                                                          Temperature                        Horizontal installation: -25°C to
          • At horizontal installation             0 to 60 °C                                                             60°C (70°C under development)
                                                                                                                          Vertical installation: -25°C to 40°C
          • At vertical installation               0 to 40 °C
          Relative humidity                        5 to 95%, no condensation
                                                                                       Relative humidity                  5 to 95%; short-term moisture
                                                                                                                          condensation allowed, corre-           4
                                                   (RH degree of severity 2 to                                            sponds to relative humidity (RH)
                                                   IEC 1131-2)                                                            degree of severity 2 at IEC 1131-2
                                                                                                                          and IEC 721 3-3 Class 3K5
          Atmospheric pressure                     795 to 1080 hPa
www.DataSheet4U.com                                                                    Temporary icing                    -25°C to 0°C
          Insulation                                                                                                      IEC 721 3-3 Class 3K5
          • 24 V DC circuit                        500 V DC test voltage               Atmospheric pressure               1080 to 795 hPa
          • 230 V AC circuit                       1460 V AC test voltage                                                 Corresponds to a height of –1000
                                                                                                                          to 2000 m
          Electromagnetis compability              Complies with EMC require-
                                                   ments;                              Pollutant concentrations           SO2: < 0.5 ppm; relative humidity
                                                                                                                          <60% Test: 10 ppm, 4 days
                                                   Noise suppression to EN 50082-
                                                   2, tested to: IEC 801-2,                                               H2S: < 0.1 ppm; relative humidity
                                                   ENV 50140, IEC 801-4,                                                  <60% Test: 1 ppm, 4 days
                                                   ENV 50141, IEC 801-5;                                                  (to IEC 721 3-3; class 3C3)
                                                   Noise emission to                   Mechanical operating conditions
                                                   EN 50081-2, tested to
                                                   EN 55011, Class A, Group 1          Vibration                          Type of vibration:
                                                                                                                          frequency sweeps with a change
          Mechanical load                                                                                                 rate of 1 octave per minute.
          • Vibration, tests acc. to/tested with   IEC 68, Part 2-6/10 to 58 Hz;                                          2 Hz ≤ f ≤ 9 Hz, constant ampli-
                                                   constant amplitude 0.075 mm;                                           tude 3.0 mm 9 Hz ≤ f ≤ 150 Hz,
                                                   58 to 150 Hz;                                                          constant acceleration 1 g
                                                   constant acceleration 1 g;                                             period of vibration: 10 frequency
                                                   period of vibration: 10 frequency                                      sweeps per axis in each of the
                                                   sweeps per axis in each of the                                         three mutually perpendicular
                                                   three mutually perpendicular                                           axes;
                                                   axes                                                                   Vibration tests according to
                                                                                                                          IEC 68 part 2-6 (sinusoidal) and
          • Shock, tests acc. to/tested with       IEC 68, Part 2-27/half-sine:
                                                                                                                          IEC 721 3-3, class 3M4
                                                   Shock strength: 15 g
                                                   (peak value), duration 11 ms        Shock                              Type of shock: half-sine
                                                                                                                          Shock strength: 15 g peak value,
                                                                                                                          11 ms duration
                                                                                                                          Shock direction: 3 shocks each in
                                                                                                                          +/- direction in each of the three
                                                                                                                          mutually perpendicular axes
                                                                                                                          Shock test according to IEC 68
                                                                                                                          part 2-27
        ■ Overview                                                            • The compact CPU with inte-        Micro memory card required to
          CPU 313C                                                              grated digital and analog in-     operate the CPU
                                                                                puts and outputs
                                                                              • For installations with high re-
                                                                                quirements in terms of pro-
                                                                                cessing power and
                                                                                response time.
                                                                              • With process-related func-
                                                                                tions
        ■ Overview                                                            • The compact CPU with inte-        Micro memory card required to
          CPU 313C-2 PtP                                                        grated digital I/Os and sec-      operate the CPU
                                                                                ond serial interface
                                                                              • For installations with high re-
                                                                                quirements in terms of pro-
                                                                                cessing power and
                                                                                response time.
                                                                              • With process-related func-
                                                                                tions
        ■ Overview         • The compact CPU with inte-         Micro memory card required to
          CPU 313C-2 DP      grated digital I/Os and            operate the CPU
                             PROFIBUS DP master/slave
                             interface
                           • With process-related func-
                             tions
                           • For tasks with special func-
                             tions                                                              4
                           • For the connection of stan-
                             dalone I/O devices
www.DataSheet4U.com
        ■ Overview         • The compact CPU with inte-         Micro memory card required to
          CPU 314C-2 PtP     grated digital and analog I/       operate the CPU
                             Os, as well as a second seri-
                             al interface
                           • For installations with high re-
                             quirements in terms of pro-
                             cessing power and
                             response time.
                           • With process-related func-
                             tions
        ■ Overview         • The compact CPU with inte-         Micro memory card required to
          CPU 314C-2 DP      grated digital and analog I/       operate the CPU
                             Os and PROFIBUS DP mas-
                             ter/slave interface
                           • With process-related func-
                             tions
                           • For tasks with special func-
                             tions
                           • For the connection of stan-
                             dalone I/O devices
        ■ Overview                           • The starter CPU for Totally      Micro memory card required to
          CPU 312 new                          Integrated Automation (TIA).     operate the CPU
                                             • For small-scale applications
                                               with moderate requirements
                                               on the processing speed.
 4
www.DataSheet4U.com
                                                                                         4
www.DataSheet4U.com
www.DataSheet4U.com
 4        • Counting range
                                         128
                                         1 to 999
                                                            256
                                                            1 to 999
                                                                               256
                                                                               1 to 999
                                                                                                  256
                                                                                                  1 to 999
                                                                                                                     256
                                                                                                                     1 to 999
                                                                                                                                        256
                                                                                                                                        1 to 999
          IEC counters                   Yes                Yes                Yes                Yes                Yes                Yes
          • Type                         SFB                SFB                SFB                SFB                SFB                SFB
www.DataSheet4U.com
          S7 timers                      128                256                256                256                256                256
          • Retentivity selectable       From T 0 to T      From T 0 to T      From T 0 to T      From T 0 to T      From T 0 to T      From T 0 to T
                                         128                256                256                256                256                256
          • Range                        10 ms to 9990 s    10 ms to 9990 s    10 ms to 9990 s    10 ms to 9990 s    10 ms to 9990 s    10 ms to 9990 s
          IEC timers                     Yes                Yes                Yes                Yes                Yes                Yes
          • Type                         SFB                SFB                SFB                SFB                SFB                SFB
          Data ranges and their
          retentivity
          Bit memories                   1024               2048               2048               2048               2048               2048
          • Retentivity selectable       From MB 0 to MB    From MB 0 to MB    From MB 0 to MB    From MB 0 to MB    From MB 0 to MB    From MB 0 to MB
                                         1024               2048               2048               2048               2048               2048
          Blocks
          Max. block size                16 KB              16 KB              16 KB              16 KB              16 KB              16 KB
          Number of
          • Watchdog interrupts          1                  1                  1                  1                  1                  1
          • Process alarms               1                  1                  1                  1                  1                  1
          • Time-of-day interrupts       1                  1                  1                  1                  1                  1
          • Delay interrupts             1                  1                  1                  1                  1                  1
          Nesting depth
          • Per priority class           8                  8                  8                  8                  8                  8
          • Additional within an error   4                  4                  4                  4                  4                  4
            OB
          FBs, max.                      64                 128                128                128                128                128
          FCs, max.                      64                 128                128                128                128                128
          Data blocks, max.              63                 127                127                127                127                127
                                         (DB 0 reserved)    (DB 0 reserved)    (DB 0 reserved)    (DB 0 reserved)    DB 0 reserved)     (DB 0 reserved)
          Programming
          Programming language           STEP 7 V5.1 SP2    STEP 7 V5.1 SP2    STEP 7 V5.1 SP2    STEP 7 V5.1 SP2    STEP 7 V5.1 SP2    STEP 7 V5.1 SP2
                                         (LAD, FBD, STL);   (LAD, FBD, STL);   (LAD, FBD, STL);   (LAD, FBD, STL);   (LAD, FBD, STL);   (LAD, FBD, STL);
                                         SCL, GRAPH,        SCL, GRAPH,        SCL, GRAPH,        SCL, GRAPH,        SCL, CFC,          SCL, CFC,
                                         HiGraph            HiGraph            HiGraph            HiGraph            GRAPH,             GRAPH,
                                                                                                                     HiGraph            HiGraph
          Nesting levels                 8                  8                  8                  8                  8                  8
          User program protection        Password           Password           Password           Password           Password           Password
                                         protection         protection         protection         protection         protection         protection
          Address areas
          (inputs/outputs)
          Total I/O address area         1024 / 1024 byte   1024 / 1024 byte   1024 / 1024 byte   1024 / 1024 byte   1024 / 1024 byte   1024 / 1024 byte
                                         (freely            (freely            (freely            (freely            (freely            (freely
                                         adressable)        adressable)        adressable)        adressable)        adressable)        adressable)
          Process image                  128 / 128 byte     128 / 128 byte     128 / 128 byte     128 / 128 byte     128 / 128 byte     128 / 128 byte
          Digital channels               256 / 256 max.     Max. 992 / 992     Max. 992 / 992     Max. 992 / 992     Max. 992 / 992     Max. 992 / 992
          Analog channels                64 / 32 max.       Max. 248 / 124     Max. 248 / 124     Max. 248 / 124     Max. 248 / 124     Max. 248 / 124
 4         Number of connections           6                    8                    8                    8                    12                   12
           Services
           • Programming device/           Yes                  Yes                  Yes                  Yes                  Yes                  Yes
             OP communications
www.DataSheet4U.com
           • Global data communica-        Yes                  Yes                  Yes                  Yes                  Yes                  Yes
             tion
           • Number of GD circuits
            - sender, max.                 4                    4                    4                    4                    4                    4
            - receiver, max.               4                    4                    4                    4                    4                    4
           • Size of the GD packets,       22 byte              22 byte              22 byte              22 byte              22 byte              22 byte
             max.
           S7 standard communication       Yes                  Yes                  Yes                  Yes                  Yes                  Yes
           • User data per job, max.       76 byte              76 byte              76 byte              76 byte              76 byte              76 byte
           S7 Communication
           • As server                     Yes                  Yes                  Yes                  Yes                  Yes                  Yes
           • As client                     No                   No                   No                   No                   No                   No
           • User data per job, max.       64 KB                64 KB                64 KB                64 KB                64 KB                64 KB
           2nd interface                   -                    -
           Functionality                   -                    -
           • MPI                           -                    -                    No                   No                   No                   No
           • DP master                     -                    -                    No                   Yes                  No                   Yes
           • DP slave                      -                    -                    No                   Yes                  No                   Yes
           • Point-to-point link           -                    -                    Yes                  No                   Yes                  No
           • Electrical isolation          -                    -                    Yes                  Yes                  Yes                  Yes
           Point-to-point                  -                    -
           Transfer media                  -                    -                    RS422 / RS485        -                    RS422 / RS485        -
                                                                                     (X.27)                                    (X.27)
           Transmission rate               -                    -                    19.2 kbit/s          -                    19.2 kbit/s          -
           Line length                     -                    -                    1,200 m              -                    1,200 m              -
           Implemented protocols           -                    -                    ASCII, 3964 (R)      -                    ASCII, 3964 (R),     -
                                                                                                                               RK 512
           DP-Master                       -                    -                    -                                         -
           Number of connections           -                    -                    -                    8 for PG/OP          -                    12 for PG/OP
                                                                                                          communication                             communication
            - Of these reserved            -                    -                    -                    1 for PG, 1 for      -                    1 for PG, 1 for
                                                                                                          OP                                        OP
           Services                        -                    -
           • Programming device/           -                    -                    -                    Yes                  -                    Yes
             OP communications
           • Support for internode         -                    -                    -                    Yes                  -                    Yes
             communications
           • Equidistance                  -                    -                    -                    Yes                  -                    Yes
           • SYNC/FREEZE                   -                    -                    -                    Yes                  -                    Yes
 4        • FC                             128 / max. 8 KBs          128 / max. 8 KBs          192 / max. 16 KBs         192 / max. 16 KBs         256 / max. 16 KBs
          • DB                             127 / max. 8 KBs          127 / max. 8 KBs          255 / max. 16 KBs         255 / max. 16 KBs         511 / max. 16 KBs
          Program execution                • Free cycle (OB 1)       • Free cycle (OB 1)       • Free cycle (OB 1)       • Free cycle (OB 1)       • Free cycle (OB 1)
www.DataSheet4U.com                        • Time-driven (OB 35) • Time-driven (OB 35) • Time-driven (OB 35) • Time-driven (OB 35) • Time-driven (OB 35)
                                           • Real-time controlled    • Real-time controlled    • Real-time controlled    • Real-time controlled    • Real-time controlled
                                             (OB 10)                   (OB 10)                   (OB 10)                   (OB 10)                   (OB 10)
                                           • Interrupt-driven        • Interrupt-driven        • Interrupt-driven        • Interrupt-driven        • Interrupt-driven
                                             (OB 40)                   (OB 40)                   (OB 40)                    (OB 40)                  (OB 40)
                                           • Start (OB 100)          • Start (OB 100)          • Start (OB 100)          • Start (OB 100)          • Start (OB 100)
          Block nesting depth              8 for each program        8 for each program        8 for each program        8 for each program        8 for each program
                                           execution level           execution level           execution level           execution level           execution level
          Nesting levels                   8                         8                         8                         8                         8
          Operation set                    Binary logic, paren-      Binary logic, paren-      Binary logic, paren-      Binary logic, paren-      Binary logic, paren-
                                           thesis commands,          thesis commands,          thesis commands,          thesis commands,          thesis commands,
                                           result assignment,        result assignment,        result assignment,        result assignment,        result assignment,
                                           save, count, load,        save, count, load,        save, count, load,        save, count, load,        save, count, load,
                                           transfer, compare,        transfer, compare,        transfer, compare,        transfer, compare,        transfer, compare,
                                           shift, rotate, generate   shift, rotate, generate   shift, rotate, generate   shift, rotate, generate   shift, rotate, generate
                                           complement, call up       complement, call up       complement, call up       complement, call up       complement, call up
                                           blocks, fixed-point       blocks, fixed-point       blocks, fixed-point       blocks, fixed-point       blocks, fixed-point
                                           and floating point        and floating point        and floating point        and floating point        and floating point
                                           arithmetic functions,     arithmetic functions,     arithmetic functions,     arithmetic functions,     arithmetic functions,
                                           jump functions            jump functions            jump functions            jump functions            jump functions
          User program protection          Password protection       Password protection       Password protection       Password protection       Password protection
          System functions (SFCs)          Interrupt and error/      Interrupt and error/      Interrupt and error/      Interrupt and error/      Interrupt and error/
                                           fault handling, data      fault handling, data      fault handling, data      fault handling, data      fault handling, data
                                           copying, real-time        copying, real-time        copying, real-time        copying, real-time        copying, real-time
                                           clock functions, diag-    clock functions, diag-    clock functions, diag-    clock functions, diag-    clock functions, diag-
                                           nostic functions,         nostic functions,         nostic functions,         nostic functions,         nostic functions,
                                           module parameter          module parameter          module parameter          module parameter          module parameter
                                           assignment, operat-       assignment, operat-       assignment, operat-       assignment, operat-       assignment, operat-
                                           ing mode transitions      ing mode transitions      ing mode transitions      ing mode transitions      ing mode transitions
                                           Operating state tran-     Operating state tran-     Operating state tran-     Operating state tran-     Operating state tran-
                                           sitions                   sitions                   sitions                   sitions                   sitions
          Execution times
          • Bit operations                 0.6 µs to 1.2 µs          0.3 to 0.6 µs             0.3 to 0.6 µs             0.3 to 0.6 µs             0.3 to 0.6 µs
          • Word operations, approx.       2 µs                      1 µs                      1 µs                      1 µs                      1 µs
          • Timer-/counter operations      15 µs                     12 µs                     12 µs                     12 µs                     12 µs
          • Fixed-point addition           3 µs                      2 µs                      2 µs                      2 µs                      2 µs
          • Floating-point addition        60 µs                     50 µs                     50 µs                     50 µs                     50 µs
          Cycle time monitoring            150 ms (preset),          150 ms (preset),          150 ms (preset),          150 ms (preset),          150 ms (preset),
                                           programmable 1 to         programmable 1 to         programmable 1 to         programmable 1 to         programmable 1 to
                                           6000 ms                   600 ms                    6000 ms                   6000 ms                   6000 ms
          Bit memories                     2048                      2048                      2048                      2048                      2048
          • Of these retentive with bat-   0 to 576 (M 0.0 to M      0 to 2048 (M 0.0 to M     0 to 2048 (M 0.0 to M     0 to 2048 (M 0.0 to M     0 to 2048 (M 0.0 to M
            tery                           71.7, selectable)         255.7, selectable)        255.7, selectable)        255.7, selectable)        255.7, selectable)
          • Of these retentive without     0 to 576 (M 0.0 to M      0 to 2048 (M 0.0 to M     0 to 2048 (M 0.0 to M     0 to 2048 (M 0.0 to M     0 to 2048 (M 0.0 to M
            battery                        71.7, selectable)         255.7, selectable)        255.7, selectable)        255.7, selectable)        255.7, selectable)
          Counter                          64                        64                        64                        64                        64
          • Of these retentive with bat-   0 to 35, selectable       0 to 63, selectable       0 to 63, selectable       0 to 63, selectable       0 to 63, selectable
            tery
          • Of these retentive without     0 to 35, selectable       0 to 63, selectable       0 to 63, selectable       0 to 63, selectable       0 to 63, selectable
            battery
          • Counting range                 1 to 999                  1 to 999                  1 to 999                  1 to 999                  1 to 999
 4          Activation/
            deactivation of DP slaves
                                                                                                                   Yes                     Yes
           Communication functions
           using CPs
           • Programming device/OP         Yes                     Yes                     Yes                     Yes                     Yes
www.DataSheet4U.com
             communications
           • Extended communications       Yes (server)            Yes (server)            Yes (server)            Yes                     Yes (server)
            • S5 compatible communi-       -                       Yes (using reloadable   Yes (using reloadable   Yes (using reloadable   Yes (using reloadable
              cations                                              blocks)                 blocks)                 blocks)                 blocks)
            • Standard communication       -                       Yes (using reloadable   Yes (using reloadable   Yes (using reloadable   Yes (using reloadable
                                                                   blocks)                 blocks)                 blocks)                 blocks)
            No. of connections,            4/4                     4/8                     4/8                     4/8                     4/8
            static/dynamic
            Supply voltage
            • Rated value                  24 V DC                 24 V DC                 24 V DC                 24 V DC                 24 V DC
            • Permitted range              20.4 to 28.8 V          20.4 to 28.8 V          20.4 to 28.8 V          20.4 to 28.8 V          20.4 to 28.8 V
            Current consumption typ.       1A                      1A                      1A                      1A                      1A
            Starting current, typ.         8A                      8A                      8A                      8A                      8A
            Power losses, typ.             8W                      8W                      8W                      8W                      8W
            Dimensions (W x H x D)         80 x 125 x 130          80 x 125 x 130          80 x 125 x 130          80 x 125 x 130          80 x 125 x 130
            in mm
            Weight
            • CPU                          530 g                   530 g                   530 g                   530 g                   530 g
            • Memory card                  16 g                    16 g                    16 g                    16 g                    16 g
            Suitable modules
            (recommendation)
            • FM                                                   4                       8                       8                       8
            • CP, point-to-point                                   2                       4                       4                       4
            • CP, LAN, (C bus)                                     1                       2                       2                       2
            Suitable software
            • Software controllers                                 Dependent on            Dependent on            Dependent on            Dependent on
                                                                   required storage        required storage        required storage        required storage
                                                                   space and resulting     space and resulting     space and resulting     space and resulting
                                                                   runtime                 runtime                 runtime                 runtime
            • Process diagnostics                                  Yes                     Yes                     Yes                     Yes
            • S7-GRAPH                                             -                       Yes                     Yes                     Yes
            • S7-HiGraph®                                          -                       Yes                     Yes                     Yes
            • S7-SCL                                               Yes                     Yes                     Yes                     Yes
            • CFC                                                  -                       Yes                     Yes                     Yes
            Backup
            • Without battery              72 byte; Bit memories, counters,         144 byte; bit memories, counters,      4 KB; bit memories, counters, timers
                                           timers and data                          timers and data                        and data
            • With battery                 -                                        All blocks                             All blocks
 4          battery
          • Range                         10 ms to 9990 s                          10 ms to 9990 s                           10 ms to 9990 s
          Integral functions                                                                                                 -
          • Counter                       1 counter with 4 inputs, counter fre-    1 counter with 4 inputs or 2 counters     -
www.DataSheet4U.com                       quency 10 kHz; 32 bit (incl. sign); 2    with 2 inputs and 2 direction-depen-
                                          direction-dependent comparators          dent comparators for each counter;
                                                                                   counter frequency 10 kHz; 32-bit
                                                                                   (incl. sign)
          • Frequency measurement         1 channel to max. 10 kHz; sample         1 channel to max. 10 kHz; sample          -
                                          times 0.1 s, 1 s, 10 s; measuring pro-   times 0.1 s, 1 s, 10 s; measuring pro-
                                          cedure: Calculation of pulse number      cedure: Calculation of pulse number
                                          per sample time                          per sample time
          • Open-loop positioning         -                                        1 channel; position detection using a     -
                                                                                   24 V asymmetric incremental
                                                                                   encoder; 3 digital inputs are occu-
                                                                                   pied by the encoder (track A, track B,
                                                                                   reference point); single interpretation
                                                                                   of count pulses (10 kHz)
          • Integral ”Closed loop         -                                        PID control function blocks               -
            control” function blocks
                                                                                   • Continuous-action manipulated vari-
                                                                                     able outputs
                                                                                   • Binary manipulated variable outputs
                                                                                   • Automatic/manual mode
                                                                                   • Manipulated variable limitation
          MPI interface
          • No. of stations, max.         32 bus nodes on the MPI bus; PG/PC,      32 bus nodes on the MPI bus; PG/PC,       32 bus nodes on the MPI bus; PG/PC,
                                          OP, other S7-300®/400®, C7; per          OP, other S7-300®/400®, C7; per           OP, other S7-300®/400®, C7; per
                                          CPU max. 4 static and 2 dynamic          CPU max. 4 static and 8 dynamic           CPU max. 4 static and 8 dynamic
                                          connections                              connections                               connections
          • Communication functions       • PG/OP communication                    • PG/OP communication                     • PG/OP communication
                                          • Global data communication              • Global data communication               • Global data communication
                                          • S7 basic communication                 • S7 basic communication                  • S7 basic communication
                                          • S7 communication                       • S7 communication                        • S7 communication
          • Data transmission rate        187.5 kbit/s                             187.5 kbit/s                              187.5 kbit/s
          • Distance between 2            With 10 repeaters in row: 9100 m,        Without repeaters: 50 m                   Without repeaters: 50 m
            adjacent stations, max.       using fiber-optic cables: 23.8 km        with 2 repeaters: 1100 m                  with 2 repeaters: 1100 m
                                          (with 16 hubs or OLM)                    with 10 repeaters in row: 9100 m          with 10 repeaters in row: 9100 m
                                                                                   using fiber-optic cables: 23.8 km         using fiber-optic cables: 23.8 km
                                                                                   (with 16 hubs or OLM)                     (with 16 hubs or OLM)
          PG/PCs with STEP® 7             Can be connected using MPI               Can be connected using MPI                Can be connected using MPI
                                          interface                                interface                                 interface
          Onboard I/Os                                                                                                       -
          • Digital inputs                10; 24 V DC of which, 4 channels can 20; 24 V DC of which, 4 channels can -
                                          be used for process interrupts or inte- be used for process interrupts or inte-
                                          grated functions                        grated functions
          • Digital outputs               6; 24 V DC; 0.5 A                        16; 24 V DC; 0.5 A                        -
          • Analog inputs; resolution     -                                        4; ±10 V, ±20 mA / 11 + sign              -
            (bit)
          • Analog outputs; resolution    -                                        1; ±10 V, ±20 mA / 11 + sign              -
            (bit)
          Real-time clock                                                          Yes
          Total address areas I/O         128/128 byte                             512/512 byte                              512/512 byte
          Process image I/O               32/32 byte                               128/128 byte                              128/128 byte
          Total no. of digital channels   Max. 256                                 Max. 992                                  Max. 1024
          Total no. of analog channels    Max. 64 inputs or 32 outputs             Max. 248 inputs or 124 outputs            Max. 256 inputs or 128 outputs
                                           CPU 312 IFM Outdoor               CPU 314 IFM Outdoor               CPU 314 Outdoor
          Input current
          • At ”1” signal, min./typ.       2 mA/7 mA                         2 mA / 7 mA                       -
          Input delay (at rated value of
          the input voltage)
             CPU 313C-2 PtP                       6ES7 313-6BE00-0AB0   Main memory 64 KB, power sup-
                                                                        ply 24 V DC, PROFIBUS DP mas-
             Compact CPU, main memory                                   ter/slave interface, MPI, slot for
             32 KB, power supply 24 V DC,                               memory card, compartment for
             16 DI/16 DO integrated, inte-                              backup battery;
             grated functions, MPI,                                     including slot number labels and
             RS 422/485 interface;                                      2 keys
             MMC required
                                                                        • Standard temperature range          6ES7 315-2AF03-0AB0
             CPU 313C-2 DP                        6ES7 313-6CE00-0AB0   • Outdoor version                     6ES7 315-2AF83-0AB0
             Compact CPU, main memory
             32 KB, power supply 24 V DC,                               CPU 316-2 DP                          6ES7 316-2AG00-0AB0
             16 DI/16 DO integrated, inte-                              Main memory 128 KB, power sup-
             grated functions, MPI,                                     ply 24 V DC, PROFIBUS DP mas-
             PROFIBUS DP master/slave inter-                            ter/slave interface, MPI, slot for
             face; MMC required                                         memory card, compartment for
                                                                        backup battery;
             CPU 314C-2 PtP                       6ES7 314-6BF00-0AB0   including slot number labels and
             Compact CPU, main memory                                   2 keys
             48 KB, power supply 24 V DC,
             24DI/16DO/4AI/2AO integrated,                              CPU 312 IFM Outdoor                   6ES7 312-5AC82-0AB0
             integrated functions, MPI, RS 422/                         Compact CPU for extended
             485 interface; MMC required                                temperature range;
                                                                        main memory 6 KB, power supply
             CPU 314C-2 DP                        6ES7 314-6CF00-0AB0   24 V DC, 10 DI/6 DO integrated,
             Compact CPU, main memory                                   integrated functions, MPI; includ-
             48 KB, power supply 24 V DC,                               ing slot number labels and 2 keys
             24DI/16DO/4AI/2AO integrated,
             integrated functions, MPI,                                 CPU 314 IFM Outdoor                   6ES7 314-5AE83-0AB0
             PROFIBUS DP master/slave inter-                            Compact CPU for extended
             face; MMC required                                         temperature range;
                                                                        main memory 32 KB, power sup-
             CPU 312 new                          6ES7 312-1AD10-0AB0   ply 24 V DC,
             Main memory 16 KB, power sup-                              20DI/16DO/4AI/1AO integrated,
             ply 24 V DC, MPI; MMC required                             integrated functions, MPI;
                                                                        including slot number labels and
             CPU 314 new                          6ES7 314-1AF10-0AB0   2 keys
             Main memory 48 KB, power sup-                              CPU 314 Outdoor                       6ES7 314-1AE84-0AB0
             ply 24 V DC, MPI; MMC required
                                                                        CPU for extended temperature
             CPU 315-2 DP new                     6ES7 315-2AG10-0AB0   range;
                                                                        main memory 24 KB, power sup-
             Main memory 128 KB,                                        ply 24 V DC, MPI, slot for memory
             power supply 24 V DC, MPI,                                 card, compartment for backup
             PROFIBUS DP master/slave                                   battery; including slot number
             interface;                                                 labels and 2 keys
             MMC required
             CPU 313                              6ES7 313-1AD03-0AB0
             Main memory 12 KB, power sup-
             ply 24 V DC, MPI, slot for memory
             card, compartment for backup
             battery, including slot number
             labels and 2 keys
 4
www.DataSheet4U.com
        ■ Technical specifications
                                6ES7 321- 1BH02-0AA0          1BH50-0AA0           1BL00-0AA0           1CH00-0AA0             1CH80-0AA0 1)2)
                                          1BH82-0AA0 1)                            1BL80-0AA0 1)
          Number of inputs                 16                 16; source input     32                   16                     16
          Interrupts                       -                  -                    -                    -                      -
          Diagnostics                      -                  -                    -                    -                      -
          Rated load voltage L+/L1
          • Rated value                    24 V DC            24 V DC              24 V DC              24 to 48 V AC/DC       48 to 125 V DC
          • Permitted range                20.4 V to 28.8 V                                             -                      -
          Input voltage
          • Rated value                    24 V DC            24 V DC              24 V DC               24 to 48 V DC         48 to 125 V DC
                                                                                                        24 to 48 V AC
          • At "1" signal                  13 to 30 V         -13 to -30 V         13 to 30 V           14 to 60 V AC          30 to 146 V DC
          • At signal "0"                  -30 to +5 V        -5 to +30 V          -30 to +5 V           -5 to 5 V AC          -30 to 15 V DC
          • Frequency                      -                  -                    -                    0 to 63 Hz             -
            16 inputs, 48 to 120 V DC,           6ES7 321-1CH80-0AA0   For 32-channel signal modules       6ES7 392-2XY10-0AA0
            extended temperature range
                                                                       S7-SmartLabel                       2XV9 450-1SL00-0YX0
            16 inputs, 24 V DC,                  6ES7 321-7BH00-0AB0
                                                                       Software for machine labelling of
            diagnostics capability
                                                                       modules directly from the STEP 7
            16 inputs, 24 V DC,                  6ES7 321-7BH80-0AB0   project
            diagnostics capability,
             extended temperature range                                Labelling sheets for machine        See page 4/123
                                                                       labelling
            32 inputs, 120 V AC                  6ES7 321-1EL00-0AA0
                                                                       SIMATIC Manual Collection           6ES7 998-8XC01-8YE0
            8 inputs, 120/230 V AC               6ES7 321-1FF01-0AA0
                                                                       Electronic manuals on CD-ROM,
            8 inputs, 120/230 V AC,              6ES7 321-1FF81-0AA0   multi-language:
            extended temperature range                                 S7-200, TD 200, S7-300, C7,
            8 inputs, 120/230 V AC,              6ES7 321-1FF10-0AA0   S7-400, STEP 7, engineering
            common reference potential                                 tools, runtime software,
                                                                       SIMATIC DP (distributed I/O),
            16 inputs, 120/230 V AC              6ES7 321-1FH00-0AA0   SIMATIC HMI (human machine
                                                                       interface), SIMATIC NET
            Front connector                                            (industrial communication)
            20-pin, with screw-type terminals
                                                                       SIMATIC Manual Collection           6ES7 998-8XC01-8YE2
            • 1 unit                             6ES7 392-1AJ00-0AA0   updating service for 1 year
            • 100 units                          6ES7 392-1AJ00-1AB0   Current S7 Manual Collection CD
                                                                       as well as the three following
                                                                       updates
            20-pin, with spring-loaded           6ES7 392-1BJ00-0AA0
            terminals                                                  S7-300 manual
            40-pin, with screw-type terminals                          Design, CPU data, module data,
            • 1 unit                             6ES7 392-1AM00-0AA0   instruction list
            • 100 units                          6ES7 392-1AM00-1AB0   German                              6ES7 398-8FA10-8AA0
                                                                       English                             6ES7 398-8FA10-8BA0
            40-pin, with spring-loaded           6ES7 392-1BM01-0AA0   French                              6ES7 398-8FA10-8CA0
            terminals
                                                                       Spanish                             6ES7 398-8FA10-8DA0
            Front door, improved version         6ES7 328-0AA00-7AA0
                                                                       Italian                             6ES7 398-8FA10-8EA0
            e.g. for 32-channel modules;
            permits connection of 1.3 mm2/
            16 AWG conductors
                                                                                                                                                                 4
www.DataSheet4U.com
        ■ Technical specifications
                             6ES7 322- 1BH01-0AA0           1BL00-0AA0          8BF00-0AB0 2)         5GH00-0AB0          1CF80-0AA0 1)3)     1BF01-0AA0
                                       1BH81-0AA0 1)                            8BF80-0AB0 1)
          Number of outputs                16               32                  8                     16                  8                   8
          Interrupts                       -                -                   Yes                   -                   -                   -
          Diagnostics                      -                -                   Configurable:         Parameters can      -                   -
                                                                                diagnostic alarm      be assigned
                                                                                channel-wise,
                                                                                short-circuit, wire
                                                                                break, missing
                                                                                load voltage
          Load voltage L+/L1               24 V DC          24 V DC             24 V DC               24/48 V DC          48 to 125 V DC      24 V DC
          • Permitted range                20.4 to 28.8V    20.4 to 28.8V       20.4 to 28.8 V        -                   40 to 140 V DC      20.4 to 28.8V
          Output voltage
          • At "1" signal                  L+ -0.8 V        L+ -0.8 V           L+ -0.8 to -1.6 V     L+ (-0.25 V)        L-1.1 V             L+ -0.8 V
          Electrical isolation to back-    Optocoupler      Optocoupler         Optocoupler           Optocoupler         Optocoupler         Optocoupler
          plane bus
          • In groups of                   8                8                   8                     1                   4                   4
          Output current
          • At "1" signal
            - rated value at 40 °C         -                -                   -                     -                   1.5 A
            - rated value at 60 °C         0.5 A            0.5 A               0.5 A                 0.5 A               -                   2A
            - minimum current              5 mA             5 mA                10 mA                                     10 mA               5 mA
            - permitted range                                                                         1.5 A (for 50 ms)   10 mA
                                                                                                      1 A2s (einmalig)
          • At "0" signal                  0.5 mA           0.5 mA              0.5 mA                10 µA               10 mA               0.5 mA
          Total current of the outputs
          (per group)
          • Up to 40 °C                    4A               4A                  2A                                        4.0 A
          • Up to 60 °C                    3A               3A                  2A                    0.5 A               4.0 A               4A
            (horiz. mounting)
          Lamp load, max.                  5W               5W                  5W                    5W                  15 W (48 V) or 40   10 W
                                                                                                                          W (120 V)
          Switching frequency of outputs
          • Resistive load, max.           100 Hz           100 Hz              100 Hz                0.5 Hz              20 Hz               100 Hz
          • Inductive loads, max.          0.5 Hz           0.5 Hz              2 Hz                  -                   0.5 Hz              0.5 Hz
          • Lamp load, max.                100 Hz           100 Hz              100 Hz                -                   10 Hz               100 Hz
          • Mechanical, max.               -                -                   -                     -                   -                   -
          Switching capacity of contacts
          • Resistive load, max.           -                -                   -                     -                   -                   -
          • Inductive loads, max.          -                -                                         -                   -                   -
          • Lamp load, max.                -                -                   -                     -                   -                   -
            Current consumption
            • From backplane bus, max.      80 mA                 110 mA                  70 mA                  100 mA             100 mA            40 mA
             SM 322 digital output modules                             SIMATIC TOP connect                  See page 4/114
             including labelling strips, bus                           Bus connector                        6ES7 390-0AA00-0AA0
             connector
                                                                       1 unit (spare part)
             8 outputs, 24 V DC, 2 A             6ES7 322-1BF01-0AA0
                                                                       Labelling strips
             16 outputs, 24 V DC, 0.5 A          6ES7 322-1BH01-0AA0
             16 outputs, 24 V DC, 0.5 A,
             extended temperature range
                                                 6ES7 322-1BH81-0AA0
                                                                       10 units (spare part)
                                                                       For signal modules (except           6ES7 392-2XX00-0AA0
                                                                                                                                         4
                                                                       32-channel), function modules
             32 outputs, 24 V DC, 0.5 A          6ES7 322-1BL00-0AA0
                                                                       and CPU 312 IFM
           8 outputs, 24 V DC, 0.5 A,            6ES7 322-8BF00-0AB0
www.DataSheet4U.com                                                    For 32-channel signal modules        6ES7 392-2XX10-0AA0
           diagnostics capability
             8 outputs, 24 V DC, 0.5 A,          6ES7 322-8BF80-0AB0   Labelling cover
             diagnostics capability, extended                          10 units (spare part)
             temperature range
                                                                       For signal modules (except           6ES7 392-2XY00-0AA0
             16 outputs, 24/48 V DC, 0.5 A       6ES7 322-5GH00-0AB0   32-channel), function modules
             8 outputs, 48 to 125 V DC,          6ES7 322-1CF80-0AA0   and CPU 312 IFM
             1.5 A, only available with                                For 32-channel signal modules        6ES7 392-2XY10-0AA0
             extended temperature range
             8 outputs, 120/230 V AC, 1 A        6ES7 322-1FF01-0AA0   S7-SmartLabel                        2XV9 450-1SL00-0YX0
        ■ Technical specifications
                              6ES7 323- 1BH01-0AA0          1BL00-0AA0                              6ES7 323- 1BH01-0AA0      1BL00-0AA0
                                        1BH81-0AA0 1)                                                         1BH81-0AA0 1)
          Inputs                                                             Output voltage
          • Number of inputs               8                16               • At "1" signal                  L+ - 0.8 V      L+ - 0.8 V
          Interrupts                       -                -                Electrical isolation             Optocoupler     Optocoupler
          Diagnostics                      -                -                • In groups of                   8               8
          Rated load voltage                                                 Maximum output current
          • Rated value                    24 V DC          24 V DC          • At "1" signal
          • Permitted range                20.4 to 28.8 V   20.4 to 28.8 V     - rated value at 60 °C         0.5 A           0.5 A
                                                                               - minimum current              5 mA            5 mA
          Input voltage
                                                                             • At signal “0”, max.            0.5 mA          0.5 mA
          • Rated value                    24 V DC          24 V DC
                                                                             Total current of the outputs
          • At “1” signal                  13 to 30 V       13 to 30 V       (per group)
          • At “0” signal                  -30 to + 5 V     -30 to + 5 V     • Up to 40°C                     4A              4A
                                                                             • Up to 60°C                     4A              3A
          • Frequency                      -                -
                                                                               (horizontal installation)
          Isolation to backplane bus       Optocoupler      Optocoupler
                                                                             Lamp load, max.                  5W              5W
          • In groups of                   8                16
                                                                             Switching frequency of outputs
          Input current
                                                                             • For resistive load, max.       100 Hz          100 Hz
          • At "1" signal, typ.            7 mA             7 mA
                                                                             • For inductive loads, max.      0.5 Hz          0.5 Hz
          Input delay
                                                                             • For a lamp load                100 Hz          100 Hz
          • Configurable                   -                -
                                                                             Voltage induced on circuit       L+ - 48 V       L+ - 48 V
          • At rated input voltage, typ.   1.2 to 4.8 ms    1.2 to 4.8 ms    interruption limited to
          No. of simultaneously con-                                         Short-circuit protection         Electronic      Electronic
          trollable inputs
                                                                             General
          • Up to 40°C                     8                16
                                                                             Line length
          • Up to 60 °C                    8                8                • Unshielded                     600 m           600 m
          Connection of 2-wire BERO        Possible         Possible         • Shielded                       1000 m          1000 m
          • Permissible quiescent          2 mA             1.5 mA           Current consumption
            current, max.
                                                                             • From backplane bus, max.       40 mA           80 mA
          Outputs
                                                                             • From L+/L1 (without load)      20 mA           100 mA
          • Number of inputs               8                16
                                                                             Power losses, typically          4.5 W           6.5 W
          Interrupts                       -                -
                                                                             Isolation tested at              500 V DC        600 V DC
          Diagnostics                      -                -
                                                                             Dimensions (W x H x D) in mm 40 x 125 x 120      40 x 125 x 120
          Rated load voltage L+/L1         24 V DC          24 V DC
                                                                             Required front connector         20-pin          40-pin
          • Permitted range                20.4 to 28.8 V   20.4 to 28.8 V
                                                                             Weight, approx.                  220 g           260 g
          1) SIMATIC Outdoor with expanded temperature range -25 to +60 °C
          Front door, improved version        6ES7 328-0AA00-7AA0   SIMATIC Manual Collection             6ES7 998-8XC01-8YE2
                                                                    updating service for 1 year
          e.g. for 32-channel modules;
          permits connection of 1.3 mm2/16                          Current S7 Manual Collection CD
          AWG conductors                                            as well as the three following
                                                                    updates
          SIMATIC TOP connect                 See page 4/114
                                                                    S7-300 manual
          Bus connector                       6ES7 390-0AA00-0AA0   Design, CPU data, module data,
          1 unit (spare part)                                       instruction list
                                                                    German                                6ES7 398-8FA10-8AA0
          Labelling strips
                                                                    English                               6ES7 398-8FA10-8BA0
          10 units (spare part)
                                                                    French                                6ES7 398-8FA10-8CA0
          For signal modules (except          6ES7 392-2XX00-0AA0
          32-channel), function modules                             Spanish                               6ES7 398-8FA10-8DA0
          and CPU 312 IFM
                                                                    Italian                               6ES7 398-8FA10-8EA0
          For 32-channel signal modules       6ES7 392-2XX10-0AA0
        ■ Technical specifications
                              6ES7 331- 7KF02-0AB0                                  1KF00-0AB0                              7KB02-0AB0
                                                                                                                            7KB82-0AB0 1)
           Number of inputs                 8                                       8                                       2
           • For resistance measure         4                                       8                                       1
             ment
           Interrupts
           • Limit value interrupt          Configurable                            No                                      Configurable
           • Diagnostics interrupt          Configurable channels 0 and 2           No                                      Configurable channels 0
           Diagnostics                      Red LED for indicating group errors;    No                                      Red LED for indicating group errors;
                                            diagnostic info can be read out                                                 diagnostic info can be read out
           Rated load voltage L+            24 V DC                                 -                                       24 V DC
           • Polarity reversal protection   Yes                                     -                                       Yes
           Input resistance/ input
           ranges
           • Voltage                        +/- 80 mV /10 MΩ, +/- 250 mV/10 MΩ      +/- 50 mV /10 MΩ                        +/- 80 mV /10 MΩ, +/- 250 mV/10 MΩ
                                            +/- 500 mV/10 MΩ +/- 1 V/10 MΩ +/-      +/- 500 mV /10 MΩ                       +/- 500 mV/10 MΩ +/- 1 V/10 MΩ +/-
                                            2,5 V/100 kΩ +/- 5 V/100 kΩ 1 to 5 V/   +/- 1 V /10 MΩ                          2,5 V/100 kΩ +/- 5 V/100 kΩ 1 to 5 V/
                                            100 kΩ +/- 10 V/100 kΩ                  +/- 5 V /100 kΩ                         100 kΩ +/- 10 V/100 kΩ
                                                                                    1 to 5 V /100 kΩ
                                                                                    +/- 10 V /100 kΩ
                                                                                    0 to 10 V /100 kΩ
           • Current                        +/- 10 mA/25 Ω                          +/- 20 mA /50 Ω                         +/- 10 mA/25 Ω
                                            +/- 3,2 mA/25 Ω                         0 to 20 mA /50 Ω                        +/- 3,2 mA/25 Ω
                                            +/- 20 mA/25 Ω 0 to 20 mA/25 Ω 4 to     4 to 20 mA /50 Ω                        +/- 20 mA/25 Ω 0 to 20 mA/25 Ω 4 to
                                            20 mA/25 Ω                                                                      20 mA/25 Ω
           • Resistance                     150 Ω /10 MΩ 300 Ω /10 MΩ               0 to 6kΩ /10 MΩ                         150 Ω /10 MΩ 300 Ω /10 MΩ
                                            600 Ω /10 MΩ                            0 to 600Ω /10 MΩ                        600 Ω /10 MΩ
           • Thermocouples                  Type E, N, J, K/10 MΩ                   -                                       Type E, N, J, K/10 MΩ
           • Resistance thermometer         Pt 100 standard/10 MΩ Ni 100 stan-      Pt 100-Standard /10 MΩ Pt 100 cli-      Pt 100 standard/ 10 MΩ Ni 100 stan-
                                            dard                                    mate /10 MΩ                             dard
           Permissible input voltage for    20 V                                    30 V                                    20 V
           voltage input, max.
           Permissible input current for    40 mA                                   40 mA                                   40 mA
           current input, max.                                                      Delete protection available
           Connection of signal
           sen sors
           • For current measurement
            - as 2-wire transmitter         Yes                                     Yes, with external supply               Yes
            - as 4-wire transmitter         Yes                                     Yes                                     Yes
           1) SIMATIC Outdoor with expanded temperature range -25 to +60 °C
           • Diagnostics interrupt          Configurable per group        Configurable per group            Configurable                  Configurable
           Diagnostics                      Red LED for indicating        Red LED for indicating            Red LED for indicating        Red LED for indicating
www.DataSheet4U.com                         group errors; diagnostic      group errors; diagnostic          group errors; diagnostic      group errors; diagnostic
                                            info can be read out          info can be read out              info can be read out          info can be read out
           Rated load voltage L+            24 V DC                       24 V DC                           -                             -
           • Polarity reversal protection   Yes                           Yes                               -                             -
           Input range
           • Voltage                        -                             -                                 ± 5 V/2 MΩ                    ± 5 V/10 MΩ
                                                                                                            1 to 5 V/2 MΩ ± 10 V/2 MΩ     1 to 5 V/10 MΩ ± 10 V/10
                                                                                                                                          MΩ
           • Current                        -                             -                                 ±20 mA/250 Ω 0 to 20 mA/      ±20 mA/250 Ω 0 to 20 mA/
                                                                                                            250 Ω 4 to 20 mA/ 250 Ω       250 Ω 4 to 20 mA/ 250 Ω
           • Resistance                     0 to 150 Ω 0 to 300 Ω 0 to    -                                 -                             -
                                            600 Ω
           • Thermocouples                  -                             Typ B, E, J, K, L, N, R, S. T,    -                             -
                                                                          U
           • Resistance thermometer         Pt 100, Pt 200, Pt 500, Pt  -                                   -                             -
                                            1000, Ni 100, Ni 120, Ni
                                            200, Ni 500, Ni 1000, Cu 10
           Permissible input voltage for    50 V                          50 V                              50 V                          75 V
           voltage input, max.
           Permissible input current for    -                             -                                 32 mA                         40 mA
           current input, max.
           Isolation to backplane bus       Yes (4 groups of              Yes (4 groups of                  Yes                           Yes
                                            2 channels each)              2 channels each)
           Connection of signal sen-
           sors
           • For current measurement
            - as 2-wire transmitter         -                             -                                 Yes with external transmit-   Yes, with external trans-
                                                                                                            ter                           ducer, power pack
            - as 4-wire transmitter         -                             -                                 Yes                           Yes
           • For impedance measure-
             ment
            - with 2 conductor              Yes                           -                                 -                             -
              connections
            - with 3 conductor              Yes                           -                                 -                             -
              connections
            - with 4 conductor              Yes                           -                                 -                             -
              connections
           Characteristic linearization
           • For thermocouples              -                             Type B, E, J, K, L, N, R, S. T,   -                             -
                                                                          U
           • For resistance                 Pt 100, Pt 200, Pt 500, Pt    -                                 -                             -
             thermometers                   1000, Ni 100, Ni 120, Ni
                                            200, Ni 500, Ni 1000, Cu 10
                                            (standard and airconditio-
                                            ning applications)
           Temperature                      Internal                      Configurable                      -                             -
           compensation
           • Internal                       -                             Possible                          -                             -
           • External with compensa-        -                             Possible                          -                             -
             tion socket
           • External with Pt 100           -                             Yes
           3) Clock alarms are also supported in the modules
            2) Other details have to be heeded to calculate the scan time. These can be found in the manual "Configuring a ”S7-300® ".
            4) In the 4-channel mode the basic execution time for all channels is 10 ms
          40-pin, with spring-loaded           6ES7 392-1BM01-0AA0   SIMATIC Manual Collection           6ES7 998-8XC01-8YE2
          terminals                                                  updating service for 1 year
          SIMATIC TOP connect                  See page 4/114        Design, CPU data, module data,
                                                                     instruction list
          Bus connector                        6ES7 390-0AA00-0AA0   German                              6ES7 398-8FA10-8AA0
          1 unit (spare part)                                        English                             6ES7 398-8FA10-8BA0
          Shield connecting element            6ES7 390-5AA00-0AA0   French                              6ES7 398-8FA10-8CA0
          80 mm wide, with 2 rows for                                Spanish                             6ES7 398-8FA10-8DA0
          4 terminal elements each
                                                                     Italian                             6ES7 398-8FA10-8EA0
                                                                                                                                                                          4
www.DataSheet4U.com
        ■ Technical specifications
                              6ES7 332- 5HB01-0AB0                        5HD01-0AB0                      5HF00-0AB0                      7ND00-0AB0
                                        5HB81-0AB0 1)
          Number of outputs               2                               4                               8                               4
          Interrupts
          • Diagnostics interrupt         Yes                             Yes                             Yes                             Yes
          Diagnostics                     Red LED for indicating          Red LED for indicating          Red LED for indicating          Red LED for indicating
                                          group errors; diagnostic        group errors; diagnostic        group errors; diagnostic        group errors; diagnostic
                                          info can be read out            info can be read out            info can be read out            info can be read out
          Rated load voltage              24 V DC                         24 V DC                         24 V DC                         24 V DC
          Output ranges
          • Voltage outputs               0 to 10 V; +/- 10 V; 1 to 5 V   0 to 10 V; +/- 10 V; 1 to 5 V   0 to 10 V; +/- 10 V; 1 to 5 V   0 to 10 V; +/- 10 V; 1 to 5 V
          • Current outputs               4 to 20 mA; +/- 20 mA;          4 to 20 mA; +/- 20 mA;          4 to 20 mA; +/- 20 mA;          4 to 20 mA; +/- 20 mA;
                                          0 to 20 mA                      0 to 20 mA                      0 to 20 mA                      0 to 20 mA
          Load impedance
          • For voltage outputs, min.     1 kΩ                            1 kΩ                            1 kΩ                            1 kΩ
          • For current outputs, max.     500 Ω                           500 Ω                           500 Ω                           500 Ω
          • For capacitive load, max.     1 µF                            1 µF                            1 µF                            1 µF
          • For inductive loads, max.     10 mH                           10 mH                           10 mH                           1 mH
          Voltage output
          • Short-circuit protection      Yes                             Yes                             Yes                             Yes
          • Short-circuit current, max.   25 mA                           25 mA                           25 mA                           40 mA
          Current output
          • Open-circuit voltage, max.    18 V                            18 V                            18 V                            18 V
          Isolation to backplane bus      Yes                             Yes                             Yes                             Yes
          Resolution                      11 bit + sign                   11 bit + sign                   11 bit + sign                   15 Bit + sign
                                          (at +/- 10 V; +/- 20mA)         (at +/- 10 V; +/- 20mA)         (at +/- 10 V; +/- 20mA)
                                          12 bit                          12 bit                          12 bit
                                          (at 0 to 10 V; 0 to 20 mA), 4   (at 0 to 10 V; 0 to 20 mA), 4   (at 0 to 10 V; 0 to 20 mA), 4
                                          to 20 mA, 1 to 5 V              to 20 mA, 1 to 5 V              to 20 mA, 1 to 5 V
          Conversion time per             0.8 ms                          0.8 ms                          0.8 ms                          1.5 ms
          channel, max.
          Transient recovery time
          • For resistive load            0.2 ms                          0.2 ms                          0.2 ms                          0.2 ms
          • For capacitive loads          3.3 ms                          3.3 ms                          3.3 ms                          3.3 ms
          • For inductive loads           0.5 ms                          0.5 ms                          0.5 ms                          0.5 ms
          Substitute values assignable    Configurable                    Configurable                    Configurable                    Configurable
          Operating error limit (0 to
          60°C, referred to the output
          range)
          • Voltage                       +/- 0.5%                        +/- 0.5%                        +/- 0.5%                        +/- 0.12%
          • Current                       +/- 0.6%                        +/- 0.6%                        +/- 0.6%                        +/- 0.18%
          1) SIMATIC Outdoor with expanded temperature range -25 to +60 °C
 4          • Voltage
            • Current
                                            +/- 0.4%
                                            +/- 0.5%
                                                                       +/- 0.4%
                                                                       +/- 0.5%
                                                                                                      +/- 0.4%
                                                                                                      +/- 0.5%
                                                                                                                                 +/- 0.01%
                                                                                                                                 +/- 0.01%
            Cable length (shielded),        200 m                      200 m                          200 m                      200 m
            max.
           Current consumption
www.DataSheet4U.com
            • From backplane bus, max.      60 mA                      60 mA                          100 mA                     60 mA
            • From L+, max.                 240 mA                     240 mA                         340 mA                     240 mA
            Power loss typ.                 3W                         3W                             6W                         3W
            Isolation tested at             500 V DC                   500 V DC                       500 V DC                   500 V DC
            Dimensions (W x H x D)          40 x 125 x 120             40 x 125 x 120                 40 x 125 x 120             40 x 125 x 120
            in mm
            Required front connector        20-pin                     20-pin                         40-pin                     20-pin
            Weight, approx.                 220 g                      220 g                          272 g                      220 g
            1) SIMATIC Outdoor with expanded temperature range -25 to +60 °C
            For 2 cables with 2 to 6 mm              6ES7 390-5AB00-0AA0                Design, CPU data, module data,
            diameter                                                                    instruction list
                                                                                                                                                                4
www.DataSheet4U.com
        ■ Technical specifications
                             6ES7 334- 0CE01-0AA0                0KE00-0AB0                                SM 334- 0CE01-0AA0                0KE00-0AB0
                                                                 0KE80-0AB0 1)                                                               0KE80-0AB0 1)
          Inputs                          4                      4                    Operational limit (in the
                                                                                      entire temperature range,
          • For voltage measurement       4                      2                    referred to input range)
          • For resistance measure-       -                      4                    • Voltage                        +/- 0.9%              +/- 0.7%
            ment
                                                                                      • Current                        +/- 0.8%              -
          Interrupts
                                                                                      • 10 kΩ                          -                     +/- 3.5%
          • Limit value interrupt         -                      -
                                                                                      • Pt 100                         -                     +/- 1.0%
          • Diagnostics interrupt         -                      -
                                                                                      Basic error (operational error
          Diagnostics                     -                      -                    at 25 °C, referred to output
          Rated load voltage L+           24 V DC                24 V DC              range)
          Input ranges / input resis-     0 to 10 V/ 100 kΩ; 0   0 to 10 V/ 100 kΩ;   • Voltage                        +/- 0.7%              +/- 0.5%
          tance                           to 20 mA/ 50 Ω         resistance 10 kΩ;    • Current                        +/- 0.6%              -
                                                                 Pt 100 (climatic
                                                                 range only)          • 10 kΩ                          -                     +/- 2.8%
          Permissible input range for     20 V                   -                    • Pt 100                         -                     +/- 0.8%
          voltage input, max.
                                                                                      Outputs                          2                     2
          Permissible input current for   20 mA                  -
          current input, max.                                                         Interrupts
        ■ Technical specifications
          Module-specific data                                                   Conversion time per channel                 200 µs
          Number of channels                    4                                • Basic conversion time for                 1 ms
                                                                                   4 channels, max.
          Number of outputs                     4
                                                                                 Resolution
          Cable length, shielded                200 m
                                                                                 • Bipolar                                   13 bit + sign
          With wire-break monitoring in range   30 m
          0 V to 10 V                                                            • Unipolar                                  14 bit
          Voltages, currents, potentials                                         Analog inputs
Basic error for rated voltage 0.1 % • For capacitive load, max. 1 µF
        ■ Technical specifications
          6ES7 326-                        1RF00-0AB0              1BK00-0AB0              6ES7 326-                       1RF00-0AB0            1BK00-0AB0
          Number of inputs                 8 (single-channel)      24                      Input delay
                                           4 (two-channel)                                 • For "0" to "1", typ.          1.2 to 3 ms           3 ms
          Interrupts                       Diagnostic inter-       Diagnostic inter-       • For "1" to "0", typ.          1.2 to 3 ms           3 ms
                                           rupt                    rupt                    No. of simultaneously con-
          Diagnostics                      Group error dis-        Group error dis-        trollable inputs
                                           play, fail-safe oper-   play, fail-safe oper-   • Horizontal arrangement
                                           ation indication;       ation indication;
                                           Diagnostic infor-       Diagnostic infor-         - up to 40 °C                                       24
                                           mation selectable       mation selectable         - up to 60 °C                 8                     24 (at 24 V)
                                                                                                                                                 18 (at 28.8 V)
          Maximum achievable safety                                                        • Vertical arrangement
          class during safety opera-
          tion                                                                               - up to 40 °C                 9                     24
          • According to IEC 61508         SIL 2 (single-chanel) SIL 3                     Connection type of the sen-     Two-wire connec-
                                           SIL 3 (two-channel)                             sors                            tion
          • According to DIN VDE           AK 4 (single-channel) AK 6                      Highest values of input cir-    (per circuit)         (per circuit)
            0801                           AK 5 and 6 (two-                                cuits (per channel)
                                           channel)
                                                                                           • U0, max.                      10.0 V                -
          • According to EN 954            Cat. 3 (single-chanel) Cat. 4
                                           Cat. 4 (two-channel)                            • I0, max.                      13.9 mA               -
                                                                                           • P0, max.                      33.1 mW               -
          Type of protection               II(2)G [EEx ib] IIC     -                       • Permissible external induc-   80 mH                 -
                                           acc. to EN 50020                                  tance L0, max.
          Test number KEMA                 99 ATEX 2671 X          -                       • Permissible external ca-      3 µF                  -
                                                                                             pacitance C0, max.
          Nominal supply voltage of        24 V DC                 24 V DC
          electronics and sensors                                                          • Fault voltage Um, max.        60 V DC               -
          1L+/2L+                                                                                                          30 V AC
                                                                                           • Permissible ambient tem-      60 °C                 60 °C
          Input voltage                    Acc. to DIN 19234                                 perature Ta, max.
                                           or NAMUR
          • Rated value                                            24 V DC                 Connection of                                         Possible
                                                                                           2-wire BERO
          • At "1" signal                                          11 to 30 V
                                                                                           • Permissible quiescent cur-                          2 mA
          • Or signal "0"                                          -30 to +5 V
                                                                                             rent, max.
          • Frequency                                              -
                                                                                           Encoder supply                  8.2 V DC              400 mA
          Electrical isolation
                                                                                           • Number of outputs             8                     4, isolated
          • To backplane bus                                       Yes
                                                                                           Cable length
            - in groups of                                         12
                                                                                           • Unshielded                    200 m                 100 m
            - input current for "1" sig-                           10 mA
                                                                                           • Shielded                      100 m                 200 m
              nal, typ.
          • Between channels and           Yes                     Yes                     Current consumption
            backplane bus                                                                  • From backplane bus, typ.      Max. 90 mA             90 mA
          • Between channels and           Yes                                             • From 1L+, 2L+ (no load),      Max. 160 mA            350 mA
            Spannungsversorgung der                                                          typ.
            Elektronik
                                                                                           Power losses, typ.              4.5 W                 9.0 W
          • Between channels               Yes                     75 V DC, 60 V AC
          Input current
          • At "1" signal, min.            2.1 mA to 7 mA          10 mA
          • At "0" signal , max..          0.35 to 1.2 mA          2 mA
        ■  Ordering data
www.DataSheet4U.com                                   Order No.                                                         Order No.
        ■ Technical specifications
          Number of outputs                   10                                  Total current of the outputs
                                                                                  (per group)
          Interrupts                          Diagnostic interrupt
                                                                                  • Vertical arrangement
          Diagnostics                         Group error display,
                                              fail-safe operation indication;      - Up to 40 °C                          5 A (without series diodes)
                                              diagnostic information selectable                                           4 A (with series diodes)
          Maximum achievable safety class                                         Lamp load, max.                         5W
          during safety operation
                                                                                  Switching frequency of outputs
          • According to IEC 61508            SIL 3
                                                                                  • For resistive load, max.              100 Hz
          • According to DIN VDE 0801         AK 5 and 6
                                                                                  • For inductive load, max.              0.5 Hz
          • According to EN 954               Cat. 4
                                                                                  • For lamp load, max.                   100 Hz
          Load voltage 1L+, 2L+, 3L+          24 V DC
                                                                                  • Mechanical, max.                      -
          Output voltage
                                                                                  Switching capacity of contacts
          • At "1" signal
                                                                                  • For resistive load, max.              30 Hz
            - without series diode, min.      L+ -1.0 V
                                                                                  • For inductive load, max.              2 Hz
            - with series diode, min.         L+ -1.8 V
                                                                                  • For lamp load, max.                   10 Hz
          Electrical isolation
                                                                                  Limitation of voltage induced on        L+ - 53 V (without series diodes)
          • Between channels and backplane    Yes                                 circuit interruption to typically.
            bus                                                                                                           L+ - 33 V (with series diodes)
          • Between channels and power sup- Yes                                   Short-circuit protection                Electronic
            ply of the electronics                                                Cable length
          • Between channels                  Yes                                 • Unshielded, max.                      600 m
          • In groups of                      5                                   • Shielded, max.                        1000 m
          Output current                                                          • At SIL 3, AK 5 and 6, Cat. 4, max.    200 m
          • At "1" signal                                                         Current consumption
            - rated value                     2A                                  • From backplane bus, max.              100 mA
            - permissible range up to 40°C,   7 mA to 2 A                         • From 1L+, max.                        70 mA
              horizontal arrangement
                                                                                  • From 2L+, 3L+, max. (no load)         100 mA
            - permissible range up to 40°C,   7 mA to 1 A
              vertical arrangement                                                Power losses, typ.                      12 W
            - permissible range to 60 °C,     7 mA to 1 A                         Isolation tested at                     75 V DC
              horizontal arrangement
                                                                                  Dimensions (W x H x D) in mm            80 x 125 x 120
          • At “0” signal, max.               0.5 mA
                                                                                  Front connector required                40-pin
          Total current of the outputs
                                                                                  Weight, approx.                         465 g
          (per group)
          • Horizontal arrangement
            - up to 40°C, max.                7.5 A (without series diode)
                                              5 A (with series diode)
            - up to 60 °C                     5 A (without series diode)
                                              4 A (with series diode)
        ■ Technical specifications
          Number of inputs                        6                                    Electrical isolation
          • For voltage measurement, max.         4                                    • Between channels and backplane         Yes
                                                                                         bus
          Interrupts
                                                                                       • Between channels and power sup- Yes (only with external supply of
          • Diagnostic interrupt                  Programmable                           ply of the electronics          sensors)
          Diagnostics                             Green LED for indicating fail-safe   • Between channels                       No
                                                  operation,
                                                  green LED for monitoring sensor      Conversion time1)/resolution (per
                                                  power supply,                        channel)
                                                  red LED for group error display;
                                                  diagnostic information selectable    • Integration time                       20 ms (at 50 Hz)
                                                                                                                                16.66 ms (at 60 Hz)
          Maximum achievable safety class
          during safety operation                                                      • Resolution                             13 bit + sign
          • According to IEC 61508                Max. SIL 3                           • Noise suppression, min.                38 dB
          • According to IEC 19250                Max. AK 6                            Operational limit (in the entire tem-
                                                                                       perature range, referred to input
          • According to EN 954-1                 Max. Kat. 4                          range), max.
          Rated load voltage L+                   24 V DC                              • Current input                          ±0.45%
          • Polarity reversal protection          Yes                                  • Voltage input                          ±0.45%
          Input impedance/                                                             Basic error (operational limits at 25
          input ranges in standard operation                                           °C, referred to input range), max.
          • Voltage                               0 to 10 V/59 kΩ                      • Current input                          ±0.35%
          • Current                               0 to 20 mA/107 Ω 4 to 20 mA/107      • Voltage input                          ±0.35%
                                                  Ω
                                                                                       Cable length (shielded), max.            200 m
          Input impedance/
          input ranges in safety operation                                             Current consumption
          • Current                               4 to 20 mA/107 Ω                     • From backplane bus, max.               90 mA
          Permissible input voltage for volt-     30 V                                 • From L+, typ.                          160 mA
          age input, max.
                                                                                       Power losses, typ.                       4.25 W
          Permissible input current for current   40 mA
          input, max.                                                                  Isolation tested at                      600 V DC
                                                                                       1)Other details have to be heeded to calculate the scan time. These can
                                                                                         be found in the manual "Configuring a ”S7-300® ".
www.DataSheet4U.com
        ■ Technical specifications
                         Ex digital input 6ES7 321-7RD00-0AB0                                    Ex digital input 6ES7 321-7RD00-0AB0
          Number of inputs               4 (NAMUR)                                  Type of protection             [EEx ib] IIC
          Electrical isolation           Yes                                        PTB no.                        Ex-96.D.2094X
          in groups of                   1                                          FMs                            CL.2, DIV 2, GP A,B,C,D T4
          Load voltage                   24 V DC                                    Input circuit maximum val-     (per circuits)
                                                                                    ues
          Input voltage
                                                                                    • U0                           10.0 V
          • Rated value                  8.2 V DC (from internal circuit supply)
                                                                                    • IK                           14.1 mA
          Input current
                                                                                    •P                             33.7 mW
          • At signal “1”, min.          2.1 mA to 7 mA
                                                                                    • Permissible ext. induc-      100 mH
          • At signal “0”, max.          0.35 to 1.2 mA                               tance La, max.
          • On short-circuit, min.       8.5 mA                                     • Permissible ext. capaci-     3 µF
          • At wirebreak, max.           0.1 mA                                       tance Ca, max.
          Delay time                                                                Ambient temperature, max.      60 °C
          • At “0” following “1”, typ.   0.1/0.5/3/15/20 ms (configurable, plus     Current consumption
                                         0.25 ms conditioning time)                 • Internal (backplane bus),    80 mA
          Input frequency, max.          2 kHz                                        max.
          Connection type for signal     Two-wire connection                        • External (load voltage),     50 mA
          encoders                                                                    max.
          Cable length (unshielded),     200 m                                      Power loss                     1.1 W
          max.                                                                      Required front connector       20-pin
          Encoder supply                 Via the inputs                             Weight, approx.                230 g
          Fault message                  Red LED (group error indicator), red LED
          ”Short-circuit”                per channel
          ■ Technical specifications
             Ex digital outputs 6ES7 322- 5SD00-0AB0                  5RD00-0AB0         Ex digital outputs 6ES7 322- 5SD00-0AB0                5RD00-0AB0
             Number of inputs                    4                    4                  FMs                               CL I, DIV 2,         AIS CL.1, DIV 1,
                                                                                                                           GP A,B,C,D T4        GP A,B,C,D
             Electrical isolation                Yes                  Yes                                                                       CL.I, DIV 2,
             • In groups of                      1                    1                                                                         GP A,B,C,D T4
             Supply voltage UP (for load)                                                Highest values of the output      (per circuits)
  4          • Rated value                       24 V DC              15 V DC
                                                                                         circuits
                                                                                         • U0                              25.2 V               15.75 V
             Output current
                                                                                         • IK                              70 mA                85 mA
             • At signal “1”, max.               10 mA +/- 10%        20 mA +/- 10%
                                                                                         •P                                440 mW               335 mW
www.DataSheet4U.com
           • On short-circuit, min.              10 mA + 10%          20.5 mA + 10%
                                                                                         • Permissible ext. Induktivität   6.7 mH               5 mH
             Short-circuit protection            Electronic           Electronic           La, max.
             Fault diagnostics                   Yes                  Yes                • Permissible ext. Kapazität      90 nF                500 nF
             Switching frequency, max.           100 Hz               100 Hz               Ca, max.
             Connection type for load            Two-wire connec-     Two-wire connec-   Current consumption
                                                 tion                 tion               • Internal (backplane bus),       70 mA                70 mA
             Cable length (unshielded),          200 m                200 m                max.
             max.                                                                        • External (load voltage),        160 mA               160 mA
             Fault message ”Short-cir-           Red LED,             Red LED,             max.
             cuit” (group fault message,         CPU message          CPU message        Power losses, typ.                3W                   3W
             additionally per channel)
                                                                                         Required front connector          20-pin               20-pin
             Type of protection                  [EEx ib] IIC         [EEx ib] IIC
                                                                                         Weight, approx.                   230 g                230 g
             PTB no.                             Ex-96.D.2093X        Ex-96.D.2102X
www.DataSheet4U.com
        ■ Technical specifications
          Ex analog input                 6ES7 331-             6ES7 331-               Ex analog input                  6ES7 331-              6ES7 331-
                                          7RD00-0AB0            7SF00-0AB0                                               7RD00-0AB0             7SF00-0AB0
          Input range                     0 to 20 mA            8 x thermocouples,      Basic error limits, bei 25 °C    +/- 0.1%               0.1%
                                          4 to 20 mA            4 x RTD resistance
                                                                thermometers.           Operating error limits           +/- 0.45%              0.09 to 0.04%;
                                                                                                                                                temperature error:
                                                                                                                                                0.001 to 0.02%/K
          Number of inputs                4                     8/4                     Type of protection               [EEx ib] IIC           [EEx ib] IIC
          Electrical isolation            Yes                   Yes                     PTB no.                          Ex-96.D.2092X          Ex-96.D.2108X
          Input resistance                50 Ω                  10 MΩ                   FMs                              CL.I, DIV 2,           CL.I, DIV 2,
                                                                                                                         GP A,B,C,D T4          GP A,B,C,D T4
          Connection of signal            2-wire                2-wire
          sensors                                                                       Input circuit maximum            (per circuits)
                                                                                        values
                                          4-wire                4-core; thermocou-
                                                                ples type T, U, E, J,   • U0                             25.2 V                 5.9 V
                                                                L, K, N, R, S, B;
                                                                resistance ther-        • IK                             68.5 mA                28.8 mA
                                                                mometers Pt 100,        •P                               431 mW                 41.4 mW
                                                                Pt 200, Ni 100
                                                                                        • Ri                             50 Ω
          Digital representation of the   10 to 15 bit + sign   10 to 15 bit + sign
          input signal                                                                  • Permissible ext. induc-        7.5 mH                 40 mH
                                                                                          tance La, max.
          Principle of measurement        SIGMA-DELTA           SIGMA-DELTA
                                                                                        • Permissible ext. capaci-       90 nF                  60 µF
          Integration time (adjustable    2.5 to 100 ms         2.5 to 100 ms             tance Ca, max.
          for optimum noise voltage
          suppression)                                                                  Ambient temperature, max.        60 °C                  60 °C
          Permissible voltage                                                           Cable length (shielded),         200 m                  200 m, HTC:50 m
                                                                                        max.
          • Between the inputs, max.      60 V DC               60 V DC
                                                                                        Supply voltage from module
          • Inputs to grounding point,    60 V DC               30 V DC                 (for 2-wire transducer)
            (destruction limit), max.
                                                                                        • No-load voltage                25.2 V DC              -
          Permissible input current,      40 mA                 -
          max. (destruction limit)                                                      • rRted value                    13 V at 22 mA          -
          Fault indication                Message, red LED      Message, red LED        Current consumption
          Fault message at                                                              • Internal (backplane bus),      60 mA                  120 mA
                                                                                          max.
          • Overflow                      Message, red LED      Message, red LED
                                                                                        • External (24 V DC), max.       150 mA
          • Wirebreak on the signal en- Message                 Message
            coder line                                                                  Power losses, typ.               3W                     0.6 W
          • Short-circuit of the signal   Message               Message                 Required front connector         20-pin                 20-pin
            encoder line
                                                                                        Weight, approx.                  290 g                  210 g
          Noise suppression for noise     10 to 400 Hz          10 to 400 Hz
          frequency
          • Common-mode noise, min. 130 dB                      130 dB
          • Series-mode noise, min.       60 dB                 60 dB
            (peak value of the noise <
            rated value of the range)
           ■ Technical specifications
              Ex analog output                    6ES7 332-5RD00-0AB0                     Ex analog output                6ES7 332-5RD00-0AB0
              Output range (nominal               0/4 to 20 mA                            Fault message at
              value)
                                                                                          • Wirebreak on the actuator     Yes
              Number of outputs                   4                                         line
              Electrical isolation                Yes                                     • Overflow                      Yes
         ■ Technical specifications
                    Number of counters                    1                                   Auxiliary voltage 1L+,
                                                                                              load voltage 2 L+
                    Counting range                        32 bit or +/- 31 bit
                                                                                              • Non-periodic skip
                    Connectable incremental encoders:     • 5-V RS422, symmetrical with two
                                                            90°-offset pulse trains;           - value                              35 V
                                                          • 24 V asymmetric                    - duration                           500 ms
                                                          • 24-V direction sensor (1 pulse     - recovery time                      50 s
                                                            train, 1 direction level);
                                                                                              • Current consumption                 40 mA
                                                          • 24 V initiator
                                                                                              5 V DC counter inputs                 According to RS422
                    Counting frequency if selected with
                                                                                              Terminating resistor, approx.         220 Ω
                    • 5-V RS422, max.                     500 kHz
                                                                                              Differential input voltage, min.      0.5 V
                    • 24-V encoder, max.                  200 kHz
                                                                                              24 V DC counter inputs, digital
                    Digital inputs                        1 for gate start                    inputs
                                                          1 for gate stop                     • Low level                           -28.8 to +5 V
                                                          1 to set counter                    • High level                          +11 to +28.8 V
                    Digital outputs                       2                                   • Input current, typ.                 9 mA
                    Electrical isolation                                                      • Minimum pulse width/interpulse      2.5 µs or 25 µs
                                                                                                period
                    • Between digital inputs, outputs     Yes (optocoupler)
                      and S7 bus                                                              Output voltage
                    • Between digital inputs, outputs     Yes (optocoupler)                   • At ”0” signal, max.                 3V
                      and counter inputs
                                                                                              • At ”1” signal , min.                2L+ - 1.5 V
                    Permissible potential difference      75 V DC, 60 V AC
                                                                                              Output current at "1" signal
                    Supply voltage for encoders
                                                                                              • Rated value                         0.5 A
                    • At 5.2 V, max.                      5.2 V +/- 2%
                                                                                              • Range                               5 mA to 0.6 A
                    • At 24 V, max.                       1L+ -3 V
                                                                                              Switching time, max.                  300 µs
                    • Output current for encoders
                                                                                              Circuit interruption voltage          Limited to 2L+ - 39 V
                    • At 5.2 V, max.                      300 mA
                                                                                              Short-circuit protection              Yes (electronic, clocked)
                    • At 24 V, max.                       300 mA
                                                                                              Current consumption
                    Auxiliary voltage 1L+,
                    load voltage 2 L+                                                         • From S7-300® bus, typ.              160 mA
        ■ Technical specifications
          Number of counters                     8                                   Input delay, max.                     50 µs
          Counting range                         32 bit or +/- 31 bit                Electrical isolation                  Against backplane bus and
                                                                                                                           shield
          Counting frequency if selected with
                                                                                     Connection of two-wire BEROs          Possible
          • 24 V incremental position encoder,   10 kHz
            max.                                                                     Cable length, shielded                100 m
          • 24 V direction sensing element,      20 kHz                              Digital outputs                       8
            max.
                                                                                     Output voltage
          • 24 V initiator, max.                 20 kHz
                                                                                     • At signal "1"                       L+ - 0.8 V
          • NAMUR sensor, max.                   20 kHz
                                                                                     Output current for sensor
          Counting inputs                        8
                                                                                     • At signal "1"                       0.5 A
          Input voltage
                                                                                     • At "0" signal                       0.5 mA
          • At "1" signal                        11 to 30.2 V
                                                                                     Aggregate current for outputs
          • At "0" signal                        -3 to +5 V
                                                                                     • Horizontal installation
          Input current
                                                                                      - up to 40°C                         4A
          • At "1" signal, typ.                  9 mA
                                                                                      - up to 60 °C                        2A
          • At "0" signal, max.                  2 mA
                                                                                     • Vertical installation
          Input delay, max.                      50 µs
                                                                                      - up to 40°C                         2A
          Electrical isolation                   Against backplane bus and
                                                 shield                              Switching frequency of outputs
www.DataSheet4U.com
        ■ Technical specifications (continued)
          Standard function blocks        FC CNT2_CTR (FC 2)           FC CNT2_WR (FC 3)             FC CNT2_RD (FC 4)             FC DIAG_RD (FC 5)
          Memory requirements
          • FB length in memory           320 byte                     992 byte                      496 byte                      278 byte
          • DB length in the memory       On request                   On request                    On request                    On request
          Runtimes in S7-300®/C7          0.5 to 0.6 ms                0.3 to 3.0 ms                 0.2 to 3.0 ms                 2.0 to 2.7 ms
          Runtimes in S7-400®             On request                   On request                    On request                    On request
          Target system                   SIMATIC® S7-300® (CPU 314 upwards), SIMATIC® S7-400®, SIMATIC® C7
          FM 350-2 counter module                6ES7 350-2AH00-0AE0                   Slot number label                   6ES7 912-0AA00-0AA0
          with 8 channels, max. 20 kHz;                                                Spare part
          for 24-V incremental encoders
          and NAMUR encoders                                                           Shield connecting element           6ES7 390-5AA00-0AA0
        ■ Technical specifications
          Voltages/Currents                                                             Inputs per channel             2 (sensor track A / sensor track B)
          Power supply                    5 V (through S7-bus)                          Setpoint, max.                 231 inkrements
          Current consumption, typ.       150 mA                                        Scanning                       1x/2x/4x
          Connection                      1 x 25-pin Sub-D connector                    Frequency, max.                2 kHz
                                          1 x 15-pin Sub-D connector
                                                                                        Digital outputs
          Pulse counter
                                                                                        Rated value                    + 24 V source output
          Number of inputs                8
                                                                                        Output current, max.           500 mA, short-circuit proof
          Counting frequency, max.        10 kHz per channel
                                                                                        Switching frequency            100 Hz resistive load
          Counting modes                  Up or down                                                                   0,5 Hz inductive load
                                                                                                                       8 Hz lamp load
          Set/read counter                All channels can be set/read separately
                                                                                        Cable length, shielded, max. 100 m
          Zero cont or counter value      Interrupt generation for “0“ or count value
          query                                                                         Digital inputs
          Period duration measure-                                                      Rated input voltage            24 V DC                 5 V DC
          ment
          Number of inputs                8                                             • At signal “1“                15 V to 30 V            2,4 V to 6 V
          Internal reference frequency    Max. 100 kHz per channel, configurable        • At signal “0“                -3 V to 5 V             -0.6 V to 0.8 V
                                          for periods, e. g.:
                                                                                        Rated input current, typ.      4.7 mA (at 24 V)        10 mA (at 5 V)
                                          Periods                Meas. frequency
                                          100 kHz                1.6 Hz to 1 kHz        Cable length, shielded, max. 25 m                      5m
                                          50 kHz                 0.8 Hz to 500 Hz       Miscellaneous
                                          25 kHz                 0.4 Hz to 250 Hz       UL/CSA/FM                      No
          Time generator                                                                Configuraton with active bus   Not supported
          Number of inputs                8                                             modules
          Number of inputs                4
          Outputs per channel             2 (forward / backward)
www.DataSheet4U.com
        ■ Technical specifications
          General specifications                                                      Synchronous-serial posi-
                                                                                      tion detection
          Supply voltage                 24 V DC
                                                                                      Accepts encoder types          Single or multi-turn encoders with SSI
          Current consumption            350 mA                                                                      (GRAY encoding)
          Supply current for position    max. 350 mA                                  Data signal                    DATA; not DATA
          encoders
                                                                                      Clock signal                   CL; not CL
          Supply voltage for position    5 V and 24 V
          encoder                                                                     Frame length                   13 or 25 bit serial
          Protection to DIN 40050        IP 20                                        Input signal                   5-V differential signal (phys. RS 422)
          Permissible humidity to        Humidity class F                             • Differential input voltage   1 to 10 V
          DIN 40040
                                                                                      Transmission rate max.         1 MHz
          Permissible ambient temper-
          ature                                                                       Encoder supply                 24 V DC, max. 400 mA per channel
• Storage and transport -40 to + 70 °C Cable length, max. 300 m (at max. 125 kHz)
www.DataSheet4U.com
        ■ Technical specifications
          General specifications                                                   Synchronous-serial posi-
                                                                                   tion detection
          Supply voltage                 24 V DC
                                                                                   Accepts encoder types          Single or multi-turn encoders with SSI
          Current consumption                                                                                     (Gray encoding)
          • L+ (without load)            200 mA                                    Data signal                    DATA; not DATA
          • From backplane bus           100 mA                                    Clock signal                   CL; not CL
          Supply current for position    Max. 300 mA                               Frame length                   13 or 25 bit
          encoders
                                                                                   Input signal                   5-V differential signal (phys. RS 422)
          Supply voltage for position    5 V or 24 V
          encoder                                                                  • Differential input voltage   1 to 10 V
          Protection to DIN 40050        IP 20                                     Transmission rate max.         1 MHz
          Permissible humidity to        Humidity class F                          Encoder supply                 24 V, max. 300 mA
          DIN 40040
                                                                                   Cable length, max.             320 m (at max. 125 kHz)
          Permissible ambient temper-
          ature                                                                    Digital inputs
           FM 352 electronic cam controller    6ES7 352-1AH01-0AE0   Labelling strips                     6ES7 392-2XX00-0AA0
           FM 352 manual                                             10 units (spare part)
           German                              6ES7 352-1AH00-8AG0   S7-SmartLabel                        2XV9 450-1SL00-0YX0
           English                             6ES7 352-1AH00-8BG0   Software for machine labelling of
                                                                     modules directly from the STEP 7
           French
           Italian
                                               6ES7 352-1AH00-8CG0
                                               6ES7 352-1AH00-8EG0
                                                                     project                                                           4
                                                                     Labelling sheets for machine         See "Accessories"
           703 connecting cable                See FM 351            labelling
        ■ Technical specifications
          General specifications                                                     Separation
          Supply voltage                        24 V DC                              Between backplane bus and digital     Yes (75 V DC, 60 V AC)
                                                                                     & sensor I/O & 1L & 2L & 3L
          Power consumption
                                                                                     Between digital I/O & 2L and sensor   Yes (75 V DC, 60 V AC)
          1L+ module supply                     150 mA (max) 60 mA (type)            I/O & 3L
          2L+ DI / DO supply                    200 mA (max) 60 mA (type)            Between 1L and 2L and 3L              Yes (75 V DC, 60 V AC)
          3L+ with encoders                     600 mA (max) 80 mA plus              Heat dissipation of electronics       6.5 W
                                                encoder power supplt (type)          module, typ.
          L3+ without encoder                   200 mA (max) 60 mA (typical)         Digital inputs
          From backplane bus                    100 mA (type)                        Number of inputs                      8 standard and up to 12 for 24 V
          Power pack for position encoder                                                                                  DC sensor inputs as digital inputs
          5 V output                            250 mA max.                          Separation                            Yes CPU, I/O and sensor units are
                                                                                                                           separated
          24 V output                           400 mA max.
                                                                                     Digital input
          Output voltage protection
                                                                                     Rated value                           24 V DC
          5 V output                            Electronic overload protection. No
                                                protection when applying normal      • 0 signal                            -30 to 5 V
                                                or counter voltage.                  • 1 signal                            11 to 30 V
          24 V output                           Overload and overheating protec-     Input current
                                                tion during overload. Diagnostics
                                                when output reaches the temper-      • 0 signal                            ≤ 1.5 mA (current at 0 signal)
                                                ature limit. No protection when
                                                applying normal or counter volt-     • 1 signal, typ.                      3.8 mA
                                                age                                  Input frequency                       200 kHz max.
          Rated load voltage L+                 24 V DC                              Hardware input delay                  3 µs max. 1.5 µs typ.
          Range                                 20.4 to 28.8 V                       Programmable digital filter delay     None, 5 µs, 10 µs, 15 µs, 20 µs,
          Polarity reversal protection          Yes                                                                        50 µs, 1.5 ms
          Supply voltage for position encoder   5 V or 24 V                          Minimum pulse width for program       1 µs, 5 µs, 10 µs, 15 µs, 20 µs, 50
                                                                                     response                              µs, 1.6 ms
          Protection according to DIN 40050     IP 20
                                                                                     Cable length, sensor                  100 meters unshielded, 600 m
          Permissible ambient temperature                                                                                  shielded, shielded cable recom-
                                                                                                                           mended when filtering is set in the
          Storage and transport                 -40 to +70 °C                                                              1.6 ms grid.
          Operation                             0 to +60 °C                          Cable length, HTL incremental         50 kHz, 25 m shielded, max.
          Required front connector              1 x 40-pin                           encoder, Siemens, type 6FX2001-4      25 kHz, 50 m shielded, max.
          Dimensions (W x H x D)                80 x 125 x 120 mm                    Minimum pulse width (max. SW          1 µs (200 kHz)
                                                                                     counter frequency)
          Shipping weight, approx.              500 g (with bus and 1L connec-
                                                tion & without I/O connection or     Connection of two-wire BEROs          Possible
                                                MMC)                                 Input characteristics                 Type 1A for PLC BEROs with less
          Module weight, approx.                434 g (with 1L connection & with-                                          than 1.5 mA cutoff current
                                                out I/O connection or MMC)
              Loss of voltage/pt @ 500 mA               125 mW                               Reset value source                    Constant 0, min/max value, load
                                                                                                                                   value
              Number of switching actuations
                                                                                             Reset signal type                     Edge, layer
              • For resistive load                      20 kHz at 0.5 A
                                                        100 kHz at 0.25 A                    Load value, source                    Constant, module application
              • For inductive load                      2 Hz at 0.5 A with external com-     Hold source                           No, HW, SW, HW and SW, HW or
                                                        mutator diodes                                                             SW
                                                        0.5 Hz at 0.5 A without external     Load value                            User entry or module application
                                                        commutator diodes
                                                                                             Counter range, minimum                User entry
              • For a lamp load                         ≤ 10 Hz 5 Watt maximum
                                                                                             Counter range, maximum                User entry
              Output delay (resistive load)
                                                                                             Main counting direction               Count forward/backward
              • ON to OFF                               1.7 µs 50 mA / 1.5 µs 0.5 A
                                                                                             Hardware hold source                  Can be set to any input between
              • OFF to ON                               0.6 µs 50 mA / 1.0 µs 0.5 A
                                                                                                                                   0 and 14
              Output protection
                                                                                             Hardware reset source                 Can be set to any input between
              Short circuit                             Yes                                                                        0 and 14
              Threshold value for response              1.7 A to 3.5 A                       Count modes
              Overvoltage                               Yes                                  Continuous                            Yes, 16-bit or 32-bit counter
              Thermal                                   Yes                                  Counter range (16-bit counter):       -32768 to 32767 (user-specific
              Inductive limitation at kickback from     Yes; 2M +45 V type, (40 to 55 V)                                           within this range)
              inductive loads                           Note: no protection against induc-   Counter range (32-bit counter):       -2,147,483,648 to 2,147,483,647
                                                        tive kickback > 55 mJ                                                      (user-specific within this range)
              Digital input control                     No                                   Periodic                              Yes, 16-bit or 32-bit counter
              Cable length                                                                   Counter range (16-bit counter):       -32768 to 32767
              • Unshielded                              100 m                                                                      (user-specific within this range)
              • Shielded                                600 m                                Counter range (32-bit counter):       -2,147,483,648 to 2,147,483,647
                                                                                                                                   (user-specific within this range)
              Status, diagnostics
                                                                                             Individual                            Yes, 16-bit or 32-bit counter
              Module malfunction                        SF, red LED
                                                                                             Counter range (16-bit counter):       -32768 to 32767
              MMC error                                 MCF, red LED
                                                                                                                                   (user-specific within this range)
              Module supply                             5V DC, green LED
                                                                                             Counter range (32-bit counter):       -2,147,483,648 to 2,147,483,647
              I/O status                                IOF, red LED                                                               (user-specific within this range)
              Run mode                                  RUN, green LED                       Encoder signals
              Stop mode                                 STOP, yellow LED                     Incremental 5 V encoder (RS422)       A, /A, B, /B, and N, /N
              Overload on sensor power supply           5VF, red LED, 24VF, red LED          Incremental 24 V encoder              A, B and N
              Status display, digital input module DI   I0 to I11, 12 green LEDs
              Status display, digital output module DO O0 to O7 8 green LEDs
Control signal buffer size Partitioned, maximum Serial interface Master - 25-bit 117
SRFF 1 None 77
        ■ Technical specifications
          General specifications                                        Digital inputs
          Supply voltage                        24 V DC                 Number of inputs                 4
          Current consumption                   300 mA                  Functions                        • Reference cam
          Protection to DIN 40050               IP 20                                                    • Set actual value on-the-fly
          Permissible humidity to DIN 40040     Humidity class F                                         • Measure on-the-fly
          Permissible ambient temperature                                                                • Start/stop positioning run
          • Storage and transport               -40 to +70 °C                                            • External block change
          • Operation                           0 to +55 °C             Electrical isolation             No
          Required front connector              1 x 20-pin              Input voltage
          Dimensions (W x H x D) in mm          80 x 125 x 118 mm       • Rated value                    24 V DC
          Weight, approx.                       500 g                   • ”0” signal, max.               -3 to +5 V
          Drive interface                                               • ”1” signal, min.               11 to 30 V
          Signal input                                                  Input current, min.
          Function                              ”Power section Ready"   • ”0” signal, max.               2 mA
          Signal outputs                                                • ”1” signal, min.               6 to 15 mA
          Output signals                        5 V difference signal   Digital outputs
                                                (phys. RS 422) for:
                                                                        Number of inputs                 4
                                                • Direction
                                                                        Functions                        • Position reached: stop
                                                • Enable
                                                                                                         • Axis traveling forward
                                                • Cycle
                                                                                                         • Axis traveling in reverse
                                                • Power regulation
                                                                                                         • Change M function M97
          Differential output voltage, min.     2 V (RL = 100 Ω)
                                                                                                         • Change M function M98
          • ”0” signal, max.                    1 V (I0 = 20 mA)
                                                                                                         • Enable start
          • ”1” signal, min.                    3.7 V (I0 = -20 mA)
                                                                                                         • Direct output using data record
          Cable length                          35 m
                                                                        Electrical isolation             No
                                                                        Output voltage
                                                                        • Rated value                    24 V DC
                                                                        • ”0” signal, max.               Residual current max. 2 mA
                                                                        • ”1” signal, min.               UP – 3 V
                                                                        Output current                   0.6 A at UPmax. (short-circuit
                                                                                                         proof)
www.DataSheet4U.com
        ■ Technical specifications
          General specifications                                                     Drive interface
          Supply voltage                         24 V DC                             Input closed-loop controller sig-
                                                                                     nal
          Current consumption                    350 mA
                                                                                     Function                            ”Drive ready”
          Supply current for position            Max. 300 mA
          encoders                                                                   Electrical isolation                Yes (optocoupler)
          Supply voltage for position encoder    5 V or 24 V                         Input voltage
          Protection to DIN 40050                IP 20                               • Rated value                       24 V DC
          Permissible humidity to DIN 40040      Humidity class F                    • ”0” signal                        -3 to +5 V
          Permissible ambient temperature                                            • ”1” signal                        15 to 30 V
          • Storage and transport                -40 to +70 °C                       Input current at "1" signal         2 mA to 6 mA
          • Operation                            0 to +55 °C                         Output closed-loop controller
                                                                                     enable (contact)
          Required front connector               1 x 20-pin
                                                                                     Function                            Safety disconnection of drives for
          Dimensions (W x H x D) in mm           80 x 125 x 118 mm                                                       operation using contact relays
          Weight, approx.                        550 g                               Load, max.                          1 A/50 V/30 VA DC
          Position detection, incremental                                            Analog output
          Accepts encoder types                  Encoders with TTL quadrature        Function                            Setpoint output for drive
                                                 signal
                                                                                     Output voltage                      • -10 to +10 V
          Track signals                          A, not A; B, not B
                                                                                     Output current                      • -3 to +3 mA
          Zero mark signal                       N, not N
                                                                                     Cable length, max.                  • 35 m
          Input signal                           5 V difference signal (phys. RS
                                                 422)                                Digital inputs
          • Input frequency, max.                1 MHz                               Number of inputs                    4
          Cable length                                                               Function (configurable)             • Reference cam
          • 5-V encoder supply, max.             35 m at max. 220 mA                                                     • Set actual value on-the-fly
          • 24-V encoder supply, max.            100 m at max. 300 mA                                                    • Measure on-the-fly
          Synchronous-serial position                                                                                    • Start/stop positioning run
          detection
                                                                                                                         • External block change
          Accepts encoder types                  Single or multiturn encoders with
                                                 SSI                                 Electrical isolation                No
          Connecting cables and               See Catalog NC 60,                Shield connecting element              6ES7 390-5AA00-0AA0
          encoders                            NC Z, CA 01 or in the             80 mm wide, with 2 rows for 4
                                              A&D Mall                          terminal elements each
          703 connecting cable                See FM 351                        Terminal elements
          Sub-D connector                                                       2 units
          15-pin, male                        6ES5 750-2AA21                    For 2 cables with 2 to 6 mm            6ES7 390-5AB00-0AA0
                                                                                diameter
          9-pin, female                       6ES5 750-2AB11
                                                                                For 1 cable with 3 to 8 mm             6ES7 390-5BA00-0AA0
                                                                                diameter
                                                                                For 1 cable with 4 to 13 mm            6ES7 390-5CA00-0AA0
                                                                                diameter
         ■ Technical specifications
           General specifications                                                        Drive interface for analog drives
           NC program memory, approx.            750 KB                                  Output closed-loop controller
                                                                                         enable (contact)
           Programmable traversing speed max.    1000 m/min
                                                                                         Function                              Safety disconnection of drives for
           Supply voltage                        24 V DC                                                                       operation via contact relays
           Power consumption max.                24 W                                    Load, max.                            1 A/50 V/30 VA DC
           Power consumption from backplane      100 mA                                  Analog output
           bus
                                                                                         Function                              Setpoint output for drive
           Protection to DIN 40050               IP 20
                                                                                         Output voltage                        • -10 to +10 V
           Required front connector              1 x 40-pin
                                                                                         Output current                        • -3 to +3 mA
           Dimensions (W x H x D) in mm          200 x 125 x 118
                                                                                         Cable length, max.                    • 35 m
           Weight approx.                        1.2 kg
                                                                                         Drive control interface for stepper
           Position detection, incremental                                               motors
           Accepts encoder types                 Encoders with TTL quadrature sig-       Output signals                        5 V difference signal (phys. RS
                                                 nal                                                                           422) for:
           Track signals                         A, not A; B, not B                                                            • Direction, enable, clock
           Zero mark signal                      N, not N                                Differential output voltage, min.     2 V (RL = 100 Ω)
           Input signal                          5 V difference signal (phys. RS 422)    • ”0” signal, max.                    1 V (I0 = 20 mA)
           Input frequency, max.                 1 MHz                                   • ”1” signal, min.                    3.7 V (I0 = -20 mA)
           Cable length                                                                  Sensor frequency for T, max.          750 kHz
           • 5-V encoder supply, max.            35 m at max. 210 mA                     Permissible cable length max.         50 m
           • 24 V encoder supply, max.           100 m at max. 300 mA                    • In mixed mode with servo axes       35 m
           Synchronous-serial position                                                     max.
           detection                                                                     Digital drive interface using         See SIMODRIVE 611 Universal,
           Accepts encoder types                 Single or multiturn encoders with SSI   PROFIBUS DP with MC                   MASTERDRIVES MC
                                                                                         expansions
           Data signal                           DATA, not DATA
                                                                                         Digital inputs
           Clock signal                          CL, not CL
                                                                                         Number of inputs                      18
           Frame length                          13, 21 or 25 bit
                                                                                         Function                              • 4 Bero
           Input signal                          5 V difference signal (phys. RS 422)                                          • 2 probe
           Transmission rate max.                1.5 Mbit/s                                                                    • 12 freely usable
           Encoder supply                        24 V DC, max. 300 mA                    Electrical isolation                  Yes
           Cable length, max.                    250 m (at max.187.5 kbit/s)
            FM 357-2LX system firmware         6ES7 357-4BH03-3AE0   Connecting cables and encoders       See Catalog NC 60,
                                                                                                          NC Z, CA 01 or have a
                                                                                                          look in the A&D Mall
            with additional functions;
            on memory card                                           Front connector
            FM 357-H system firmware           6ES7 357-4CH03-3AE0   40-pin, with screw-type terminals
                                                                     • 1 unit                             6ES7 392-1AM00-0AA0
            with additional functions for
            handling range;                                          • 100 units                          6ES7 392-1AM00-1AB0
            on memory card
                                                                     40-pin, with spring-loaded           6ES7 392-1BM01-0AA0
                                                                     terminals
                                                                     Battery                              6ES7 971-1AA00-0AA0
        ■ Technical specifications
          Supply voltage                          115 V /230 V AC ± 20% select-         Max. cable length                 Up to 50 m (164 ft) with 1.5 mm2
                                                  able                                                                    Up to 30 m (98 ft 5 in) with 0.75 mm2
          Max. input current                      11 A / 5.5 A                          Terminals                         For max. 2.5 mm2
          Frequency                               47 Hz to 63 Hz                        Number of steps/revolution        Can be set to 500, 1000, 5000,
                                                                                                                          10000
          Connection system                       Via terminals max. 2.5 mm2
                                                                                        Degree of protection to           IP 20, must be installed in cabinet
          Supply voltage (signals)                24 V DC (20.4 V to 28.8 V)            DIN EN 60529 (IEC 60529)
          Max. input current                      1.5 A                                 Moisture condensation             Not permissible
          DC link voltage                         325 V                                 Permissible ambient temperature
          Pulse interface                         5 V signals 1)                        • Storage and transport           -40 °C to +70 °C (-40 °F to +158 °F)
                                                  15-pin sub D sokket connector,
                                                  standard cable                        • Operation                       0 °C to +50 °C (+32 °F to +122 °F)
                                                                                                                          with reduction in power, and depen-
          Signal interface                        24 V, I/O signals 1)                                                    dent on mounting position
          Motor connection                        3 x 325 V (connected to supply)       Weight, approx.                   0.85 kg (1 lb 14 oz)
          Phase current                           1.7 A to 6.8 A                        Dimensions (W x H x D)            80 mm x 125 mm x 118 mm
                                                  (adjustable on unit)                                                    (3.15 in x 4.92 in x 4.65 in)
          1) Enable signal (enabling of power unit) either 5 V via pulse interface or
              24 V via signal interface.
        ■ Technical specifications
          Motor type                            3-phase stepper motor                 Shaft end                                 Plain shaft with 1FL304.
                                                                                                                                Fitted key with 1FL306.
          Motor voltage                         325 V
                                                                                      Permissible dynamic shaft load
          Insulation according to EN 60034-1    Temperature class F for a wind-
          (IEC 60034-1)                         ing temperature of ∆T = 100 K at      • Axial, approx.                          60 N
                                                an ambient temperature of             • Radial, approx.                         (on half shaft protrusion, engaged
                                                +40 °C (+104°F)                                                                 from the motor flange)
                                                                                                                                100 N (with 1FL3041, 1FL3042)
          Type according to DIN 42950           IM B5 (IM V1, IM V3)                                                            110 N (with 1FL3043)
          Degree of protection according to     IP 56; IP 41 on shaft protrusion                                                300 N (with 1FL3061,1FL3062)
          IEC 60529                                                                   Rotational accuracy, concentricity        Tolerance N (Normal)
          Cooling                               Natural air cooling                   and axial runout according to
                                                                                      DIN 42955 (IEC 60072-1)
          Permissible ambient temperature
                                                                                      Vibration severity according to           Grade N (Normal)
          • Storage and transport               -40 °C to +70 °C                      EN 60034-14 (IEC 60034-14)
          • Operation                           0 °C to +40 °C
                                                                                      Sound pressure level max.                 • 1FL3041: 65 dB(A)
          Max. pulse frequency                  5.3 kHz (at 1FL304.)                  EN 21680                                  • 1FL3042: 72 dB(A)
                                                4.3 kHz (at 1FL306.)                                                            • 1FL3043: 75 dB(A)
                                                                                                                                • 1FL3061: 69 dB(A)
          Number of steps/revolution            500/1000/5000/10000 adjust-                                                     • 1FL3062: 72 dB(A)
                                                able via FM STEPDRIVE                                                           • 1FL304.: 50 g
                                                                                      Impact load
          Max. speed                            6000 rpm                              DIN 40046, T7                             • 1FL306.: 50 g
          Step angle in degrees                 0.72°/0.36°/0.072°/0.036°             Paint finish                              Black
          Systematic angle tolerance (mea-      ± 6 per step                          Connection                                Terminal block
          sured at 1000 steps/revolution)
        ■ Technical specifications
          Number of controllers                   4                   Input current at ”1” signal, typ.         7 mA
          General specifications                                      Input characteristic                      In accordance with ICE 1131, type 2
          Rated load voltage L+                   24 V DC             Connection of two-wire BEROs              Possible
          • Permitted range                       20.4 to 28.8 V      • Permissible quiescent current, max.     1.5 mA
          Electrical isolation                                        Line length
          • To backplane bus                      Yes (optocoupler)   • Unshielded                              600 m
          • Between channels                      No                  • Shielded                                1000 m
          Permissible potential difference                            Digital outputs
          • between input (frame terminal and     75 V DC, 60 V AC    • Number                                  8 (only FM 355S)
            the central grounding point)
                                                                      Output voltage
          • Between analog inputs and NANA        2.5 V DC
            (UCM )                                                    • At ”1” signal                           L+ (-2.5 V)
          Total current of the digital outputs,   400 mA              Switch 2 outputs in parallel              For logic operations
          max.                                                        Setting a digital input                   Possible
          Power loss                                                  Switching frequency
          • FM 355 C, typ.                        6.5 W               • With resistive load/lamp load, max. 100 Hz
          • FM 355 C, max.                        7.8 W               • Inductive loads, max.                   0.5 Hz
          • FM 355 S, typ.                        5.5 W               Voltage induced on circuit interrup-      L+(-1.5 V)
          • FM 355 S, max.                        6.9 W               tion limited to (internally), typ.
          • Rated value                           24 V DC
          • At ”0” signal                         -3 to +5 V
          • At ”1” signal                         13 to 30 V
        ■ Technical specifications
          Number of controllers                   4                              Connection of two-wire BEROs            Possible
          General specifications                                                 • Permissible quiescent current,        1.5 mA
                                                                                   max.
          Rated load voltage L+                   24 V DC
                                                                                 Line length
          • Permitted range                       20.4 to 28.8 V
                                                                                 • Unshielded                            600 m
          Electrical isolation
                                                                                 • Shielded                              1000 m
          • To backplane bus                      Yes (optocoupler)
                                                                                 Digital outputs
          • Between channels                      No
                                                                                 • Number of inputs                      8 (only FM 355-2S)
          Permissible potential difference
                                                                                 Output voltage
          • Between input (frame terminal and     75 V DC, 60 V AC
            the central grounding point)                                         • At signal ”1”                         L+ (-2.5 V)
          • Between analog inputs and NANA        2.5 V DC                       Output current
            (UCM )
                                                                                 • At ”1” signal
          • Isolation tested at                   500 V DC
                                                                                  - rated value                          0.1 A
          Current consumption
                                                                                  - permitted range                      5 to 150 mA
          • From backplane bus, typ./max.         50 mA/75 mA
                                                                                 • At ”0” signal, residual current,      0.5 mA
          • From L+ (without load)                                                 max.
            - FM 355-2 C, typ.                    260 mA                         Load resistance                         240 Ω to 4 kΩ
            - FM 355-2 C, max.                    310 mA                         Output power
            - FM 355-2 S, typ.                    220 mA                         • Lamp load, max.                       5W
            - FM 355-2 S, max.                    270 mA                         Switch 2 outputs in parallel            For logic operations
          Total current of the digital outputs,   400 mA                         Setting a digital input                 Possible
          max.
                                                                                 Switching frequency
          Power loss
                                                                                 • With resistive load/lamp load, max. 100 Hz
          • FM 355-2 C, typ.                      6.5 W
                                                                                 • Inductive loads, max.                 0.5 Hz
          • FM 355-2 C, max.                      7.8 W
                                                                                 Voltage induced on circuit interrup-    L+(-1.5 V)
          • FM 355-2 S, typ.                      5.5 W                          tion limited to (internally), typ.
          • FM 355-2 S, max.                      6.9 W                          Short-circuit protection of output      Yes, electronic
          Required front connector                2 x 20-pin                     Line length
          Dimensions (W x H x D) in mm            80 x 125 x 120                 • Unshielded                            600 m
          Weight, approx.                         470 g                          • Shielded                              1000 m
          Digital inputs                                                         Analog inputs
          • Number                                8                              Number of inputs                        4
          Input voltage                                                          Input range (rated values/ display
                                                                                 range/ input resistance)
          • Rated value                           24 V DC
                                                                                 • Voltage                               0 to 10V/ -1.75 to 11.75V/
          • At ”0” signal                         -3 to +5 V                                                             100 kΩ
          • At ”1” signal                         13 to 30 V                     • Current                               0 to 20 mA/
          Input current at ”1” signal, typ.       7 mA                                                                   -3.5 to 23.5 mA/50 Ω
                                                                                                                         4 to 20 mA/ 0 to 23.5 mA; 50 Ω
          Input characteristic                    In accordance with ICE 1131,
                                                  Typ 2
             Connection for transducer               For voltage measurement and for      • Short-circuit protection              Yes
                                                     current measurement (as 4-wire       • Short-circuit current, max.           25 mA
                                                     transducers)
                                                                                          Current output
             Linearization of characteristic         Yes, parameterizable
                                                                                          • Idle voltage, max.                    18 V
             • For thermocouples                     Type B,E, J, K, R, S
                                                                                          Connection of actuators
             • For resistance thermometers           Pt 100 (standard range)
                                                                                          • For voltage output                    2-lead connection
             Temperature compensation                Yes, parameterizable, via internal
                                                     sensor or externally with Pt 100     • For current output                    2-lead connection
             Noise voltage suppression for f = n                                          Operating error limit (in the entire
             x (fl +/- 1 %), fl = noise frequency                                         temperature range of the modules,
                                                                                          relative to input range)
             • Common-mode noise, min.               70 dB
               (Vpp < 2.5 V)                                                              • Voltage                               +/- 0.5%
             • Series-mode noise, min.               40 dB                                • Current                               +/- 0.6%
               (peak value of fault < rated value                                         Basic error threshold (operating
               of input range)                                                            error threshold at 25 °C, with refer-
             Operational limit (in the entire tem-   +/-0.06 to +/-0.7%                   ence to output range)
             perature range, referred to input                                            • Voltage                               +/- 0.2%
             range)
                                                                                          • Current                               +/- 0.3%
                                                                                          Temperature                             +/- 0.02%/K
                                                                                          Linearity error                         +/- 0.05%
                                                                                          Cable length (shielded)                 200 m, 50m at 80 mV and ther-
                                                                                                                                  mocouples
        ■ Technical specifications
          Position sensors                                                              Polarity reversal protection        Yes
          Number                                 Up to 4                                Operating conditions
          Max no. of measuring points            8, up to 4 per sensor                  Ambient temperature
          Measuring range                        3 m and 6 m                            • Horizontal mounting position      0 °C to 60 °C
          Resolution                             0.05 mm (up to 3 m measuring           • for vertical installation         0 °C to 40 °C
                                                 range) and 0.1 mm
                                                                                        Relative air humidity               5 % to 95 % (without condensation)
          Programmable measuring cycle           0.5 ms to 16 ms
                                                                                        Atmospheric pressure                860 hPa to 1080 hPa
          Supply voltage for sensors
                                                                                        Pollutant concentration
          • With Electrical isolation                                                   • SO2 max.                          10 ppm
            - voltage                            ± 15 V                                 • H2S max.                          1 ppm
            - current                            200 mA                                 Vibration
          • Without electrical isolation                                                • 10 Hz to 57 Hz                    0.075 mm amplitude
            - voltage                            24 V                                   • 57 Hz to 150 Hz                   1 g constant acceleration
            - current, total                     300 mA, without electrical isolation   Conditions for storage and trans-
          Total power for supplying              7.2 W                                  port (in original packaging)
          the sensors max.                                                              • Free fall (to IEC 1131-2)         <1m
          Supply voltage for the module                                                 • Temperature (to IEC 1131-2)       -40 °C to +70 °C
          Current consumption                                                           • Atmospheric pressure              < 700 hPa (3000 m above sea level)
          • Internal from S7-300 backplane bus   Typ. 80 mA; max. 1000 mA,              • Relative air humidity             5 % to 95 % (without condensation)
          • External voltage                     20.4 V to 28.8 V                       Casing
          • Without sensors max.                 0.1 A                                  Dimensions (W x H x D in mm)        80 x 125 x 120
          • With sensors max.                    0.85 A                                 Weight                              500 g
          Fuse                                   1.0 A slow-acting                      Degree of protection                IP 20
        ■ Technical specifications
          General                                                    SSI encoder inputs
          Rated load voltage L+                24 V DC               Position encoders                   Absolute
          • Permitted range                    20.4 to 28.2 V        Cable length (shielded), max.       320 m at 125 kHz
          Electrical isolation                 No                                                        160 m at 250 kHz
          Encoder supply                                                                                 60 m at 500 kHz
          • Output voltage                     L+ - 0.8 V                                                20 m at 1 MHz
          • Output current, max.               900 mA                Digital inputs
          Interrupts                                                 Input voltage
          • Diagnostics interrupt              Configurable          • At ”1” signal                     11 to 30,2 V
          Current consumption                                        • At "0" signal                     -3 to 5 V
          • From S7-300 ® backplane bus, max. 160 mA                 Input current
          • From L+, max.                      10 mA                 • At "1" signal, typ.               9 mA
          Power loss                           3W                    • At "0" signal, max.               2 mA
          Dimensions (W x H x D) in mm         40 x 125 x 120        Input delay                         300 µs
          Required front connector             20-pin                Connection of 2-wire BERO           Yes
          Weight                               235 g                 Cable length (shielded), max.       600 m
          SM 338 POS input module              6ES7 338-4BC00-0AB0   SIMATIC Manual Collection           6ES7 998-8XC01-8YE0
          for position detection with                                Electronic manuals on CD-ROM,
          ultrasonic sensors with start/stop                         multi-language
          interface
                                                                     SIMATIC Manual Collection           6ES7 998-8XC01-8YE2
          Front connector                                            updating service for 1 year
          20-pin, with screw-type terminals                          Current S7 Manual Collection CD
                                                                     as well as the three following
          • 1 unit                             6ES7 392-1AJ00-0AA0   updates
          • 100 units                          6ES7 392-1AJ00-1AB0
                                                                     S7-300 manual
          20-pin, with spring-loaded           6ES7 392-1BJ00-0AA0   Design, CPU data, module data,
          terminals                                                  instruction list
                                                                     German                              6ES7 398-8FA10-8AA0
          Front door, improved version         6ES7 328-0AA00-7AA0
                                                                     English                             6ES7 398-8FA10-8BA0
          e.g. for 32-channel modules;
          permits connection of 1.3 mm2/16                           French                              6ES7 398-8FA10-8CA0
          AWG conductors
                                                                     Spanish                             6ES7 398-8FA10-8DA0
                                                                     Italian                             6ES7 398-8FA10-8EA0
        ■ Technical specifications
          Main applications                                             Measuring properties
          • Load measurement on cranes           •                      Class III EU type approval for com-    –
                                                                        mercial scales (with verification
          • Overload protection                  •                      capability)
          • Belt tensioning devices              •                      Accuracy (definition acc. to mea-      0.05%
          • Platform scales                      •                      suring technology)
          • Fill level measurements (contain-    •                      nIND acc. to EN 45 501                 3000 (*)
            ers/bins)                                                   min. measuring signal ∆Umin pro d      1.5 µV
                                                                        (*) no verification capability
          • Proportioning and mixing scales      –
                                                                        Internal resolution                    65 535
          • Scales with verification capacity    –
                                                                        Data format for weight values          2 byte (fixed point)
          Intrinsically-safe load cell power-    Optional (Ex-l)
          ing                                                           No. of measurements/second             50
          Stand-alone (without SIMATIC)          With IM 153-1          Filters                                Exponent filter: 0.05 to 5 Hz
                                                                                                               Mean value filter
          Integration in:
                                                                        Scale functions
          • S5-90/S5-95U/S5-100U                 –
                                                                        • Weight values                        Gross weight
          • S5-95U/DP (PROFIBUS master)          Via ET 200M
                                                                        • Limit                                2 (min/max)
          • S5-115U/ -135U/ -155U                Via ET 200M
                                                                        • Scale standstill                     –
          • S7-300                               Direct integration
                                                                        • Zero setting function                Via command
          • S7-400                               Via ET 200M
                                                                        Proportioning functions
          • PCS 7                                Via ET 200M
                                                                        • Control of coarse/fine flow valves   –
          • M7-300                               Direct integration
                                                                        • Tolerance monitoring                 –
          • M7-400                               Via ET 200M
                                                                        • Material flow monitoring             –
          • C7                                   Via IM bzw. ET 200M
                                                                        • Automatic proportioning optimiza-    –
          • TELEPERM M (AS 388/488/TM)           –                        tion
          Communication interfaces               SIMATIC S7 (P-Bus)     • Automatic reproportioning            –
                                                 RS 232                 • Inching mode                         –
          Process interfaces                                            Integral display and operator          –
          • Digital inputs                       –                      panel
          • Digital outputs                      –                      Module parameterization                Using SIMATIC S5/S7/M7/C7 or
                                                                                                               PC parametizaton software
          • Pulse input                          –                                                             SIWATOOL U
          • Analog output/analog input           –/–                    UL/CSA/FM approval                     •
          Remote display connection              •                      IP degree of protection to             IP 20
          (via serial interface)                 Gross, channel 1, 2    DIN EN 60 529; IEC 60 529
                                                 specified value 1, 2
          Printer connection                     –
          •    Function included
          –    Function not included
        ■ Technical specifications
          Main applications                                                         Measuring properties
          • Load measurement on cranes           –                                  Class III EU type approval for com-    6000 d
                                                                                    mercial scales (with verification
          • Overload protection                  –                                  capability)
          • Belt tensioning devices              –                                  Accuracy (definition acc. to mea-      0.01%
          • Platform scales                      •                                  suring technology)
          • Fill level measurement               •                                  nIND acc. to EN 45 501                 6000
            (container/bins)                                                        min. measuring signal ∆umin pro d      0.5 µV
                                                                                    (*) no verification capability
          • Proportioning and mixing scales      •
                                                                                    Internal resolution                    ± 524,288
          • Scales with verification capacity    •
                                                                                    Data format for weight values          4 byte (fixed point)
          Intrinsically safe load cell           Optional (Ex-l)
          powering                                                                  No. of measurements/second             50
          Stand-alone (without SIMATIC)          •                                  Filters                                Exponent filter: 0.05 to 5 Hz
                                                                                                                           Mean value filter
          Integration in:
                                                                                    Scale functions
          • S5-90/S5-95U/S5-100U                 Via RS 232/TTY + CP
                                                                                    • Weight values                        Gross/net/tare
          • S5-95U/DP (PROFIBUS master)          Via RS 232/TTY + CP
                                                                                    • Limit                                4 (min/max/empty/overfill)
          • S5-115U/S5-135U/S5-155U              Via ET 200M
                                                                                    • Scale standstill                     •
          • S7-300                               Direct integration
                                                                                    • Zero setting function                Via command and automatically
          • S7-400                               via ET 200M
                                                                                    Proportioning functions
          • PCS 7                                via ET 200M
                                                                                    • Control of coarse/fine flow valves   •
          • M7-300                               –
                                                                                    • Tolerance monitoring                 •
          • M7-400                               –
                                                                                    • Material flow monitoring             •
          • C7                                   Via IM or ET 200M
                                                                                    • Automatic proportioning optimiza-    •
          • TELEPERM M (AS 388/488/TM)           Via ET 200M                          tion
          Communication interfaces               SIMATIC S7 (P bus) RS 232, TTY     • Automatic reproportioning            •
          Process interfaces                                                        • Inching mode                         •
          • Digital inputs                       3 (assignable)                     Integral display and operator          –
          • Digital outputs                      4 (assignable)                     panel
• Signal level In acc. with EIA-RS 232 MTBF (SN 29500) 172 000 h at +40°C
          • Protocols                          SIWAREX-Protokoll
                                               3964R, XON/XOFF (printer) 2)
          Serial interface 2                   TTY:
          • Transmission rate                  9600 bps
          • Parity                             Even
          • No. of data bit / stop bit         8/1
          1) Up to 1000 m, depending on the gas group.
          2) Serial printer, ANSI-, EPSON-, IBM-compatible
          SIWAREX M weighing module            7MH4 553-1AA41                 Cable LI2Y (ST)                       7MH4 702-8AB
                                                                              to connect SIWAREX M to
          with verification capability                                        junction boxes
          Configuring package                  7MH4 583-3FA63                 Front connector
          incl. SIWATOOL parameterization                                     20-pin, with screw-type terminals
          software, manual on CD-ROM
          and example programs                                                • 1 unit                              6ES7 392-1AJ00-0AA0
                                                                              • 100 units                           6ES7 392-1AJ00-1AB0
          SIWAREX M manual
          German                               7MH4 593-3AA11                 20-pin, with spring-loaded            6ES7 392-1BJ00-0AA0
          English                              7MH4 593-3AA21                 terminals
          9-conductor cable
                                                                              Shield connecting element             6ES7 390-5AA00-0AA0
          to connect SIWAREX M to 9-pin
          PC interface (RS 232C)                                              80 mm wide, with 2 rows for
                                                                              4 terminal elements each
          2m                                   7MH4 702-8CA
                                                                              Terminal elements
          5m                                   7MH4 702-8CB
                                                                              2 units
                                                                              For 1 cable with 4 to 13 mm           6ES7 390-5CA00-0AA0
                                                                              diameter
        ■ Technical specifications
          Main applications                                                     Accuracy (definition in acc. with      0.01%
                                                                                measuring technology)
          • Load measurement on cranes            –
                                                                                nIND in acc. with EN 45 501            6000
          • Overload protection                   –
                                                                                Min. measuring signal umin pro d (*)   0.5 µV
          • Belt tensioning devices               –                             no verification capability
          • Platform scales                       –                             Internal resolution                    1,048,576
          • Fill level measurement                •                             Data format for weight values          4 byte (fixed point)
            (containers/bins)
                                                                                No. of measurements/second             50
          • Propoortioning and mixing scales      •
                                                                                Filters                                Mean value filter, 4 stages
          • Scales with verification capability   •
                                                                                Scale functions
          Intrinsically-safe load cell            Optional (Ex-l)
          powering                                                              • Weight values                        Gross/net
          Stand-alone (without SIMATIC)           •                             • Limits                               –
          Integration in                                                        • Scales standstill                    •
          • S5-90/-95U/-100U                      –                             • Zero setting function                Via command or automatically
          • S5-95U/DP (PROFIBUS-master)           –                             Proportioning functions
          • S5-115U/-135U/-155U                   –                             • Control of coarse/fine flow valves   •
          • S7-300                                Direct integration            • Tolerance monitoring                 •
          • S7-400                                Via ET 200M                   • Material flow monitoring             •
          • PCS 7                                 –                             • Autom. proportioning optimization    •
          • M7-300                                –                             • Automatic reproportioning            •
          • M7-400                                –                             • Inching mode                         •
          • C7                                    Via IM or ET 200M             Integral display and operator          –
                                                                                panel
          • TELEPERM M (AS 388/488/TM)            –
                                                                                Module parameterization                Via SIMATIC S7 or SIWATOOL A
          Communication interfaces                SIMATIC S7 (P-Bus)
                                                                                                                       PC-parameterization software
                                                  RS 232, TTY
                                                                                UL/CSA/FM approval                     –
          Process interfaces
                                                                                IP degree of protection to             In S7 frame: IP 20
          • Digital input                         3                             DIN EN 60 529; IEC 60 529              Stand-alone: IP 10
          • Digital output                        4                             Load cell supply
          • Pulse input                           –                             • Supply voltage Us (rated value)      10.2 V DC
          • Analog output/analog input            •/–                           • Max. supply current                  ≤ 180 mA
          Remote display connection               • (verification capability)   Permiss. load resistance:
          (via serial interface)                  Gross/net                      - RLmin                               > 60 Ω
          Printer connection                      • (verification capability)    - RLmax                               < 4010 Ω
          Measuring properties                                                                                         With Ex(i) interface:
          Class III EU type approval for com-     6000 d (2 x 6000 d)            - RLmin                               > 87 Ω
          mercial scales (with verification
          capability)                                                            - RLmax                               < 4010 Ω
          •    Function included
          –    Function not included
            SIWAREX A weighing module           7MH4 421-1AA01              Cable LI2Y (ST)                       7MH4 702-8AB
                                                                            to connect SIWAREX M to
            with verification capability, for                               junction boxes
            maximum accuracy and fast pro-
            cesses                                                          Front connector
        ■ Technical specifications
          Inputs                                16 switches           Power losses, typ.                0.35 W
          Outputs                               16 LEDs               Dimensions (W x H x D) in mm      40 x 125 x 120
          Electrical isolation                  No                    Weight, approx.                   190 g
          Power consumption max.                80 mA
        ■ Technical specifications
          Current consumption                                         Dimensions (W x H x D) in mm      40 x 125 x 120
          • From backplane bus, max.            5 mA                  Weight                            180 g
          Power losses, typ.                    0.03 W
        ■ Technical specifications
          CP 340 Version                                      RS 232 (V.24)                      20 mA (TTY)                    RS 422/485 (X.27)
          Interfaces
          • Number of inputs                                  1, electrical isolation
          • Transmission rate max.                            19.2 kbit/s                        9.6 kbit/s                     19.2 kbit/s
          • Transmission rate min.                            2.4 kbit/s                         2.4 kbit/s                     2.4 kbit/s
          • Cable length, max.                                15 m                               100 m /1000 m (act./passive)   1200 m
          ASCII:
          • Max. frame length                                 1024 byte
          • Transmission rate, max.                           9.6 kbit/s
          3964 (R):
          • Max. frame length                                 1024 byte
          • Transmission rate, max..                          19.2 kbit/s
          Printer driver:
          • Transmission rate, max.                             9.6 kbit/s
          • Supported printers                                  HP-Deskjet, HP-Laserjet, IBM-Proprinter, user-defined
          • Memory requirements of the handling blocks, approx. 2700 byte (data communications, sending and receiving)
          Current consumption typ.                            165 mA                             220 mA                         165 mA
          Power loss                                          0.85 W
          Dimensions (W x H x D) in mm                        40 x 125 x 120
          Weight, approx.                                     300 g
www.DataSheet4U.com
        ■ Technical specifications
          Version                             RS 232C (V.24)                     20 mA (TTY)             RS 422/485 (X.27)
          Interfaces
          • Number of inputs                  1, electrical isolation
          • Transmission rate
            - Max.                            76.8 kbit/s                        19.2 kbit/s             76.8 kbit/s
            - Min.                            0.3 kbit/s                         0.3 kbit/s              0.3 kbit/s
          • Cable length, max.                15 m                               1000 m                  1200 m
          • Connection technique              9-pin Sub-D male                   9-pin Sub-D female      15-pin Sub-D socket connec-
                                                                                                         tor
          Implemented protocol driver         ASCII;
                                              3964 (R) (not with RS 485);
                                              RK 512 (not with RS 485);
                                              customized driver can be loaded
          ASCII
          • Max. frame length                 1024 byte
          • Transmission rate, max.           76.8 kbit/s (half-duplex) / 38.4 kbit/s (full-duplex)
          3964 (R)
          • Max. frame length                 1024 byte
          • Transmission rate, max.           76.8 kbit/s
          RK 512
          • Max. frame length                 1024 byte
          • Transmission rate, max.           76.8 kbit/s
          Memory requirements                 5500 byte (data communication, sending and receiving)
          of the function blocks, approx.
          External voltage supply             24 V DC (3 screw-type terminals: L+, M, GND)
          Current consumption typ.            200 mA                             200 mA                  240 mA
          • From backplane bus, max.          70 mA                              70 mA                   70 mA
          Power loss                          4.8 W                              4.8 W                   5.8 W
          Dimensions                          40 x 125 x 120
          (W x H x D) in mm
          Weight, approx.                     300 g
                                       10 m     6ES7 902-1AC00-0AA0
                                                                      MODBUS Master (RTU format)
                                       15 m     6ES7 902-1AD00-0AA0
                                                                      • Single license                       6ES7 870-1AA01-0YA0
www.DataSheet4U.com
           CP 341 communications                6ES7 341-1BH01-0AE0
           processor                                                  • Single license, without software     6ES7 870-1AA01-0YA1
           with one 20 mA (TTY) interface                               or documentation
                                                                      MODBUS Slave (RTU format)
           20 mA (TTY) connecting cable
                                                                      • Single license                       6ES7 870-1AB01-0YA0
           for linking to SIMATIC S7
                                       5m       6ES7 902-2AB00-0AA0
                                                                      • Single license, witout software or   6ES7 870-1AB01-0YA1
                                       10 m     6ES7 902-2AC00-0AA0     documentation
                                       50 m     6ES7 902-2AG00-0AA0   Data Highway (DF1 protocol)
        ■ Technical specifications
          AS-Interface specification          V 2.1                           Power loss                         2W
          Bus cycle time                      5 ms for 31 slaves              Permissible ambient conditions
                                              10 ms for 62 slaves
                                                                              • Operating temperature            0 °C to +60 °C
          Interfaces
                                                                              • Transport/storage temperature    -40 °C to +70 °C
          • Assignment of analog address      16 byte I/O and P-bus S7-300
            space in PLC                                                      • Relative humidity                Max. 95% at +25 °C
        ■ Technical specifications
           Data transmission rate              9.6 to 12 Mbit/s              Multi-protocol operation
                                               (exception: 3 and 6 Mbit/s)
                                                                             • Number of usable connections      Max. 32 (without DP); max. 28
           Interfaces                                                                                            (with DP)
           • Connection to PROFIBUS            9-pin Sub-D socket            • Size of DP diagnostics data per
           • Supply voltage                    4-pole terminal block           connected slave                   Max. 240 byte
        ■ Technical specifications
          Data transmission rates                9.6 kbit/s to 12 Mbit/s       DP master function
                                                 (exception: 3 and 6 Mbit/s)
                                                                               • DP master                             DP-V0
          Interfaces
                                                                               • Number of operational DP slaves       124
          • Connection to PROFIBUS               2 x duplex socket
                                                                               • Size of the DP data ranges in total
          • Supply voltage                       4-pin terminal block
                                                                                - DP input range                       2160 byte
          Supply voltage                         24 V DC
                                                                                - DP output range                      2160 byte
          Current consumption
                                                                               • Size of the DP data ranges per
          • From backplane bus                   150 mA                          connected slave
          • From 24 V DC                         250 mA                         - DP input range                       244 byte
          Power loss                             6.75 W                         - DP output range                      244 byte
          Maximum distance between 2 adja-                                     • Size of the DP diagnostic data per    Max. 240 byte
          cent network stations                                                  connected slave
          • Plastic FOC                          Max. 50 m                     DP slave function
          • PCF FOC                              Max. 300 m                    • Size of DP data storage areas
          Perm. ambient conditions                                              - DP input range                       240 byte
          • Operating temperature                0 °C to +60 °C                 - DP output range                      240 byte
          • Transport/storage temperature        -40 °C to +70 °C              PG/OP communication
          • Relative humidity                    Max. 95% at +25°C             • Number of operable OP connec-         16
                                                                                 tions (acyclic services)
          • Operating altitude
                                                                               S5-compatible interface (SEND/
          Design                                 Compact assembly              RECEIVE)
          • Module format                        40 x 125 x 120                • No. of usable connections             Max. 16
          • Dimensions (W x H x D) in mm         Approx. 300 g                 • Useful data/connections               Max. 240 byte
          • Weight                               4                                                                     (send and receive)
          Performance data                                                     Multi-protocol operation
          S7 communication                                                     • No. of usable connections             32 (without DP); max. 28 (with DP)
          • No. of usable connections            Max. 16
www.DataSheet4U.com
        ■ Technical specifications
          Data transmission rate              9.6 to 12 Mbit/s           S7 communication
          Interfaces                                                     performance data
        ■ Technical specifications
          Data transmission rate                10 Mbit/s und 100 Mbit/s           Design
          Interfaces                                                               • Dimensions (W x H x D) in mm          80 x 125 x 120
          • Connection to Industrial Ethernet   15-pin Sub-D socket                • Weight                                Approx. 600 g
            (10/100 Mbit/s)                     (automatic switching between
                                                AUI and industrial twisted pair)   Configuration software                  NCM S7 for Industrial Ethernet
          • 10BaseT, 100BaseTX                  RJ45                                                                       (supplied with STEP 7 V5.x)
          • Supply voltage                      4-pin terminal block               Performance data
          Supply voltage                        +5 V DC (±5%) and +24 V DC         S5-compatible communication
                                                (±5%)                              (SEND/RECEIVE)
          Current consumption                                                      Sum of all simultaneously operable      Max. 16
          • From backplane bus                  70 mA                              ISO/TCP/UDP connections
          • From external 24 V DC               Typ. 400 mA                        • No. of useful data                    Max. 8 KB
                                                max. 580 mA (depending on the        - ISO or TCP                          Max. 8 KB
                                                interface used)                      - UDP                                 Max. 2 KB
          Power loss                            8.3 W                              S7 communication
          Perm. ambient conditions                                                 • Number of connections                 Max. 16
          • Operating temperature               0 °C to +60 °C                     PG/OP communication
          • Transport/storage temperature       -40 °C to +70 °C                   • Number of operable OP connec-         16
          • Relative humidity                   Max. 95% at +25 °C                   tions (acyclic services)
          Design                                                                   Multi-protocol operation
          • Module format                       Compact S7-300 module              • Sum of all simultaneously operable    Max. 32
                                                double width                         connections
        ■ Technical specifications
          Data transmission rate                10 Mbit/s or 100 Mbit/s              Design
          Interfaces                                                                 Configuration software                 NCM S7 for Industrial Ethernet
          • Connection to Industrial Ethernet   15-pin Sub-D socket (automatic                                              (supplied with STEP 7 V5.x)
            (10/100 Mbit/s)                     switching betw. AUI and industrial   Performance data
                                                and twisted pair)
          • 10BaseT, 100BaseTX                  RJ45                                 IT communications
          • Supply voltage                      4-pin terminal block                 Number of connections to an e-mail     Max. 1
          Supply voltage                        +5 V DC (±5%) and                    server
                                                +24 V DC (±5%)                       Memory capacity of the file system     10 MB
          Current consumption                                                        S5-compatible communication
          • From backplane bus                  70 mA                                (SEND/RECEIVE)
          • From external 24 V DC               Typ. 400 mA                          • Sum of all simultaneously operable   Max. 16
                                                max. 580 mA                            ISO/TCP/UDP connections
                                                (depending on the interface
                                                                                     • Number of useful data
                                                used)
                                                                                       - ISO or TCP                         Max. 8 KB
          Power loss                            8.3 W                                  - UDP                                Max. 2 KB
          Perm. ambient conditions                                                   S7 communication
          • Operating temperature               0 °C to +60 °C                       • Number of connections 1)             Max. 16
          • Transport/storage temperature       –40 °C to +70 °C
                                                                                     PG/OP communication
          • Relative humidity                   Max. 95% at +25 °C
                                                                                     • Number of usable                     Max. 16
          Design                                                                       OP connections
          • Module format                       Compact module S7-300 double           (acyclic utilities)
                                                width
                                                                                     Multi protocol operation
          • Dimensions (B x H x T) in mm        80 x 125 x 120
                                                                                     • Sum of all simultaneously            Max. 32
          • Weight                              Approx. 600 g                          operable connections
          1) Depends on the S7 CPU being used
          CP 343-1 IT communications            6GK7 343-1GX11-0XE0                  NCM S7 configuration software          Delivered with STEP 7 V5
          processor®                                                                 for Industrial Ethernet                upwards
          for connecting SIMATIC S7-300 to                                           NCM S7 manual for Industrial           See CP 343-1
          Industrial Ethernet for S5-compati-                                        Ethernet
          ble communication, S7 communi-
          cation, e-mail and www server,
          10/100 Mbit/s, with electronic
          manual on CD-ROM
        ■ Technical specifications
          Data transmission rate                10 Mbit/s and 100 Mbit/s          Design
                                                autosensing                       • Dimensions (W x H x D) in mm          80 x 125 x 120
          Interfaces                                                              • Weight                                Approx. 600 g
          • Connection to Industrial Ethernet   15-pin Sub-D socket with slide    Degree of protection                    IP 20
            AUI/industrial twisted pair         catch (automatic switchover
                                                between AUI and twisted pair)     Configuration
          • Twisted pair (10Base/100BaseT)      RJ45 socket                       • Configuration software for            Option package SIMATIC iMap
          • Connection for power supply         4-pin terminal block                PROFInet
                                                                                  • Configuration software for            NCM S7 for Industrial Ethernet
          Supply voltage                        +5 V DC (±5%) and +24 V DC          additional services                   (supplied with STEP 7 v.5.x)
                                                (±5%)
                                                                                  Performance data
          Current consumption
          • From backplane bus                  70 mA                             PROFInet Communication
          • From external 24 V DC               Typ. 400 mA max. 580 mA           • Number of communication partners      Max. 64
                                                (depends on the interface being   S5 compatible communication
                                                used)                             (SEND/RECEIVE)
          Power loss, approx.                   10 W                              • Sum of all simultaneously operable    Max. 16
                                                                                    TCP/UDP connections
          Perm. ambient conditions                                                • Number of useful data,
          • Operating temperature               0 °C to +60 °C                      - TCP                                 Max. 8 KB
          • Transport/storage temperature       -40 °C to +70 °C                    - UDP                                 Max. 2 KB
          • Relative humidity                   Max. 95% at +25 °C
                                                                                  S7 and PG/OP communication
                                                                                  • Number of connections1)               Max. 16
          Design
                                                                                  • Multi-protocol operation
          • Module format                       Compact module S7-300, double
                                                width                             • Sum of all simultaneously             Max. 32
                                                                                    operable connections
          1) Depends on the S7 CPU being used
          CP 343-1 PN communications            6GK7 343-1HX00-0XE0               NCM S7 configuration software           Delivered with STEP 7 V5
          processor                                                               for Industrial Ethernet                 onwards
          for connecting SIMATIC S7-300 to                                        NCM S7 manual for Industrial            See CP 343-1
          Industrial Ethernet with PROFInet                                       Ethernet
          function, TCP/IP, S7 communica-
          tion, FETCH/WRITE, SEND/                                                SIMATIC iMap V1.1
          RECEIVE, with/without RFC 1006,
                                                                                  Linking editor for configuring of
          10/100 Mbit/s, with electronic
                                                                                  communication with Component
          manual on CD-ROM
                                                                                  based Automation
                                                                                  Single license                          6ES7 820-0CC01-0YX0
www.DataSheet4U.com
        ■ Technical specifications
          Front connector module                                           Front connector module 16-core and 2 x 16-core twisted ribbon
                                                                           cable from SIMATIC S7 to terminal block
          Rated operating voltage               24 V DC
                                                                           Operating voltage                   60 V DC
          Max. permissible operating voltage    60 V DC
                                                                           Continuous current per signal       1A
          Max. permissible continuous current                              conductor
          • Per connector pin                   1A
                                                                           Max. total current                  4 A/byte
          Max. permissible continuous           4 A/byte
          current                                                          Operating temperature               0 to + 60 °C
          Permissible ambient temperature       0 to + 60 °C               Outer diameter in mm 16-core/       Approx. 9.5/11.5
                                                                           2 x 16-core
          Test voltage                          0.5 kV, 50 Hz, 60 s
          Clearances and creepage               IEC 664 (1980),
          distances                             IEC 664 A (1981),
                                                to DIN VDE 0110 (01.89),
                                                overvoltage class II,
                                                pollution severity 2
          10 units
          • Spring-loaded terminals            6ES7 924-0BB00-1AB0
          • Screw-type terminals               6ES7 924-0BB00-1AA0
                                                                                                               } Available ex works
           4/116        Siemens ST 70 · 2003
                                                                                                               SIMATIC S7-300
                                                                                                                    Connection methods
                                                                                             SIMATIC TOP connect; flexible connection
        ■ Technical specifications
          Front connector with single cores, 16 channels                        Front connector with single cores, 32 channels
          Rated operating voltage             24 V DC                           Rated operating voltage             24 V DC
          Max. permissible continuous cur-    1.5 A                             Max. permissible continuous cur-    1.5 A
          rent with simultaneous loading of                                     rent with simultaneous loading of
          all cores                                                             all cores
          Permissible ambient temperature     0 to +60 °C                       Permissible ambient temperature     0 to +60 °C
          Cores types                         H05V-K single cores or UL-Style   Number of cores                     40 H05V-K- or UL/CSA-Adern
                                              1007/1569 CSA-AWM TR64
                                                                                Cross-section                       0.5 mm2, copper
          Cross-section                       0.5 mm2, copper
                                                                                Bunch diameter in mm                Approx. 17
          Bunch diameter in mm                Approx. 15
                                                                                Core color                          Blue, numbered 1 to 40 (adapter
          Core color                          Blue, numbered 1 to 20 (adapter                                       contact = core number)
                                              contact = core number)
                                                                                Contact type                        Screw contacts
          Contact type                        Screw contacts
www.DataSheet4U.com
        ■ Technical specifications
          Interface modules                               IM 365                        IM 360                       IM 361
          Max. interface modules per CPU                  1 pair                        1                            3
          Supply voltage (external)                       -                             -                            24V DC
          Current consumption
          • From 24 V DC line                             -                             -                            0.5 A
          • From internal bus (5 V)                       100 mA                        350 mA                       -
          Power loss typ.                                 0.5 W                         2W                           5W
          Dimensions (W x H x D) in mm                    40 x 125 x 120 per module     40 x 125 x 120               80 x 125 x 120
          Weight, approx.                                 580g (total)                  225 g                        505 g
IM 361 interface module 6ES7 361-3CA01-0AA0 Standard temperature range 6ES7 365-0BA01-0AA0
        ■ Technical specifications
          Power supply, type               2A                        2A                          5A                       5A                        10 A
          Order No. 1)                     6ES7 307-1BA00-           6ES7 305-1BA80-             6ES7 307-1EA00-          6ES7 307-1EA80-           6ES7 307-1KA01-
                                           0AA0                      0AA0                        0AA0                     0AA0                      0AA0
          Input                            Single-phase AC           Direct voltage              Single-phase AC          Single-phase AC           Single-phase AC
          Rated voltage Vin rated          120/230 V AC              24 to 110 V DC              120/230 V AC             120/230 V AC              120/230 V AC
                                           set with selector         Wide-range input            set with selector        set with selector         set with selector
                                           switch on the unit                                    switch on the unit       switch on the unit        switch on the unit
          Voltage range                    85 to 132 V/              16.8 to 138 V DC            85 to 132 V/170 to       93 to 132 V/187 to        85 to 132 V/170 to
                                           170 to 264 V AC                                       264 V AC                 264 V AC                  264 V AC
          Surge strength                   2.3 x Vin rated, 1.3 ms   154 V; 0.1 s                2.3 x Vin rated,1.3 ms   2.3 x Vin rated, 1.3 ms   2.3 x Vin rated, 1.3 ms
          Mains buffering at Iout rated    > 20 ms at Vin =          > 10 ms at Vin rated        > 20 ms at Vin =         > 20 ms at Vin =          > 20 ms at Vin =
                                           93/187 V                                              93/187 V                 93/187 V                  93/187 V
          Rated line frequency, range      50/60 Hz, 47 to 63 Hz -                               50/60 Hz, 47 to 63 Hz    50/60 Hz, 47 to 63 Hz 50/60 Hz, 47 to 63 Hz
          Rated current Iin rated          0.9/0.6 A                 2.7-0.6 A (4-0.9 A)         2,1/1, 3 A               2.1/1.2 A                 4.1/1.8 A
          Inrush current limiting          < 20 A, < 3 ms            < 20 A, < 10 ms             < 45 A, < 3 ms           < 45 A, < 3 ms            < 55 A, < 3 ms
          (+25 °C)
          I2t                              < 1.0 A2s                 < 5 A 2s                    < 1.2 A2s                < 1.8 A2s (typ. 1.2       < 3.3 A2s
                                                                                                                          A2s)
          Integral input fuse              T 1.6 A/250 V (not        T 6.3 A/250 V (not          F 4 A/250 V (not         T 3.15 A/250 V (not       T 6.3 A/250 V (not
                                           accessible)               accessible)                 accessible)              accessible)               accessible)
          Recommended circuit-             From 3 A, character-      From 10 A, character- From 6 A, character-           From 10 A, character- From 10 A, character-
          breaker (IEC 898) in the         istic C                   istic C, suitable for istic C                        istic C or from 6 A,  istic
          supply cable                                               DC                                                   characteristic D
          Output                           Regulated, floating       Regulated, floating         Regulated, floating      Regulated, floating       Regulated, floating
                                           direct voltage            direct voltage              direct voltage           direct voltage            direct voltage
          Rated voltage Vout rated         24 V DC                   24 V DC                     24 V DC                  24 V DC                   24 V DC
          Total tolerance                  ±3%                       ±3%                         ±3%                      ±3%                       ±3%
          • Steady-state line             • Approx. 0.1 %            Approx. 0.2 %               Approx. 0.1 %            ± 0.2 %                   Approx. 0.1 %
            compensation
          • Steady-state load             • Approx. 0.2 %            Approx. 0.4 %               Approx. 0.2 %            ± 0.4 %                   Approx. 0.5 %
            compensation
          Residual ripple (switching       < 150 mVpp                < 150 mVpp (                < 150 mVpp               < 150 mVpp                < 150 mVpp
          frequency: approx. 50 kHz)       (typ. < 20 mVpp)          typ. < 30 mVpp)             (typ. 40 mVpp)           (typ. 40 mVpp)            (typ. 40 mVpp)
          Spikes (bandwidth: 20 MHz)       < 240 mVpp                < 240 mVpp                  < 240 mVpp               < 240 mVpp                < 240 mVpp
                                           (typ. < 150 mVpp)         (typ. < 150 mVpp)           (typ. 90 mVpp)           (typ. 90 mVpp)            (typ. 100 mVpp)
          Setting range                    -                         -                           -                        -                         -
          Status indicator                 Green LED for 24 V        Green LED for 24 V          Green LED for 24 V       Green LED for 24 V        Green LED for 24 V
                                           O.K.                      O.K.                        O.K.                     O.K.                      O.K.
          Turn-on/off response             No overshoot of Vout      No overshoot of Vout        No overshoot of Vout     No overshoot of Vout      No overshoot of Vout
                                           (soft starting)           (soft starting)             (soft starting)          (soft starting)           (soft starting)
          Starting delay/voltage rise      < 3 s/typ. 60 ms          < 3 s (typ.7 ms)/typ. 5     < 2 s/typ.60 ms          < 3 s/typ.100 ms          < 1.5 s/typ. 80 ms
                                                                     ms
          1) For mounting on a standard rail (35 mm x 15 mm), versions are
             available with an integrated mounting adapter:
             Order No. 6EP1331-1SL11
                                                                                                                                                } Available ex works
             4/122        Siemens ST 70 · 2003
                                                                                                                SIMATIC S7-300
                                                                                                                                  Accessories
                                                                                                                                            DIN rail
                                                                                                                                                          4
www.DataSheet4U.com
Labeling sheets
        ■ Technical specifications
          Dimensions                         DIN A4                              Weight, approx.                      0.1 kg
          Labeling strips per sheet,         10
          pre-perforated
          ■ Overview                             • Teal-colored writable plastic   • For insertion in the front con-   • Spare part, 10 units
                                                   strips                            nector
Labelling cover