UNIVERSITY INSTITUTE OF ENGINEERING
DEPARTMENT OF MECHANICAL ENGINEERING
                REFRIGERATION & AIR CONDITIONING LAB (MEY-303)
Experiment No. 3
Aim: To evaluate the performance of domestic air conditioner.
List of Equipment Used:
                                  Table 3.1: List of Equipments
                 S.N. Equipment                      Range                  Quantity
                 1.   Power supply                   Single Phase, 220 V 1
                 2.   Socket with earth connection 5-15 amp                 1
Introduction:
      Air conditioning is the simultaneous control of the temperature, humidity, motion and purity of
      the atmosphere in a confined space. Air conditioning applies in the heating season as well as in
      the cooling season. TheAir conditioning has wide applications in submarine ships, aircrafts and
      rockets. Air conditioning is associated with the human comfort and controlling the humidity
      ratio.
Theory:
      Air conditioning may be defined as the process of removing heat from a substance under
      controlled conditions. It also includes the process of reducing and maintaining the temperature
      of a body below the general temperature of its surroundings. This is widely used for cooling of
      storage chambers in which perishable foods, drinks, and medicines are stored. Figure shows the
      schematic of the unit with complete description.
                   UNIVERSITY INSTITUTE OF ENGINEERING
                  DEPARTMENT OF MECHANICAL ENGINEERING
       REFRIGERATION & AIR CONDITIONING LAB (MEY-303)
                          Figure 3.1: VC cycle components
Compressor:
      The main function of compressor is to raise the pressure and temperature of the
      refrigerant by the compression of the refrigerant vapour and then pump it into the
      condenser.
Condenser:
      Condense the high pressure vapour refrigerant into the high pressure liquid by condenser
      fan and passes it into the receiver tank for recirculation
Capillary tube:
      Expands the liquid refrigerant at high pressure to the sub cooled liquid refrigerant at low
      pressure so that a measured quantity of liquid refrigerant is passed into the evaporator.
                   UNIVERSITY INSTITUTE OF ENGINEERING
                DEPARTMENT OF MECHANICAL ENGINEERING
      REFRIGERATION & AIR CONDITIONING LAB (MEY-303)
Evaporator:
      Evaporates the sub cooled liquid refrigerant by absorbing the sensible heat into vapour
      refrigerant and sends back into the compressor.
Vapour compression cycle:
      The refrigerant starts at some initial state or condition, passes through a series of
      processes in a definite sequence and returns to the initial condition. This series of
      processes is called a cycle.
               Figure 3.2: Standard vapour compression cycle (svcc):
The Standard Vapour Compressor Cycle (SVCC) consists of the following processes:
      • Reversible adiabatic compression from the saturated vapour to a super-heated
              condition.
      • Reversible heat rejection at constant pressure (sub cooling liquid and condensation of
              the refrigerant)
                           UNIVERSITY INSTITUTE OF ENGINEERING
                        DEPARTMENT OF MECHANICAL ENGINEERING
                REFRIGERATION & AIR CONDITIONING LAB (MEY-303)
               • Irreversible enthalpy expansion from saturated liquid to a low pressure sub cool liquid.
               • Reversible heat addition at constant pressure.
      Coefficient of performance (c.o.p):
               The coefficient of performance of (C.O.P.) of a refrigerating cycle is defined as the ratio
               between net refrigeration (output) and compressor work (input).
               COP = RE/ CW
               RE=H1 −H4
               CW=H2 −H1
               C.O.P= (H1–H4) / H2–H1
Description:
      The window air-conditioning test rig unit is required to conduct experiments and demonstrate
      the processes of cooling of atmospheric air. The unit consists of a compressor. Both evaporator
      and the air cooled condenser are mounted on board with separate fans. Air is sucked from the
      room and is supplied to the room after cooling. The system is provided with energy meter, a
      digital temperature indicator. The unit will be fitted with all instrumentation facilities so that
      temperature and pressure can be measured at different points in the air-conditioning system.
Experimental procedure:
      Starting procedure:
       1       Close valves of pressure gauges.
       2       Switch ‘ON’ the main power supply.
       3       Switch ‘ON’ the compressor.
       4       Wait for 2-3 minutes for switch ‘ON’ the compressor.
       5       Open the valves of pressure gauges.
       6       After 10 minutes note down the reading of temperature sensor.
                           UNIVERSITY INSTITUTE OF ENGINEERING
                          DEPARTMENT OF MECHANICAL ENGINEERING
                REFRIGERATION & AIR CONDITIONING LAB (MEY-303)
       7        Note down the reading of pressure gauges.
       8      Note down the voltage & ampere.
       9        Repeat steps 6 to 9 after every 10 minutes till the temperature of outlet of air   come
              constant.
      Closing procedure:
      1    Switch ‘OFF’ the compressor.
      2    Switch ‘OFF’ the mains.
Observation & Calculations:
   8.1 OBSERVATION TABLE:
   Sr.    P1              P2        T1     T2     T3      T4     T5      T6       V          I
   No. (kg/cm2)        (kg/cm2)    (°C)   (°C)   (°C)    (°C)   (°C)    (°C)    (Volts)   (Amp)
Calculations:
                H1 = (0.011×T1 −1.98)P1+ (0.652×T1) + 415.723
                H2 = (0.011×T2 −1.98)P2+ (0.652×T2) + 415.723
                H4 =1.228×T3 +199.93         (H3 =H4)
                       C.O.P = H1 –H4
                               H1 −H 2
                       UNIVERSITY INSTITUTE OF ENGINEERING
                    DEPARTMENT OF MECHANICAL ENGINEERING
            REFRIGERATION & AIR CONDITIONING LAB (MEY-303)
Nomenclature:
    Nom.                  Column Heading                         Units        Type
   C.O.P.   Co-efficient of performance for compressor             *      Calculated
     P1     Pressure at compressor suction                       kg/cm2   Measured
     P2     Pressure at compressor discharge                     kg/cm2   Measured
     T1     Temperature at compressor suction                     °C      Measured
     T2     Temperature at compressor discharge                   °C      Measured
     T3     Temperature at condenser outlet                       °C      Measured
     T4     Temperature at evaporator inlet                       °C      Measured
     T5     Temperature of air at inlet of duct                   °C      Measured
     T6     Temperature of air at outlet of duct                  °C      Measured
     H1     Enthalpy of refrigeration             effects   at   kJ/ kg   Calculated
            compressor inlet
     H2     Enthalpy of compressor work at compressor            kJ/ kg   Calculated
            outlet
                         UNIVERSITY INSTITUTE OF ENGINEERING
                       DEPARTMENT OF MECHANICAL ENGINEERING
              REFRIGERATION & AIR CONDITIONING LAB (MEY-303)
      H3      Enthalpy of sub cooling at the outlet of           kJ/ kg        Calculated
              condenser
      H4      Enthalpy of refrigerant inlet of evaporator        kJ/ kg        Calculated
       I      Ampere meter reading                               Amps           Measured
       V      Voltmeter reading                                   Volts         Measured
Precaution & maintenance instructions:
      10.1   Operate the Valves gently.
      10.2   Never run the apparatus if power supply is less than 180 volts and above 230 volts.
      10.3   Duct should be free from dust particles.
Result(s): COP of the vapour compression refrigeration system
Review Questions
Q1 What is COP?
Q2 What is VC cycle?
Q3 Explain various components of VC cycle
Q.4 what are pychrometric processes?
                  UNIVERSITY INSTITUTE OF ENGINEERING
                 DEPARTMENT OF MECHANICAL ENGINEERING
          REFRIGERATION & AIR CONDITIONING LAB (MEY-303)
Prepared By-            Reviewed By-             Approved By-
Vishal Mahajan          Dr. Gurpinder Dhindsa    Dr. Ishbir Singh