Dual Source Meter
3 Phase 4 Wire LT operated CT
                           USER MANUAL
                                  L&T Electrical & Automation
Doc. No. 4D060151 Rev E.
1. Technical Specifications
Enclosure               Engineering Plastic complying to IP-51
Dimension               96 X 96 X105 mm (HXWXD)Panel Cutout: 92 X 92 mm
Connection              3P 4W
Display                 LCD with Backlit
 Type                   kWh Meter
 Measurements           kWh / kW / Frequency/ Voltage / Current
 Starting Current       0.2% of rated current (5A)
 Class of Accuracy      Class 1.0
 Current                5A (rated), 10A (max)
Voltage (P-N)           3 X 240 V (-30 % to +20 % of Vref)
 Frequency              50 Hz ± 5%
Auxiliary Supply        88V TO 300 V AC/DC
DG Sensing Input        10V-60V DC/20V-300V AC
Weight(approximate)     470 g
Weight with Packaging   630 g
(approximate)
2. Standards Applicable
Accuracy                :   IEC62053-21 (Class 1.0)
Radio Interference      :   CISPR22
Fast Transient Burst    :   IEC61000-4-4
Surge Withstand         :   IEC61000-4-5
ESD                     :   IEC61000-4-2
Impulse Voltage         :   IEC62052-11
3. Dual Energy Registers
Two separate energy registers are provided, one for EB (Electricity Board supply) and another for
G(Generator Supply).Normally meter accumulates energy in EB register. Whenever the DG sensing
signal (10 to 60V dc /20 to 300V ac) is present, meter accumulates energy in G register. Separate
LED indication is provided on the meter front Panel,which glows when DG sensing signal is present.
4. Power On Display
Display check                                 will be the first display when meter is powered ON.
Followed by meter serial number and then firmware version will be displayed.
5. Display Modes
1) Auto Scroll Mode
  By default meter will be in auto-scroll mode. All the display
  parameters will be scrolling automatically in this mode. Scrolling
  period for two energy parameters is 8 sec and 2 sec for all other
  parameters.
2) Toggle Mode
  Press and hold SELECT Key to move to Energy-toggle mode. The display
  will alternately show“Generator energy”(indicated “G” on LCD display)
  and “Electricity Board energy” (indicated“Eb” on LCD display. There is
  no time out period in this mode. To exit from this mode press up/down
  key.
3) Manual Scroll Mode
  Press UP/DOWN Key to Scroll Manually. In this mode all the parameters
  can be scrolled through manually. If no key is pressed for 1 minute,it
  will go back to auto scroll mode.
4) Freeze Mode
To see the selected parameter continuously,press up & down buttons together
for 2 seconds. There is no time out period for freeze mode.Press up or down
button to come out of Freeze mode.The meter will go back to its previous
scroll mode(auto/manual).Freeze mode is not available in toggle mode.
6. Display Parameters
  1.Cumulative Energy KWh
  2.Cumulative Gen. Energy KWh
  3. Average Voltage
  4. Average Current
  5. Total Active Power
  6. Frequency
  7. R Phase Voltage
  8. Y Phase Voltage
  9. B Phase Voltage
  10. R Phase Current
  11. Y Phase Current
  12. B Phase Current
  13. R Phase Active Power
  14. Y Phase Active Power
 15. B Phase Active Power
  16. Phase Sequence
  17. Power on duration (ddddd.hh.mm) - Eb Cumulative
  18. Power on duration (ddddd.hh.mm) - Eb Resettable
  19. Power on duration (ddddd.hh.mm) - G Cumulative
  20. Power on duration (ddddd.hh.mm) -G Resettable
  21. Slave id
  22. Baud rate
  23. Parity
Note:
· Power on duration will be incremented only when Phase voltage is present. Time will not be
  incremented if meter is powered on in Aux voltage without any phase voltage
· Press SELECT key and DOWN key together to see the RS-485 parameters(last 3 Display parameters)
7.Entering in to Programming Mode
 Press and hold the SELECT and scroll UP key together to move
 to the Programming Mode. Press scroll DOWN key (used as
 Escape key in programming mode) to come out from the
 programming mode. “ESCAPE” will be displayed.
 Enter the Password by pressing & holding the scroll UP key.
 The default password is “0000”. Press and hold scroll UP
 to increment the value of the blinking digit. Press and hold
 SELECT and scroll UP together to shift to next digit.
Press SELECT key to enter the password. Password Accepted
('PASS ACPTD') or Password Error ('PASS Err') will be displayed.
Only if password is accepted meter will enter into programming
mode.
The following programming options are available
      -Programming CT/PT ratio
      -Reset Power on time
      -Setting slave Id
      -Setting communication port
      -Set Password
Meter will not record energy when it is in programming mode.Time out period of 2 min is
provided for programming mode.
8. Communication Port Setting
  In the Programming Menu, press and hold scroll UP key
  to get “Set Port” and then press SELECT key.
  Baud rate selection (1200 to 19200): Use UP key to
  select the desired baud rate then press SELECT
  key to set. Similarly parity (Even/odd/none)
  can be set here.
9. Password Setting
  In the Programming Menu, press and hold scroll UP key
  to get “Set Pass” and then press SELECT key
  Press UP key to change the blinking digit. Press UP and SELECT key
  together to shift to next digit. Press SELECT key to save the password
10.Programming CT/PT ratio
 In the Programming Menu, press and hold scroll UP key to get
 “Ct Pt Ratio” and then press SELECT key.
    -Press SELECT key When “Ct Pr 0001” is displayed to
     program CT Primary current.
    -Press and hold SELECT and scroll UP keys together to shift digit.
    -Press scroll UP key to change value.
    -Press SELECT key to save change. “L UPdAtE” will’
     come in display. Again press select key to store the value.
    -Scroll UP and press SELECT key When “Ct Se 0001” is displayed
     to program CT Secondary current.
    -Same as CT primary, program CT secondary.
    -Scroll UP and press SELECT key When “Pt Pr 0001”
     is displayed to program PT Primary voltage.
    -Press and hold SELECT key and scroll UP key together
     to shift digit.
    -Press scroll UP key to change value.
    -Press SELECT key to save changes. “L UPdAtE” will come in
     display. Again press select key to store the value.
    -Scroll UP and press SELECT key When “Pt SE0001”
     is displayed to program PT Secondary voltage.
    -In Same process program the PT Secondary value.
·CT RATIO * PT RATIO should not exceed 999999, if exceeded the meter will display “dAtA Err”
·Pulse Rate = 2500 imp / kWh (for CT * PT ratio = 1).
·Pulse rate will vary if CT/PT ratio is changed
·When CTPT Ratio is programmed ≥1000, energy in Mwh (Mega watthour) will be displayed as “kkWh”
.Decimal points on the display format will be changed according to the CTPT ratio programmed.
11. Reset Power On Time
In the Programming Menu, press and hold scroll
UP key to get “rSt Prt In” and then press Select key.
Press SELECT key to reset the power on duration.
Once reset is done, “rStdnE” will be displayed.
12. Slave ID Setting
In the Programming Menu, press and hold scroll UP to get “Set SL Id”
and then press SELECT key.
Press UP key to increment the SL Id value. Press together UP and
SELECT key to shift to next digit. Press select key to set the id.
Slave id can be set from 1 to 247.
Note: Once the parameters are set, press the DOWN key to come out of the programming mode.
“ESCAPE” will be displayed.This is followed by a “rEstArt” message and the meter gets restarted.
13. Communication Interface Details
RS485 interface is available to communicate with the meter.
The interface is available at the terminals. Refer “CONNECTION DETAILS” diagram.
The configuration details to communicate with the meter are given below
 Standard      RS485 (half duplex)
 Baud Rate Selectable (19200, 9600,4800, 2400, 1200) Default is 9600.
 Parity    Selectable (None, Odd, Even) Default is Even.
               The RS485 interface uses MODBUS Protocol in RTU mode.Communicating with the
               meter involves sending commands to the meter for reading and writing the
 Protocol
               particular register. The meter can be addressed with specific user defined
               meter address (Slave ID) from1 to 247
14. Memory Map
Password:
(Function Code 16)
Note: For changing any parameter, first password has to be entered, and then the parameters will
be enabled for writing. Once password is enabled, idle time is 2 minutes and then comes out of
programming mode.
 Address        Parameters                                               Words
  40513         Password for programming (PRIDES)                         3
Read Only Parameters:
(Function Code 04)
     Address                     Parameters                       Words          MF
                           Instantaneous Parameters
     30,001      Phase 1 Voltage                                     2           0.01
     30,003      Phase 2 Voltage                                    2            0.01
     30,005      Phase 3 Voltage                                    2            0.01
     30,007      Phase 1 Current                                    2            0.001
     30,009      Phase 2 Current                                    2            0.001
     30,011      Phase 3 Current                                    2            0.001
     30,013      Phase 1 Active Power                               2            0.0001
     30,015      Phase 2 Active Power                               2            0.0001
     30,017      Phase 3 Active Power                               2            0.0001
     30,019      Average Voltage                                    2            0.01
     30,021      Average Current                                    2            0.001
     30,023      Total Active Power                                 2            0.0001
     30,025      Line Frequency                                     2            0.01
     30,027      Cumulative Energy – Forward kWh (EB)               2            0.01
     30,029      Cumulative Energy – Forward kWh (DG)               2            0.01
     30,031      EB/DG status and Power in Mega/Kilo
                                                                     2
                     00:EB and Power in Kilo
                     01:EB and Power in Mega
                     10:DG and Power in Kilo
                     11:DG and Power in Mega
     30,033     Cumulative power on time EB Supply in minutes             2         1
     30,035     Resettable power on time EB Supply in minutes             2         1
     30,037     Cumulative power on time DG Supply in minutes             2         1
     30,039     Resettable power on time DG Supply in minutes             2         1
                                 st
For address 07 to 17,23 if MSB (1 word) is 1 then 2's complement of the value is to be
taken.
Read write Parameters:
(Supported by function code 6 and 16 for writing and by function code 3 for reading)
    Address          Parameters                                        Words            MF
                Communication Parameters
                 Meter Address                                            1             1
    42,385
                Baud Rate
     42,386
                2->1200; 3->2400; 4->                                     1             1
                4800; 5->9600; 6->19200
                Parity
     42,387     0->None; 1->Odd; 2->Even                                  1              1
                 CT PT ratio settings (1 to 999999)
     42,049      CT Primary                                               1              1
     42,050      CT Secondary                                             1              1
     42,051      PT Primary                                               1              1
     42,052      PT Secondary                                             1              1
 15. Warranty
Larsen & Toubro warrants that 3 Phase 4 Wire kWh Meter type Gemini is free from defects in workmanship
and material . Larsen & Toubro obligation under this warranty shall be for a period of 1 year from the
date of sale subject to the following terms and conditions provided the notice of defects and
satisfactory proof thereof is given to Larsen & Toubro by its customer within the warranty period.
1. Larsen & Toubro shall provide only repairs for the sold item.
2. Defective parts shall be serviced or replaced by Larsen & Toubro.
This warranty does not cover any defect in the product caused by accident, misuse, mishandling
includes improper electrical, mechanical installation), tamper, neglect, alteration/modification/
substitution of any of the components or parts or any attempt of internal adjustment by unauthorized
service personnel. For applicability of warranty, Larsen & Toubro shall be the sole judge. Under no
circumstance shall Larsen & Toubro Limited be liable for any consequential or resulting injury or for loss,
damage or expense directly or indirectly from the use of this product.The foregoing warranty is in lieu
of all other warranties expressed or implied and is the sole and exclusive remedy for any claim arising
from any defect in the product.
16. Disclaimer
Sufficient care is taken to provide all information regarding the product but Larsen & Toubro
does not claim any responsibility for the damage caused by using the product directly or indirectly.
OVERALL DIMENSIONS (mm)                                                               CONNECTION DETAILS
1.Meter connection should be done exactly as shown in above diagram
2.Make the CT connections on terminals 1-2 (R-Ph), 3-4 (Y-Ph) and 5-6 (B-Ph)
3.Make the PT connections on the terminals 9 (R), 10 (Y), 11 (B) and 12 (N)
4.Connect the Auxiliary Supply (88V TO 300 V AC/DC) to the terminals 13 (-ve)
  and 14 (+ve) to power ON the meter. It can be done by shorting one phase
  with auxiliary as shown in the above picture.
5.Connect the DG sensing input (10V-60V DC/20V-300V AC) on terminal
  15 (-ve) & 16 (+ve).
17. Precautions
1.The device must be installed, wired and serviced only by qualified personnel
2.Prior to any work on the device, de-energize the connected circuits before meter
   installation and disconnection.
3.Always use an appropriate voltage detection device to confirm the absence of voltage
4.Always supply the device with the correct rated voltage.
5.Failure to take these precautions could cause serious injuries
                   L&T Electrical & Automation
   Manufactured by:
     L&T Electrical & Automation
     Larsen & Toubro Limited
     KIADB Industrial Area
     Hebbal, Hootagalli
     Mysore 570018
     Karnataka, INDIA
       © 2013 LARSEN & TOUBRO