POWER POINT PRESENTATION
ON
            EHVAC Transmission
                   2018 - 2019
       IV B. Tech II semester (JNTUH-R15)
      Mr. B NAVOTHNA, Assistant Professor
ELECTRICAL AND ELECTRONICS ENGINEERING
    INSTITUTE OF AERONAUTICAL ENGINEERING
                     (Autonomous)
             DUNDIGAL, HYDERABAD - 500 043
General Overview of HVDC
  Transmission System
HISTORY
   The first 735 kV system was commissioned in Canada in 1965.
   Since then, voltage levels up to 765 kV have been introduced in Russia
    with neighboring countries, U.S.A, South Africa, Brazil, Venezuela and
    South Korea.
   The general trend of 800 kV investments is indicated in the diagram,
    which shows the total capacity of power transformers and generator step-
    up transformers for 800 kV delivered by ABB.
    Since the 90’s, the investments in 800 kV systems have been much lower
    compared to the 70’s and 80’s.
    However, plans are under way for future introduction of 800 kV in India
    and China.
UNIT-I
INTRODUCTION
WHY EHVAC?
   Reduced line losses
   High transmission efficiency
   Improved voltage regulation
   Flexibility for future system growth
   Increase in transmission capacity of the line
INTRODUCTION
   •The increased demand of electricity needs more
   generation of electrical power.
   •As the generation takes place at remote places, an
   efficient distribution system is necessary.
TYPES OF HVAC TRANSMISSION
   HVAC Transmission system can be divided into two parts
    (a) Transmission System
    (b) Distribution System
   Each part is again subdivided into two parts:
   1. Primary Transmission
   2. Secondary Transmission
HVAC TRANSMISSION SYSTEM
ADVANTAGES
   With increase in the transmission voltage size of the conductors is
  reduced (Cross section of the conductors reduce as current required to
  carry reduces).
   As the reduction in current carrying requirement losses reduces results
  in better efficiency
   Due to low current voltage drop will be less so voltage regulation
  improves
COMPARISON WITH HVDC
POINTS                 EHVAC                     HVDC
Voltage levels         220 KV,400 KV,765 KV      ± 500
Amount of power        There is limit due to     No limit
delivered              power angle and
                       inductance
Equivalent essential   Step-up transformer and   Step-up transformer,
                       step-down transformer     rectifier and inverter, step-
                                                 down transformer
Economical viability   EHVAC is economical for   HVDC is economical to
                       bulk power is to be       transmit bulk amount of
                       transmitted over a long   power and above. Over a
                       distance. 500 KM and      long distance(800 KM and
                       above                     above)
  POWER TRANSFER CAPABILITY
  V(KV)         220          400          765          1200
  P(KW)        193.6         640          2341         5760
•One765kv transmission line can carry nearly 4 times the
power carried by 400kv line.
•One  1200kv transmission line can carry more than twice
that of 765kv line.
POWER EQUATION
   The electric power transmitted by overhead AC system is approximately
    given by
                                   P=V2/Z
                       Where , V= Operating Voltage
                                Z= Surge Impedance
   The power transfer capability increases as it proportional to square of
    voltage
POWER HANDLING CAPACITY AND LINE
LOSS
   The power handling capacity of a single circuit is
                          P=E2 sinδ/Lx
                   where P = power in MW, 3-phase, Es, Er = voltages at
    the sending-end and receiving end, respectively, in kV line-line, δ =
    phase difference between Es and Er, x = positive-sequence reactance per
    phase, ohm/km, and L = line length, km.
 MECHANICAL CONSIDERATIONS IN LINE PERFORMANCE
   Conductor tension,
 Span length,
 Conductor size,
 Type of conductor
 Terrain of line,
    Direction of prevailing winds,
    Type of supporting clamp of conductor-insulator assemblies from the tower,
    Tower type,
    Height of tower,
 Type of spacers and dampers, and
    The vegetation in the vicinity of line.
In general, the most severe vibration conditions are created by winds without turbulences
    that hills, buildings, and trees help in reducing the severity.
TYPES OF VIBRATION
(1)Aeolian Vibration,
(2) Galloping, and
(3) Wake-Induced
Oscillations.
Fig 1:Stockbridge
Damper
Fig 2: Suspension Clamp
Fig 3: Spacer for two-
conductor bundle
DAMPERS AND SPACERS
COMPARISON OF AC AND DC TRANSMISSION
  RESISTANCE OF CONDUCTORS
•Conductors   used for e.h.v.
transmission lines are always
stranded. Most common
conductors
•Use a steel core for reinforcement
of the strength of aluminium, but
recently high tensile strength
aluminium is being increasingly
used, replacing the steel.
•The former is known as ACSR
(Aluminium Conductor Steel
Reinforced) and the latter ACAR
(Aluminium Conductor Alloy
Reinforced).
       SKIN EFFECT RESISTANCE IN
       ROUND CONDUCTORS
•The  skin effect causes the effective resistance of the conductor to
increase at higher frequencies where the skin depth is smaller, thus
reducing the effective cross-section of the conductor.
•The skin effect is due to opposing eddy currents induced by the
changing magnetic field resulting from the alternating current.
WHAT IS THE NEED OF BUNDLED
CONDUCTORS IN EHV TRANSMISSION
LINE?
   Primarily used to reduce the potential gradient on the surface of the
    conductors so that occurrence of Corona can be reduced.
    As an advantage we get less Inductance more capacitance less radio
    interference, reduced value of surge impedance and hence more power
    carrying capacity of the line.
ADVANTAGES OF BUNDLED CONDUCTORS
   Bundled conductors are primarily employed to reduce the corona loss and radio
    interference. However they have several advantages:
   Bundled conductors per phase reduces the voltage gradient in the vicinity of
    the line. Thus reduces the possibility of the corona discharge. (Corona effect will be
    observed when the air medium present between the phases charged up and start to
    ionize and acts as a conducting medium. This is avoided by employing bundled
    conductors)
   Improvement in the transmission efficiency as loss due to corona effect is countered.
   Bundled conductor lines will have higher capacitance to neutral in comparison with
    single lines.
    Thus they will have higher charging currents which helps in improving the power
    factor.
RESISTANCE AND INDUCTANCE OF GROUND
RETURN
   Situations that occur in practice when ground currents have important
    effect on system performance.
    Some of these are:
    Flow of current during short circuits involving ground.
    Switching operations and lightning phenomena.
   Propagation of waves on conductors.
    Radio Noise studies.
UNIT II
VOLTAGE GRADIENTS OF
CONDUCTORS
ELECTROSTATICS
   Conductors used for e.h.v. transmission lines are thin long cylinders
    which are known as 'line charges'.
   Their charge is described in coulombs/unit length which was used for
    evaluating the capacitance matrix of a multi-conductor line
   Types of important electrode configurations useful for extra high voltage
    practice in the field and in laboratories.
   Examples of this type are sphere-plane gaps, sphere-to-sphere gaps,
    point-to-plane gaps, rod-to-plane gaps, rod-rod gaps, conductor-to-tower
    gaps, conductor to-conductor gap above a ground plane, etc.
•This   is one of the oldest technique
adopted for the measurement of all the
types (dc =, ac ~ and impulse ) high
voltages of either polarity.
•   It remained the most widely used
method for decades. The field between
two identical spheres is a classical
example       of          "weakly     non
uniform" field.
• The breakdown characteristic of such a
gap is linear for the gap distances not
greater than the radius of the spheres.
•Measurement voltage is made as a
function of minimum distance at which
it can flash over or spark over.
                             FIELD OF SPHERE GAP
SURFACE VOLTAGE GRADIENT ON
CONDUCTORS
   The surface voltage gradient on conductors in a bundle governs
    generation of corona on the line which have serious consequences
    causing audible noise and radio interference.
   They also affect carrier communication and signaling on the line and
    cause interference to television reception.
   Since corona generation depends on the voltage gradient on conductor
    surfaces, this will be taken up now for e.h.v. conductors with number of
    sub-conductors in a bundle ranging from 1 to N.
   The maximum value of N is 8 at present but a general derivation is not
    difficult.
CALCULATION FOR CONDUCTOR SURFACE GRADIENT
   The conductor surface gradient is calculated from the following equation:
            E=(V/√3)*(b/(r*ln ((a/Re)*2h/ √(4h2+a2))))
            where E : conductor surface voltage gradient (kV/cm)
                 V : line voltage (kV)
                  b : factor for multiple conductors
                   r : radius of conductor (cm)
                 R : outside radius of bundle (cm)
                Re : equivalent radius of bundle conductor (cm)
                 S : distance between component conductor centers (cm)
                 a : phase spacing (cm)
                 h : height of conductor above ground (cm)
                 n : number of component conductors in bundle
WHAT ARE BUNDLED CONDUCTORS?
   At voltages above 300 kV, corona causes a significant power loss
    and radio interference if a single conductor per phase is used.
   Instead of using a single conductor, it is preferable to use two or
    more conductors per phase, in close proximity, which is
    called bundled conductors.
   Thus, a bundled conductor is a conductor made up of two or more
    sub-conductors and is used as one phase conductor.
    The high voltage gradient is reduced considerably by the use of
    bundled conductors.
NUMBER OF
SUB-
CONDUCTORS
•The  number of sub-
conductors used per phase in
an Indian transmission system
are two (for 400 kV), and four
(for 765 kV).                    Fig.1: Bundled conductors with twin, triple and quadruple sub-
                                                         conductors.
•The bundled conductors for
the proposed 1200 kV Ultra
High Voltage (UHV)
transmission system in India
will have 8 sub-conductors.
• Figure 1 shows Bundled
conductors with twin, triple
and quadruple conductor.
•Figure 2 shows a 765 kV
                                     Fig.2: 765 kV transmission line in India with 4 sub-
Transmission line in India               conductors per phase (Quadruplex bundle).
with quadruplex sub-
conductors.
BUNDLE SPACING:
   The spacing between adjacent sub-conductors is called bundle spacing and is
    almost 30 cm or more. In figure 1, bundle spacing is denoted by 'B'.
    In almost all cases, the sub-conductors are uniformly distributed on a circle.
   The radius of the pitch circle on which the sub-conductors are located is called
    bundled radius.
   The various advantages of using bundled conductors are reduced reactance,
    voltage gradient, corona loss, radio interference, and surge impedance.
UNIT III
CORONA EFFECTS
WHAT IS CORONA?
   Electric transmission lines can generate a small amount of sound energy as a result of corona.
   Corona is a phenomenon associated with all transmission lines. Under certain conditions, the
    localized electric field near energized components and conductors can produce a tiny electric
    discharge or corona that causes the surrounding air molecules to ionize, or undergo a slight
    localized change of electric charge.
   Utility companies try to reduce the amount of corona because in addition to the low levels of
    noise that result, corona is a power loss, and in extreme cases, it can damage system
    components over time.
   Corona occurs on all types of transmission lines, but it becomes more noticeable at higher
    voltages (345 kV and higher). Under fair weather conditions, the audible noise from corona is
    minor and rarely noticed.
   During wet and humid conditions, water drops collect on the conductors and increase corona
    activity. Under these conditions, a crackling or humming sound may be heard in the
    immediate vicinity of the line.
   Corona results in a power loss. Power losses like corona result in operating inefficiencies and
    increase the cost of service for all ratepayers; a major concern in transmission line design is
    the reduction of losses.
CORONA PHENOMENON AT HIGH VOLTAGE
   Corona phenomenon is the ionization of air surrounding the power
    conductors.
    Free electrons are normally present in the atmosphere.
   The free electrons will move with certain velocity depending upon the
    field strength.
    These electrons on their movement collide with the molecules of air and
    liberate more electrons.
    The process of ionization is cumulative and ultimately forms and
    electron avalanche.
ELECTRICAL BREAKDOWN
   The electrical breakdown of surrounding air around the conductor is
    accompanied by-
   a faint glow around the conductor,
   a hissing sound,
   vibration in conductors,
   formation of ozone and oxides of nitrogen,
   loss of power, and
   radio interference.
FACTORS AFFECTING CORONA LOSS IN
AN OVERHEAD TRANSMISSION LINE
   The important factors that affect the corona loss in an overhead transmission
    line are -
   frequency and waveform of supply,
   spacing between conductors,
   condition of conductor surface,
   atmospheric conditions,
   conductor diameter and
   number of conductors per phase.
 CORONA CALCULATIONS
    The following corona calculations are from Dielectric Phenomena in High Voltage
     Engineering
1.    For Concentric Cylinders in Air:
      Corona will not form when RO / RI < 2.718. (Arcing will occur instead when the voltage is
     too high.)
     2.   For Parallel Wires in Air:
     Corona will not form when X / r < 5.85. (Arcing will occur instead when the      voltage is
     too high.)
3.    For Equal Spheres in Air:
    Corona will not form when X / R < 2.04. (Arcing will occur instead when the voltage is too
     high.)
    Arcing difficult to avoid when X / R < 8
EFFECTS OF CORONA
(1) Audible Noise
(2)Radios and Television Interference
(3) Gaseous Effluents
(4) Induced Currents
(5) Fuel Ignition
(6) Cardiac Pacemakers
(7) Computer Interference
AUDIBLE NOISE
   During corona activity, transmission lines (primarily those rated at 345 kV and
    above) can generate a small amount of sound energy. This audible noise can
    increase during foul weather conditions.
   Water drops may collect on the surface of the conductors and increase corona
    activity so that a crackling or humming sound may be heard near a transmission
    line.
   Transmission line audible noise is measured in decibels using a special
    weighting scale, the “A” scale that responds to different sound characteristics
    similar to the response of the human ear.
   Audible noise levels on typical 230 kV lines are very low and are usually not
    noticeable.
   For example, the calculated rainy weather audible noise for a 230 kV
    transmission line at the right-of-way edge is about 25 dBA, which is less than
    ambient levels in a library and much less than background noise for wind and
    rain.
CORONA LOSS
   When an alternating potential difference is applied across two conductors
    whose spacing is large in compares ion with their diameter then the atmosphere
    air surrounding the conductor realize electrostatic stress.
   At low voltage there is no change in the condition of atmospheric air around the
    conductors but when the potential difference is gradually increased, a stage
    arrive when fan is luminous glow of violet color appears with the hissing sound
    .
    This phenomenon is known as visual corona. If the potential difference raised
    still further, the glow and the noise will increase eventually a spark over of air
    insulation will take place.
    This phenomenon is lies in transmission line of 100KV and above.
REDUCING POWER LOSS DUE TO
CORONA
   The use of bundle conductors reduce corona loss
    Spacing between conductors is selected so that corona is tolerable
    Since the shape of conductors affect corona loss, cylindrical shape conductors
    have uniform field that reduces corona loss than any other shape
   The voltage stress and electric field gradient should be minimized which can be
    accomplished by using good high voltage design practices. Using conductors
    with large radii reduce corona loss
    Void free solid conductors and insulators should be used
    Corona formation can be suppressed, if the terminals on high voltage
    equipment are designed with smooth round diameter rounded shapes like balls
    and the addition of corona rings to insulators of high voltage transmission lines
 CHARGE-VOLTAGE DIAGRAM WITH
           CORONA
•When   corona is absent the
capacitance of a conductor
is based on the physical
radius of the metallic
conductor. The charge-
voltage relation is a straight
line OA as shown in Figure
3 and C = q0/V0, where
V0 = the corona-inception
voltage     and     q0     the
corresponding charge.
                                 Fig. 3. Charge-Voltage diagram of corona.
RADIO INTERFERENCE
   Pulse type of corona gives interference to radio broadcast in the range of 0.5 MHz to 1.6
    MHz.
   In addition to corona generated on line conductors, there are spark discharges from
    broken insulators and loose wires which interfere with TV reception in the 80 – 20 MHz
    range.
   Corona on conductors also causes interference to Carrier Communication and Signaling
    in the frequency range 30-500 KHz. As in most gas discharge phenomenon under high
    impressed electric fields, free electrons and ions are created in space which contain very
    few initial electrons.
   We can therefore expect a buildup of resulting current in the conductor from a zero value
    to maximum or peak caused by the avalanche mechanism and their motion towards the
    proper electrode. Once the peak value is reached there is fall in current because of
    lowering of electric field due to relatively heavy immobile space charge cloud which
    lowers the velocity of ions.
   We can therefore expect pulses to be generated with short crest times and relatively
    longer fall times.
UNIT IV
ELECTRO STATIC FIELD
ELECTROSTATIC EFFECT ON
ELECTRIC-FIELD OF EHV LINE
   Electric fields are due to voltage so they are present in electrical appliances and
    cords whenever the electric cord to an appliance is plugged into an outlet (even
    if the appliance is turned off).
   Electric fields (E) exist whenever a (+) or (-) electrical charge is present. They
    exert forces on other charges within the field.
   Any electrical wire that is charged will produce an electric field (i.e. Electric
    field produces charging of bodies, discharge currents, biological effects and
    sparks). This field exists even when there is no current flowing.
    The higher the voltage, the stronger is electric field at any given distance from
    the wire.
   The strength of the electric field is typically measured in volts per meter (V/m)
    or in kilovolts per meter (kV/m). Electric fields are weakened by objects like
    trees, buildings, and vehicles. Burying power lines can eliminate human
    exposure to electric fields from this source.
ELECTROSTATIC EFFECT ON HUMAN
BEINGS
   The human body is a composed of some biological materials like blood, bone,
    brain, lungs, muscle, skin etc. The permeability of human body is equals to
    permeability of air but within a human body has different electromagnetic
    values at a certain frequency for different material.
   The human body contains free electric charges (largely in ion-rich fluids such as
    blood and lymph) that move in response to forces exerted by charges on and
    currents flowing in nearby power lines. The processes that produce these body
    currents are called electric and magnetic induction.
   In electric induction, charges on a power line attract or repel free charges within
    the body. Since body fluids are good conductors of electricity, charges in the
    body move to its surface under the influence of this electric force.
    For example, a positively charged overhead transmission line induces negative
    charges to flow to the surfaces on the upper part of the body. Since the charge
    on power lines alternates from positive to negative many times each second, the
    charges induced on the body surface alternate also.
ELECTROSTATIC EFFECT ON HUMAN
BEINGS-1
   Negative charges induced on the upper part of the body one instant flow into the
    lower part of the body the next instant. Thus, power-frequency electric fields
    induce currents in the body (Eddy Current) as well as charges on its
    surface.
   The currents induced in the body by magnetic fields are greatest near the
    periphery of the body and smallest at the center of the body.
   It is believed that, the magnetic field might induce a voltage in the tissue of
    human body which causes a current to flow through it due to its conductivity of
    around them.
   The magnetic field has influence on tissues in the human body. These influences
    may be beneficial or harmful depending upon its nature.
   The magnitude of surface charge and internal body currents that are induced by
    any given source of power-frequency fields depends on many factors.
ELECTROSTATIC EFFECT ON HUMAN
BEINGS-2
   These include the magnitude of the charges and currents in the source, the
    distance of the body from the source, the presence of other objects that might
    shield or concentrate the field, and body posture, shape, and orientation.
    For this reason the surface charges and currents which a given field
    induces are very different for different Human and animals.
   When a person who is isolated from ground by some insulating material comes
    in close proximity to an overhead transmission line, an electrostatic field is set
    in the body of human being, having a resistance of about 2000 ohms.
   When the same person touches a grounded object, it will discharge through his
    body causing a large amount of discharge current to flow through the body.
    Discharge currents from 50-60 Hz electromagnetic fields are weaker than
    natural currents in the body, such as those from the electrical activity of the
    brain and heart.
ELECTROSTATIC EFFECT ON HUMAN
BEINGS-3
   Short term Health Problem
   Headaches.
   Fatigue
   Anxiety
   Insomnia
   Prickling and/or burning skin
   Rashes
   Muscle pain
   Long term Health Problem
    Risk of damaging DNA.
    Risk of Cancer
    Risk of Leukemia
    Risk of Neurodegenerative disease:
    Risk of Miscarriage
ELECTROSTATIC EFFECT ON ANIMALS
   Many researchers are studying the effect of Electrostatic field on animals. In
    order to do so they keeps the cages of animals under high Electrostatic field of
    about 30 kV/m.
   The results of these Experiments are shocking as animals (are kept below high
    Electrostatic field their body acquires a charge & when they try to drink water, a
    spark usually jumps from their nose to the grounded Pipe) like hens are unable
    to pick up grain because of chattering of their beaks which also affects their
    growth.
 ELECTROSTATIC EFFECT ON PLANT
LIFE
   Most of the areas in agricultural and forest lands where high power transmission
    lines pass. The voltage level of high power transmission Lines are 400KV,
    230KV, 110KV, 66KV etc. The electromagnetic field from high power
    transmission lines affects the growth of plants.
   Gradually increases or decreases and reaches to maximum current or minimum
    current and thereafter it starts to fall down to lowest current or raises to
    maximum current or a constant current. Again the current, it evinces with little
    fluctuations till the next day morning.
   Current in Power transmission lines varies according to Load (it depending
    upon the amount of electricity consumed by the consumers). Hence the effect of
    EMF (due to current flowing in the power lines) upon the growth of plants
    under the high power transmission lines remains unaltered throughout the year.
   From various practically study it was found that the response of the crop to
    EMF from 110 KV and 230 KV Power lines showed variations among
    themselves. Based on the results the growth characteristics like shoot length,
    root length, leaf area, leaf fresh weight, specific leaf weight, shoot/root ratio,
    total biomass content and total water content of the four crop plants were
    reduced significantly over the control plants.
ELECTROSTATIC EFFECT ON PIPE
LINE/FENCE/CABLES
   A fence, irrigation pipe, pipeline, electrical distribution line forms a conducting
    loops when it is grounded at both ends. The earth forms the other portion of the
    loop. The magnetic field from a transmission line can induce a current to flow
    in such a loop if it is oriented parallel to the line.
    If only one end of the fence is grounded, then an induced voltage appears
    across the open end of the loop. The possibility for a shock exists if a person
    closes the loop at the open end by contacting both the ground and the conductor.
   For fences, buried cables, and pipe lines proper care has been taken to prevent
    them from charging due to Electrostatic field.
   When using pipelines which are more than 3 km in length & 15 cm in Diameter
    they must be buried at least 30 laterally from the line center.
UNIT V
VOLTAGE CONTROL
SYNCHRONOUS CONDENSER
   Synchronous          Condenser       is      also      known       as      Synchronous
    Compensator or Synchronous Phase Modifier.
    A synchronous condenser or a synchronous compensator is a synchronous motor
    running without a mechanical load.
   It can generate or absorb reactive volt-ampere (VAr) by varying the excitation of its
    field winding.
   It can be made to take a leading current with over-excitation of its field winding.
   When the motor power factor is unity, the DC excitation is said to be normal. Over-
    excitation causes the motor to operate at a leading power factor. Under excitation
    causes it to operate at a lagging power factor. When the motor is operated at no load
    with over-excitation, it takes a current that leads the voltage by nearly 90 degrees.
   Thus, it behaves like a capacitor and under such operating conditions, the
    synchronous motor is called a synchronous capacitor.
   Since a synchronous condenser behaves like a variable inductor or a variable
    capacitor, it is used in power transmission systems to regulate line voltage.
VOLTAGE CONTROL BY
SYNCHRONOUS CONDENSERS:
   Synchronous condensers are over excited synchronous motors installed in the
    power system to deliver the reactive power.
   These synchronous phase modifiers are located near the load improves the
    voltage profile of the power system.
   The main advantage of synchronous phase modifiers are the ability to deliver
    the reactive power can be adjusted unlike static shunt capacitors.
SERIES COMPENSATION
   Voltage Control by Series Capacitors
    In Extra High Voltage (EHV) or Ultra High Voltage System (UHV) systems
    series capacitors are connected in series with the transmission line to reduce the
    effect of inductive reactance XL between the sending end and receiving end of
    the line.
   One of the major drawbacks of series capacitors is that high over voltages are
    produced across the capacitor terminals under short circuit condition.
    Series capacitors are usually employed for increasing the power transfer
    capability of the transmission line and not for voltage regulation
SHUNT COMPENSATION
   Voltage Control by Shunt reactors
   Voltage Control by Shunt Capacitors
   Voltage Control by Static Shunt Compensation
VOLTAGE CONTROL BY SHUNT REACTORS
   Shunt reactors are provided at sending end and receiving end of the long EHV
    and UHV transmission lines.
   They are switched in when the line is to be charged or during line is on low load
   When the line is on no load or low load, shunt capacitance predominates and
    receiving end voltage is higher than the sending end voltage. This phenomenon
    is called Ferranti effect.
   The receiving end voltage of 400kV, 1000 km long line may be as high as
    800kV. The shunt capacitance of such lines is neutralized by switching in the
    shunt reactor.
   During high loads, the series inductive reactance of the line produces IXL drop
    and the receive end voltage drops, the shunt reactors are switched off Shunt
    treactors may be connected to the low voltage tertiary winding of a transformer
    via a suitable circuit breaker, EHV shunt reactors may be connected to the
    transmission line without any circuit breaker.
VOLTAGE CONTROL BY SHUNT
CAPACITORS
   Shunt capacitors are usually switched in during high loads.
   Static shunt capacitors are installed near the load terminals, in industries,
    substations, … Most of the industrial loads (induction motors, transformers,
    welding sets, furnaces) draws inductive current of poor power factor (0.3 to 0.6
    lag).
   The shunt capacitors provide leading VARs there by the total KVA loading of
    substation transformer and the current is reduced.
   Thereby IXL drop in the line is reduced and voltage regulation is improved.
   Shunt capacitors are switched in when KVA demand on the distribution line
    goes up and voltage on the bus comes down.
   Switching in shunt capacitor should improve the bus voltage if the
    compensation is effective
VOLTAGE CONTROL BY STATIC SHUNT
COMPENSATION
   A step-less variable compensation is possible by thyristorized control of shunt
    capacitor and reactors.
   During heavy loads, the thyristors of the capacitor control are made to conduct
    for longer duration in each cycle.
   During low loads, the thyristors in reactor circuit are made to conduct for longer
    duration in each cycle.
   Thus a step-less variation of shunt compensation is achieved by means of static
    shut compensation
SUB-SYNCHRONOUS RESONANCE
PROBLEM
   When the electrical system operates in such a manner that the rotating fields in
    the generator due to sub-synchronous currents produce torques of the same
    frequency as one of the mechanical torsional frequencies of the shaft and of the
    correct phase, torques up to 10 times the break away or ultimate strength of the
    shaft can be reached resulting in shaft damage.
    This phenomenon of electromechanical interaction between electrical resonant
    circuits of the transmission system and the torsional natural frequencies of the
    T-G rotor is known as "Sub-Synchronous Resonance", and designated SSR.
   Three distinct problems have been identified in SSR problem which are called
    Induction Generator Effect,
   Torsional Interaction, and
    Transient Torque Problem.
INDUCTION GENERATOR EFFECT
    An oscillatian of generator rotor due to disturbances produces two
    components of currents or voltages.
    To the super synchronous component the generator is an induction
    motor. To the subsynchronous component the generator is an induction
    generator.
   At resonant electrical frequency f, below the synchronous frequency, the
    apparent, generator rotor resistance is negative. The equivalent
    resistance contains a term R/s where R is the effective rotor resistance
    and 's' is the slip. If this apparent negative resistance exceeds the
    network resistance i.e., when the system resistance is negative, the
    subsynchronous component will be amplified with time.
   Such a condition will result in self excitation of oscillntory currents at
    the resonant frequency. The phenomenon is known as induction
    generator effect.
TORSIONAL INTERACTION
   When the rotor field flux which rotates at the speed of the rotor, overtakes the
    more slowly rotating positive sequence subsynchronous flux of the-rotor, a
    subsynchronous oscillatory component of electrical torque is produced whose
    frequency is the difference between fr and fs, If this torque frequency coincides
    with or in close to a rotational modal frequency fn, of the shaft system a
    regenerative feed back saturation may arise.
   If the enhanced subsynchronous electrical torque exceeds the inherent
    mechanical damping of the rotating system, the system will become self
    excited.
   This interply between electrical and the mechanical system is called the
    torsional interaction
METHODS OF ANALYSIS
   Methods of analysis of SSR The various methods available in the frequency
    domain to analyse the phenomenon of SSR are:
   Routh- hurwitz stability criteria
   Frequency scanning techniques and
   Eigen value analysis.
COUNTER MEASURES
   Remedy for Countering Induction Generator Effect:
   Addition of pole-face
   Addition of series reactance in stator circuit
   System switching and unit tripping
   Armature-current relay protection
   Remedy for Countering Torsional Interaction
   Dynamic Stabilizer
   Reduction in Series-Capacitor Compensation or Complete Removal
   Filters
COUNTER MEASURES-2
   Remedy for Countering Transient Torque Problem.
    Filtering and Damping: These utilize
             (a) Static Blocking Filter,
            (b) Line Filter,
           (c) Bypass Damping Filter,
          (d) Dynamic Filter,
          (e) Dynamic Stabilizer,
          (f) Excitation System Damper.
      Relaying and Detecting: These are
         (a) Torsional Motion Relay,
        (b) Armature Current Relay,
        (c) Torsional Monitor.
   System Switching and Unit Tripping.
   Modification to Generator and System: These include
      (a) T-G modifications for new units altering stiffness, inertia and damping of rotors,
      (b) Generator Series Reactance,
      (c) Pole-Face Amortiseur Winding.
   Removal or Short-Circuiting the Series Capacitor
THANK YOU