Iti Bcu 480 Rev GB
Iti Bcu 480 Rev GB
Technical Information · GB
6 Edition 11.19
Contents
Burner control units BCU 480 . . . . . . . . . . . . . . . . . . . . . . . . 1 5.1.2 Program sequence . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
5.1.3 Test period tP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
Contents . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
5.1.4 Opening time tL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
1 Application . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 5.1.5 Measurement time tM . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
1.1 Application examples . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7 5.2 Proof of closure function . . . . . . . . . . . . . . . . . . . . . . . . . 39
1.1.1 Stage-controlled main burner with alternating 5.2.1 Program sequence . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
pilot burner . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
1.1.2 Stage-controlled main burner with permanent
6 BCSoft . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
pilot burner . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8 7 Fieldbus communication . . . . . . . . . . . . . . . . . . . . . . . . . 41
1.1.3 Two-stage-controlled main burner with 7.1 BCU and bus module BCM . . . . . . . . . . . . . . . . . . . . . . . 42
permanent pilot burner . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9 7.2 Configuration, planning . . . . . . . . . . . . . . . . . . . . . . . . . . 43
1.1.4 Staged control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10 7.2.1 Device master data file (GSD), electronic data
1.1.5 Modulating control with defined ignition position . . 11 sheet (EDS) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
1.1.6 Flame control using the temperature . . . . . . . . . . . . . . . . 12
1.1.7 ON/OFF rotary impulse control . . . . . . . . . . . . . . . . . . . . . . 13 7.3 PROFINET, EtherNet/IP . . . . . . . . . . . . . . . . . . . . . . . . . . 44
1.1.8 Modulating burner control . . . . . . . . . . . . . . . . . . . . . . . . . . . 15 7.3.1 Modules for process data . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44
1.1.9 PROFINET connection using bus module BCM . . . . . 16 7.3.2 Device parameters and statistics . . . . . . . . . . . . . . . . . . . . 49
2 Certification . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17 7.4 PROFIBUS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50
3 Function . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18 8 Program step/status . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51
3.1 Part designations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18 9 Fault signalling . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53
3.2 Connection diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19 10 Parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 56
3.2.1 BCU 480..E1/LM 400..F3..E1 10.1 Application parameters . . . . . . . . . . . . . . . . . . . . . . . . . 56
with ionization control in double-electrode operation . . . . 19 10.2 Interface parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . 60
3.2.2 BCU 480..P3..E1/LM 400..F3..E1
with industrial plug for ionization control in double-
10.3 Scanning the parameters . . . . . . . . . . . . . . . . . . . . . . . 63
electrode operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20 10.4 Flame control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 63
3.2.3 Flame control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21 10.4.1 Burner 1 flame signal FS1 switch-off threshold . . . 63
3.2.4 Assignment of connection terminals . . . . . . . . . . . . . . . . 23 10.4.2 Burner 2 flame signal FS2 switch-off threshold . . . 64
10.4.3 Flame simulation check in standby position . . . . . . . 65
3.3 BCU 480 program sequence . . . . . . . . . . . . . . . . . . . . . 25
10.4.4 High temperature operation . . . . . . . . . . . . . . . . . . . . . . . . 67
4 Air control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27 10.5 Behaviour during start-up . . . . . . . . . . . . . . . . . . . . . . 70
4.1 Capacity control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28 10.5.1 Burner 1 start-up attempts . . . . . . . . . . . . . . . . . . . . . . . . . 70
4.1.1 BCU..F1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28 10.5.2 Burner 2 start-up attempts . . . . . . . . . . . . . . . . . . . . . . . . . 71
4.1.2 BCU..F3 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30 10.5.3 Burner application . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 72
5 Valve proving system . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31 10.5.4 Pilot burner . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 75
10.5.5 Safety time 1 tSA1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 77
5.1 Tightness control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
10.5.6 Flame proving period 1 tFS1 . . . . . . . . . . . . . . . . . . . . . . . . 77
5.1.1 Test instant . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
10.5.7 Safety time 2 tSA2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 78
S
UV
µC 43 2
HT 6 60 burner start-up time.
61
P 3 63 The UV sensor monitors the flame
65 23 signal from pilot and main burners.
VR..L
The BCU provides the cooling and
purging processes.
35 42 1
µC 43 2
HT 6 60
61
P 3 63
65 23
VR..L
66 65 40 41
10 16
4 µC
14
7 M 12
IC 40 + BVA
60 61 62 63 65 66 40 41
23 on the actuator IC 40. Depending on the capacity de-
mand of the temperature controller, the butterfly valve
V3
BVA moves steplessly between the low-fire rate and the
high-fire rate to the position specified by the analogue
V1
V2
input IN, see page 100 (Operating mode 27).
DI 1/V1 DI 2/Air valve IC 40 position Valve position
VAS VAG
Off Off closed Closed
Ignition position/Low-
On Off low
V4
fire rate
On On analogue chart 1 In acc. with chart 1
S
UV
IC 40 + BVA
TE
M VAS VAG
PZL PDZ
DG DG VR..L
TE
L1 FCU HT P
PLC BUS
PROFINET
BCU 4xx
BCU 4xx
BCU 4xx
BCM BCM BCM
1 1 1
2 2 2
3 Function There are two control keys for the control unit:
L1
P
Start 1 Start 2
A
HT LDS
L 1 2 3 4 5 6 7 35 39 40 41 BCU 480 82 81 80 85 86 87 92 91 90 95 96 97
F2
F1 (BCU..E0)
(BCU..E1)
F 3,15 A
LM 400..F3
N1
N1 F3 3,15 A UA-Sk VLuft
O
230 V
UVS
I 1 2
51 21 BM N1 N1 N1 N1 V1
N1 N1 N1 V2 N1 V3 N1 V4 N1 N1
PE L N L N L N
N PE 22 23 52 53 BM 54 24 55 25 56 26 57 27 36 58 28 37 59 29 38 60 30 61 31 62 32 63 33 65 34 66 67
V1 V2 V3 V4
pU Luft
2 PE PE PE PE PE
TC
N
PE
1 HT 2 P A
2
8 7 6 5 4 3 2
16 15 14 12 11 10 9
1
PE
L1
N
16 8 14 4
6 3
6 6 7 LDS 9 10 11 12 2
L 1 2 3 4 5 6 7 35 39 40 41 BCU 480 82 81 80 85 86 87 92 91 90 95 96 97
F2
F1 (BCU..E0)
(BCU..E1)
F 3,15 A
LM 400..F3
N1
N1 F3 3,15 A UA-Sk VLuft
O
230 V
UVS
I 1 2
51 21 BM N1 N1 N1 N1 V1
N1 N1 N1 V2 N1 V3 N1 V4 N1 N1
PE L N L N L N
N PE 22 23 52 53 BM 54 24 55 25 56 26 57 27 36 58 28 37 59 29 38 60 30 61 31 62 32 63 33 65 34 66 67
15 pU V1 V2 V3 V4
2 Luft
PE PE PE PE PE
TC
N1 N1 N1
UVS
2 2
Pilot burner = single-electrode operation/main
1 2 1
51 21 BM PE 51 21 BM PE 51 21 BM PE
burner = ionization:
N1 PE
N1 N1 LM 400..F3
N1 PE
23 Parameter I004
52 BM= 0.
PE 22 23 BM 54 24 PE 22 23 BM 54 24 PE
230 V
N1
UVS
1
UVS 2 1 2 4 4
3 3 3
UVC 1 2 UVC 1 2
51 21 BM PE 1 1
22 23 52 BM PE
Pilot burner = UVS/main burner = ionization:
Parameter A002 ≥ 5 �A.
Parameter I004 = 5.
230 V
N1
UVS
Pilot burner = single-electrode operation/main 1 2
burner = UVS: 51 21 BM PE
1
UVS 2
3
230 V
230 V
N1 N1 N1
UVS
UVS
1 2 1 2 1 2
E 51 21 BM PE 51 21 BM PE N1 PE
N1 51 21 BM PE
52 BM PE 22 23 52 BM PE 22 23 BM 54 24 PE 22 23 BM 5
1 1
2 UVS 2 4 4
3 3 3 3
UVC 1 2 UVC 1 2
1 1
51 21 BM PE N1 PE
N1
22 23 BM 54 24 PE
UVC 1 2
1
4
3
4
3
UVC 1 2
1
N1
1 2
51 21 BM PE N1 PE
N1
22 23 BM 54 24 PE
UVC 1 2
1
4
3
▼ ▼
In the event of flame failure:
In the event of fault signal: reset Fault lock-out
▼ ▼
00 Safety interlocks 04 Pilot burner operation signalling contact closes,
Start-up position/Standby valve for 2nd gas stage opens and
min. operating time tB starts to elapse (A061)
▼ ▼
Flame simulation check In the event of flame failure:
(if parameter A003 = 0) restart or fault lock-out
▼ ▼
P0 External actuation of the air valve for purging A4 External actuation of the air valve for capacity control
▼ ▼
A0 External actuation of the air valve for cooling
05 Main burner start-up with start-up signal (start 2)
▼ ▼
01 Pilot burner start-up with start-up signal (start 1) Wait until the min. pause has elapsed (parameter A062)
▼ ▼
Wait until the min. pause has elapsed (parameter A062) Flame simulation check
(if parameter A003 = 1)
▼
Flame simulation check ▼
(if parameter A003 = 1) Safety time 2 tSA2 (A096) running,
06
▼ ignition in process,
valves for 2nd gas stage open and
02 Safety time 1 tSA1 (A094) running, min. operating time starts to elapse (A061)
ignition in process,
valves for 1st gas stage open and ▼
min. operating time starts to elapse (A061) If no flame detected:
max. 3 start-up attempts (A008)
▼ or fault lock-out
If no flame detected:
max. 3 start-up attempts (A007) ▼
or fault lock-out
4 Air control
A central protective system such as the FCU 500 takes
over air control. It monitors the static air pressure as
well as the air volume required for pre-purge, start-up
and after the furnace has been shut down. The air ac-
tuators (BCU with LM..F1 = actuator IC 40, BCU with
LM..F3 = air valve) are actuated for this purpose by the
capacity control system of the BCU.
After being enabled by the protective system, the BCU
can start the burners. The capacity is controlled during
operation by an external temperature control system.
VAS M
BCU 480..F3
BCU/LM..F3
PZL PZH PZ
VAS
DG DG VAS DG VAS
VAS VAG
DG min DG max
49 50 15 14 13
46
45
ϑ 1
pu/2 VR..L
2
µC
3 P BCU 480..F3
BCU/LM..F3
>750°
FCU
FCU 500..F0
500..F0
58 STM 47 48
DL min DL Purge VAS
M VAS VAG
PZL PDZ
DG DG VR..L
TE
4.1 Capacity control The protective system (e.g. FCU 500) starts the pre-
purge time if there is adequate air flow. After the elapse
4.1.1 BCU..F1
of the pre-purge time, the control element moves to the
Process control (PCC) ignition position. Once the protective system (termi-
FCU 500 PLC
mA nal 35, safety interlocks) has issued the enable signal,
the pilot and main burners can be started by the start-
P HT LDS Start 1 A Start 2 up signals at terminals 1 and 5. The control element
BCU 480/ 3 6 35 39 1 2 4 5
81
can be activated to control the burner’s capacity de-
LM..F1 82
pendent on parameters A048 and A049.
µC 95
96
23 ▼
40 41 65 66 60 61 62 64 22
V3
V1
V2
VAS VAG S
UV
4 7 VAS 1
16 DI 1 DI 2
12
µC V4
18
M IC 40
BVA
S
UV
61
µC 63
HT 6
23
P 3 22
10
VR..L
V2 V1
tL = A059 tL = A059
V2 V1
tM = A056 tM = A056
p + – p
pZ > u pZ > u
2 2
– +
V1 OK V1 V2 V2 OK
V1 V2
PZ
pd
pu pz Vp1
61 60
38
pu/2
ϑ 1
P
3
µC
The test period
2 tP is calculated
>750° from:
TC
– Opening BCU
times tL for V1 and V2,
560..C1
– Measurement times36tM 37 for V1 and V2.
tM [s] = ( 2 x pu x Vp1
DN )
For a large test volume Vp1 with reduced testing
time
Adjustable using parameter A056
L Vp1 = VV + L x VR
Valves Pipe
Volume per metre
Type Volume V V [l] DN VR [l/m]
VAS 1 0.08 10 0.1
VAS 2 0.32 15 0.2
VAS 3 0.68 20 0.3
VAS 6 1.37 25 0.5
VAS 7 2.04 40 1.3
VAS 8 3.34 50 2
VAS 9 5.41 65 3.3
VG 10 0.01 80 5
VG 15 0.07 100 7.9
VG 20 0.12 125 12.3
VG 25 0.2 150 17.7
VG 40/VK 40 0.7 200 31.4
VG 50/VK 50 1.2 250 49
VG 65/VK 65 2
VG 80/VK 80 4
VK 100 8.3
VK 125 13.6
VK 150 20
VK 200 42
VK 250 66
Q(N) max. =
VAS 665 VAS 665
200 m3/h
pu Vp1
= 50 mbar
62 61 60 9,5 m
DN65
1
3
µC
2 >750°
TC
BCULeakage
570..C1rate 200 m3/h x 1000 l/h
Q47 = = 200 l/h
L 48 1000 x 1 m3/h
Test volume Vp1 = 1.1 l + 9.5 m x 3.3 l/m = 32.45 l,
see page 37 (Test volume Vp1)
PZL PDZ
5.2 Proof of closure function As soon as the BCU has opened valve V1, it queries the
The proof of closure function monitors the function of open position of the valve via the POC switch. If a sig-
the gas solenoid valve V1. The proof of closure function nal is still being received at terminal 38 from the POC
can be activated by setting parameter A051 to 4, see switch after a timeout time of 10 s, the BCU performs a
page 90 (Valve proving system). fault lock-out with fault message “E c8”.
V1 V2
PZL PZH GZL
36 37 61 60
38
ϑ 1
P
2
µC
By checking the closed position
>750° using the proof of clo-
sure function, the BCU complies with the requirements
TC
BCU 46x..C1
of NFPA 85 58(Boiler and Combustion Systems Hazards
47 48
Code) and NFPA 86 (Standard for Ovens and Furnaces).
M
5.2.1 Program sequencePZL PDZ
When the start-up signal is received at terminal 1, the
BCU checks that valve V1 is in its closed position using
the POC switch. If a signal is not received at terminal 38
from the POC switch after a timeout time of 10 s (valve
V1 is closed), the BCU performs a fault lock-out with
fault message “E c1”.
7 Fieldbus communication The signals from the devices are read into the controller
PROFIBUS DP, PROFINET and EtherNet/IP are man- cyclically. There, they are processed and then output to
ufacturer-independent, open standards for industrial the devices again.
network communication. They cover the requirements
for automation technology (manufacturing automa-
tion, process automation, drive applications without
functional safety). They are bus variants for fieldbus
communication optimized for speed and low connec-
tion costs.
L1 FCU HT P
SPS BUS
PROFINET
BCU 4xx
BCU 4xx
BCU 4xx
1 1 1
2 2 2
7.1 BCU and bus module BCM munication direct between the BCU and the protective
The optional bus module BCM 400 is required to in- system (e.g. FCU).
tegrate the BCU in a standardized fieldbus system
FCU HT P
(PROFIBUS, PROFINET or EtherNet/IP).
PLC BUS PROFINET,
Control signals (for start and reset, for example), signal
PROFIBUS,
states from the device inputs and outputs and informa- ETHERNET/IP
tion about the device status (operating states, flame
BCU L1,
BCM
signal and current program step), warnings and faults Temperature
controller
can be transferred simultaneously via the bus module
ϑ
between the BCU and PLC.
0 ➔ 90°
90° ➔ 0
The bus module BCM 400..B1 has a 9-pin D-Sub con- 3PS 66 67 65
nection socket on the front, while the bus modules
BCM 400..B2 and B3 have two RJ45 connection sock-
ets on the front for connection to the fieldbus. The
RJ45 connection sockets are combined with an internal M
Fault and warning signals (BCU ➔ PLC) Remaining times (BCU ➔ PLC)
The fault and warning signals are transferred from the This module transfers the remaining times of various
BCU to the PLC using this module. The fault and warn- processes from the BCU to the PLC. The remaining
ing signals each occupy one word. time occupies one word.
The same allocation table applies to the fault signals Bit Byte n Byte n+1 Data type Format Value
and the warning signals. 0
1
Bit Byte n Byte n+1 Data type Format Value 2
0 3 0 – 6554
Remaining times Word DEC
1 4 (0 – 6554 s)
2 5
3 6
Fault signals Word DEC 0 – 6555351) 7
4
5
6
7
Temperature (BCU ➔ PLC)
Bit Byte n+2 Byte n+3 Data type Format Value
This module transfers the internal device temperature.
0
1 The temperature occupies one word.
2
Bit Byte n Byte n+1 Data type Format Value
3
Warning signals Word DEC 0 – 6555351) 0
4
5 1
6 2
7 3 0 – 6554
Temperature Word DEC
1) 4 (0 – 6554 K)
See code tables “BusCommunication_BCU4_R2.xlsx” at www.
docuthek.com. 5
6
7
7.4 PROFIBUS I/O bytes: the programmer can choose the data to be
transferred.
Input bytes (BCU ➔ master)
Inputs Outputs
Bit Byte 0 Byte 1 Byte 2 Byte 3 Byte 4
480 basic I/O 1 byte 1 byte
0 Reset
480 standard I/O 5 bytes 1 byte
step/status)
The max. range per segment depends on the baud rate:
0 – 25.5 µA
0 – 25.5 µA
3 Purge ON
255 steps
255 steps
Free
8 Program step/status
DISPLAY1) Program step/status
00 Start-up position/Standby
A0 Cooling2)
P0 Pre-purge
H0 Delay
01 Minimum pause time tMP
A1 Pre-ventilation2)
0 “No flow” state check of low air pressure protection device
1 Low air pressure protection check
A Approaching minimum capacity/closed position2)
A Approaching maximum capacity2)
P0 Pre-purge
P1 Pre-purge
A Approaching ignition capacity2)
HX Delay (in program step X)
H2 Delay
Valve check
02 Safety time 1
A2 Safety time 1 (with air)
03 Flame proving period 1 tFS1
A3 Flame proving period 1 tFS1 (with air)
04 Burner 1 operation/controller enable
A4 Burner 1 operation/controller enable (with air)
H4 Delay
05 Burner 2 waiting time
A5 Delay
9 Fault signalling
Fault message (blinking) DISPLAY Description
Burner 1 flame simulation E 01 Flame simulation/Flame signal before ignition
No flame after safety time 1 E 02 No flame formation to end of 1st safety time
Flame failure during flame proving period 1 tFS1 E 03
Flame failure during burner 1 operation E 04 Flame failure during operation
Burner 2 flame simulation E 05 Flame simulation/Flame signal before ignition
No flame after safety time 2 E 06 No flame formation to end of 2nd safety time
Flame failure during flame proving period 2 tFS2 E 07
Flame failure during burner 2 operation E 08 Flame failure during operation
Too many remote resets E 10 Remote reset activated > 5 × in 15 min.
Too many restarts for burner 1 E 11 > 5 restarts in 15 minutes
Too many restarts for burner 2 E 12 > 5 restarts in 15 minutes
“Maximum capacity” and “Ignition capacity” position feedback
Simultaneous activation (terminals 40 and 41) E 21 from butterfly valve set simultaneously
Actuator wiring (terminals 65 – 67) E 22 Faulty wiring of terminals 65 – 67
Maximum or ignition capacity is not constantly signalled back to
Actuator feedback (terminals 40, 41) E 23 terminal 40 or 41
“Open actuator” and “Close actuator” bus signals set
Simultaneous Min./Max. bus command E 24 simultaneously
Non-fail-safe parameters (NFS) inconsistent E 30 NFS parameter range is inconsistent
Fail-safe parameters (FS) inconsistent E 31 FS parameter range is inconsistent
Mains voltage E 32 Operating voltage too high/low
Faulty parameterization E 33 Parameter set contains illegal settings
Faulty actuation of the air valve. Voltage is applied to the outputs
Air valve control defective E 34 at terminals 65 – 67 for the air valve.
Incompatible bus module E 35 Bus module does not support the selected function.
Relay contact fault caused by defective relay contacts, EMC
Power module defective E 36 influence, by applying voltage to outputs or by an incorrect load
module
▼
BCU 480 · Edition 11.19 53
Fault signalling
10 Parameters
Any changes to parameters will be saved to the parameter chip card.
Factory default
Name Parameter Value range Description settings
0 Off
1 Burner 1
2 Burner 2
Restart A009 3 Burner 1 and burner 2 (pilot and main burners) 0
4 Max. 5 × in 15 min. for burner 1
5 Max. 5 × in 15 min. for burner 2
6 Max. 5 × in 15 min. for burner 1 and burner 2
Safety time during operation A019 0; 1; 2; 3, 4 Time in seconds 1
Over-run time tN A039 0 – 60 Time in seconds 0
0 Off; checking the positions for minimum/maximum
capacity
1 On; for approaching the positions for minimum/maximum
Running time selection A041 0
capacity
2 On; for approaching the position for maximum capacity
3 On; for approaching the position for minimum capacity
Running time in seconds (can only be selected if
Running time A042 0 – 250 250
I020 = 2 or 3)
0 Off
Over-run A043 2 Low fire; actuator feedback 0
3 Low fire; time-bound
0 Opens on external activation
1 Opens with gas stage 1
Air actuator control A048 0
2 Opens with gas stage 2
4 Opens with V4 burner 1
Air actuator can be activated externally on 0 Cannot be activated
A049 0
start-up 1 Can be activated externally
0 Cannot be activated
Air actuator in the event of fault A050 1
1 Can be activated externally
0 Off
1 Tightness test before start-up
Valve proving system A051 0
2 Tightness test after shut-down
3 Tightness test before start-up and after shut-down
0 V0
1 V1
2 V2
Relief valve (VPS) A052 2
3 V3
4 V4
5 V5
Factory default
Name Parameter Value range Description settings
Measurement time for Vp1 A056 3 – 3600 Time in seconds 3600
Valve opening time tL1 A059 2 – 25 Time in seconds 2
Proof of closure function test period A060 0 – 6000 Time in seconds 10
Minimum operating time tB A061 0 – 250 Time in seconds 0
Minimum pause time tMP A062 0 – 3600 Time in seconds 0
0 Unlimited
Operating time in Manual mode A067 1
1 5 minutes
0 Flame mode
Combustion mode A074 2 High temperature operation without ignition 0
3 High temperature operation without burner 1 start
0 Burner 1
1 Burner 1 with pilot gas
Burner application 2 Burner 1 and burner 2
A078 0
3 Burner 1 and burner 2 with pilot gas
4 Two-stage burner 1
5 Burner 1 and two-stage burner 2
0 With shut-down
Pilot burner A079 1 Controlled externally 1
2 To start
0 Off
Fieldbus communication A080 1 With address check 0
2 No address check
0 Off
K-SafetyLink A081 0
1 On
1 Via fail-safe bus (K-SafetyLink)
Safety interlocks (bus) A085 2 Via terminal 2
5 Via fail-safe bus (K-SafetyLink) and terminal
0 Off
1 Via fail-safe bus (K-SafetyLink)
Purge (bus) A087 2 Via terminal 2
3 Via non-fail-safe bus
4 Via fail-safe bus (K-SafetyLink) or terminal
0 Off
1 Via fail-safe bus (K-SafetyLink)
High temperature operation (bus) A088 2
2 Via terminal
5 Via fail-safe bus (K-SafetyLink) and terminal
Factory default
Name Parameter Value range Description settings
0 Off
1 Via fail-safe bus (K-SafetyLink)
LDS (bus) A089 2
2 Via terminal
5 Via fail-safe bus (K-SafetyLink) and terminal
Safety time 1 tSA1 A094 2 – 15 s Time in seconds 3
Flame proving period 1 tFS1 A095 0 – 25 s Time in seconds 2
Safety time 2 tSA2 A096 2 – 10 s Time in seconds 3
Flame proving period 2 tFS2 A097 0 – 25 s Time in seconds 2
0 No function
48 POC V1
49 POC V2
Function of sensor 1 A101 50 POC V3 0
51 POC V4
52 POC V5
53 TC
Function of sensor 2 A102 See A101 See A101 0
Function of sensor 3 A103 See A101 See A101 0
0 Off
Air actuator I020 2 IC 40 0
5 Air valve
0 Off
Function of terminal 64 I040* 2 V5 0
3 Bus output 1
0 Off
1 Ready signal
2 Air signal
4 Cooling air valve
Contact 80, 81/82 function I050* 6
5 Flue gas valve
6 Fault signal
7 Burner 1 operating signal
8 Burner 2 operating signal
0 Off
1 Ready signal
2 Air signal
4 Cooling air valve
Function of contact 90, 91/92 I051* 1
5 Flue gas valve
6 Fault signal
7 Burner 1 operating signal
8 Burner 2 operating signal
Factory default
Name Parameter Value range Description settings
0 Off
1 Ready signal
2 Air signal
4 Cooling air valve
Function of contact 95/96 I052* 7
5 Flue gas valve
6 Fault signal
7 Burner 1 operating signal
8 Burner 2 operating signal
0 Off
1 Ready signal
2 Air signal
4 Cooling air valve
Function of contact 95/97 I053* 8
5 Flue gas valve
6 Fault signal
7 Burner 1 operating signal
8 Burner 2 operating signal
0 Off
1 Ready signal
2 Air signal
4 Cooling air valve
Function of contact 85/86, 87 I054* 2
5 Flue gas valve
6 Fault signal
7 Burner 1 operating signal
8 Burner 2 operating signal
0 Off
4 Safety interlocks
5 Air
6 Cooling air
7 Air actuator R1
8 Air actuator R2
Function of input 1 I061* 9
9 Start 1
10 Start 2
11 Reset
12 Purge
13 LDS start-up conditions
14 High temperature operation
Function of input 2 I062* See I061 See I061 11
Factory default
Name Parameter Value range Description settings
Function of input 3 I063* See I061 See I061 12
Function of input 4 I064* See I061 See I061 5
Function of input 5 I065* See I061 See I061 10
Function of input 6 I066* See I061 See I061 14
Function of input 7 I067* See I061 See I061 0
Function of input 35 I068* See I061 See I061 4
0 Off
1 Sensor 1
2 Sensor 2
3 Sensor 3
4 Safety interlocks
5 Air
6 Cooling air
Function of input 36 I069* 0
7 Air actuator R1
8 Air actuator R2
9 Start 1
11 Reset
12 Purge
13 LDS start-up conditions
14 High temperature operation
Function of input 37 I070* See I069 See I069 0
Function of input 38 I071* See I069 See I069 0
Function of input 39 I072* See I061 See I061 13
Function of input 40 I073* See I061 See I061 7
Function of input 41 I074* See I061 See I061 8
* Interface parameters I040 to I099 are set at the factory and normally do not need to be adjusted.
10.3 Scanning the parameters (parameter A094) or during operation after the elapse
During operation, the four-digit 7-segment display of the safety time during operation (parameter A019).
shows the program step/status. In the case of UV control, this value can be increased,
In addition to the flame signal and the fault history, all should the burner to be monitored be influenced by
the parameters of the BCU can be scanned in numeri- other burners, for example.
cal order by repeatedly pressing the Reset/Information The adjustable range for the flame signal switch-off
button (for 1 s). threshold for burner 1 is dependent on the setting of
The parameter display is ended 60 seconds after the interface parameter I004 (Flame control):
last time the button is pressed or by switching off I004 = 0, 3 or 4
the BCU. (ionization control of burner 1): 2 – 20 µA,
I004 = 1, 5 or 6
The BCU indicates when the mains switch has been
(control of burner 1 using UVS sensor): 5 – 20 µA,
switched off. The parameters cannot be scanned when
I004 = 2
the BCU is switched off or when a fault or warning is
(control of burner 1 using UVC sensor): 5 µA
displayed.
tW t 00 01 E 01 88
L
1 ϑ
Parameter A003 = 1: flame simulation check on start- 51
22
00 simulation check is conducted
up. The flame 02 . . . 88 after ap- 60 V1
Start 1 61 V2
plying the start-up signal (start 1 or start 2)V1during the 96
waiting time tW. t t
tLV1
What is flame simulation?
Flame simulation means that an extraneous signal is The flame simulation check of the pilot burner is always
detected as a flame signal out of sequence. If the BCU active until valve V3 is enabled.
detects such an extraneous signal during the flame simu-
▼
00 E 05 88
L
35
1 ϑ1
1 ϑ2
51
22
23
60 V1
61 V2
62 V3
63 V4
96 1
97 2
82
tLV1 t
00 01 02 03 04 05 E 05 88
L
1 ϑ1
5 ϑ2
51
22 1
23 2
60 V1
61 V2
62 V3
63 V4
96
tLV1 tLV2 t
10.5 Behaviour during start-up If no flame is formed during the start-up, so that at the
end of the safety time tSA1 no flame signal is detected,
10.5.1 Burner 1 start-up attempts
this will result in a BCU safety shut-down with subse-
Parameter A007
quent fault lock-out. The fault message E 04 will flash
This parameter defines the maximum number of pos- in the BCU display depending on the burner operating
sible start-up attempts of burner 1. mode.
Taking into account national standards and require- Parameter A007 = 2, 3:
ments, it must be clarified whether multiple start-up 2 or 3 start-up attempts.
attempts are permitted.
00 02 01 02 E 04 88
In accordance with EN 746-2, a restart may be con- L L1
35
ducted only if the safety of the installation is not im- 1 ϑ
51
paired. 22
60 V1
Multiple start-up attempts are not permitted under 61 V2
62 V3
NFPA 86. If no flame forms during start-up, this must 82
96
result in a fault lock-out. t
tZ tZ
If no flame is detected during start-up, an immediate tSA1 tW tSA1
fault lock-out (A007 = 1) or up to two additional start-
up attempts (A007 = 2, 3) are performed depending on If no flame is formed during the start-up, so that at the
parameter A007. end of the safety time tSA1 no flame signal is detected,
the BCU closes the gas valves and repeats the start-up.
Parameter A007 = 1: 1 start-up attempt.
Each start-up attempt begins with the parameterized
00 02 E 04 8888 start-up behaviour.
L L1
35 If the safety time tSA1 elapses without a flame signal
1 ϑ
51 having been detected, even after the last parameterized
22
60 V1 start-up attempt, this will result in a BCU safety shut-
61 V2
62 V3 down with subsequent fault lock-out. The fault mes-
82
96 sage E 04 will flash in the BCU display depending on the
t
tZ burner operating mode.
t SA1
V1 V2
V1 V2 60 61 62
BCU 46x
60 61 62
01 02 03
µC 04
BCU 46x 52 51
01 02 03 04 55
54 60 1
µC
52
51 53
61 2
55 60 1 58 47 48 56
62 3
54
53 61 2 22
58 47 48 56 62 3 96 1
22
96 1
tBP tSA1 tFS1 t
tBP tSA1 tFS1 t
▼
Parameter A078 = 1: burner 1 with pilot gas. Three
valves (V1, V2 and V3) are included for a burner with a
pilot gas valve. These are connected to the valve out-
puts (terminals 60, 61 and 62). Valves V1 and V3 open
V1 V2
V1 V2
60 61 63 V4
BCU 480 60 61 62 63 V4
H1 02 03
µC
06 07 H8 08 BCU 480..C1F1
51
55
54
60 1 H1 02 03
µC 06 07 H8 08
53 61 2 52 51
55
56 62 3 54 60 1
53
63 4 61 2
58 47 48 56
22 1 62 3
23 2 63 4
96 2
22 1
23 2
tSA1 tFS1 tSA2 tFS2 tRF t 96 2
Parameter 78 = 3: burner 1 and burner 2 with pilot gas. tSA1 tFS1 tSA2 tFS2 tRF t
In this application, the burner has an additional pilot
gas valve V3. The valves are connected to the valve ▼
outputs (terminals 60, 61, 62 and 63). Valves V1 and V4
open to start the pilot burner. The burner is started with
a limited ignition capacity using gas valve V3. After the
elapse of the safety time tSA2 (program step 06), valve
BCU 46x
µC
01 02 03 0452
55 V1 V2
54 51
53
60 1
58 47 48 56
61 2 60 61 62 63 V4
62 3
22 BCU 480..C1F1
96 1
02 03 04
µC H 04 06 07 08
t
52
55
51
tBP tSA1 tFS1 54 60 1
53
61 2
58 47 48 56
Valves V1 and V3 open to start the burner. The burner 62 3
63 4
is started with a limited ignition capacity using gas 22 1
valve V3. After the flame proving period tFS1 has 23 2
elapsed, valve V2 opens to enable the 2nd gas stage. 96 2
10.6.1 Restart
08 08 88
Parameter A009 L L1
35
Restart can be programmed for burners which occa- 1 ϑ1
51
sionally display unstable behaviour during operation. 60 V1
22 1
This parameter determines whether the BCU initiates 95 1
5 ϑ2
an immediate fault lock-out or an automatic restart 61 V2
23 2
after a safety shut-down during operation. Excessive 96 2
82
restarts, however, can be detected. t
tSB
Taking into account national standards and require-
ments, it must be clarified whether the restart func- A safety shut-down with subsequent fault lock-out
tion may be used. takes place in the event of flame failure during opera-
In accordance with EN 746-2, a restart may be con- tion.
ducted only if the safety of the installation is not im-
▼
paired.
The precondition for an automatic restart is that the
burner can restart (as intended in all operating phases).
In this case, it must be ensured that the program se-
quence started by the BCU matches the application.
tW2
If a safety shut-down occurs during operation (mini-
mum operating time of 2 s), the valves are closed and
If a safety shut-down occurs during operation (mini-
the operation signalling contact is opened within the
mum operating time of 2 s), valve V2 is closed and the
safety time during operation tSB. The burner control
operation signalling contact opened within the safety
unit then attempts to restart the burner once. If the
time during operation tSB. The burner control unit then
burner does not function, a safety shut-down with fault
attempts to restart burner 2 once. If burner 2 does not
lock-out occurs. The display blinks and shows the fault
function, a safety shut-down with fault lock-out occurs.
message.
The display blinks and shows the fault message.
10.8 Air control the BCU will initiate the next program step. Approach-
ing the position for maximum capacity is signalled and
10.8.1 Running time selection
monitored.
Parameter A041
Parameter A041 = 0: Off; checking the positions for
minimum/maximum capacity. A signal that the posi-
tions for minimum and maximum capacity have been
reached is returned and monitored with a timeout time
of max. 250 s. When the position has been reached, the
BCU will initiate the next program step.
Parameter A041 = 1: On; for approaching the positions
for minimum/maximum capacity. The running time
set using parameter A042 is activated for approaching
these positions, see page 84 (Running time). After
this time has elapsed, the BCU will initiate the next pro-
gram step.
Parameter A041 = 2: On; for approaching the position
for maximum capacity. The running time set using pa-
rameter A042 is activated for approaching the position
for maximum capacity, see page 84 (Running time).
After this time has elapsed, the BCU will initiate the next
program step. Approaching the position for minimum
capacity is signalled and monitored.
Parameter A041 = 3: On; for approaching the position
for minimum capacity. No signal is returned that the
position for minimum capacity has been reached. The
running time set using parameter A042 is activated for
approaching the position for minimum capacity, see
page 84 (Running time). After this time has elapsed,
VAS VAG V4
VAS 1
BCU 480..F3
µC 60
61
63
23
65 22
VR..L
61 V2
62 V3 96 1
63 V4 97 2
4 A M
82
65 ∨ 66 t
22 1 tZ tFS1 tSA2 tFS2
23 2
tSA1
82
tZ tSA2 t
tA042 tFS1 tFS2 The air actuator opens at the same time as safety
tSA1 time tSA2 begins and the main burner starts.
63 V4 65 ∨ 66
4 A 96 1
65 ∨ 66
M
97 2
96 1 82
97 2
tZ tSA2 t
82 tFS1 tFS2
t tSA1
tZ tFS1 tSA2 tFS2
tSA1 The air valve opens with the start fuel flow rate. The air
valve can be activated externally via the input at ter-
This setting is required in the case of two-stage main
minal 4 for cooling the burner in the start-up position/
burners which are switched ON/OFF via the ϑ2 input.
standby.
The air valve opens simultaneously with the operating
signal for the main burner. The air valve can be acti-
vated externally via the input at terminal 4 for cooling
the burner in the start-up position/standby. This func-
tion is not available during burner start-up and during
operation.
22 1 65 ∨ 66
96 1 82
5 ϑ2 tZ tSA2 t
61 V2 tFS1 tFS2
23 2 tSA1
97 2
4 A
65 ∨ 66
M
The air actuator can be activated externally via the input
82
at terminal 4 during start-up. Parameter A048 must be
tZ tFS1 tSA2 t
tFS2 set to 0 for this purpose, see also page 86 (Air actua-
tSA1
tor control).
During start-up, the air actuator remains closed. The air 10.8.6 Air actuator in the event of fault
actuator cannot be activated externally. Parameter A050
Parameter A049 = 1: can be activated externally. This parameter decides whether the air actuator can
be activated externally via the input at terminal 4 in the
event of a fault lock-out.
Parameter A050 = 0: cannot be activated. The air ac-
tuator remains closed in the event of a fault lock-out. It
cannot be activated externally via terminal 4.
Parameter A050 = 1: can be activated externally. The
air actuator can be activated externally via the input at
terminal 4 during a fault, e.g. for cooling.
V1 V2
PZ
Vp1
60 61
38
pu/2
ϑ 1
P
2
The required
3
measurement
µC time for the tightness test
>750°
of Vp1 can be set using parameter A056.
TC It is adjustable
BCU 56x..C1
from 3 to 3600 s.
See also page 36 (Measurement time tM).
10.9.4 Valve opening time tL1
Parameter A059
This parameter is used to define the opening time for
the valves (2 to 25 s) which are opened to fill or dis-
charge the test volume between the gas valves. If the
preset opening time tL = 3 s is inadequate (e.g. if slow
opening valves are used) to fill the test volume or re-
duce the pressure between the valves, bypass valves
can be used instead of the main valves.
On condition that the gas volume which flows into the
combustion chamber is no larger than 0.083% of the
10.13 Communication
10.13.1 Fieldbus communication
Parameter A080
Fieldbus communication can be enabled using param-
eter A080 when bus module BCM 400 is connected.
A device name/network name must be entered in the
automation system/BCSoft for the unique identifica-
tion of the control unit (BCU/FCU) in the fieldbus sys- Code switch setting: upper switch (S1) = 102 (hundreds), cen-
tem. tre switch (S2) = 101 (tens), lower switch (S3 = 10 0 (ones)
10.14 Interface parameters er 2 flame control is performed with a UV sensor for
Interface parameters I040 to I099 are set at the fac- continuous operation (UVC).
tory and normally do not need to be adjusted. Chang- Parameter 04 = 7: burner 1 flame control is performed
ing the default settings of the interface parameters with a UV sensor for continuous operation (UVC), burn-
will change the functions of the inputs at terminals 1 er 2 flame control is performed with a flame rod.
to 41 and terminals 85 to 90, see also from page 19 Parameter 04 = 8: burner 1 flame control is performed
(Connection diagram). with a UV sensor for continuous operation (UVC), burn-
10.14.1 Flame control er 2 flame control is performed with a UV sensor for
Parameter I004 intermittent operation (UVS).
Parameter I004 = 0: flame control is performed with a Flame control using UV sensors
flame rod. For intermittent operation, the operating state of the
Parameter I004 = 1: flame control is performed with a complete system is limited to 24 h pursuant to EN 298.
UV sensor for intermittent operation (UVS). To meet the requirement for intermittent operation, the
burner is shut down and restarted automatically after a
Parameter 04 = 2: flame control is performed with a UV
continuous operating time of 24 hours if it is not oper-
sensor for continuous operation (UVC).
ated in compliance with the standard. The restart does
Parameter 04 = 3: burner 1 flame control is performed not meet the requirements of EN 298 for UV sensor
with a flame rod, burner 2 flame control is performed continuous operation because the required self-test (at
with a UV sensor for intermittent operation (UVS). least once per hour) is not performed while the burner
Parameter 04 = 4: burner 1 flame control is performed is operating. This shut-down and subsequent restart
with a flame rod, burner 2 flame control is performed are performed in the same way as a normal controlled
with a UV sensor for continuous operation (UVC). shut-down. Depending on the parameterization, the
Parameter 04 = 5: burner 1 flame control is performed burner is started with or without pre-purge. This pro-
with a UV sensor for intermittent operation (UVS), burn- cess is controlled independently by the BCU and there-
er 2 flame control is performed with a flame rod. fore it must be checked whether the industrial process
Parameter 04 = 6: burner 1 flame control is performed permits the pause in heat supply it creates.
with a UV sensor for intermittent operation (UVS), burn- ▼
0°➔90°
BCU..F1
N1 N1
90°
N1 ▼
L N L N
36 58 28 37 59 29 38 40 41 56 26 64 65 66 67
mA
22 21 20 19 18 16 15 14 12 11 10 8 7 5 4 2 1
A AC
D DC
IC 40
M
R..
PE
t1 t2 t3 t4 t5 t6 t1 t2 t3 t4 t5 t6
Purge Purge
High 0–20
fire mA
Ignition Ignition
Closed Closed
t [s] t [s]
DI 1 DI 1
DI 2 DI 2
t [s] t [s]
BCU IC 40 (operating mode 11) BCU IC 40 (operating mode 27)
Signal at Signal at
terminal terminal Position Butterfly valve position
Position Butterfly valve position
65 66
65 66
OFF OFF Closed Closed
OFF OFF Closed Closed
ON OFF Ignition Minimum/Ignition capacity
ON OFF Ignition Minimum/Ignition capacity
Any position between minimum and
ON ON High-fire rate High-fire rate ON ON 0 – 20 mA maximum capacity
OFF ON Purge Maximum capacity OFF ON Purge Maximum capacity
S
UV
61
µC 63
In Manual mode, no external controller is enabled. The 22
23
actuator can be moved to the positions for maximum
capacity or ignition capacity by the user. 3-point step 10
VR..L
operation is not possible. No timeout is active when ap-
proaching these positions.
10.16 Functions of inputs at terminals 1 to 7 signal to actuate the cooling air actuator through the
and 35 to 41 input.
Parameter I061 = 7: air actuator R1. The BCU receives
The BCU has multiple physical and logical interfaces
the feedback signal for the ignition position from actua-
to receive its input signals and set output signals. Pa-
tor IC 40 through the input.
rameters I061 to I074 are used to define which input
Parameter I061 = 8: air actuator R2. The BCU receives
signals can be received at the various terminals (1 to 7
the feedback signal for the High position from actuator
and 35 to 41).
IC 40 through the input.
Sensors (pressure switches for the tightness test and Parameter I061 = 9: start 1. The BCU receives the start-
POC switches) can be connected to inputs 36, 37 up signal for the pilot burner (start 1) through the input.
and 38 depending on the parameter setting. Parameter I061 = 10: start 2. The BCU receives the start-
BCU..E0 up signal for the main burner (start 2) through the input.
Input 35 is reserved for the safety interlock function. All Parameter I061 = 11: reset. The BCU receives the signal
other inputs can also be parameterized for the safety for a remote reset through the input.
interlock function (I061 = 4). Parameter I061 = 12: purge. The BCU receives the
purge signal through the input.
10.16.1 Function of input 1
Parameter I061 Parameter I061 = 13: LDS. The BCU does not perform
a burner start-up, restart or start-up attempt until the
To define the input signal for terminal 1.
central actuator is in ignition position, see the applica-
Parameter I061 = 0: Off. The input has no function. tion example on page 11 (Modulating control with
Parameter I061 = 4: safety interlocks. The “safety inter- defined ignition position). To ensure that the burn-
locks” signal can be applied via the input and/or Safe- ers only start with the start fuel flow rate, the higher-
tyLink. No start-up is commenced if there is no signal at level control system sends a signal to start the burner
the input. If the signal drops out during operation, the through the terminal to the BCU.
gas valves are closed immediately (< 1 s).
▼
Parameter I061 = 5: air. The BCU receives the signal for
controlled air flow or for external air actuator control
through the input.
Parameter I061 = 6: cooling air. The BCU receives the
11 Replacement possibilities
Burner control units BCU 480 can be replaced by the next-generation devices BCU 480 (2019).
By comparison to the previous generation, the next-generation BCU 4 (2019) units feature new technologies and
functions which can be freely parameterized.
Code Description of BCU (previous generation) Description of BCU (2019) Code2)
BCU Burner control unit
Series 4 burner control unit BCU 4
4 Series 4
80 Version for pilot and main burners Series 480 80
3; 5; 10 1st safety time on start-up tSA [s] Can be adjusted using parameter A094: 2 to 15 s
/3; /5 2nd safety time on start-up tSA [s] Can be adjusted using parameter A096: 2 to 15 s
/1; /2 Safety time during operation tSB [s] Can be adjusted using parameter A019: 0, 1, 2, 3, 4 s
In conjunction with LM..F1 = with interface for IC 40,
L1) Air valve control
LM 400..F3 = with air valve control
51); 151); Can be adjusted using parameter A039 (Over-run time): 0 to
Low fire over-run time [s]
251) 60 s
W Mains voltage: 230 V AC, -15/+10%, 50/60 Hz Mains voltage: 230 V AC, -15/+10%, 50/60 Hz W
R 115 V AC, -15/+10%, 50/60 Hz 120 V AC, -15/+10%, 50/60 Hz Q
11) Ignition transformer: TZI 5-15/100 Ignition transformer: 5 kV, 15 mA, 100% duty cycle 1
21) TZI 7-25/20 8 KV, 20 mA, 19% duty cycle 2
31) TZI 7,5-12/100 8 KV, 12 mA, 100% duty cycle 3
81) TZI 7,5-20/33 8 KV, 20 mA, 33% duty cycle 8
GB1) Front film in English with additional stickers in D, F, I, NL, E Set of language stickers in GB, F, NL, I, E, see accessories
Flange plate: none P0
standard P1
M32 P2
P1) Industrial plug connector industrial plug connector, 16-pin P3
PROFIBUS P6
conduit P7
No valve proving system C0
– With TC and POC valve proving system C1
With POC valve proving system C2
D21) High temperature operation in conjunction with: … UVS No high temperature operation D0
D31) … ionization or UVD For high temperature operation D1
S2 – 31) Number of start-up attempts, pilot burner Can be adjusted using parameter A007: 1, 2 or 3
/2 – 31) Number of start-up attempts, main burner Can be adjusted using parameter A008: 1, 2 or 3
▼
BCU 480 · Edition 11.19 107
Replacement possibilities
12 Selection
12.1 Burner control unit BCU
Q W 1 2 3 8 P0 P1 P2 P3 P6 P7 C0 C1 C2 D0 D1 0 2 0 K0 K1 K2 E0 E1
BCU 480
= standard, = available
Order example
BCU 480W2P1C1D00K1E1
12.1.1 Type code
Code Description Code Description
BCU 4 Series 4 burner control unit E0 Energy supply: via safety interlocks
E1 via L1
80 Series 480
Q Mains voltage: 120 V AC, 50/60 Hz
W 230 V AC, 50/60 Hz
1 Ignition transformer: 5 kV, 15 mA, 100% duty cycle
2 8 kV, 20 mA, 19% duty cycle
3 8 kV, 12 mA, 100% duty cycle
8 8 kV, 20 mA, 33% duty cycle
P0 Flange plate: none
P1 standard
P2 M32
P3 industrial plug connector, 16-pin
P6 PROFIBUS
P7 conduit
C0 No valve proving system
C1 With TC and POC valve proving system
C2 With POC valve proving system
D0 No high temperature operation
D1 For high temperature operation
0 Input functions: none
2 LDS
0 Pressure switches: none
K0 No connection plugs
K1 Connection plugs with screw terminals
K2 Connection plugs with spring force terminals
Order example
LM 400WF100E1K1
12.2.1 Type code
Code Description
LM Power module
400 For series 400
Q Mains voltage: 120 V AC, 50/60 Hz
W 230 V AC, 50/60 Hz
F0 Air actuator: none
F1 with IC 40 interface
F3 with air valve control
O0 Optional outputs: none
O1 not fail-safe
O2 fail-safe
E0 Energy supply: via safety interlocks
E1 via L1
K0 No connection plugs*
* Connection plugs for the power module are supplied with the
BCU..K1 and BCU..K2.
8888
163 mm
6.42"
Distance between BCU and burner: recommended
< 1 m (3.3 ft), max. 5 m (16.4 ft). For other mounting options using a fastening set or ex-
When installing, ensure that there is sufficient space to ternal securing bars, see page 116 (Accessories).
open the BCU.
13.2 Commissioning
Securing the device from inside Do not start the BCU until the parameter settings and
wiring are correct and the faultless processing of all
input and output signals complies with the local stand-
ards.
L1
0,6 × IN
P
Start 2
A
HT LDS
Start 1
L 1 2 3 4 5 6 7 35 39 40 41 BCU 465 82 81 80 85 86 87 92 91 90 95 9
F2
(BCU..E0)
F1
(BCU..E1) LM 400..F3
F 3,15 A
N1
N1 F3 3,15 A UA-Sk vLuft
O
230 V
UVS
I 1
51 21 BM N1 N1 N1 N1 N1 N1 V1 V2 N1 V3 N1 N1
N1
PE L N L N L N
N PE 22 23 52 53 BM 54 24 55 25 56 26 57 27 36 58 28 37 59 29 38 60 30 61 31 62 32 65 34 66
V1 V2 V3
pU
Calculation 2 PE PE PE PE
I Z
185 mm
200 mm
14.6 Fastening set
To ensure a gap between the BCU and the mounting
surface with higher temperatures.
74960414 Ø 4mm
mm
174 14.8 Bus module BCM 400
Communication interface for connecting the BCU to an
automation system.
263 mm
22 mm 45
230 mm
mm
12 mm
7 mm
16.5 mm
m
222 m
20 mm
74960712
74960707
74960709
74960711
15.2 Function
The bus system transfers the control signals for start-
ing, resetting and for controlling the air valve to purge
the furnace or kiln or for cooling in start-up position
and heating during operation from the automation
system (PLC) to the BCM. In the opposite direction, it
sends operating status, the level of the flame signal and
the current program step.
PROFIBUS DP
BCM..B2/B3
Connect the shield on both sides and over a wide area
Use shielded RJ45 plugs.
with shield clips in the plug.
Switch on the terminal resistors on the first and last Installation guidelines
subscriber in the segment. For PROFIBUS, PROFINET, see www.profibus.com,
for Ethernet installation guidelines, see www.odva.org.
The power supply for the bus terminator is provided by
the BCU. The bus terminator can be activated in the
PROFIBUS plug connector.
Ensure there is an equipotential bond between the de-
vices.
To connect the BCM..B1 to the PROFIBUS fieldbus
communications system, use an RS 485 9-pin PROFI-
BUS plug connector with a deactivatable bus termi-
nator and axial cable routing, e.g. 6GK1500-0FC00
or 6GK1500-0EA02 from Siemens. If other connec-
tors are used, ensure that metal parts are adequately
grounded.
BCU..P6: for connection to the BCU mounting plate,
use only a 9-pin Variosub PROFIBUS plug connector
with a deactivatable bus terminator,
Order No. 74960431
270
mm
The BCU 4 is suitable for continuous operation (pursu- Internal voltages are neither SELV nor PELV. Floating
ant to EN 298:2012-12, Section 3.126) and for inter- contacts meet the requirements for SELV.
mittent operation (pursuant to EN 298:2012-11, Sec-
19.3 Communication
tion 3.127).
Safety over EtherCAT® technology (FSoE, FailSafe over
Type of action EtherCAT) is used for K-SafetyLink communication.
The automatic action corresponds to Type 2 pursuant Safety over EtherCAT® is a registered trademark and
to EN 60730-1. patented technology licensed by Beckhoff Automation
Behaviour under fault conditions GmbH, Germany.
Switching off the safety-relevant output signals: The K-SafetyLink technology complies with SIL 3 in ac-
The output signals are switched off electronically in cordance with EN 61508 and is standardized pursuant
accordance with the criteria of automatic action type to IEC 61784-3-12 and ETG 5100.
B.V.AC.AD.AF.AG.AH (pursuant to EN 60730-2-5:2015, Safety over EtherCAT® uses the fail-safe principle which
Section 6.4.3.). means that a safe state is restored in the case of an
Maximum reaction time in the event of a flame failure: inactive signal. In the case of communication errors, all
This corresponds to the safety time during operation signals are interpreted as inactive.
and can be parameterized to between 1 and 4 s. Safety-relevant data are transmitted on the basis of the
black channel principle.
▼
20 Maintenance
The fail-safe outputs (valve outputs V1, V2, V3 and V4)
of the power module are monitored for correct func-
tioning. In the event of a fault, the system is set to a safe
status using a second shut-down path (isolation of the
valve outputs from the mains). In the event of a defect
(e.g. fault E 36), the power module must be replaced.
Order No. for the power module, see type label:
22.7 Safety shut-down In the event of a fault lock-out, the fault signalling con-
tact closes, the display flashes and shows the current
The burner control unit performs a safety shut-down
program step, see page 53 (Fault signalling). The
immediately after receiving a signal from a safety de-
gas valves are disconnected from the electrical power
vice or after a fault is detected (e.g. flame or air pressure
supply. The fault signalling contact opens if the mains
failure). The safety shut-down prevents operation of the
voltage fails.
burner by closing the fuel shut-off valves and deacti-
vating the ignition device. In order to restart, the BCU can only be reset manually
using the button on the front panel, the OCU or the re-
For this, the BCU disconnects the gas valves and the ig-
mote reset input (terminal 3).
nition transformer from the electrical power supply. The
operation signalling contact and the controller enable 22.9 Warning signal
signal are deactivated. The fault signalling contact re-
The BCU reacts to operating faults, e.g. in the case of
mains open. The display blinks and displays the current
permanent remote resets, with a warning signal. The
program step, see page 53 (Fault signalling).
display blinks and shows the corresponding warning
After a safety shut-down, the BCU can restart auto- message. The warning signal ends once the cause has
matically. been eliminated.
The program sequence continues. No safety shut-down
or fault lock-out occurs.
Remarks
Michael Rehkamp
m.rehkamp@kromschroeder.com
Osnabrück
Contact
The current addresses of our international agents
Elster GmbH are available on the Internet:
Postfach 2809 · 49018 Osnabrück https://thermalsolutions.honeywell.com ➔
Strotheweg 1 · 49504 Lotte (Büren) contact us
Germany
Tel. +49 541 1214-0 We reserve the right to make technical
Fax +49 541 1214-370 modifications in the interests of progress.
hts.lotte@honeywell.com Copyright © 2019 Elster GmbH
03251608
www.kromschroeder.com All rights reserved.