0% found this document useful (0 votes)
571 views5 pages

EPW30-48A Product Description: Power-One Co., Limited

The EPW30-48A rectifier module provides reliable DC power output in a high density form factor. It operates on the principle of active load sharing to tightly control output across multiple rectifiers. The module incorporates monitoring and status indicators through an internal microprocessor. It is equipped with fan cooling and various protections like overvoltage shutdown, thermal protection, and short circuit protection. The rectifier is intended to be installed in an EPS210-4830A system and can be installed or removed while the system is powered.

Uploaded by

Bys
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
571 views5 pages

EPW30-48A Product Description: Power-One Co., Limited

The EPW30-48A rectifier module provides reliable DC power output in a high density form factor. It operates on the principle of active load sharing to tightly control output across multiple rectifiers. The module incorporates monitoring and status indicators through an internal microprocessor. It is equipped with fan cooling and various protections like overvoltage shutdown, thermal protection, and short circuit protection. The rectifier is intended to be installed in an EPS210-4830A system and can be installed or removed while the system is powered.

Uploaded by

Bys
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 5

EPW30-48A

Product Description

Power-One Co., Limited


EPW30-48A Product Description

1.1. General
The Power-one EPW30-48A rectifier provides extremely reliable DC power in the highest
possible density. The module incorporates the latest power monitoring solutions through an
internal microprocessor by giving nearly real time updates to the system controller and adjacent
rectifiers. This guarantee tightly controlled load sharing among rectifiers and provides status and
identification information to the controller.
The rectifiers operate on the principle of active load sharing and can operate in parallel. They
incorporate "soft start" at the input and at the output, which avoids high incoming and outgoing
currents. The output voltage of the rectifier is automatically adjusted to the required voltage at
installation, by a reference in the backplane.
The rectifiers are primary switched power supplies, based upon modern resonance technology,
also known as "soft-switching". Benefits of this technique include high reliability, compact units,
self-protecting design and low emitted/conducted noise.
The EPW30-48A rectifiers are equipped with fan cooling. The module will turn off if a fault or
thermal problem should occur with the fan.
The EPW30-48A rectifiers be installed in EPS210-4830A system.

Figure 2-1 EPW30-48A rectifier module

Screw hands’s
Hands
Front board

Status LED’s

1
EPW30-48A Product Description

1.2. Technical Specification


1.2.1. Mains Input
Rating voltage: 220 VAC
Voltage range: 90 VAC ~ 300 VAC
Current(Max.): 10A per module
Frequency: 44 Hz -66 Hz
Power Factor: >0.98 typical

1.2.2. DC Output
Rating voltage: -48 VDC
Voltage range: -44 VDC ~ -58 VDC
Current limit: 33 A
Power: 1600 W (176 VAC-300 VAC)
700 W (85 VAC-176 VAC)
Efficiency: 220 VAC input: >92%
110 VAC input: >88%

1.2.3. Module Dimension and Weight


Height: 88.1 mm
Width: 105.4 mm
Depth: 249.5 mm
Weight: 2.2 kg

1.2.4. Other Technical Data


Protection: Short circuit proof
Automatic current limiting
Selective shut down of modules at excess output voltage.
Thermal protection reduces the output power at environmental temp. above
maximum level
Shut down at > 75 °C with automatic restart
Input over-voltage disconnection over 300 VAC with automatic reset over 290VAC.
Alarms: High output voltage/shut down
Low voltage/module failure
Each alarm has an LED indicator on the front panel and a common potential free
contact for external signalling
Storage temperature: -40 °C to +85 °C
Operating temperature: -40 °C to +55 °C, full power output
+55 °C to +65 °C, reduced output to 80% rated power

2
EPW30-48A Product Description

Cooling: Fan cooled, speed controlled and alarmed


EMC: EN 61000-6-2, EN 61000-6-3

1.2.5. Vibration / Shock


Zone 4 Compliant

1.2.6. Safety
CSA C22-2 No. 950
UL 950 and IEC60950 / EN 60950

1.3. Installation an Removing of Rectifiers


Rectifier modules should be installed starting from the leftmost position in the rectifier
sub-rack/shelf.
1. Before installing the module, first determine the install location.
2. Check to make sure that the rectifier handle is in the “OPEN” position.
3. Place the module into the correct mounting slot on the shelf.
4. Slide the module until it contacts the interface connection at the rear of the shelf.
5. Fully insert the rectifier by pushing the module handle towards the shelf, the handle will rise
up and lock the unit into place.
6. Repeat this procedure for additional modules.

Figure2-2 Installation and removing of rectifier module


Installation of rectifier Removing of rectifier

3
EPW30-48A Product Description

1.4. Operation
EPW30-48A has no specific operation except status indicators that is located on the front panel
of the module. The output voltage is adjusted from the controller.
EPW30-48A has LED indicators as follows:

LED Normal Abnormity Description

Indicating input voltage to module


Green LED light turn off
and module OK.
POWER ON

Yellow LED Indicating over temperature alarm


turn off light
WARNING and fan warning.

Indicating over voltage shutdown, fan


Red LED
shutdown, current sharing fault,
ALARM turn off light
temperature shutdown and other
reasons resulting in no output.

Note! The module is hot swappable and can be plugged or unplugged in a powered system
without interfering other modules or load.