Statrite Hs Manual
Statrite Hs Manual
4” Submersible Pumps
Two and Three Wire, Single and Three
Phase, 1/2 through 10 H.P., 60 Hz
NOTICE D’INSTALLATION ET DE
FONCTIONNEMENT
Pompes submersibles de 4 pouces
Moteurs bifilaires et trifilaires,
Monophasés et triphasés, Puissance de
1/2 à 10 ch, 60 Hz
MANUAL DE INSTALACIÓN Y
FUNCIONAMIENTO
Bombas sumergibles de 4”
Bifilares y Trifilares, Monofásicas y
trifásicas, 1/2 hasta 10 H.P., 60 Hz
English.......................................................Pages 2-12
Français...................................................Pages 13-23
Español.................................................. Paginas 24-34
Tables • Tableaux • Cuadros....................Pages 35-47
Diagrams • Schémas • Diagramas............Pages 48-64
Record the following information from the motor and Sur les lignes qui suivent, indiquer les informations Anote la siguiente información de las chapas del motor y de la
pump nameplates for future reference: suivantes qui se trouvent sur les plaques signalétiques bomba para referencia futura:
du moteur et de la pompe de façon à pouvoir s’y reporter
ultérieurement :
Pump Model No.
N° de modèle de la pompe
No. de modelo de la bomba
Pump Serial No.
N° de série de la pompe
No. de serie de la bomba
Motor Model No.
N° de modèle du moteur
No. de modelo del motor
Motor Serial No.
N° de série du moteur
No. de serie del motor
H.P., Volts/Hz/Ph
Puissance en CH Volts/Hz/Phase(s)
H.P. Voltios/Hz/Fase
Rated Amp Draw
Débit nominal en ampères
Corriente nominal extraída
Figure 9
Figure 6
Figure 10
Figure 7
Figure 11
Figure 8
Installation 8
Butt Connectors with plastic insulators - For wire supplying current to motor. Consult current
sizes AWG 14, 12 and 10 (2, 3, and 5.5mm²): National Electrical Code, Canadian Electrical
1. Cut off motor leads. Stagger lead and wire Code and local codes (as applicable) for
length so that 2nd lead is 4” (100mm) longer grounding information.
than 1st lead and 3rd lead is 4” (100mm) 4. Use only submersible cable supplied by pump
longer than second. manufacturer. When lowering pump into well,
2. Cut off cable ends. Be sure to match colors secure cable to discharge pipe at 10’ (3.5m)
and lengths of wires in drop cable to colors intervals with electrical tape. Take care not to
and lengths of motor leads. damage pump cable.
NOTICE To avoid dropping the pump down
3. Trim insulation back 1/2” (13mm) from cable
the well or damaging cable or cable splices,
ends and motor lead ends.
NEVER allow pump cable to support weight
4. Unscrew plastic caps from insulators. Place a of pump.
cap and a neoprene gasket sleeve on each wire
end to be spliced (see Figure 9). Pump Installation
5. Slide insulator body onto one wire end 1. If a standard air over water pressure tank is
(Figure 9). being used, install two bleeder orifices about
6. Insert wire end into butt connector and crimp 2’ (60cm) apart as shown on page 63. These
(see Figure 10). Be sure to match cable and orifices will automatically charge the tank with
motor wire colors. air. See page 62 to determine orifice location.
7. Center insulator body over splice and slide NOTICE If a pre-charged tank is used, DO
neoprene sleeves into body as far as they NOT install bleeder orifices. If pump and
will go. Screw caps onto insulator body pre-charged tank are replacing a standard
(Figure 11) and tighten by hand for a strong, tank system, remove bleeder orifices before
waterproof splice. installing pump in well.
2. To prevent losing pump down the well,
Cable Installation connect a safety rope strong enough to support
1. To test submersible pump, momentarily pump and drop pipe (minimum 5/16” [8mm]
connect it to proper power supply. Power twisted polypropylene or pronila rope) to
supply frequency and voltage must match eyelet on pump discharge. Tie off other end of
motor nameplate frequency and voltage safety rope securely to well seal, well cap or
to within ±10%. See Rotation for three pitless adapter.
phase pumps. 3. Discharge outlet is threaded 2” NPT (60 Hz) or
2. Fasten cable leads securely to pump discharge 2” BSP (50 Hz).
section; leave 4-5” (100-127mm) of slack in Use 100 PSI rated polyethylene plastic pipe for
leads at this point. Securely fasten leads to installations up to 100’ (30m) depth.
plastic pipe within 6” (150mm) of the pump Use 160 PSI rated polyethylene plastic pipe for
discharge section. Use properly-installed installation up to 220’ (67m) depth.
torque arresters to protect pump and pipe from For depths beyond 220’ (67m), use galvanized
twisting damage as pump starts and stops. steel pipe for the entire drop pipe.
3. Connect copper ground wire to motor bracket.
Ground wire must be at least as large as wires
Installation 9
Initial Start-Up Effluent Applications
NOTICE NEVER operate pump with discharge valve Pumps designed and tested for effluent applications
completely closed. Pump can destroy itself if run must meet the following:
with discharge shut off (“deadheaded”). Risk of electric shock. Do not remove
NOTICE To avoid sand-locking pump, follow cord and strain relief. Do not connect conduit
procedure below when starting pump for the to pump.
first time. NEVER start a pump with discharge 1. Only qualified personnel should install the
completely open unless you have done this pump and associated control equipment.
procedure first. 2. Vent sewage or septic tank according to
1. Connect a pipe elbow, a short length of pipe local codes.
and a gate valve to pump discharge at well 3. Do not install pump in any location classified
head (see Figure 12). as hazardous by National Electrical Code,
Control Temporary wiring ANSI/NFPA 70-2001.
center to control center or 4. These pumps are intended for permanent
or electrical disconnect box
electrical connection only. Provide strain relief at control
disconnect Temporary piping box for power supply cord connection to box.
box Gate valve All control components must be UL listed and
suitable for end use application.
Connecting To Tank /
Water System
Hazardous pressure. Submersible
Pump installation Pump in well
pumps can develop very high pressure in some
for developing a well
situations. To prevent tank failure, install a pressure
relief valve able to pass full pump flow at 75 PSI
(517 kPa) when using an air over water pressure
tank. Install a pressure relief valve capable of
689 0993 passing entire pump flow at 100 PSI (690 kPa)
Figure 12 - Typical pump start-up when using a pre-charged pressure tank. Install this
relief valve between pump and tank.
2. Mount motor control box (3-wire pump), fused NOTICE Allowing pump or piping system to
disconnect switch (2-wire pump), or magnetic freeze may severely damage pump and will void
starter (three-phase pump) in a permanently warranty. Protect pump and entire piping system
weather proofed place. Make sure that controls (including pressure tank) from freezing.
will not be subjected to extreme heat or
excess moisture. Standard Tank Hookup:
3. Make sure controls are in OFF position. See page 62 for piping connections to standard
4. Connect motor leads and power supply to pressure tank and for correct distance of bleeder
motor control box, fused disconnect switch, or orifices from pressure tank.
magnetic starter (see Diagrams). Do not start Pre-charged Pressure Tank
pump yet.
5. Set gate valve on discharge 1/3 open; start Hookup:
pump (see Figure 12). See page 63 for piping connections to pre-charged
6. Keep gate valve at this setting while water pressure tank.
pumps out on ground. Let it run until water is NOTICE Check air pre-charge in tank before
clear of sand or silt. To check solids in water, fill starting pump. Adjust pre-charge to 2 PSI (13.8 kPa)
a glass from pump and let solids settle out. below pump cut-in setting. (For example, a pre-
7. When water is completely clear at 1/3 setting, charge tank used with a 30-50 switch should be
open gate valve to approximately two-thirds pre-charged with air to 28 PSI (193 kPa). Adjust
open and repeat process. pre-charge by either adding or bleeding air through
8. When water is completely clear at 2/3 setting, air pressure valve located on top of tank. Check
open gate valve completely and run pump until pre-charge annually and adjust as needed.
water is completely clear.
9. Remove gate valve for permanent installation
near tank (see pages 62 and 63).
10. Install sanitary well seal or pitless adapter unit,
well unit, electrical conduit and surface piping
according to local code requirements.
Troubleshooting 10
Problem Check Corrective Action
Motor will not start but fuses do not blow.
No voltage at fuse box. Consult power supplier, check generator.
Troubleshooting
Check connections, rewire from fuse box
No voltage at control box.
to control box.
Check connections, replace control box,
No voltage at pressure switch.
rewire from control box to pressure switch.
No voltage.
No voltage on load side of pressure Check connections, replace pressure
switch. switch.
Cable or splices bad. Consult serviceman or licensed electrician.
Reconnect control box correctly (see
Control box incorrectly wired.
Diagrams).
Fuses blow or overload protector trips when motor starts.
Wrong size fuse or
Check fuse size against Fuse Size
wrong size time delay Install correct fuse or time delay fuse.
tables.
fuse.
Check wire size against Cable Sizing
Wire size too small. Install correct size wire.
tables.
Starting capacitor Check control box to see if starting
Replace starting capacitor.
defective or blown. capacitor has blown out.
Check that line voltage is within
If voltage variation is greater than ±10%,
Low or high voltage. ±10% of nameplate rated voltage
call power company to adjust voltage.
while motor is running.
Check control box wiring diagram Reconnect leads to match wiring diagram
Cable leads not against incoming power hookup. in control box cover.
correctly connected to
control box. Reconnect drop cable so cable color code
Check drop cable color coding.
matches motor lead color code.
Broken wire in control Examine all connections and wiring in Disconnect power and repair or replace
box. control box. faulty wire.
If necessary, pull pump (make all possible
Pump or motor stuck or above ground checks first). If pump is
Check for locked rotor in pump.
binding. locked, replace it. Clean well of all sand or
lime before reinstalling pump.
Fuses blow or overload protector trips when motor is running.
Check that line voltage is within
If voltage variation is more than ±10%, call
Low or high voltage. ±10% of rated nameplate voltage
power company to adjust voltage.
while motor is running.
High ambient
Do not mount control box in direct
(atmospheric Check temperature of control box.
sunlight.
temperature).
Compare voltage and horsepower on
Control box with wrong
motor nameplate with those given on Replace control box if numbers do not
voltage or horsepower
control box nameplate or on circuit match.
rating.
diagram inside control box cover.
Check wire size against Cable Sizing
Wire size too small. Install correct wire size.
tables.
Cable splices or motor
Consult licensed electrician or Do not attempt to disassemble pump or
leads grounded,
qualified serviceman. motor.
shorted, or open.
Troubleshooting 11
Problem Check Corrective Action
Pump starts too frequently.
Check all tank connections with
Leaks in system. soapsuds for air leaks. Check System must be air and water tight.
plumbing for leaks.
Check for defective switch or switch
Pressure switch. Re-adjust or replace pressure switch.
out of adjustment.
Pre-charge tanks: adjust air pressure
Pre-charged tanks; check tank pre- to 2 PSI (13.8 kPa) less than pump
charge air pressure, check for leak in cut-in pressure (when there is no
bladder. water pressure on system). Replace
Tank waterlogged. bladder if necessary.
Air over water tanks: check for air
Air over water tanks: repair or replace
leaks. Check Air Volume Control
tanks; replace air pressure valve if
(AVC). Check air pressure valve
necessary.
operation.
Raise drop pipe one length at a time
Leak in drop pipe. Replace pipe above that point.
until water stands in pipe.
Pressure switch too far from Measure distance from pressure Move switch to within one foot (.3m)
tank. switch to tank. of tank.
Little or no water delivered.
Bleeder orifice check valve
If stuck, free valve; if installed
stuck or installed backwards Examine valve.
backwards, reverse it.
(standard tank only).
Lower pump further into well (but
at least 5’ (1.6m) above bottom of
well). Throttle pump discharge until
Determine lowest water level in well
discharge equals recovery rate of
Low water level. while pump is running and compare
well.
to pump depth setting.
NOTICE Running pump while
airlocked can cause loss of prime and
seriously damage pump.
Install larger wire from meter to
Check voltage at control box with
control box. Install larger wire from
pump running. Check incoming
Low voltage. control box to pump. If necessary,
wire size and drop cable size against
have power company raise supply
Cable Sizing tables.
voltage.
Pull pump and check condition of
Plugged intake screen. Clean or replace as necessary.
screen.
Check valve at pump
Pull pump and examine check valve. Free check valve.
discharge stuck.
Make sure system is clear of
Worn impellers and diffusers. obstructions and pump is in solid Replace pump.
water and operation normal.
Air or milky water discharge from faucets.
Remove bleeder orifices; plug tees.
Check for presence of gas in well Be sure plugged tees do not leak.
Gas in well water.
water. If necessary, separate gas from air
before it enters pressure tank.
Air volume control not
Make sure ports and ball check valves
working (standard tanks Replace control if necessary.
are clear.
only).
Warranty 12
Limited Warranty
PENTAIR warrants to the original consumer purchaser (“Purchaser” or “You”) of the products listed below, that they will be free
Warranty
from defects in material and workmanship for the Warranty Period shown below.
Product Warranty Period
whichever occurs first:
Water Systems Products — jet pumps, small centrifugal pumps,
12 months from date of original installation,
submersible pumps and related accessories
18 months from date of manufacture
12 months from date of original installation, or
PENTEK INTELLIDRIVE™
18 months from date of manufacture
Pro-Source® Composite Tanks 5 years from date of original installation
Pro-Source® Steel Pressure Tanks 5 years from date of original installation
Pro-Source® Epoxy-Line Tanks 3 years from date of original installation
12 months from date of original installation, or
Sump/Sewage/Effluent Products
18 months from date of manufacture
Our warranty will not apply to any product that, in our sole judgment, has been subject to negligence, misapplication,
improper installation, or improper maintenance. Without limiting the foregoing, operating a three phase motor with single
phase power through a phase converter will void the warranty. Note also that three phase motors must be protected by three-
leg, ambient compensated, extra-quick trip overload relays of the recommended size or the warranty is void.
Your only remedy, and PENTAIR’s only duty, is that PENTAIR repair or replace defective products (at PENTAIR’s choice). You must
pay all labor and shipping charges associated with this warranty and must request warranty service through the installing dealer
as soon as a problem is discovered. No request for service will be accepted if received after the Warranty Period has expired. This
warranty is not transferable.
PENTAIR IS NOT LIABLE FOR ANY CONSEQUENTIAL, INCIDENTAL, OR CONTINGENT DAMAGES WHATSOEVER.
THE FOREGOING LIMITED WARRANTIES ARE EXCLUSIVE AND IN LIEU OF ALL OTHER EXPRESS AND IMPLIED WARRANTIES,
INCLUDING BUT NOT LIMITED TO IMPLIED WARRANTIES OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR
PURPOSE. THE FOREGOING LIMITED WARRANTIES SHALL NOT EXTEND BEYOND THE DURATION PROVIDED HEREIN.
Some states do not allow the exclusion or limitation of incidental or consequential damages or limitations on how long an implied
warranty lasts, so the above limitations or exclusions may not apply to You. This warranty gives You specific legal rights and You
may also have other rights which vary from state to state.
This Limited Warranty is effective June 1, 2011 and replaces all undated warranties and warranties dated before June 1, 2011.
PENTAIR
293 Wright St., Delavan, WI 53115
Phone (262) 728-5551 • Fax (262) 728-7323