0% found this document useful (0 votes)
840 views5 pages

SEC Circuit Breaker Specs

This 3 sentence summary provides the key details from the document: This specification document from the Saudi Electricity Company sets technical requirements for 400 amp molded case circuit breakers intended for use in low voltage distribution panels in Saudi Arabia's electricity distribution system. The specification outlines design, construction, rating and additional requirements for circuit breakers, including that they must have a minimum 50kA interrupting rating and be interchangeable between at least 3 approved manufacturers. The breakers must be fixed at 400 amps capacity and rated to operate at full load in an ambient temperature of 55 degrees Celsius.
Copyright
© Attribution Non-Commercial (BY-NC)
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
840 views5 pages

SEC Circuit Breaker Specs

This 3 sentence summary provides the key details from the document: This specification document from the Saudi Electricity Company sets technical requirements for 400 amp molded case circuit breakers intended for use in low voltage distribution panels in Saudi Arabia's electricity distribution system. The specification outlines design, construction, rating and additional requirements for circuit breakers, including that they must have a minimum 50kA interrupting rating and be interchangeable between at least 3 approved manufacturers. The breakers must be fixed at 400 amps capacity and rated to operate at full load in an ambient temperature of 55 degrees Celsius.
Copyright
© Attribution Non-Commercial (BY-NC)
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 5

Saudi Electricity Company

SEC DISTRIBUTION MATERIALS SPECIFICATION


37-SDMS-02 DATE: 23-01-2006G

37-SDMS-02

SPECIFICATIONS FOR MOLDED CASE CIRCUIT BREAKER FOR LOW VOLTAGE DISTRIBUTION PANELS 400 AMPS

This specification is property of SEC and subject to change or modification without any notice

Saudi Electricity Company


SEC DISTRIBUTION MATERIALS SPECIFICATION


37-SDMS-02 DATE: 23-01-2006G

CONTENTS
Clause Page

1.0 2.0 3.0 4.0 5.0 6.0 7.0

SCOPE CROSS REFERENCES APPLICABLE CODES AND STANDARDS DESIGN AND CONSTRUCTION REQUIREMENTS CONTINUOUS CURRENT RATINGS INTERRUPTING RATING ADDITIONAL REQUIREMENTS

3 3 3 3 4 4 4

Page 2 of 4

Saudi Electricity Company


SEC DISTRIBUTION MATERIALS SPECIFICATION


37-SDMS-02 DATE: 23-01-2006G

1.0 SCOPE: This material standard specification is an additional technical requirements for a 400Amps circuit breakers specified in a SEC Specification No: 37-SDMS-01 (latest revision) for "Low Voltage Molded Case Circuit Breakers", to achieve the minimum technical requirements for design, engineering, manufacture, inspection, testing and performance of outgoing Circuit Breaker, intended to be used for protection of the outgoing feeders of the low voltage distribution panel of the substations used in the distribution system of Saudi Electricity Company (SEC) in Saudi Arabia 2.0 CROSS REFERENCES: This material standard specification shall be read in conjunction with SEC Specification No: 01-SDMS-01 (latest revision) for "General Requirements for all Equipments/ Materials", 37-SDMS-01 (latest revision) for "Low Voltage Molded Case Circuit Breakers" and 31SDMS-01 (latest revision) for "low voltage distribution panel", which shall be considered as an integral part of this SDMS. This SDMS shall also be read in conjunction with SEC Purchase Order requirements. 3.0 APPLICABLE CODES & STANDARDS: As per SEC Specification No: 37-SDMS-01 (latest revision) for "Low Voltage Molded Case Circuit Breakers". 4.0 DESIGN & CONSTRUCTION REQUIREMENTS: 4.1 Breakers described in this specification are suitable for operation in 400 or 230V, 60 Hz, 4 wires distribution system with solidly earthed neutral. 4.1 Breakers shall be in accordance with SEC Specification No: 37-SDMS-01 (latest revision) for "Low Voltage Molded Case Circuit Breakers" with the following additional requirements: 4.1.1 Break trip free-mechanism as per 37-SDMS-01 (latest revision). 4.1.2 Breaker can be equipped by an electronic solid state trip-control unit for overload and short circuit protection. 4.1.3 Breakers should be with current limiting functions.

Page 3 of 4

Saudi Electricity Company


SEC DISTRIBUTION MATERIALS SPECIFICATION


37-SDMS-02 DATE: 23-01-2006G

4.1.4 The breaker shall be able to sustain short-time overloads without tripping, so that magnetic in-rush current experienced by the starting of inductive loads such as air-conditioner compressor will not affect operation. 4.1.5 The breaker shall have instantaneous short circuit tripping characteristics such that the fault will trip the breaker in a fraction of a second. 4.1.6 Outgoing terminals shall be suitable for front direct connection of 300mm Al. cables as per SEC spec. 11-SDMS-01 by means of bimetallic lugs with M10 bolt and palm width of 30mm.as per fig # 5 of spec 12-SDMS-02 4.1.7 Incoming terminals shall be designed to accept a size of busbar suitable for the breaker rated current. 4.1.8 All outgoing terminals shall be equipped with terminal separators, covers, and without terminal spreaders or extended terminals. 4.1.9 All breakers shall be without lock or locking device. 4.1.10 These MCCBs shall be easily interchangeable with at least 3 SEC approved manufacturers, if possible. 5.0 CONTINUOUS CURRENT RATINGS: 5.1 The circuit breakers shall be in one fixed capacity of 400 amps, adjustable type is not acceptable. 5.2 The breakers shall be designed to work at full rating in an ambient temperature of 55C. 6.0 INTERRUPTING RATING: The Circuit Breaker must have minimum ultimate interrupting rating of 50 KA symmetrical at 220 Volts. 7.0 ADDITIONAL REQUIREMENTS: Name plate, Testing, Inspection, Packing & Shipping, Guarantee and Submittals shall be according to SEC Specification No: 37-SDMS-01 (latest revision) for "Low Voltage Molded Case Circuit Breakers".

Page 4 of 4