Alfa Laval CB60 / CBH60 / CBP60
Brazed plate heat exchanger
Alfa Laval CB brazed plate heat exchangers provide efficient
heat transfer with a small footprint.
Applications
• HVAC heating and cooling
• Refrigeration
• Oil cooling
• Industrial heating and cooling
Benefits
• Compact
• Easy to install
• Self-cleaning
• Low level of service and maintenance is required
• All units are pressure and leak tested
• Gasket free
Design
The brazing material seals and holds the plates together at the
contact points ensuring optimal heat transfer efficiency and
pressure resistance. Using advanced design technologies and
extensive verification guarantees the highest performance and
longest possible service life.
Different pressure ratings are available for different needs.
The unit can be supplied with a refrigerant distribution system
.for optimal evaporator performance. Examples of connections
Based on standard components and a modular concept, each
unit is custom-built to meet the specific requirements of each
individual installation.
External thread Internal thread Soldering
Welding
Technical Data Design pressure and temperature
Standard materials CB60/CBH60 – PED approval pressure/temperature graph
Cover plates Stainless steel
Connections Stainless steel
Plates Stainless steel
Brazing filler Copper
Dimensions and weight 1
A measure (mm) CB, CBH: 13 + (2.32 * n) 2
CBP: 17 + (2.32 * n)3
A measure (inches) CB, CBH: 0.51 + (0.09 * n) 3
CBP:0.67 + (0.09 * n) 3
Weight (kg)4 CB, CBH:2.1 + (0.18 * n)
CBP:2.26 + (0.18 * n)
Weight (lb)4 CB, CBH: 4.63 + (0.4 * n)
CBP: 4.98 + (0.4 * n)
CB60/CBH60 – UL approval pressure/temperature graph
1. n = number of plates
2. Excluding reinforcements
3. Excluding reinforcements
4. Excluding connections
Standard data
Volume per channel, litres (gal) 0.103 (0.027)
Max. particle size, mm (inch) 1 (0.039)
Max. flowrate1 m3/h (gpm) 14 (62)
Flow direction Parallel
Min. number of plates 4
Max. number of plates 150
1. Water at 5 m/s (16.4 ft/s) (connection velocity)
Dimensional drawing CBP60 – PED approval pressure/temperature graph
Measurements in mm (inches)
113 (4.45)
50 A
(1.97)
S4 S1
466 (18.34)
527 (20.74)
Alfa Laval is a trademark registered and owned by Alfa Laval Corporate AB.
Designed for full vacuum.
Alfa Laval plate heat exchangers are available with a wide
range of pressure vessel approvals. Please contact your Alfa
S3 S2 Laval representative for more information.
NOTE: Values above are to be used as an indication. For exact
values, please use the drawing generated by the Alfa Laval
configurator or contact your local Alfa Laval representative.
CHE00026EN 2016-09 Alfa Laval reserves the right to change specifications without prior notification.
How to contact Alfa Laval
Contact details for all countries are continually updated on our
website. Please visit www.alfalaval.com to access the information
direct.