30gxn-4pd Product Data
30gxn-4pd Product Data
30GXN,GXR080-528
Data High-Efficiency
Air-Cooled Chillers
with ComfortLinkTM Controls
60 Hz
80 to 525 Nominal Tons (267 to 1750 kW)
Features/Benefits
Easy installation
The 30GXN,R unit has a compact
design that is up to 50% smaller than
earlier air-cooled chillers. The compact
footprint can yield substantial installa-
tion savings by requiring less structural
steel, concrete, security fencing or
architectural screening. The 30GXN,R
unit is delivered as a complete package
for easy installation.
A quick start-up is assured once
installation is complete, since each
30GXN,R unit is manufactured at an
ISO 9001:2000 listed manufacturing
facility to ensure quality. In addition, all
units are factory run tested under full
load to provide reliable start-up.
Easy to live with
The 30GXN,R units have a quiet, low-
vibration design featuring rotary screw
compression and AeroAcoustic™ fans
that reduce sound levels and
improve sound quality. Lower sound
levels help avoid the need for costly
sound barriers that may be needed
with other screw compressor chillers.
The 30GXN,R controls are fully auto-
matic. The leaving-fluid temperature is
directly controlled, and the entering-
fluid temperature is continuously
monitored to detect load and flow
changes. This combination (an exclu-
sive ComfortLink controls advantage)
provides the most precise temperature
2
Features/Benefits (cont)
Features • Superior full and part-load efficiency.
• Simple and easy to use ComfortLinkTM
communicating • Precise multiple-step capacity.
controls. • Low noise operation.
• Wide operating envelope from –20 to 125 F (–29 to 52 C). • Dual independent refrigerant circuits.
• Accurate temperature control with return fluid • Full load factory run tested.
compensation. • Wide range of sizes available from stock.
• Built-in dual chiller control, reset from return. • Compact size.
Com
fort
NA Lin
VIG
ATO k
R™
L e a vi
ng W
a te r
4 4 . 0 Te m p e
°F ra tu
re
MO
DE
Run Ala rm
Status St atu
s
Servi
ce Te
st
Temp
eratur
es
Pres
sures
Setpo
ints
Inputs
Outpu
ts
Confi
gurat
ion
Time
Clock
Opera ESC
ting
Mode
Alarm s
s
ENT
ER
HFC-134a
800
700
200
100
0
SCHOOL HEALTH INDUSTRY LODGING OFFICE RETAIL
SMALL FOOTPRINT
3
Model number nomenclature
30GX N 128 M S – 6 4 1 AA
Quality Assurance
Approvals:
ISO 9001
®
EN 9000:2000
60
IS O
22
90
01:2000 #A
4
Physical data — English
60 Hz UNITS
UNIT SIZE 30GXN,R 080 083 090 093 106 108 114 118 125 128 135 138 150 153 160
OPERATING WEIGHT (lb)
Cu-Al 6313 6907 6333 7201 7514 7662 7524 8649 7553 8664 7714 8789 8784 9,684 9,072
Cu-Cu 6988 7602 7008 7896 8209 8357 8219 9699 8248 9714 8414 9739 9834 11,084 10,172
REFRIGERANT TYPE HFC-134a
Refrigerant Charge (lb)
Ckt-A/Ckt-B 106/96 128/123 115/96 135/123 150/123 135/123 160/123 170/151 160/141 190/151 175/175 190/175 156/228 263/178 181/243
COMPRESSORS Semi-Hermetic, Twin Screw
Quantity 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2
Economized No No No No No Yes No Yes Yes Yes Yes Yes Yes Yes Yes
No. Capacity Steps
Standard 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6
Optional (maximum) 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8
Min. Capacity Step (%)
Standard 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20
Optional 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10
COOLER* Flooded Type Shell and Tube with Enhanced Copper Tubes
Net Fluid Volume (gal) 18.9 18.9 18.9 18.9 22.6 22.6 22.6 20.9 33.4 24 33.4 24 24 24 28.5
Maximum Refrigerant 220 220 220 220 220 220 220 220 220 220 220 220 220 220 220
Pressure (psig)
Maximum Fluid Side 300 300 300 300 300 300 300 300 300 300 300 300 300 300 300
Pressure (psig)
FLUID CONNECTIONS (in.) Victaulic Connections
Inlet and Outlet 4 4 4 4 5 5 5 4 5 4 5 4 4 4 5
Drain (NPT) 1/ 1/ 1/2 1/ 1/2 1/2 1 /2 1/2 1 /2 1/2 1/2 1/2 1/2 1 /2 1/2
2 2 2
CONDENSER FANS
Standard/Low Noise Type Shrouded Axial Type, Vertical Discharge
Fan Speed (rpm) 1140 1140 1140 1140 1140 1140 1140 1140 1140 1140 1140 1140 1140 1140 1140
No. Blades...Dia. (in.) 11...30 11...30 11...30 11...30 11...30 11...30 11...30 11...30 11...30 11...30 11...30 11...30 11...30 11...30 11...30
No. Fans...Total kW 4...6.4 6...9.6 4...6.4 6...9.6 6...9.6 6...9.6 6...9.6 8...12.8 6...9.6 8...12.8 6...9.6 8...12.8 8...12.8 10...16 8...12.8
Total Airflow (cfm) 45,600 68,400 45,600 68,400 68,400 68,400 68,400 91,200 68,400 91,200 68,400 91,200 91,200 114,000 91,200
High Static Type Propeller Type, Vertical Discharge
Fan Speed (rpm) 1750 1750 1750 1750 1750 1750 1750 1750 1750 1750 1750 1750 1750 1750 1750
No. Blades...Dia. (in.) 12...30 12...30 12...30 12...30 12...30 12...30 12...30 12...30 12...30 12...30 12...30 12...30 12...30 12...30 12...30
No. Fans...Total kW 4...16.4 6...24.6 4...16.4 6...24.6 6...24.6 6...24.6 6...24.6 8...32.8 6...24.6 8...32.8 6...24.6 8...32.8 8...32.8 10...41 8...32.8
Total Airflow (cfm)† 39,200 58,800 39,200 58,800 58,800 58,800 58,800 78,400 58,800 78,400 58,800 78,400 78,400 98,000 78,400
CONDENSER COILS 3/ -in. OD Copper Tubes with Aluminum Fins
8
Fins/in. 17 17 17 17 17 17 17 17 17 17 17 17 17 17 17
No. Rows 3 3 3 4 4 4 4 4 3 4 4 4 4 4 4
Total Face Area (sq ft) 135 162 135 162 162 162 162 216 162 216 162 216 216 270 216
Maximum Working 450 450 450 450 450 450 450 450 450 450 450 450 450 450 450
Pressure (psig)
UNIT SIZE 30GXN,R 163 174 178 204 208 225 228 249 253 264 268 281 301 325 350
OPERATING WEIGHT (lb)
Cu-Al 10,279 9,714 10,294 12,747 14,099 12,985 14,114 13,867 16,736 13,902 16,751 18,718 18,738 18,778 18,828
Cu-Cu 11,947 11,114 11,962 14,147 19,941 14,360 19,956 15,567 19,941 15,602 19,956 21,923 21,943 21,983 22,033
REFRIGERANT TYPE HFC-134a
Refrigerant Charge (lb)
Ckt-A/Ckt-B 263/220 263/207 263/263 270/208 330/175 285/215 340/175 339/205 410/205 339/215 410/215 385/385 400/400 415/415 430/430
COMPRESSORS Semi-Hermetic, Twin Screw
Quantity 2 2 2 3 3 3 3 3 3 3 3 4 4 4 4
Economized Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes
No. Capacity Steps
Standard 6 6 6 8 8 8 8 8 8 8 8 10 10 10 10
Optional (maximum) 8 8 8 10 10 10 10 10 10 10 10 12 12 12 12
Min. Capacity Step (%)
Standard 20 20 20 15 15 15 15 15 15 15 15 10 10 10 10
Optional 10 10 10 10 10 10 10 10 10 10 10 5 5 5 5
COOLER* Flooded Type Shell and Tube with Enhanced Copper Tubes
Net Fluid Volume (gal) 28.5 28.5 28.5 38.5 38.5 43.1 43.1 47.2 47.2 47.2 47.2 56.1 56.1 56.1 56.1
Maximum Refrigerant 220 220 220 220 220 220 220 220 220 220 220 220 220 220 220
Pressure (psig)
Maximum Fluid Side 300 300 300 300 300 300 300 300 300 300 300 300 300 300 300
Pressure (psig)
FLUID CONNECTIONS (in.) Victaulic Connections
Inlet and Outlet 5 5 5 6 6 6 6 6 6 6 6 8 8 8 8
Drain (NPT) 1/2 1 /2 1/2 1 /2 1/2 1/2 1 /2 1/2 1 /2 1/2 1/2 1/2 1/2 1 /2 1/2
CONDENSER FANS
Standard/Low Noise Type Shrouded Axial Type, Vertical Discharge
Fan Speed (rpm) 1140 1140 1140 1140 1140 1140 1140 1140 1140 1140 1140 1140 1140 1140 1140
No. Blades...Dia. (in.) 11...30 11...30 11...30 11...30 11...30 11...30 11...30 11...30 11...30 11...30 11...30 11...30 11...30 11...30 11...30
No. Fans...Total kW 12...19.2 10...16 12...19.2 10...16 14...22.4 10...16 14...22.4 12...19.2 16...25.6 12...19.2 16...25.6 16...25.6 16...25.6 16...25.6 16...25.6
Total Airflow (cfm) 136,800 114,000 136,800 114,000 159,600 114,000 159,600 136,800 182,400 136,800 182,400 182,400 182,400 182,400 182,400
High Static Type Propeller Type, Vertical Discharge
Fan Speed (rpm) 1750 1750 1750 1750 1750 1750 1750 1750 1750 1750 1750 1750 1750 1750 1750
No. Blades...Dia. (in.) 12...30 12...30 12...30 12...30 12...30 12...30 12...30 12...30 12...30 12...30 12...30 12...30 12...30 12...30 12...30
No. Fans...Total kW 12...49.2 10...41 12...49.2 10...41 14...57.4 10...41 14...57.4 12...49.2 16...65.6 12...49.2 16...65.6 16...65.6 16...65.6 16...65.6 16...65.6
Total Airflow (cfm)† 117,600 98,000 117,600 98,000 137,200 98,000 137,200 117,600 156,800 117,600 156,800 156,800 156,800 156,800 156,800
CONDENSER COILS 3/8-in. OD Copper Tubes with Aluminum Fins
Fins/in. 17 17 17 17 17 17 17 17 17 17 17 17 17 17 17
No. Rows 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4
Total Face Area (sq ft) 324 270 324 270 378 270 378 324 432 324 432 432 432 432 432
Maximum Working 450 450 450 450 450 450 450 450 450 450 450 450 450 450 450
Pressure (psig)
LEGEND
Ckt — Circuit
Cu-Al — Standard Coils with Copper Tubes and Aluminum Fins
Cu-Cu — Optional Coils with Copper Tubes and Copper Fins
*Each cooler is shipped with approximately 5 gallons of propolyene glycol to provide freeze pro-
tection during storage and shipment.
†Based on rated external static pressure of 0.4 in. wg or 0.8 in. wg as appropriate.
5
Physical data — English (cont)
60 Hz DUPLEX UNITS
UNIT SIZE 30GXN,R 283 303 328 353 370 373 390 393 415
OPERATING WEIGHT (lb) HFC-134a
Cu-Al 18,473 19,068 19,978 20,588 21,769 25,525 21,617 26,420 22,974
Cu-Cu 20,823 21,686 23,046 23,924 24,194 29,680 24,017 31,025 25,774
REFRIGERANT CHARGE
Circuits Qty 4 4 4 4 4 4 4 4 4
Module A Ckt A/Ckt B (lb) 263/178 263/220 263/263 263/263 285/215 410/205 339/215 410/205 339/215
Module B Ckt A/Ckt B (lb) 190/175 190/175 263/178 263/263 156/228 190/175 175/175 263/178 181/243
COMPRESSORS Semi-Hermetic, Twin Screw
Quantity 4 4 4 4 5 5 5 5 5
Economized Yes Yes Yes Yes Yes Yes Yes Yes Yes
No. Capacity Steps
Standard 12 12 12 12 14 14 14 14 14
Optional (maximum) 16 16 16 16 18 18 18 18 18
Min. Capacity Step (%)
Standard 10 10 10 10 8 8 7 8 8
Optional 5 5 5 5 4 4 3.5 4 4
COOLER* Flooded Type Shell and Tube with Enhanced Copper Tubes
Net Fluid Volume (gal) 48.0 52.5 52.5 57.0 67.1 71.2 80.6 71.2 75.7
Max Refrigerant 220 220 220 220 220 220 220 220 220
Pressure (psig)
Max Fluid Side 300 300 300 300 300 300 300 300 300
Pressure (psig)
FLUID CONNECTIONS Victaulic Connections
Inlet and Outlet (in.) 8 8 8 8 8 8 8 8 8
Cooler Interconnecting (in.) 8 8 8 8 8 8 8 8 8
Drain — Qty...Size (in.) 2...1/2 2...1/2 2...1/2 2...1/2 2...1/2 2...1/2 2...1/2 2...1/2 2...1/2
CONDENSER FANS
Standard/Low Noise Type Shrouded Axial Type, Vertical Discharge
Fan Speed (rpm) 1140 1140 1140 1140 1140 1140 1140 1140 1140
No. Blades...Dia. (in.) 11...30 11...30 11...30 11...30 11...30 11...30 11...30 11...30 11...30
No. Fans...Total kW 18...28.8 20...32 22...35.2 24...38.4 18...28.8 24...38.4 18...28.8 26...41.6 20...32
Total Airflow (cfm) 205,200 228,000 250,800 273,600 205,200 273,600 205,200 296,400 228,000
High Static Type Propeller Type, Vertical Discharge
Fan Speed (rpm) 1750 1750 1750 1750 1750 1750 1750 1750 1750
No. Blades...Dia. (in.) 12...30 12...30 12...30 12...30 12...30 12...30 12...30 12...30 12...30
No. Fans...Total kW 18...73.8 20...82 22...90.2 24...98.4 18...73.8 24...98.4 18...73.8 26...107 20...82
Total Airflow (cfm)† 176,400 196,000 215,600 235,200 176,400 235,200 176,400 254,800 196,000
CONDENSER COILS 3/8-in. OD Copper Tubes with Aluminum Fins
Fins/in. 17 17 17 17 17 17 17 17 17
No. Rows 4 4 4 4 4 4 4 4 4
Total Face Area (sq ft) 486 594 593 648 476 648 486 702 540
Maximum Working 450 450 450 450 450 450 450 450 450
Pressure (psig)
UNIT SIZE 30GXN,R 418 450 453 475 478 500 503 525 528
OPERATING WEIGHT (lb) HFC-134a
Cu-Al 26,435 25,970 28,228 26,852 30,850 27,734 33,472 27,804 33,502
Cu-Cu 31,040 28,720 39,912 29,927 39,897 31,134 33,502 31,204 39,912
REFRIGERANT CHARGE
Circuits Qty 4 4 4 4 4 4 4 4 4
Module A Ckt A/Ckt B (lb) 410/215 285/215 340/175 339/205 410/205 339/205 410/205 339/215 410/215
Module B Ckt A/Ckt B (lb) 263/178 285/215 340/175 285/215 340/175 339/205 410/205 339/215 410/215
COMPRESSORS Semi-Hermetic, Twin Screw
Quantity 5 6 6 6 6 6 6 6 6
Economized Yes Yes Yes Yes Yes Yes Yes Yes Yes
No. Capacity Steps
Standard 14 16 16 16 16 16 16 16 16
Optional (maximum) 18 20 20 20 20 20 20 20 20
Min. Capacity Step (%)
Standard 8 7.5 7.5 8 8 7.5 7.5 7.5 7.5
Optional 4 5 5 4 4 5 5 5 5
COOLER* Flooded Type Shell and Tube with Enhanced Copper Tubes
Net Fluid Volume (gal) 71.2 86.2 86.2 90.3 90.3 94.4 94.4 94.4 94.4
Max Refrigerant 220 220 220 220 220 220 220 220 220
Pressure (psig)
Max Fluid Side 300 300 300 300 300 300 300 300 300
Pressure (psig)
FLUID CONNECTIONS Victaulic Connections
Inlet and Outlet (in.) 8 8 8 8 8 8 8 8 8
Cooler Interconnecting (in.) 8 8 8 8 8 8 8 8 8
Drain — Qty...Size (in.) 2...1/2 2...1/2 2...1/2 2...1/2 2...1/2 2...1/2 2...1/2 2...1/2 2...1/2
CONDENSER FANS
Standard/Low Noise Type Shrouded Axial Type, Vertical Discharge
Fan Speed (rpm) 1140 1140 1140 1140 1140 1140 1140 1140 1140
No. Blades...Dia. (in.) 11...30 11...30 11...30 11...30 11...30 11...30 11...30 11...30 11...30
No. Fans...Total kW 26...41.6 20...32 28...44.8 22...35.2 30...48 24...38.4 32...51.2 24...38.4 32...51.2
Total Airflow (cfm) 296,400 228,000 319,200 250,800 342,000 273,600 364,800 273,600 364,800
High Static Type Propeller Type, Vertical Discharge
Fan Speed (rpm) 1750 1750 1750 1750 1750 1750 1750 1750 1750
No. Blades...Dia. (in.) 12...30 12...30 12...30 12...30 12...30 12...30 12...30 12...30 12...30
No. Fans...Total kW 26...107 20....82 28...115 22...90.2 30...123 24...98.4 32...131 24...98.4 32...131
Total Airflow (cfm)† 254,800 196,000 274,400 215,600 294,000 235,200 313,600 235,200 313,600
CONDENSER COILS 3/8-in.
OD Copper Tubes with Aluminum Fins
Fins/in. 17 17 17 17 17 17 17 17 17
No. Rows 4 4 4 4 4 4 4 4 4
Total Face Area (sq ft) 702 540 756 593 864 594 864 648 864
Maximum Working 450 450 450 450 450 450 450 450 450
Pressure (psig)
LEGEND *Each cooler is shipped with approximately 5 gallons of propolyene glycol to provide freeze pro-
Ckt — Circuit tection during storage and shipment.
Cu-Al — Standard Coils with Copper Tubes and Aluminum Fins †Based on rated external static pressure of 0.4 in. wg or 0.8 in. wg as appropriate.
Cu-Cu — Optional Coils with Copper Tubes and Copper Fins
6
Physical data — SI
60 Hz UNITS
UNIT SIZE 30GXN,R 080 083 090 093 106 108 114 118 125 128 135 138 150 153 160
OPERATING WEIGHT (kg)
Cu-Al 2863 3133 2872 3266 3408 3475 3413 3923 3426 3930 3499 3987 3984 4393 4115
Cu-Cu 3169 3448 3179 3582 3724 3791 3728 4399 3741 4406 3817 4418 4461 5028 4614
REFRIGERANT TYPE HFC-134a
Refrigerant Charge (kg)
Ckt-A/Ckt-B 48/44 58/56 52/44 61/56 68/56 61/56 73/56 77/68 73/64 86/68 79/79 86/79 71/103 119/81 82/110
COMPRESSORS Semi-Hermetic, Twin Screw
Quantity 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2
Economized No No No No No Yes No Yes Yes Yes Yes Yes Yes Yes Yes
No. Capacity Steps
Standard 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6
Optional (maximum) 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8
Min. Capacity Step (%)
Standard 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20
Optional 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10
COOLER* Flooded Type Shell and Tube with Enhanced Copper Tubes
Net Fluid Volume (L) 72 72 72 72 86 86 86 79 126 91 126 91 91 91 108
Maximum Refrigerant 1517 1517 1517 1517 1517 1517 1517 1517 1517 1517 1517 1517 1517 1517 1517
Pressure (kPa)
Maximum Fluid Side 2069 2069 2069 2069 2069 2069 2069 2069 2069 2069 2069 2069 2069 2069 2069
Pressure (kPa)
FLUID CONNECTIONS (in.) Victaulic Connections
Inlet and Outlet 4 4 4 4 5 5 5 4 5 4 5 4 4 4 5
Drain (NPT) 1/ 1/ 1/ 1/ 1/ 1/ 1/ 1/ 1/ 1/ 1/ 1/ 1/ 1/ 1/
2 2 2 2 2 2 2 2 2 2 2 2 2 2 2
CONDENSER FANS
Standard/Low Noise Type Shrouded Axial Type, Vertical Discharge
Fan Speed (r/s) 19.0 19.0 19.0 19.0 19.0 19.0 19.0 19.0 19.0 19.0 19.0 19.0 19.0 19.0 19.0
No. Blades...Dia. (mm) 11...762 11...762 11...762 11...762 11...762 11...762 11...762 11...762 11...762 11...762 11...762 11...762 11...762 11...762 11...762
No. Fans...Total kW 4...6.4 6...9.6 4...6.4 6...9.6 6...9.6 6...9.6 6...9.6 8...12.8 6...9.6 8...12.8 6...9.6 8...12.8 8...12.8 10...16 8...12.8
Total Airflow (L/s) 21 521 32 281 21 521 32 281 32 281 32 281 32 281 43 042 32 281 43 042 32 281 43 042 43 042 53 802 43 042
High Static Type Propeller Type, Vertical Discharge
Fan Speed (r/s) 29.2 29.2 29.2 29.2 29.2 29.2 29.2 29.2 29.2 29.2 29.2 29.2 29.2 29.2 29.2
No. Blades...Dia. (mm) 12...762 12...762 12...762 12...762 12...762 12...762 12...762 12...762 12...762 12...762 12...762 12...762 12...762 12...762 12...762
No. Fans...Total kW 4...16.4 6...24.6 4...16.4 6...24.6 6...24.6 6...24.6 6...24.6 8...32.8 6...24.6 8...32.8 6...24.6 8...32.8 8...32.8 10...41 8...32.8
Total Airflow (L/s)† 18 500 27 751 18 500 27 751 27 751 27 751 27 751 37 001 27 751 37 001 27 751 37 001 37 001 46 251 37 001
CONDENSER COILS 9.53-mm. OD Copper Tubes with Aluminum Fins
Fins/m 669 669 669 669 669 669 669 669 669 669 669 669 669 669 669
No. Rows 3 3 3 4 4 4 4 4 3 4 4 4 4 4 4
Total Face Area (sq m) 12.6 15.1 12.6 15.1 15.1 15.1 15.1 20.1 15.1 20.1 15.1 20.1 20.1 25.1 20.1
Maximum Working 3103 3103 3103 3103 3103 3103 3103 3103 3103 3103 3103 3103 3103 3103 3103
Pressure (kPa)
UNIT SIZE 30GXN,R 163 174 178 204 208 225 228 249 253 264 268 281 301 325 350
OPERATING WEIGHT (kg)
Cu-Al 4663 4406 4669 5782 6395 5890 6402 6290 7591 6306 7598 8490 8499 8517 8540
Cu-Cu 5419 5041 5426 6417 9045 6514 9052 7061 9045 7077 9052 9944 9953 9971 9994
REFRIGERANT TYPE HFC-134a
Refrigerant Charge (kg)
Ckt-A/Ckt-B 119/100 119/94 119/119 122/93 150/79 129/98 154/79 154/93 186/93 154/88 186/98 175/175 181/181 188/188 195/195
COMPRESSORS Semi-Hermetic, Twin Screw
Quantity 2 2 2 3 3 3 3 3 3 3 3 4 4 4 4
Economized Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes
No. Capacity Steps
Standard 6 6 6 8 8 8 8 8 8 8 8 10 10 10 10
Optional (maximum) 8 8 8 10 10 10 10 10 10 10 10 12 12 12 12
Min. Capacity Step (%)
Standard 20 20 20 15 15 15 15 15 15 15 15 10 10 10 10
Optional 10 10 10 10 10 10 10 10 10 10 10 5 5 5 5
COOLER* Flooded Type Shell and Tube with Enhanced Copper Tubes
Net Fluid Volume (L) 108 108 108 146 146 163 163 179 179 179 179 212 212 212 212
Maximum Refrigerant 1517 1517 1517 1517 1517 1517 1517 1517 1517 1517 1517 1517 1517 1517 1517
Pressure (kPa)
Maximum Fluid Side 2069 2069 2069 2069 2069 2069 2069 2069 2069 2069 2069 2069 2069 2069 2069
Pressure (kPa)
FLUID CONNECTIONS (in.) Victaulic Connections
Inlet and Outlet 5 5 5 6 6 6 6 6 6 6 6 8 8 8 8
Drain (NPT) 1/ 1/ 1/2 1/2 1/ 1/2 1 /2 1 /2 1/ 1/2 1/2 1/ 1 /2 1 /2 1/2
2 2 2 2 2
CONDENSER FANS
Standard/Low Noise Type Shrouded Axial Type, Vertical Discharge
Fan Speed (r/s) 19.0 19.0 19.0 19.0 19.0 19.0 19.0 19.0 19.0 19.0 19.0 19.0 19.0 19.0 19.0
No. Blades...Dia. (mm) 11...762 11...762 11...762 11...762 11...762 11...762 11...762 11...762 11...762 11...762 11...762 11...762 11...762 11...762 11...762
No. Fans...Total kW 12...19.2 10...16 12...19.2 10...16 14...22.4 10...16 14...22.4 12...19.2 16...25.6 12...19.2 16...25.6 16...25.6 16...25.6 16...25.6 16...25.6
Total Airflow (L/s) 64 563 53 802 64 563 53 802 75 323 53 802 75 323 64 563 86 084 64 563 86 084 86 084 86 084 86 084 86 084
High Static Type Propeller Type, Vertical Discharge
Fan Speed (r/s) 29.2 29.2 29.2 29.2 29.2 29.2 29.2 29.2 29.2 29.2 29.2 29.2 29.2 29.2 29.2
No. Blades...Dia. (mm) 12...762 12...762 12...762 12...762 12...762 12...762 12...762 12...762 12...762 12...762 12...762 12...762 12...762 12...762 12...762
No. Fans...Total kW 12...49.2 10...41 12...49.2 10...41 14...57.4 10...41 14...57.4 12...49.2 16...65.6 12...49.2 16...65.6 16...65.6 16...65.6 16...65.6 16.65.6
Total Airflow (L/s)† 55 501 46 251 55 501 46 251 64 752 46 251 64 752 55 501 74 002 55 501 74 002 74 002 74 002 74 002 74 002
CONDENSER COILS 9.53-mm. OD Copper Tubes with Aluminum Fins
Fins/m 669 669 669 669 669 669 669 669 669 669 669 669 669 669 669
No. Rows 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4
Total Face Area (sq m) 30.1 25.1 30.1 25.1 35.1 25.1 35.1 30.1 40.1 30.1 40.1 40.1 40.1 40.1 40.1
Maximum Working 3103 3103 3103 3103 3103 3103 3103 3103 3103 3103 3103 3103 3103 3103 3103
Pressure (kPa)
LEGEND *Each cooler is shipped with approximately 18.9 liters of propolyene glycol to provide freeze
protection during storage and shipment.
Ckt — Circuit †Based on rated external static pressure of 100 Pa or 200 Pa as appropriate.
Cu-Al — Standard Coils with Copper Tubes and Aluminum Fins
Cu-Cu — Optional Coils with Copper Tubes and Copper Fins
7
Physical data — SI (cont)
60 Hz DUPLEX UNITS
UNIT SIZE 30GXN,R 283 303 328 353 370 373 390 393 415
OPERATING WEIGHT (kg) HFC-134a
Cu-Al 8379 8649 9 062 9 339 9 874 11 578 9 805 11 984 10 421
Cu-Cu 9445 9837 10 454 10 852 10 974 13 463 10 894 14 073 11 691
REFRIGERANT CHARGE
Circuits Qty 4 4 4 4 4 4 4 4 4
Module A Ckt A/Ckt B (kg) 119/81 119/100 119/119 119/119 129/84 186/93 154/98 186/93 154/98
Module B Ckt A/Ckt B (kg) 86/79 86/79 119/81 119/119 71/103 86/79 79/79 119/81 82/110
COMPRESSORS Semi-Hermetic, Twin Screw
Quantity 4 4 4 4 5 5 5 5 5
Economized Yes Yes Yes Yes Yes Yes Yes Yes Yes
No. Capacity Steps
Standard 12 12 12 12 14 14 14 14 14
Optional (maximum) 16 16 16 16 18 18 18 18 18
Min. Capacity Step (%)
Standard 10 10 10 10 8 8 7 8 8
Optional 5 5 5 5 4 4 3.5 4 4
COOLER* Flooded Type Shell and Tube with Enhanced Copper Tubes
Net Fluid Volume (L) 182 199 199 216 254.0 270 305.1 270 286.6
Max Refrigerant 1517 1517 1517 1517 1517 1517 1517 1517 1517
Pressure (kPa)
Max Fluid Side 2069 2069 2069 2069 2069 2069 2069 2069 2069
Pressure (kPa)
FLUID CONNECTIONS Victaulic Connections
Inlet and Outlet (in.) 8 8 8 8 8 8 8 8 8
Cooler Interconnecting (in.) 8 8 8 8 8 8 8 8 8
Drain — Qty...Size (in.) 2...1/2 2...1/2 2...1/2 2...1/2 2...1/2 2...1/2 2...1/2 2...1/2 2...1/2
CONDENSER FANS
Standard/Low Noise Type Shrouded Axial Type, Vertical Discharge
Fan Speed (r/s) 19.0 19.0 19.0 19.0 29.2 19.0 29.2 19.0 29.2
No. Blades...Dia. (mm) 11...762 11...762 11...762 11...762 11...762 11...762 11...762 11...762 11...762
No. Fans...Total kW 18...28.8 20...32 22...35.2 24...38.4 18...28.8 24...38.4 18...28.8 26...41.6 20...32
Total Airflow (L/s) 96 844 107 605 118 365 129 126 96 845 129 126 96 845 139 886 107 605
High Static Type Propeller Type, Vertical Discharge
Fan Speed (r/s) 29.2 29.2 29.2 29.2 19 29.2 19 29.2 19
No. Blades...Dia. (mm) 12...762 12...762 12...762 12...762 12...762 12...762 12...762 12...762 12...762
No. Fans...Total kW 18...73.8 20...82 22...90.2 24...98.4 18...73.8 24...98.4 18...73.8 26...107 20...82
Total Airflow (L/s)† 83 252 92 502 101 752 111 003 83 252 111 003 83 252 120 253 92 503
CONDENSER COILS 3/ -in. OD Copper Tubes with Aluminum Fins
8
Fins/m 669 669 669 669 669 669 669 669 669
No. Rows 4 4 4 4 4 4 4 4 4
Total Face Area (sq m) 48.2 50.2 55.2 60.2 45.2 60.2 45.2 65.2 50.2
Maximum Working 3103 3103 3103 3103 3103 3103 3103 3103 3103
Pressure (kPa)
UNIT SIZE 30GXN,R 418 450 453 475 478 500 503 525 528
OPERATING WEIGHT (kg) HFC-134a
Cu-Al 11 991 11 780 12 804 12 180 13 994 12 580 15 183 12 612 15 197
Cu-Cu 14 080 13 027 18 104 13 575 18 097 14 122 15 197 14 154 18 104
REFRIGERANT CHARGE
Circuits Qty 4 4 4 4 4 4 4 4 4
Module A Ckt A/Ckt B (kg) 186/98 129/98 154/79 154/93 186/93 154/93 186/93 154/98 186/98
Module B Ckt A/Ckt B (kg) 119/81 129/98 154/79 129/98 154/79 154/93 186/93 154/98 186/98
COMPRESSORS Semi-Hermetic, Twin Screw
Quantity 5 6 6 6 6 6 6 6 6
Economized Yes Yes Yes Yes Yes Yes Yes Yes Yes
No. Capacity Steps
Standard 14 16 16 16 16 16 16 16 16
Optional (maximum) 18 20 20 20 20 20 20 20 20
Min. Capacity Step (%)
Standard 8 7.5 7.5 8 8 7.5 7.5 7.5 7.5
Optional 4 5 5 4 4 5 5 5 5
COOLER* Flooded Type Shell and Tube with Enhanced Copper Tubes
Net Fluid Volume (L) 270 326.3 326 342 342 357 357 357 357
Max Refrigerant 1517 1517 1517 1517 1517 1517 1517 1517 1517
Pressure (kPa)
Max Fluid Side 2069 2069 2069 2069 2069 2069 2069 2069 2069
Pressure (kPa)
FLUID CONNECTIONS Victaulic Connections
Inlet and Outlet (in.) 8 8 8 8 8 8 8 8 8
Cooler Interconnecting (in.) 8 8 8 8 8 8 8 8 8
Drain — Qty...Size (in.) 2...1/2 2...1/2 2...1/2 2...1/2 2...1/2 2...1/2 2...1/2 2...1/2 2...1/2
CONDENSER FANS
Standard/Low Noise Type Shrouded Axial Type, Vertical Discharge
Fan Speed (r/s) 19.0 29.2 19.0 19.0 19.0 19.0 19.0 19.0 19.0
No. Blades...Dia. (mm) 11...762 11...762 11...762 11...762 11...762 11...762 11...762 11...762 11...762
No. Fans...Total kW 26...41.6 20...32 28...44.8 22...35.2 30...48 24...38.4 32...51.2 24...38.4 32...51.2
Total Airflow (L/s) 139 886 107 605 150 646 118 365 161 407 129 126 172 167 129 126 172 167
High Static Type Propeller Type, Vertical Discharge
Fan Speed (r/s) 29.2 19 29.2 29.2 29.2 29.2 29.2 29.2 29.2
No. Blades...Dia. (mm) 12...762 12...762 12...762 12...762 12...762 12...762 12...762 12...762 12...762
No. Fans...Total kW 26...107 20....82 28...115 22...90.2 30...123 24...98.4 32...131 24...98.4 32...131
Total Airflow (L/s)† 120 253 92 503 129 503 101 752 138 753 111 003 148 004 111 003 148 004
CONDENSER COILS 3/ -in. OD Copper Tubes with Aluminum Fins
8
Fins/m 669 669 669 669 669 669 669 669 669
No. Rows 4 4 4 4 4 4 4 4 4
Total Face Area (sq m) 65.2 50.2 70.2 55.2 75.2 60.2 80.3 60.2 80.3
Maximum Working 3103 3103 3103 3103 3103 3103 3103 3103 3103
Pressure (kPa)
LEGEND *Each cooler is shipped with approximately 18.9 liters of propolyene glycol to provide freeze
protection during storage and shipment.
Ckt — Circuit †Based on rated external static pressure of 100 Pa or 200 Pa as appropriate.
Cu-Al — Standard Coils with Copper Tubes and Aluminum Fins
Cu-Cu — Optional Coils with Copper Tubes and Copper Fins
8
Options and accessories
ITEM FACTORY-INSTALLED OPTION FIELD-INSTALLED ACCESSORY
Trim Kit X
Wye-Delta Start* X
Copper-Fin Condenser Coil X
Enviro-Shield™ System Condenser Coil Coatings X
Alternate Cooler Heads (plus 1 pass, minus 1 pass) X
Suction Isolation Valves X
Medium Temperature Brine X
Non-Fused Disconnect X
High-Static/High Ambient Condenser Fans X
Low-Ambient Control X X
Low-Ambient Protection † X
Control Power Transformer X X
Minimum Load Control X X
Security Guards X X
Control Display Access Door X
Cooler Head Insulation X
Remote Enhanced Display X
Chillervisor System Manager III Multi-Unit Control X
125 F (51.7 C) Electric Service Relay X
115 F (46.1 C) Electric Service Relay X
Sound Reduction Enclosure/Hail Guards/Wind Baffles X
Vibration Isolation X
GFI Convenience Outlet X X
Energy Management Module X X
Remote Service Port X X
*Standard on 208/230 and 230 v units.
†Standard on all units except 380 v, 60 Hz
Factory-installed options Alternate cooler heads (plus one pass, minus one
115 F (46.1 C) electric service rating — Lower electric pass) — This option changes the standard cooler head to
service temperature ratings reduce the units rated Minimum a Plus-One-Pass (for use with low temperature brines), or a
Current Amps (MCA) and Maximum Overcurrent Protection Minus-One-Pass (reduced pressure drop for series flow
(MOCP) for moderate ambient temperature applications applications). Consult the Carrier 30GXN,R electronic cat-
(sizes 080 to 125 and all high-efficiency models). alog for performance data.
125 F (51.7 C) electric service rating — Higher elec- Suction isolation valves — Standard refrigerant dis-
tric service temperature ratings allows maximum ambient charge isolation and liquid valves enable service personnel
temperature operation (460 and 575 v only). to store the refrigerant charge in the cooler or condenser
during servicing. This factory-installed option allows for
Remote service port — Provides secondary connection further isolation of the compressor from the cooler vessel.
port for Navigator display. Port is conveniently located out-
side of the control box for easy access to information dur- Medium temperature brine — This option permits sup-
ing operation and maintenance routines. ply liquid temperatures to be set below 40 F (4.4 C).
Refrigeration circuit components, such as the expansion
Low ambient protection to 0° F (–17.7 C) — Factory-
device, are modified at the factory to adjust for lower refrig-
installed cooler head heaters and liquid line solenoid valves
erant flow rates.
combined with a pump down cycle provide cooler ambient
protection to 0° F (–17.7 C). Standard on all units except Low-ambient Motormaster® control — This factory-
380 v, 60 Hz. installed option permits operation of the 30GXN,R units
down to –20 F (–29 C) outdoor ambient temperature. The
Energy Management Module — This module provides control is also available as a field-installed accessory. Also
energy management capabilities to minimize chiller energy
requires field-installed wind baffles.
consumption. Several features are provided with this mod-
ule including leaving fluid temperature reset, cooling set Non-fused disconnect — This option provides non-
point reset or demand limit control from a 4 to 20 mA sig- fused disconnect capability for main unit power located at
nal, 2-point demand limit control (from 0 to 100%) acti- the unit.
vated by a remote contact closure, and discrete input for Control power transformer (460 v only) — The trans-
“Ice Done” indication for ice storage system interface. former is sized to supply the needs of the control circuit,
Wye-delta start — Reduced inrush current start is avail- sourcing power from the main unit power connection. The
able as a factory-installed option. It is standard on 208/ transformer is also available as a field-installed accessory.
230 and 230 v units. High-static condenser fans — The high-static fans
Condenser coil options — Several options are available allow the 30GXN,R unit to be used in applications with an
to match coil construction to the site conditions for the best external static pressure of up to 0.8 in. wg (200 Pa) at
durability. Consult your Carrier representative for further nominal condenser airflow. Two options are available:
information. 0.4 in. wg (100 Pa) or 0.8 in. wg (200 Pa).
GFI Convenience outlet — The factory-installed conve- Security guards — This option covers the condenser
nience outlet includes 15-amp GFI (Ground Fault coils, cooler, and compressor areas to protect the area
Interrupter) receptacle with independent fuse protection. from intrusion.
Convenience outlet is 115-v female receptacle.
9
Options and accessories (cont)
CONDENSER COIL CORROSION PROTECTION OPTIONS
ENVIRONMENT
ENVIRO-SHIELD™
OPTION* Mild Moderate Severe Combined
Standard Industrial
Coastal Coastal Coastal Industrial/Coastal
AL Fins (Standard Coils) X
CU Fins X
AL Fins, E-coat X X
CU Fins, E-coat X
AL Fins, Precoated X
LEGEND
AL — Aluminum
CU — Copper
*See page 68 for further description, also see “Environmental Corrosion Protection” for more information (Publications 810-217 and 811-019).
Minimum load control — This option allows additional 30GXN,R chiller program for sound power data and dBA
capacity reduction for unit operation below the minimum reduction.
step of unloading (below 10% of the unit capacity). Low ambient Motormaster® head pressure control
Minimum load control is also available as a field-installed — Permits starting and operating down to –20 F (–29 C)
accessory. outside ambient temperature. Requires field-installed wind
Field-installed accessories baffles.
Control power transformer — The transformer is sized Energy Management Module — This module provides
to supply the needs of the control circuit, sourcing power energy management capabilities to minimize chiller energy
from the main unit power connection. The transformer is consumption. Several features are provided with this mod-
also available as a factory-installed option (460-v and ule including leaving fluid temperature reset, cooling set
575-v only). point reset or demand limit control from a 4 to 20 mA sig-
nal; 2-point demand limit control (from 0 to 100%) acti-
Security guards — This accessory covers the condenser
vated by a remote contact closure; and discrete input for
coils, cooler, and compressor areas to protect the unit from
“Ice Done” indication for ice storage system interface.
intrusion.
Vibration isolation — The field-installed 1/4-in. neo-
Minimum load control — This option allows additional
prene isolator pads (24-in. x 3-in.) reduce vibration trans-
capacity reduction for unit operation below the minimum
mission from the compressor through the floor and into
step of unloading (down to 10% of the minimum unit the conditioned space.
capacity). Minimum load control is also available as a
factory-installed option. Cooler head insulation — This accessory is designed
with flexible, 3/4-in. (19 mm) PVC foam (closed-cell) to
Control display access door — This option provides insulate the cooler heads and economizer vessel to mini-
easy access to the unit control module through a
mize heat loss and head sweating.
see-through door without having to open or remove the
control box panels. Remote service port — Provides secondary connection
port for Navigator display. Port is conveniently located
Remote enhanced display — This accessory kit con-
outside of the control box for easy access to information
tains a remotely mounted 40-character per line, 16-line
during operation and maintenance routines.
display panel for unit diagnostics.
GFI convenience outlet — The field-installed conve-
Chillervisor System Manager III multi-unit control
nience outlet includes 15-amp GFI (Ground Fault Inter-
— This accessory allows sequencing of between 2 and 8
rupter) receptacle with independent fuse protection.
chillers in parallel or 2 chillers in series. Pump control is Convenience outlet is 115-v female receptacle.
also provided.
Trim kit accessory — The trim kit accessory is available
Sound reduction enclosures/hail guards/wind baf-
for field installation between 2 unit modules. The kit con-
fles — This kit contains a sound enclosure that covers the tains sheet metal base rail pieces and all required mounting
entire unit to reduce sound levels. Coil protection and wind
hardware. The kit also allows for interconnecting piping
baffles are also provided. See Carrier electronic catalog
support.
10
TYPICAL ACCESSORY SOUND REDUCTION/HAIL GUARD/
WIND BAFFLE HOODS
11
12
30GXN,R080, 090
Dimensions
30GXN,R083, 093, 106, 108, 114, 125, 135*
13
14
30GXN,R118, 128, 138, 150, 160*
Dimensions (cont)
15
16
30GXN,R163, 178*
Dimensions (cont)
17
18
30GXN,R208, 228*
Dimensions (cont)
19
20
30GXN,R253, 268*
Dimensions (cont)
21
22
30GXN,R283
NOTES:
1. Unit must have clearances for airflow as follows:
Top — Do not restrict in any way.
Ends — (1524 mm) 5 ft from solid surface.
Sides — (1829 mm) 6 ft from solid surface.
2. Unit with sound hoods requires clearances for airflow as follows:
Top — Do not restrict in any way.
Ends — (1524 mm) 5 ft to outside edge of hoods.
Sides — (1829 mm) 6 ft to outside edge of hoods.
3. Refer to drawings 30GX505245 & 5246 for information not
included in this drawing.
Dimensions (cont)
30GXN,R303
NOTES:
1. Unit must have clearances for airflow as follows:
Top — Do not restrict in any way.
Ends — (1524 mm) 5 ft from solid surface.
Sides — (1829 mm) 6 ft from solid surface.
2. Unit with sound hoods requires clearances for airflow as follows:
Top — Do not restrict in any way.
Ends — (1524 mm) 5 ft to outside edge of hoods.
Sides — (1829 mm) 6 ft to outside edge of hoods.
3. Refer to drawings 30GX505245 & 5247 for information not
included in this drawing.
23
24
30GXN,R328
NOTES:
1. Unit must have clearances for airflow as follows:
Top — Do not restrict in any way.
Ends — (1524 mm) 5 ft from solid surface.
Sides — (1829 mm) 6 ft from solid surface.
2. Unit with sound hoods requires clearances for air-
flow as follows:
Top — Do not restrict in any way.
Ends — (1524 mm) 5 ft to outside edge of hoods.
Sides — (1829 mm) 6 ft to outside edge of hoods.
3. Refer to drawings 30GX505246 & 5247 for infor-
mation not included in this drawing.
Dimensions (cont)
30GXN,R353
NOTES:
1. Unit must have clearances for airflow as follows:
Top — Do not restrict in any way.
Ends — (1524 mm) 5 ft from solid surface.
Sides — (1829 mm) 6 ft from solid surface.
2. Unit with sound hoods requires clearances for airflow as follows:
Top — Do not restrict in any way.
Ends — (1524 mm) 5 ft to outside edge of hoods.
Sides — (1829 mm) 6 ft to outside edge of hoods.
3. Refer to drawing 30GX505247 for information not included in this
drawing.
25
Dimensions (cont)
30GXN,R370
26
30GXN,R373
27
Dimensions (cont)
30GXN,R390
28
30GXN,R393,418
29
Dimensions (cont)
30GXN,R415
30
30GXN,R450
31
Dimensions (cont)
30GXN,R453
32
30GXN,R475
33
Dimensions (cont)
30GXN,R478
34
30GXN,R500,525
35
Dimensions (cont)
30GXN,R503,528
36
Dimensions — mounting weights
99 in.
6 in. (2515)
(152)
A B
CONTROL
BOX 30GXN,R 080,090 85 1/8 in.
END (2162)
D C
WEIGHT DISTRIBUTION, ALUMINUM-FIN UNITS — lb (kg) WEIGHT DISTRIBUTION, COPPER-FIN UNITS — lb (kg)
A B
CONTROL
30GXN,R 083, 093-114, 125, 135, 85 1/8 in.
BOX 390B (2162)
END
D C
WEIGHT DISTRIBUTION, ALUMINUM-FIN UNITS — lb (kg) WEIGHT DISTRIBUTION, COPPER-FIN UNITS — lb (kg)
NOTES:
1. Install a 12-in. x 4-in. (305-mm x 102-mm) mounting pad (minimum) at mounting hole location. Do not point load base rail.
2. Dimensions in ( ) are in millimeters.
3. •Indicates mounting hole location on side base rail.
37
Dimensions — mounting weights (cont)
153 3/16 in.
(3891)
106 in.
6 in. (2692)
(152)
A B C
F E D
WEIGHT DISTRIBUTION, ALUMINUM-FIN UNITS — lb (kg) WEIGHT DISTRIBUTION, COPPER-FIN UNITS — lb (kg)
NOTES:
1. Install a 24-in. x 4-in. (610-mm x 102-mm) mounting pad (minimum) at mounting hole location. Do not point load base rail.
2. Dimensions in ( ) are in millimeters.
3. •
Indicates mounting hole location on side base rail.
22 3/4 in. A B C D
(578)
CONTROL
BOX 30GXN,R 153, 174, 283A, 328B, 85 1/8 in.
END 393B, 418B (2162)
H G F E
231 in.
(5867)
WEIGHT DISTRIBUTION, ALUMINUM-FIN UNITS — lb (kg) WEIGHT DISTRIBUTION, COPPER-FIN UNITS — lb (kg)
NOTES:
1. Install a 24-in. x 4-in. (610-mm x 102-mm) mounting pad (minimum) at mounting hole location. Do not point load base rail.
2. Dimensions in ( ) are in millimeters.
3. •
Indicates mounting hole location on side base rail.
38
244 1/16 in.
(6199)
169 3/4 in.
(4312)
97 1/16 in.
(2466)
22 3/4 in.
(578) A B C D
CONTROL
BOX 30GXN, R 163, 178, 85 1/8 in.
END 303A, 328A, 353A/B (2162)
H G F E
WEIGHT DISTRIBUTION, ALUMINUM-FIN UNITS — lb (kg) WEIGHT DISTRIBUTION, COPPER-FIN UNITS — lb (kg)
NOTES:
1. Install a 24-in. x 4-in. (610-mm x 102-mm) mounting pad (minimum) at mounting hole location. Do not point load base rail.
2. Dimensions in ( ) are in millimeters.
3. • Indicates mounting hole location on side base rail.
39
Dimensions — mounting weights (cont)
208 1/16 in.
(5285)
173 11/16 in.
(4412)
107 1/2 in.
(2731)
58 1/2 in.
22 3/4 in. (1486)
(578)
A B C D E
CONTROL
BOX 30GXN,R 204, 225, 85 1/8 in.
END 370A, 450A/B, 475B (2162)
J I H G F
231 in.
(5867)
NOTES:
1. Install a 24-in. x 4-in. (610-mm x 102-mm) mounting pad (minimum) at mounting hole location. Do not point load base rail.
2. Dimensions in ( ) are in millimeters.
3. • Indicates mounting hole location on side base rail.
40
280 1/16 in.
(7114)
229 7/8 in.
(5839)
166 11/16 in.
(4233)
130 3/16 in.
(3307)
73 1/16 in.
(1856)
22 3/4 in.
(578)
A B C D E F
L K J I H G
NOTES:
1. Install a 24-in. x 4-in. (610-mm x 102-mm) mounting pad (minimum) at mounting hole location. Do not point load base rail.
2. Dimensions in ( ) are in millimeters.
3. • Indicates mounting hole location on side base rail.
41
Dimensions — mounting weights (cont)
219 11/16 in.
(5580)
169 3/4 in.
(4312)
97 1/16 in.
(2465)
47 11/16 in.
22 3/4 in. (1211)
(578)
A B C D E
J I H G F
NOTES:
1. Install a 24-in. x 4-in. (610-mm x 102-mm) mounting pad (minimum) at mounting hole location. Do not point load base rail.
2. Dimensions in ( ) are in millimeters.
3. • Indicates mounting hole location on side base rail.
42
316 1/8 in. (8030)
22 11/16 in.
(525)
A B C D E F G
CONTROL BOX END
N M L K J I H
NOTES:
1. Install a 24-in. x 4-in. (610-mm x 102-mm) mounting pad (minimum) at mounting hole location. Do not point load base rail.
2. Dimensions in ( ) are in millimeters.
3. • Indicates mounting hole location on side base rail.
43
Selection procedure (with example)
Carrier’s electronic catalog chiller selection program pro- NOTE: For other than 10° F temperature rise, data
vides quick, easy selection of Carrier chillers. The program corrections must be made using the chiller program
considers specific temperature, fluid, and flow require- in the electronic catalog. On some units, a change
ments and other factors, such as fouling and altitude cor- of controls is also necessary.
rection. To select a 30GXN,R chiller, use the electronic II From Cooling Capacities table on page 46
catalog or follow one of the procedures below. and pressure drop curves on page 52, deter-
ENGLISH (60 Hz) mine operating data for selected unit.
I Determine 30GXN,R unit size and operating Unit . . . . . . . . . . . . . . . . . . . . . . . . . 30GXN114
conditions required to meet given capacity at Capacity. . . . . . . . . . . . . . . . . . . . . . . . .106 tons
given conditions. Power Input . . . . . . . . . . . . . . . . . . . . .131.0 kW
Given: Cooler Water Flow . . . . . . . . . . . . . . . 254.2 gpm
Cooler Pressure Drop . . . . . . . . . .13.8 ft of water
Capacity. . . . . . . . . . . . . . . . . . . . . . . . 105 Tons
Leaving Chilled Water Temp (LCWT) . . . . . . .44 F
Cooler Water Temp Rise . . . . . . . . . . . . . . . 10° F
Condenser Entering Air Temp . . . . . . . . . . . .95 F
Fouling Factor (Cooler) . . . . . . . . . . . . . .0.00010
44
ARI* capacity ratings
ARI STANDARD RATINGS — 60 Hz
STANDARD EFFICIENCY
COOLER WATER
UNIT CAPACITY COMPRESSOR FAN POWER COOLER FLOW
PRESSURE DROP EER COP
30GXN,R POWER INPUT (kW) (kW)
Tons kW GPM L/s ft water kPa
080 75.9 267 85.9 6.4 182.1 11.5 10.1 30.2 9.86 2.89
090 83.0 292 97.8 6.4 199.3 12.6 11.9 35.6 9.56 2.80
106 97.5 343 108.2 10.5 234.0 14.8 11.9 35.6 9.86 2.89
114 106.0 373 120.5 10.5 254.5 13.8 13.8 41.2 9.72 2.85
125 116.0 408 136.1 9.6 278.5 17.6 11.9 35.6 9.56 2.80
135 127.0 447 147.5 10.5 304.7 14.0 14.0 41.8 9.65 2.83
150 139.8 492 160.2 12.8 335.6 21.2 13.4 40.1 9.70 2.84
160 151.5 533 177.4 12.8 363.6 22.9 11.3 33.8 9.56 2.80
174 166.8 587 190.7 16.0 400.3 25.3 13.4 40.1 9.68 2.84
204 191.9 675 223.8 17.0 460.5 29.0 13.5 40.4 9.56 2.80
225 208.9 735 245.2 17.0 501.3 31.6 12.5 37.4 9.56 2.80
249 233.9 823 272.5 21.0 561.2 35.4 12.6 37.7 9.56 2.80
264 245.0 862 286.6 21.0 588.1 37.1 13.8 41.2 9.56 2.80
281 267.1 940 300.4 24.0 641.0 40.4 10.3 30.8 9.88 2.89
301 286.7 1009 329.9 24.0 688.2 43.4 11.6 34.7 9.72 2.85
325 308.7 1087 363.5 24.0 740.9 46.7 13.3 39.8 9.56 2.80
350 333.5 1174 408.6 24.0 800.4 50.5 15.3 45.7 9.25 2.71
370 357.1 1257 409.8 29.8 858.4 54.1 14.3 42.7 9.75 2.86
390 378.7 1333 437.6 31.5 909.0 57.3 9.2 27.5 9.69 2.84
415 405.8 1428 468.5 33.8 974.8 61.5 14.4 43.0 9.69 2.84
450 429.4 1511 496.0 34.0 1030.8 65.0 13.4 40.1 9.72 2.85
475 454.3 1599 526.4 35.2 1090.0 68.8 13.7 40.9 9.71 2.85
500 479.1 1686 554.3 38.4 1150.0 72.5 13.9 41.5 9.70 2.84
525 502.7 1770 582.7 38.4 1206.6 76.1 15.2 45.4 9.71 2.85
HIGH EFFICIENCY
COOLER WATER
UNIT CAPACITY COMPRESSOR FAN POWER COOLER FLOW
PRESSURE DROP EER COP
30GXN,R POWER INPUT (kW) (kW)
Tons kW GPM L/s ft water kPa
083 77.1 271 79.3 9.6 185.0 11.7 10.4 31.1 10.41 3.05
093 85.2 300 89.0 9.6 204.5 12.9 12.5 37.4 10.37 3.04
108 98.0 345 104.8 9.6 235.2 14.8 12.0 35.9 10.28 3.01
118 106.2 374 109.6 12.8 254.9 16.1 10.4 31.1 10.41 3.05
128 116.1 409 122.5 12.8 278.7 17.6 9.6 28.7 10.30 3.02
138 127.5 449 137.3 12.8 306.0 19.3 11.4 34.1 10.19 2.99
153 141.0 496 148.8 16.0 338.5 21.4 13.6 40.7 10.27 3.01
163 153.1 539 159.9 19.2 367.3 23.2 11.5 34.4 10.25 3.00
178 168.5 593 179.1 19.2 404.5 25.5 11.1 33.2 10.20 2.99
208 200.1 704 207.9 22.4 480.3 30.3 14.6 43.6 10.43 3.06
228 210.1 740 222.9 22.4 504.3 31.8 12.6 37.7 10.28 3.01
253 240.4 846 257.2 25.6 577.1 36.4 13.3 39.7 10.20 2.99
268 252.5 888 277.3 25.6 605.9 38.2 14.5 43.3 10.00 2.93
283 274.7 967 288.6 28.8 659.0 41.6 13.5 40.4 10.39 3.04
303 287.4 1012 300.1 32.0 690.0 43.5 13.2 39.5 10.39 3.05
328 316.8 1115 331.7 35.2 760.4 48.0 14.3 42.7 10.36 3.04
353 345.6 1217 362.5 38.4 830.1 52.4 15.9 47.5 10.34 3.03
373 375.7 1321 398.1 38.4 901.6 56.9 18.2 54.4 10.33 3.03
393 384.8 1354 404.9 41.6 923.9 58.3 15.5 46.3 10.34 3.03
418 401.3 1411 430.5 41.6 964.1 60.8 16.7 49.9 10.20 2.99
453 429.4 1511 450.2 44.8 1030.8 65.0 13.4 40.1 10.41 3.05
473 460.6 1620 484.6 48.0 1105.2 69.7 14.1 42.0 10.38 3.04
503 491.7 1729 519.4 51.2 1180.4 74.5 14.6 43.5 10.34 3.03
528 516.5 1817 560.1 51.2 1240.9 78.3 16.0 47.6 10.14 2.97
LEGEND Condenser Conditions:
Entering Air Temperature: 95 F (35 C)
COP — Coefficient of Performance (Capacity [kW] ÷ Input Power [kW]) 3. All data in this table is rated in accordance with ARI Standard 550/590 as
EER — Energy Efficiency Ratio (Capacity [Btuh] ÷ Input Power [W]) represented in the Packaged Chiller Selection Program (E-Cat) version 2.6.
*Air Conditioning and Refrigeration Institute (U.S.A.).
Certified in accordance with the ARI Water-
NOTES: Chiller Packages using the Vapor Compression
1. Rated in accordance with ARI Standard 550/590-98 at standard rating Cycle Certification Program, which is based on
conditions. ARI Standard 550/590.
2. Standard rating conditions are as follows:
Cooler Conditions:
Leaving water temperature: 44 F (6.7 C)
Entering water temperature: 54 F (12.2 C)
Fouling Factor:
0.00010 hr x sq ft °F/Btu (0.000018 m2 x °C/W) 60 Hz Only
45
Performance data
COOLING CAPACITIES — 60 Hz, ENGLISH
STANDARD UNITS
CONDENSER ENTERING AIR TEMPERATURE (F)
UNIT 85 95 105 115 125
LCWT SIZE
(F) Cooler Cooler Cooler Cooler Cooler
30GXN,R Cap. Input Cap. Input Cap. Input Cap. Input Cap. Input
Flow Flow Flow Flow Flow
Tons kW Tons kW Tons kW Tons kW Tons kW
Rate Rate Rate Rate Rate
080 75.8 84.0 181.5 70.0 88.7 167.5 63.8 93.7 152.6 57.5 100.5 137.7 52.0 108.3 124.4
090 83.2 95.0 199.1 76.6 100.0 183.3 69.8 106.1 167.1 63.3 114.0 151.4 57.3 122.6 137.1
106 97.0 107.7 232.1 89.7 113.2 214.6 81.9 119.8 196.1 74.2 127.8 177.7 67.0 137.1 160.3
114 105.4 118.7 252.4 97.5 125.1 233.3 88.9 132.4 212.9 80.4 142.2 192.6 72.6 152.8 173.7
125 114.5 130.1 274.1 108.4 141.6 259.4 102.9 154.0 246.4 97.3 170.1 232.9 70.4 152.8 168.6
135 125.2 140.4 299.8 118.1 153.0 282.8 112.4 166.3 269.0 106.3 184.0 254.5 93.2 204.7 223.1
150 136.9 155.4 327.7 130.2 169.0 311.7 123.9 183.5 296.5 117.5 201.9 281.3 110.7 224.1 265.1
160 149.4 170.5 357.6 141.3 185.0 338.3 134.8 200.9 322.7 127.8 222.0 306.0 115.2 246.7 275.7
174 161.5 187.6 386.7 155.1 202.2 371.2 147.3 220.0 352.7 140.1 240.4 335.5 88.2 196.2 211.2
204 188.7 214.6 451.7 178.5 233.5 427.4 170.0 253.0 407.0 161.1 279.9 385.6 148.4 309.4 355.2
225 205.7 235.2 492.4 195.2 254.8 467.4 186.1 277.8 445.4 176.1 306.1 421.6 111.5 222.5 266.9
249 229.5 263.7 549.4 218.7 285.7 523.6 208.2 311.3 498.4 197.4 342.3 472.6 142.7 306.0 341.5
40.00 264 241.6 276.6 578.4 229.5 299.2 549.5 219.1 325.8 524.4 207.5 358.6 496.8 146.1 326.5 349.7
281 259.5 293.8 621.1 248.4 319.0 594.7 235.6 346.8 564.0 223.8 380.9 535.9 211.2 421.5 505.5
301 281.1 319.6 672.8 266.9 347.2 638.9 254.2 376.2 608.6 241.2 415.2 577.4 227.3 460.2 544.2
325 304.0 347.9 727.8 288.4 377.0 690.4 275.2 410.5 658.8 261.1 453.2 625.0 229.1 503.9 548.5
350 327.7 389.4 784.5 312.8 420.5 748.9 298.3 460.4 714.1 282.7 506.3 676.8 162.7 340.1 389.5
370 350.8 394.6 841.1 333.6 428.1 799.8 317.8 465.1 761.5 301.2 512.1 723.1 229.1 449.9 549.7
390 373.4 419.8 894.9 353.6 455.6 847.9 337.4 495.4 810.1 319.8 546.4 768.0 0.0 0.0 0.0
415 400.1 450.6 959.8 379.1 488.8 908.9 362.1 530.9 867.7 343.5 585.2 824.2 268.1 575.7 641.2
450 422.4 475.6 1013.0 401.7 515.4 963.8 382.7 561.0 917.6 362.6 618.1 868.8 230.9 448.6 554.0
475 446.2 503.6 1069.1 424.6 546.1 1018.4 404.7 593.9 970.8 383.6 654.3 920.0 262.9 532.8 630.4
500 470.2 532.0 1127.3 448.0 577.3 1073.4 426.7 627.4 1023.2 404.9 689.8 971.5 0.0 0.0 0.0
525 495.4 558.3 1187.9 470.3 604.6 1127.5 449.1 657.1 1076.1 426.0 722.9 1021.5 0.0 0.0 0.0
080 78.8 85.7 188.7 73.0 90.4 174.9 66.5 95.3 159.4 60.0 101.8 143.7 54.2 109.7 129.8
090 86.4 97.0 206.9 79.8 102.1 191.1 72.7 108.0 174.2 65.8 115.6 157.7 59.6 124.3 142.8
106 101.0 110.0 241.9 93.5 115.5 224.0 85.6 121.8 205.1 77.7 129.5 186.0 69.9 138.7 167.5
114 109.8 121.0 263.1 101.7 127.6 243.6 92.9 134.8 222.6 84.0 144.2 201.3 75.8 154.7 181.6
125 118.4 131.9 283.6 112.1 143.6 268.5 106.4 155.9 254.8 100.5 171.9 240.8 72.2 153.7 173.1
135 129.3 142.2 309.8 122.5 155.0 293.4 116.2 168.1 278.4 109.9 185.5 263.4 93.2 204.5 223.4
150 141.3 157.5 338.4 134.9 171.1 323.2 128.1 185.7 306.8 121.5 203.8 291.2 112.3 224.9 269.1
160 154.4 172.6 369.9 146.2 187.6 350.3 139.3 203.4 333.6 132.1 224.0 316.5 115.3 246.7 276.1
174 167.1 189.9 400.3 160.5 204.8 384.5 152.4 222.4 365.1 144.9 242.9 347.2 91.6 198.1 219.4
204 194.7 217.6 466.3 185.1 236.7 443.5 175.8 256.7 421.1 166.6 282.6 399.1 150.3 309.9 360.0
225 212.9 238.4 510.1 201.9 258.5 483.7 192.4 280.8 460.8 182.1 309.1 436.3 115.6 224.4 276.9
42.00 249 237.4 266.9 568.7 226.2 289.5 541.8 215.3 314.8 515.7 204.1 345.9 489.0 147.7 308.0 353.8
264 250.2 280.0 599.3 237.1 303.2 568.0 226.4 329.3 542.4 214.6 362.4 514.1 149.2 327.7 357.4
281 267.8 297.3 641.6 257.7 322.5 617.4 243.7 350.9 583.9 231.7 383.8 555.1 218.6 424.9 523.6
301 290.0 323.8 694.7 276.7 351.3 663.0 262.8 381.2 629.6 249.5 418.9 597.6 235.2 462.6 563.4
325 314.9 351.8 754.4 298.2 382.4 714.3 284.5 414.1 681.4 269.9 457.2 646.6 227.3 504.5 544.4
350 339.3 394.2 812.9 323.1 426.4 774.0 308.3 465.1 738.6 292.1 511.1 699.8 168.5 342.3 403.7
370 362.3 399.8 868.7 345.2 434.0 828.6 328.2 471.1 787.2 311.3 517.2 746.5 234.9 452.6 564.0
390 386.5 425.0 927.5 365.7 461.9 876.8 348.6 500.3 836.6 330.6 551.6 792.8 0.0 0.0 0.0
415 413.7 456.5 993.2 392.2 495.7 941.3 374.0 537.1 897.1 354.9 591.1 851.0 270.5 579.1 648.6
450 436.7 482.0 1047.6 415.3 522.7 997.0 395.3 567.8 949.0 374.6 623.8 898.7 239.3 452.8 574.5
475 461.3 509.8 1106.4 439.4 553.9 1054.0 418.0 601.1 1003.5 396.4 660.1 951.7 272.4 538.9 653.9
500 485.8 538.7 1165.6 463.6 585.0 1111.8 440.9 635.3 1058.3 418.4 697.1 1004.2 328.7 701.9 786.9
525 512.2 565.5 1228.4 486.4 612.6 1167.0 464.0 664.7 1112.9 440.1 730.7 1056.3 305.9 661.3 734.4
080 81.8 87.5 196.2 75.9 92.3 181.9 69.3 97.3 166.2 62.7 103.4 150.2 56.5 111.0 135.3
090 89.7 99.1 215.0 83.0 104.2 199.0 75.8 110.0 181.8 68.6 117.3 164.6 62.1 125.9 148.9
106 105.0 112.2 251.7 97.5 117.8 233.8 89.5 123.9 214.5 81.1 131.6 194.5 73.1 140.5 175.2
114 114.3 123.5 274.0 106.0 130.1 254.2 97.1 137.1 232.8 87.8 146.1 210.5 79.2 156.6 189.9
125 122.3 133.7 293.1 116.0 145.7 278.2 109.9 157.8 263.4 103.9 173.4 249.1 73.6 154.7 176.3
135 133.3 144.2 319.6 127.0 157.1 304.4 120.1 170.6 287.9 113.6 187.3 272.4 93.3 204.5 223.6
150 145.7 159.4 349.3 139.8 172.9 335.2 132.4 188.0 317.3 125.6 205.7 301.0 113.9 225.8 273.0
160 159.3 175.3 381.9 151.5 190.1 363.2 143.9 206.0 344.9 136.4 226.5 327.1 115.3 246.9 276.4
174 172.6 192.3 413.8 165.7 207.7 397.3 157.9 225.1 378.4 149.9 245.6 359.2 95.1 199.7 227.9
204 200.8 220.8 481.3 191.9 239.8 459.9 181.6 260.4 435.5 172.2 285.4 412.7 150.3 309.9 360.3
225 219.9 241.8 527.1 208.9 262.2 500.8 198.7 284.5 476.4 188.2 312.5 451.2 119.6 226.3 286.8
44.00 249 245.4 270.2 588.4 233.9 293.5 560.6 222.4 318.4 533.2 210.9 349.4 505.6 152.8 310.9 366.3
264 258.8 283.7 620.4 245.1 307.6 587.4 233.9 332.8 560.8 221.8 366.3 531.7 152.4 329.7 365.3
281 276.5 300.7 662.7 267.1 326.0 640.3 252.0 355.4 604.1 239.6 386.9 574.5 226.2 428.6 542.2
301 299.1 327.9 717.1 286.7 355.5 687.4 271.6 386.3 651.0 257.9 422.4 618.3 237.2 464.2 568.6
325 325.1 356.7 779.3 308.7 387.6 740.0 293.8 419.7 704.4 278.8 461.7 668.4 229.3 503.9 549.6
350 351.1 399.4 841.7 333.5 432.4 799.5 318.4 469.8 763.3 301.8 516.8 723.4 174.4 345.2 418.1
370 373.8 405.3 897.1 357.1 439.7 858.4 338.9 477.2 814.6 321.5 522.0 771.6 240.8 455.6 578.7
390 398.6 431.1 957.2 378.7 468.2 909.0 360.0 507.0 863.7 341.4 557.2 820.4 0.0 0.0 0.0
415 426.8 463.3 1024.7 405.8 502.4 974.8 386.1 544.4 927.1 366.5 596.8 879.3 273.0 582.5 655.0
450 450.8 488.7 1081.5 429.4 530.0 1030.8 408.2 574.8 980.5 386.8 630.3 929.2 247.8 457.2 595.3
475 475.9 517.7 1142.4 454.3 561.6 1090.0 431.8 609.7 1036.5 409.4 666.9 983.6 281.9 544.5 677.5
500 501.3 546.2 1203.5 479.1 592.7 1150.0 455.4 643.5 1092.9 432.1 704.1 1037.0 345.8 773.4 830.0
525 528.9 573.5 1271.5 502.6 621.1 1206.6 479.0 673.2 1149.9 454.5 738.2 1090.4 0.0 0.0 0.0
080 83.4 88.4 200.1 77.3 93.3 185.5 70.8 98.2 169.8 64.0 104.2 153.4 57.6 111.7 138.1
090 91.4 100.2 219.1 84.6 105.4 202.9 77.3 111.0 185.5 70.0 118.3 168.0 63.3 126.7 151.9
106 107.2 113.3 257.0 99.6 118.9 238.9 91.4 125.0 219.2 82.8 132.7 198.5 74.7 141.6 179.1
114 116.6 124.8 279.6 108.3 131.3 259.6 99.3 138.2 238.0 89.7 147.1 215.1 80.9 157.5 194.1
125 124.1 134.6 297.7 118.1 146.7 283.2 111.7 158.9 267.8 105.6 174.2 253.2 74.2 155.4 177.9
135 135.4 145.1 324.6 129.2 158.1 309.9 122.1 171.7 292.8 115.5 187.9 277.1 93.3 204.3 223.8
150 148.0 160.4 354.9 142.2 173.8 341.0 134.5 189.5 322.6 127.7 206.7 306.1 114.7 225.9 275.1
160 161.7 176.4 387.9 154.1 191.5 369.6 146.2 207.5 350.6 138.7 227.4 332.5 115.3 247.1 276.5
174 175.4 193.6 420.7 168.4 209.2 403.8 160.6 226.4 385.2 152.3 247.2 365.3 96.9 200.7 232.4
204 203.9 222.4 488.9 195.3 241.3 468.2 184.7 262.1 442.8 175.1 286.6 419.8 150.3 310.0 360.4
225 223.4 243.5 535.8 212.5 264.0 509.5 202.0 286.3 484.3 191.3 314.1 458.8 121.7 227.3 291.9
45.00 249 249.5 271.9 598.2 238.0 295.5 570.7 226.1 320.5 542.2 214.4 351.1 514.1 155.4 312.6 372.7
264 263.1 285.6 630.8 249.3 309.8 597.9 237.6 335.0 569.9 225.4 368.3 540.4 154.1 330.8 369.5
281 280.8 302.4 673.5 271.7 328.0 651.4 256.4 357.6 614.8 243.7 388.8 584.3 230.0 430.1 551.6
301 303.8 329.9 728.5 291.9 357.4 699.8 276.0 388.8 661.9 262.2 424.3 628.8 237.2 464.1 568.9
325 330.1 359.2 791.6 314.1 390.0 753.3 298.6 422.5 716.1 283.4 463.6 679.5 227.4 504.4 545.2
350 357.1 401.9 856.4 338.8 435.2 812.5 323.6 472.3 775.9 306.7 519.5 735.4 177.5 346.9 425.6
370 379.6 407.8 911.5 363.2 442.4 871.6 344.3 480.1 827.4 326.7 525.1 784.2 243.7 457.6 585.8
390 404.6 434.2 972.1 385.3 471.3 925.4 365.8 510.7 878.0 346.8 559.7 833.3 253.1 540.7 608.3
415 433.3 466.9 1041.7 412.7 505.6 991.7 392.2 548.2 942.2 372.3 599.4 893.7 274.8 584.0 659.3
450 457.9 492.4 1099.0 436.6 533.7 1050.0 414.6 579.0 996.2 391.9 633.1 941.6 252.1 459.6 605.6
475 483.3 521.4 1160.5 461.8 565.2 1108.6 438.8 613.6 1053.4 415.9 670.9 999.3 286.7 547.3 687.6
500 509.3 549.8 1222.6 486.9 597.3 1169.3 462.8 648.0 1110.9 438.9 708.1 1053.8 346.9 773.8 833.5
525 537.4 577.5 1289.6 511.0 625.9 1226.8 486.5 677.5 1168.2 461.7 741.9 1108.3 332.4 742.6 797.0
46
COOLING CAPACITIES — 60 Hz, ENGLISH (cont)
STANDARD UNITS (cont)
CONDENSER ENTERING AIR TEMPERATURE (F)
UNIT 85 95 105 115 125
LCWT SIZE
(F) Cooler Cooler Cooler Cooler Cooler
30GXN,R Cap. Input Cap. Input Cap. Input Cap. Input Cap. Input
Flow Flow Flow Flow Flow
Tons kW Tons kW Tons kW Tons kW Tons kW
Rate Rate Rate Rate Rate
080 84.9 89.4 203.7 78.8 94.3 189.0 72.3 99.2 173.3 65.4 104.9 156.9 58.8 112.4 141.0
090 93.1 101.2 223.4 86.3 106.5 207.0 78.9 112.0 189.3 71.5 119.2 171.5 63.8 127.1 153.1
106 109.3 114.5 262.3 101.6 120.1 243.7 93.3 126.2 223.8 84.6 133.9 202.9 76.4 142.6 183.2
114 118.9 126.0 285.2 110.5 132.5 265.1 101.4 139.5 243.3 91.8 148.2 220.3 82.7 158.5 198.4
125 126.0 135.6 302.2 120.1 147.6 288.1 113.5 160.1 272.2 107.3 175.2 257.3 74.8 155.8 179.5
135 137.5 146.0 329.7 131.5 159.1 315.4 124.1 173.0 297.7 117.4 188.8 281.7 93.3 204.4 223.9
150 150.3 161.5 360.4 144.5 175.2 346.7 136.8 190.5 328.2 129.8 207.6 311.3 115.6 226.1 277.3
160 164.3 177.6 394.0 156.8 192.7 376.2 148.6 208.9 356.4 141.0 228.3 338.1 115.4 246.5 276.8
174 178.3 194.7 427.6 171.1 210.6 410.4 163.4 227.6 391.9 154.8 248.8 371.4 98.8 201.7 237.0
204 207.1 223.7 496.7 198.7 242.9 476.6 187.7 264.0 450.2 178.0 287.8 426.9 150.4 309.8 360.7
225 227.0 245.2 544.6 216.1 265.8 518.3 205.2 288.2 492.2 194.4 316.0 466.2 123.8 228.4 297.1
249 253.3 273.9 607.6 241.9 297.8 580.3 229.8 322.8 551.3 217.9 353.0 522.7 158.1 314.7 379.2
46.00 264 267.1 287.8 640.7 253.7 312.0 608.5 241.4 337.6 579.1 229.0 370.3 549.3 155.7 332.4 373.5
281 285.2 304.2 684.1 276.1 330.0 662.2 261.1 359.9 626.2 247.8 390.9 594.3 233.9 432.0 561.0
301 308.5 332.1 739.9 296.9 359.6 712.2 280.5 391.3 672.9 266.6 425.9 639.4 237.3 464.1 569.1
325 335.2 361.6 803.9 319.6 392.7 766.6 303.4 425.6 727.8 288.0 465.7 690.9 227.4 504.4 545.4
350 363.1 404.6 870.9 344.2 438.4 825.7 328.7 474.4 788.5 311.6 522.1 747.5 180.6 348.9 433.2
370 385.4 410.8 926.0 369.3 445.4 886.7 349.7 483.7 840.0 330.8 526.7 794.2 246.7 459.5 592.8
390 410.7 437.4 987.0 391.9 474.3 941.6 371.6 514.6 892.2 352.4 562.0 846.9 0.0 0.0 0.0
415 439.9 470.1 1056.8 419.7 509.2 1008.7 398.3 551.9 957.4 378.1 602.8 908.0 276.7 584.8 664.0
450 464.9 495.8 1116.4 443.9 537.6 1065.4 421.0 583.2 1011.7 397.1 635.5 954.0 256.4 462.2 616.0
475 490.7 524.9 1178.7 469.3 569.4 1127.0 445.8 618.0 1070.0 422.5 674.5 1015.2 289.8 549.0 695.7
500 517.1 553.9 1242.6 495.0 601.1 1189.2 470.2 652.7 1129.3 446.0 711.4 1070.6 332.3 702.4 799.2
525 545.6 581.5 1309.9 519.7 630.3 1250.0 494.1 682.1 1186.8 469.0 745.5 1126.2 0.0 0.0 0.0
080 88.1 91.4 211.5 81.9 96.2 196.4 75.1 101.2 180.3 68.0 106.6 163.3 61.1 113.8 146.7
090 96.5 103.5 231.7 89.5 108.8 214.9 82.1 114.1 197.1 74.4 121.2 178.5 64.8 127.7 155.5
106 113.7 116.7 272.8 105.8 122.7 253.8 97.2 128.9 233.3 88.4 136.1 212.2 79.6 144.7 191.1
114 123.6 128.6 296.7 115.1 135.1 276.1 105.8 142.3 253.9 95.9 150.4 230.2 86.3 160.5 207.0
125 129.8 137.4 311.5 124.3 149.5 298.2 117.1 162.3 281.1 110.7 176.5 265.7 76.3 156.3 183.1
135 141.6 147.8 339.9 136.1 160.8 326.7 128.2 175.2 307.7 121.2 190.4 290.9 93.3 204.5 224.0
150 154.9 163.7 371.8 149.2 177.3 358.2 141.4 193.0 339.3 134.0 209.8 321.6 116.2 226.6 278.8
160 169.3 179.8 406.3 162.2 195.1 389.4 153.4 211.8 368.0 145.5 230.2 349.2 115.4 246.7 276.9
174 183.9 197.3 441.3 176.8 213.4 424.3 168.9 230.7 405.5 160.0 251.5 383.9 102.5 204.5 245.9
204 213.4 226.6 512.2 205.6 245.9 493.4 193.7 267.7 465.0 183.8 290.5 441.2 150.4 310.0 360.9
225 234.2 248.5 562.1 223.4 269.5 536.1 211.8 292.0 508.2 200.7 318.9 481.6 128.1 231.1 307.4
48.00 249 261.0 278.2 626.5 250.0 301.8 599.9 237.3 327.5 569.6 224.9 356.9 539.7 162.5 318.4 389.9
264 275.3 292.1 660.7 262.4 316.3 629.8 249.1 342.4 597.9 236.3 373.8 567.1 158.2 335.9 379.6
281 293.9 308.0 705.2 284.7 334.3 683.1 270.4 364.0 649.0 255.9 396.1 614.1 241.6 435.1 579.8
301 318.1 335.8 763.3 307.2 363.5 737.4 289.8 396.3 695.5 275.3 429.7 660.6 237.3 464.0 569.5
325 345.4 366.4 828.9 330.6 397.5 793.5 313.2 431.3 751.6 297.2 469.7 713.3 227.5 504.4 545.9
350 375.2 409.5 900.5 355.6 444.4 853.5 339.1 479.9 813.8 316.6 524.7 759.7 186.8 353.5 448.3
370 397.1 416.1 954.8 381.5 451.1 917.0 361.0 490.5 866.9 339.0 531.1 815.1 251.5 462.1 604.8
390 423.1 443.7 1016.9 405.2 480.9 974.3 383.4 521.7 921.4 361.3 566.5 867.6 257.0 543.0 617.8
415 453.1 477.0 1088.2 433.9 516.2 1043.5 410.8 559.6 988.0 387.8 607.4 931.4 279.5 585.3 669.8
450 479.2 502.5 1151.1 458.6 544.7 1101.5 434.5 591.1 1044.5 407.3 641.7 978.6 263.8 466.6 634.7
475 505.8 532.3 1215.3 484.7 576.7 1164.6 460.1 626.0 1105.1 433.5 680.3 1042.4 296.0 552.6 712.3
500 532.7 561.7 1279.4 511.5 608.9 1228.6 485.4 661.2 1166.4 455.5 716.8 1094.1 332.6 641.3 799.8
525 562.1 590.1 1350.3 537.3 638.5 1290.3 509.5 691.9 1223.9 479.2 750.9 1150.9 328.1 740.3 787.0
080 91.3 93.5 219.3 85.0 98.1 204.1 78.3 103.2 187.9 70.9 108.3 170.2 63.6 115.4 152.7
090 100.0 105.8 240.2 93.0 111.1 223.3 85.3 116.6 204.9 77.4 123.1 185.9 65.2 127.8 156.5
106 118.1 119.1 283.7 109.9 125.4 263.9 101.4 131.5 243.5 92.3 138.5 221.6 83.2 146.6 199.8
114 128.5 131.0 308.6 119.6 137.9 287.2 110.2 145.1 264.5 100.1 153.0 240.3 89.0 162.0 213.8
125 133.6 139.3 320.7 128.3 151.6 308.0 120.9 164.6 290.3 114.2 178.4 274.2 77.8 157.2 186.7
135 145.9 149.7 350.3 140.7 163.0 337.9 132.4 177.5 317.8 125.2 191.9 300.6 93.4 204.6 224.2
150 159.5 165.7 383.1 154.0 179.5 369.9 145.9 195.4 350.4 138.2 212.0 331.9 118.1 226.9 283.5
160 174.3 182.4 418.5 167.7 197.6 402.6 158.1 214.8 379.7 150.0 232.5 360.3 115.4 246.8 277.2
174 189.4 200.0 454.7 182.5 216.4 438.2 174.6 233.7 419.3 165.0 254.6 396.3 106.3 207.6 255.2
204 219.8 229.4 527.9 212.5 249.1 510.2 200.2 271.4 480.8 189.6 293.7 455.3 150.4 310.0 361.2
225 241.3 252.2 579.5 230.9 273.3 554.4 218.4 296.4 524.3 204.7 320.9 491.5 132.4 233.9 317.9
50.00 249 268.9 282.3 645.6 258.0 306.0 619.5 245.0 331.8 588.3 232.0 360.7 557.0 167.2 321.2 401.5
264 283.6 296.7 680.8 271.2 320.7 651.1 256.8 347.5 616.6 243.7 377.6 585.1 162.0 338.1 388.9
281 302.6 311.6 726.5 293.4 338.6 704.4 279.9 368.2 672.1 264.1 401.1 634.2 243.5 435.7 584.8
301 327.6 339.9 786.7 316.8 368.5 760.7 299.8 401.2 719.9 284.0 435.4 682.0 237.5 464.0 570.2
325 355.7 371.4 854.0 341.8 402.6 820.6 322.9 437.1 775.3 306.5 473.9 736.0 227.5 504.3 546.3
350 386.6 415.9 928.2 367.4 450.8 882.3 349.5 487.4 839.2 316.6 525.1 760.3 193.3 358.0 464.1
370 406.7 421.0 978.1 391.5 456.1 940.9 368.4 494.5 885.2 343.5 533.3 826.2 254.2 463.6 611.5
390 435.6 449.7 1047.0 418.6 487.2 1006.4 395.2 529.2 949.9 368.1 569.4 884.5 257.2 543.0 618.4
415 466.5 483.5 1120.5 445.4 521.6 1070.1 421.0 566.1 1012.2 395.2 610.9 949.7 278.6 586.2 669.4
450 489.4 507.9 1176.2 469.1 550.3 1127.1 443.9 596.9 1066.5 410.9 642.6 988.3 269.2 470.2 647.6
475 518.3 538.4 1245.7 497.4 583.5 1195.3 471.8 633.4 1133.3 437.9 682.5 1052.4 300.6 555.6 723.2
500 544.6 568.1 1308.7 523.5 615.9 1259.1 496.9 668.6 1194.4 463.9 721.6 1115.1 337.4 644.2 812.2
525 576.0 597.7 1383.9 551.9 646.4 1329.3 520.1 699.1 1250.0 488.0 755.9 1172.5 324.9 677.3 780.8
47
Performance data (cont)
COOLING CAPACITIES — 60 Hz, ENGLISH
HIGH-EFFICIENCY UNITS
CONDENSER ENTERING AIR TEMPERATURE (F)
UNIT 85 95 105 115 125
LCWT SIZE
(F) Cooler Cooler Cooler Cooler Cooler
30GXN,R Cap. Input Cap. Input Cap. Input Cap. Input Cap. Input
Flow Flow Flow Flow Flow
Tons kW Tons kW Tons kW Tons kW Tons kW
Rate Rate Rate Rate Rate
083 76.5 81.6 183.1 71.1 85.9 170.1 65.4 90.8 156.4 59.0 96.3 141.1 52.8 103.7 126.3
093 84.5 90.4 202.3 78.7 95.3 188.3 72.5 100.7 173.5 65.6 106.9 157.1 59.0 115.1 141.2
108 95.0 102.3 227.3 91.6 111.8 219.2 86.3 122.2 206.5 81.7 133.4 195.5 76.7 148.0 183.7
118 102.6 109.7 245.5 99.6 119.8 238.3 94.4 131.0 226.0 89.3 142.5 213.7 84.2 157.7 201.6
128 112.1 121.1 268.5 108.6 132.0 260.0 102.5 143.9 245.5 97.2 156.7 232.8 91.8 173.6 219.7
138 123.3 134.4 295.1 118.9 146.4 284.6 112.2 159.2 268.5 106.4 174.0 254.8 100.4 192.6 240.4
153 136.4 149.2 326.6 131.4 161.4 314.5 124.3 174.9 297.6 118.2 190.6 283.1 111.7 210.0 267.5
163 147.8 161.9 353.7 143.1 174.8 342.5 135.6 189.5 324.5 129.0 205.5 308.8 122.2 226.6 292.5
178 162.9 179.7 390.0 156.7 193.5 375.1 148.5 209.0 355.4 141.4 227.5 338.5 133.7 249.9 320.2
208 193.2 206.8 462.5 187.5 224.9 448.9 177.0 244.6 423.6 168.3 265.9 402.8 159.2 294.5 381.2
228 203.1 220.9 486.1 195.9 239.3 468.9 185.5 259.5 444.1 176.5 282.7 422.5 166.9 312.1 399.6
253 232.2 254.6 555.9 224.8 275.6 538.2 212.5 299.7 508.7 202.6 326.6 485.1 191.9 361.6 459.5
40.00 268 245.6 272.6 587.8 236.3 294.3 565.7 224.2 319.5 536.8 213.8 348.8 511.8 197.5 385.9 472.9
283 265.6 285.7 637.8 256.7 310.0 616.0 242.8 336.7 582.7 230.7 366.6 553.5 218.1 405.0 522.8
303 277.6 298.9 665.2 268.6 324.1 644.2 255.1 351.9 611.9 242.1 383.2 580.9 229.1 422.2 549.7
328 306.4 332.0 735.7 295.6 358.2 709.3 280.4 387.8 672.0 266.9 421.6 640.6 252.7 463.7 606.2
353 334.3 362.9 801.4 322.5 390.7 773.0 306.1 422.4 735.3 291.7 459.0 699.8 276.4 504.6 662.3
373 362.9 392.1 869.6 351.3 425.4 843.6 332.8 462.8 799.4 316.5 504.3 758.6 299.7 557.8 719.2
393 372.0 403.4 891.5 359.0 435.4 860.1 340.1 471.7 816.4 324.0 512.8 776.6 306.8 564.6 736.6
418 389.5 425.3 934.0 374.9 460.0 898.7 356.8 498.6 856.1 339.4 544.2 814.9 314.5 598.9 755.3
453 415.1 445.5 995.8 401.4 482.7 963.0 380.7 524.1 913.0 362.0 570.1 867.5 342.7 628.5 822.6
478 444.8 479.6 1065.8 430.4 519.6 1031.9 408.9 564.2 981.1 388.8 614.8 932.7 368.5 678.3 883.1
503 474.7 513.8 1138.2 460.0 556.5 1102.4 436.9 605.0 1047.5 415.8 659.2 997.5 394.2 728.3 945.7
528 502.1 550.1 1203.9 483.7 594.7 1159.8 460.9 645.2 1104.6 438.7 704.4 1051.1 402.6 776.9 966.3
083 79.6 83.0 190.6 74.1 87.2 177.5 68.2 92.3 163.4 61.7 97.6 147.8 55.1 104.6 132.1
093 87.8 92.0 210.4 81.9 96.9 196.2 75.6 102.4 181.1 68.7 108.3 164.5 61.7 116.2 147.8
108 98.1 103.4 235.0 94.9 113.0 227.3 89.5 123.6 214.4 84.6 134.7 202.6 79.5 149.1 190.5
118 106.0 111.0 253.8 102.8 121.1 246.3 98.2 132.4 235.3 92.5 144.3 221.7 87.4 158.9 209.3
128 115.9 122.5 277.6 112.5 133.5 269.4 106.5 145.8 255.1 100.8 158.3 241.4 95.1 175.0 227.9
138 127.3 136.0 304.9 123.4 148.1 295.7 116.2 161.4 278.5 110.3 175.4 264.2 104.1 194.3 249.3
153 140.9 150.8 337.5 136.4 162.8 326.9 128.7 176.8 308.3 122.5 191.7 293.5 115.8 211.6 277.5
163 152.7 163.8 365.7 148.2 176.8 355.0 140.6 191.8 336.9 133.7 207.8 320.3 126.6 228.6 303.4
178 168.4 181.9 403.4 162.7 195.6 389.9 153.8 211.7 368.5 146.7 229.6 351.4 138.8 252.5 332.4
208 199.5 209.3 477.9 193.9 227.4 464.5 183.8 247.7 440.4 174.3 268.5 417.5 165.0 296.7 395.3
228 209.7 223.7 502.3 203.1 242.1 486.5 192.3 262.9 460.7 182.8 285.6 438.0 173.0 314.9 414.5
42.00 253 239.9 257.7 574.7 232.8 279.0 557.7 220.6 303.4 528.4 210.0 329.6 503.0 198.9 364.9 476.6
268 253.7 276.0 607.8 244.3 298.4 585.2 232.4 323.6 556.8 221.2 353.0 529.9 201.6 388.5 482.9
283 274.1 288.9 657.2 265.8 313.6 638.5 251.8 340.9 604.7 238.8 370.4 573.5 225.9 408.4 542.1
303 286.5 302.4 687.4 278.1 328.1 666.8 264.6 356.3 634.8 250.6 387.7 601.9 237.3 425.8 569.8
328 316.3 335.9 758.7 306.3 362.4 735.9 290.5 392.7 697.5 276.4 425.8 662.7 261.8 467.8 628.1
353 345.2 367.4 828.9 334.2 395.7 801.5 317.4 428.0 761.3 302.1 464.1 725.6 286.3 509.1 686.9
373 374.5 396.9 898.2 363.6 431.0 871.7 345.4 468.8 829.3 327.7 510.4 786.0 310.4 563.0 744.4
393 383.9 408.3 921.2 371.9 441.0 891.9 352.6 477.9 846.5 335.4 518.3 806.1 317.8 569.9 762.2
418 401.9 430.6 965.0 388.0 466.0 931.3 369.6 504.8 886.4 351.1 550.5 843.8 323.5 603.3 775.8
453 428.4 451.3 1027.9 415.3 488.8 997.0 394.8 531.0 947.8 374.9 576.7 899.2 355.0 634.3 851.4
478 459.1 485.3 1100.9 445.4 526.3 1067.9 424.1 571.6 1017.8 402.6 621.9 966.5 381.6 684.6 915.7
503 490.0 519.8 1175.8 476.2 563.2 1142.5 453.1 612.4 1086.5 430.5 666.7 1032.8 408.3 734.8 980.4
528 518.3 557.3 1243.9 500.2 602.9 1200.0 477.3 653.6 1145.1 453.6 713.2 1087.6 412.6 781.6 990.7
083 82.7 84.4 198.3 77.1 88.9 184.8 71.1 93.9 170.4 64.6 99.2 154.8 57.8 105.7 138.6
093 91.2 93.6 218.7 85.2 98.6 204.3 78.8 104.2 188.9 71.8 109.9 172.1 64.4 117.5 154.5
108 101.3 104.7 242.7 98.0 114.4 235.0 92.9 125.0 222.8 87.6 136.0 210.0 82.4 150.3 197.5
118 109.4 112.1 262.4 106.2 122.4 254.6 102.1 133.7 244.8 95.9 146.1 229.9 90.6 160.1 217.1
128 119.6 124.1 286.8 116.1 135.3 278.4 110.7 147.6 265.4 104.4 160.6 250.3 98.6 176.4 236.4
138 131.4 137.8 315.0 127.5 150.0 305.6 120.8 163.6 289.5 114.2 177.5 273.8 107.8 196.0 258.4
153 145.4 152.5 348.6 141.0 164.8 338.1 133.6 179.0 320.2 126.9 193.7 304.1 119.9 213.3 287.5
163 157.6 165.8 377.8 153.1 179.1 366.9 146.1 194.2 350.3 138.4 210.6 331.8 131.2 230.6 314.5
178 173.9 184.2 416.8 168.5 198.3 404.0 159.6 214.7 382.6 151.9 232.1 364.2 143.9 255.1 345.0
208 206.0 212.0 493.7 200.1 230.3 479.8 191.0 250.9 457.8 180.5 272.4 432.8 170.8 299.0 409.5
228 216.6 226.4 519.2 210.1 245.3 503.7 199.5 266.6 478.3 189.3 288.9 453.7 179.2 318.0 429.5
44.00 253 247.5 261.0 593.4 240.4 282.8 576.4 229.2 307.5 549.3 217.3 334.5 520.9 206.0 368.4 493.9
268 261.7 280.0 627.4 252.5 303.0 605.2 240.9 328.2 577.4 228.7 357.9 548.3 206.6 391.2 495.2
283 282.8 292.3 678.7 274.7 317.4 659.0 261.3 344.8 627.4 247.2 374.5 593.9 233.8 411.4 561.7
303 295.6 305.9 710.2 287.4 332.1 690.0 274.6 360.7 658.6 259.5 392.2 623.1 245.7 429.3 590.3
328 326.3 339.7 783.1 316.8 366.9 760.4 301.3 397.3 724.4 286.0 430.5 686.6 271.0 471.9 650.0
353 356.2 371.9 855.4 345.6 400.9 830.1 329.3 433.4 790.2 312.5 470.0 750.1 296.5 514.0 712.3
373 386.3 401.6 927.6 375.7 436.5 901.6 358.5 474.8 859.9 339.2 516.8 815.3 321.4 567.9 771.4
393 396.1 412.8 951.4 384.8 446.5 923.9 365.7 483.9 877.5 347.2 523.9 833.8 329.1 574.7 789.9
418 414.6 435.8 995.8 401.3 472.1 964.1 382.7 511.1 918.7 363.1 556.8 871.2 332.7 607.3 800.0
453 442.0 456.9 1062.5 429.4 495.0 1030.8 409.4 537.8 983.5 387.9 583.9 931.4 367.4 640.1 881.6
478 473.7 491.2 1137.0 460.6 532.6 1105.2 439.8 578.9 1056.0 416.5 629.7 1000.6 394.9 690.8 948.7
503 505.5 526.1 1213.4 491.7 570.6 1180.4 470.3 620.2 1128.8 445.4 675.6 1068.4 422.6 741.5 1014.9
528 534.6 564.5 1282.5 516.5 611.3 1240.9 494.2 662.3 1186.5 468.7 722.7 1125.1 422.7 786.5 1014.8
083 84.4 85.0 202.3 78.6 89.7 188.5 72.6 94.7 174.0 66.0 100.0 158.4 59.2 106.3 141.9
093 93.1 94.4 223.1 86.9 99.4 208.4 80.4 105.1 192.8 73.3 110.8 175.9 65.9 118.2 158.1
108 102.9 105.3 246.6 99.6 115.1 238.8 94.7 125.8 227.0 89.1 137.0 213.7 83.9 150.9 201.1
118 111.2 112.8 266.7 107.9 123.1 258.8 104.0 134.4 249.5 97.6 147.0 234.1 92.2 160.6 221.1
128 121.6 124.8 291.5 118.0 136.1 282.9 112.9 148.5 270.7 106.3 161.7 254.9 100.4 177.2 240.7
138 133.5 138.7 320.2 129.5 151.1 310.5 123.1 164.7 295.1 116.2 178.8 278.8 109.7 196.9 263.1
153 147.7 153.4 354.1 143.3 165.8 343.6 136.1 180.0 326.4 129.0 195.1 309.3 122.1 214.1 292.7
163 160.1 166.8 383.9 155.5 180.2 373.0 149.0 195.4 357.2 140.8 212.1 337.7 133.5 231.6 320.2
178 176.7 185.4 423.6 171.3 199.7 410.8 162.7 216.1 390.2 154.6 233.6 370.7 146.5 256.3 351.3
208 209.2 213.4 501.8 203.3 231.8 487.5 194.6 252.3 466.7 183.7 274.2 440.6 173.9 300.1 416.9
228 220.0 227.9 527.5 213.5 246.9 512.0 203.3 268.3 487.6 192.6 291.0 461.8 182.3 319.4 437.2
45.00 253 251.4 262.6 602.8 244.3 284.7 585.9 233.5 309.5 559.9 221.1 336.8 530.2 209.6 370.0 502.7
268 265.7 281.8 637.2 256.7 305.2 615.4 245.2 330.4 587.9 232.6 360.3 557.7 209.2 392.4 501.6
283 287.2 294.1 689.6 279.0 319.4 669.5 266.1 346.8 639.6 251.4 376.9 604.2 237.8 413.1 571.5
303 300.2 307.8 721.7 291.9 334.1 701.3 279.6 363.1 670.9 264.1 394.8 634.1 249.9 431.6 600.7
328 331.3 341.6 795.3 321.9 369.2 772.8 307.0 399.6 738.4 290.9 433.2 698.7 275.7 473.8 661.6
353 361.7 374.2 867.9 351.4 403.6 844.8 335.2 436.2 806.2 317.9 472.9 763.2 301.5 516.6 725.2
373 392.3 404.2 942.5 381.6 439.3 916.4 365.2 477.7 876.4 345.0 520.5 829.0 326.9 570.3 784.8
393 402.2 415.4 966.3 390.9 449.5 939.1 372.5 487.0 894.4 353.1 527.7 848.0 334.7 577.0 805.1
418 420.9 438.5 1011.0 407.9 475.0 980.0 389.5 514.5 935.6 369.2 560.4 886.1 337.4 609.2 811.2
453 449.0 459.7 1077.5 436.2 498.3 1047.3 416.9 541.4 1001.6 394.5 587.9 947.8 373.7 643.0 897.0
478 481.1 494.0 1155.1 467.9 536.2 1123.3 448.0 582.5 1075.2 423.6 633.9 1017.6 401.7 693.8 965.4
503 513.2 529.1 1234.5 499.5 574.4 1199.4 479.1 623.9 1150.4 453.0 680.2 1087.1 429.9 745.1 1032.2
528 542.7 568.3 1302.6 524.9 615.8 1261.1 502.8 666.7 1207.3 476.5 727.5 1144.2 427.8 789.4 1027.0
48
COOLING CAPACITIES — 60 Hz, ENGLISH (cont)
HIGH-EFFICIENCY UNITS (cont)
CONDENSER ENTERING AIR TEMPERATURE (F)
UNIT 85 95 105 115 125
LCWT SIZE
(F) Cooler Cooler Cooler Cooler Cooler
30GXN,R Cap. Input Cap. Input Cap. Input Cap. Input Cap. Input
Flow Flow Flow Flow Flow
Tons kW Tons kW Tons kW Tons kW Tons kW
Rate Rate Rate Rate Rate
083 86.0 85.7 206.2 80.2 90.6 192.3 74.1 95.5 177.7 67.5 100.8 161.9 60.5 106.9 145.2
093 94.8 95.2 227.5 88.6 100.4 212.4 82.1 105.9 196.8 74.9 111.7 179.8 67.4 118.9 161.8
108 104.5 106.0 250.7 101.2 115.7 242.7 96.5 126.5 231.4 90.6 137.9 217.4 85.3 151.4 204.6
118 113.0 113.3 271.1 109.6 123.9 263.0 105.8 135.2 253.8 99.5 147.9 238.7 93.8 161.4 225.1
128 123.5 125.5 296.3 119.9 136.8 287.6 115.1 149.4 276.0 108.2 162.8 259.4 102.2 177.9 245.1
138 135.7 139.6 325.4 131.6 151.9 315.7 125.4 165.8 300.8 118.3 180.2 283.7 111.6 197.8 267.7
153 150.0 154.2 359.8 145.6 166.8 349.2 138.7 180.9 332.8 131.3 196.2 314.8 124.2 214.9 297.9
163 162.6 167.7 390.0 158.1 181.4 379.1 151.8 196.6 364.0 143.3 213.5 343.7 135.9 232.6 325.9
178 179.4 186.6 430.2 174.1 201.1 417.6 165.8 217.5 397.7 157.2 235.4 377.1 149.0 257.6 357.5
208 212.6 214.6 509.9 206.5 233.1 495.4 198.3 253.6 475.8 186.9 276.2 448.3 176.9 301.4 424.3
228 223.4 229.3 535.9 216.9 248.6 520.3 207.2 270.0 496.9 195.9 293.1 469.9 185.5 320.9 444.9
253 255.3 264.1 612.4 248.3 286.6 595.5 237.9 311.4 570.6 224.9 339.2 539.5 213.3 371.7 511.6
46.00 268 269.8 283.8 647.1 260.9 307.3 625.8 249.5 332.7 598.4 236.5 362.6 567.2 211.8 393.6 508.0
283 291.6 295.7 700.7 283.3 321.3 680.4 271.0 349.0 650.7 255.6 379.6 614.5 241.9 414.5 581.5
303 304.9 309.6 733.4 296.5 336.3 712.7 284.5 365.4 683.4 268.7 397.5 646.5 254.2 433.6 611.1
328 336.3 343.8 809.0 327.0 371.6 785.3 312.6 402.1 750.7 295.8 436.1 711.0 280.4 475.9 673.2
353 367.3 376.4 881.7 357.1 406.3 858.7 341.4 439.1 820.9 323.4 476.0 776.6 306.7 519.1 738.0
373 398.4 406.6 957.4 387.6 442.1 931.3 371.9 480.7 893.1 350.9 524.0 844.1 332.5 572.7 800.0
393 408.3 418.1 981.3 397.1 452.4 954.3 379.5 490.0 911.5 359.1 531.2 862.0 340.5 579.6 818.7
418 427.3 441.2 1026.3 414.4 478.1 995.8 396.3 517.9 952.6 375.2 563.8 901.2 342.1 611.5 822.3
453 455.9 462.6 1094.6 443.0 501.5 1065.7 424.4 544.9 1019.7 401.3 592.1 964.4 380.0 646.2 913.0
478 488.4 497.0 1173.3 475.2 539.6 1141.5 456.2 586.2 1095.2 430.9 638.3 1034.8 408.6 697.1 982.1
503 521.1 532.2 1250.9 507.4 577.9 1218.6 487.7 627.9 1171.5 460.9 684.8 1106.7 437.3 748.1 1050.0
528 550.9 572.1 1322.6 533.4 620.1 1280.2 511.2 671.5 1227.6 484.6 732.3 1163.9 432.8 792.3 1040.9
083 89.3 87.0 214.3 83.3 92.2 200.0 77.1 97.0 185.1 70.5 102.4 169.1 63.3 108.1 151.9
093 98.4 96.8 236.2 92.0 102.3 220.9 85.4 107.7 204.8 78.2 113.6 187.6 70.5 120.3 169.2
108 107.8 107.2 258.7 104.3 117.0 250.4 100.0 127.8 240.0 93.8 139.7 225.0 88.2 152.5 211.8
118 116.7 114.5 280.1 113.2 125.3 271.6 109.4 136.7 262.5 103.3 149.6 247.8 97.2 163.1 233.2
128 127.5 127.0 306.0 123.7 138.5 296.9 119.2 151.2 286.1 112.1 165.0 269.0 105.7 179.5 253.7
138 140.0 141.5 335.9 135.7 154.0 325.7 130.1 167.8 312.3 122.4 182.8 293.7 115.5 199.5 277.1
153 154.6 155.9 371.1 150.3 168.7 360.6 143.9 182.7 345.4 135.7 198.5 325.8 128.5 216.3 308.3
163 167.7 169.6 402.5 163.2 183.5 391.6 157.2 198.9 377.4 148.4 216.4 356.2 140.6 234.7 337.4
178 184.9 188.9 443.7 179.8 203.9 431.5 172.1 220.2 413.0 162.7 238.6 390.4 154.2 259.9 370.1
208 219.3 217.1 526.3 213.0 235.7 511.2 205.7 256.5 493.7 193.4 279.8 464.1 183.0 303.7 439.1
228 230.4 232.3 552.9 223.8 251.8 537.2 214.8 273.5 515.4 202.7 297.3 486.4 191.9 323.7 460.5
48.00 253 263.2 267.2 631.7 256.3 290.2 615.0 246.8 315.1 592.3 232.6 343.9 558.2 220.6 374.9 529.5
268 278.0 287.5 667.3 269.4 311.6 646.6 258.2 337.2 619.6 244.2 367.5 586.1 217.0 396.2 520.7
283 300.6 299.2 723.3 292.2 324.9 702.5 280.9 353.1 674.7 264.5 384.4 636.5 250.1 418.3 601.4
303 314.4 313.1 755.2 305.8 340.5 736.0 294.4 370.2 707.9 278.4 402.8 668.6 262.9 438.6 631.7
328 346.6 347.4 832.9 337.4 376.2 811.6 323.8 406.9 779.3 306.0 441.8 736.0 290.1 480.5 696.6
353 378.4 380.7 908.9 368.5 411.8 885.1 353.6 445.0 850.0 334.6 482.5 804.8 317.2 524.8 763.1
373 410.7 411.2 987.6 399.8 447.6 961.4 385.2 486.9 925.8 363.3 531.3 872.5 343.8 578.5 826.9
393 420.8 422.8 1011.6 409.7 458.1 985.2 393.5 495.8 946.1 371.6 538.1 892.8 351.2 584.5 844.7
418 440.2 446.5 1058.4 427.6 484.3 1027.4 409.8 524.9 985.4 388.2 571.0 933.2 351.7 616.7 845.8
453 470.0 468.2 1129.2 456.9 508.1 1097.5 439.7 551.7 1057.1 415.3 600.3 998.6 393.0 652.9 945.0
478 503.4 502.7 1209.7 490.2 546.5 1178.1 472.0 593.9 1134.0 446.4 647.0 1071.9 422.6 705.0 1015.8
503 537.1 537.9 1290.0 523.5 585.2 1258.1 504.6 636.1 1212.4 477.3 694.0 1146.9 452.2 756.9 1086.0
528 567.4 579.2 1363.3 550.4 628.6 1322.0 528.0 680.9 1270.8 500.8 742.0 1203.6 443.3 798.7 1064.5
083 92.6 88.4 222.4 86.6 93.8 208.0 80.2 98.6 192.6 73.5 104.1 176.5 66.2 109.6 158.9
093 102.0 98.4 245.0 95.5 104.1 229.4 88.7 109.5 213.1 81.4 115.6 195.5 73.6 122.0 176.7
108 111.2 108.4 267.0 107.6 118.4 258.3 103.4 129.4 248.2 97.1 141.4 233.1 91.3 154.0 219.1
118 120.5 115.7 289.3 116.8 126.8 280.4 112.8 138.4 270.9 107.2 151.3 257.5 100.6 165.3 241.5
128 131.6 128.4 315.9 127.6 140.2 306.5 123.3 153.1 296.1 116.2 167.2 279.0 109.3 181.5 262.6
138 144.4 143.1 346.7 140.0 155.8 336.1 135.0 169.9 324.0 126.6 185.4 303.9 119.4 201.2 286.7
153 159.3 157.5 382.6 154.9 170.7 372.0 149.1 184.7 358.0 140.3 201.0 336.8 132.8 217.9 318.9
163 172.9 171.4 415.1 168.3 185.9 404.2 162.6 201.4 390.4 153.7 219.1 369.2 145.4 237.4 349.2
178 190.5 191.0 457.5 185.5 206.7 445.5 178.4 223.0 428.4 168.1 242.0 403.7 159.5 262.4 383.0
208 226.1 219.4 543.0 219.6 238.3 527.4 212.6 259.8 510.5 200.5 283.3 481.4 189.2 306.7 454.4
228 237.5 235.1 570.2 230.8 255.2 554.2 222.3 277.1 533.7 209.7 301.4 503.5 198.4 327.1 476.3
50.00 253 271.3 270.0 651.4 264.4 293.9 634.9 255.4 319.0 613.3 240.8 348.5 578.1 228.2 378.6 548.0
268 286.4 291.2 687.6 278.1 315.9 667.7 266.9 342.0 640.8 252.4 372.3 606.1 222.3 399.0 533.8
283 309.8 302.3 745.5 301.1 328.6 724.1 290.3 357.5 697.7 272.3 388.6 655.6 257.2 421.9 618.5
303 322.7 316.3 777.1 313.8 344.1 755.6 302.9 374.2 728.8 286.8 407.4 688.7 269.3 441.7 647.8
328 354.3 350.2 851.3 345.2 379.5 830.0 332.4 410.3 799.9 313.7 445.9 755.3 297.2 483.7 714.6
353 387.0 384.0 930.3 377.3 415.9 906.5 363.3 449.2 874.5 343.2 487.8 825.2 324.1 528.1 780.5
373 410.7 411.2 987.6 399.8 447.6 961.4 385.2 486.9 925.8 363.3 531.3 872.5 343.8 578.5 826.9
393 433.5 427.6 1042.8 422.4 463.7 1015.3 407.0 502.1 978.4 384.6 545.2 923.8 357.3 587.6 858.2
418 440.2 446.5 1058.4 427.6 484.3 1027.4 409.8 524.9 985.4 388.2 571.0 933.2 351.7 616.7 845.8
453 480.8 472.5 1155.3 467.5 513.1 1124.1 451.0 557.2 1083.5 426.1 606.6 1024.0 402.8 658.5 968.3
478 503.4 502.7 1209.7 490.2 546.5 1178.1 472.0 593.9 1134.0 446.4 647.0 1071.9 422.6 705.0 1015.8
503 537.1 537.9 1290.0 523.5 585.2 1258.1 504.6 636.1 1212.4 477.3 694.0 1146.9 452.2 756.9 1086.0
528 567.4 579.2 1363.3 550.4 628.6 1322.0 528.0 680.9 1270.8 500.8 742.0 1203.6 443.3 798.7 1064.5
49
Performance data (cont)
COOLING CAPACITIES — 60 Hz, SI
STANDARD UNITS
CONDENSER ENTERING AIR TEMPERATURE (C)
UNIT 30 35 40 45 50
LCWT SIZE
(C) Cooler Cooler Cooler Cooler Cooler
30GXN,R Cap. Input Cap. Input Cap. Input Cap. Input Cap. Input
Flow Flow Flow Flow Flow
kW kW kW kW kW kW kW kW kW kW
Rate Rate Rate Rate Rate
080 269.8 85.3 11.6 251.5 89.5 10.8 231.5 93.9 9.9 211.0 99.7 9.1 192.6 106.6 8.3
090 296.0 96.5 12.7 274.9 101.0 11.8 253.1 106.3 10.9 231.6 113.1 9.9 212.2 120.8 9.1
106 345.6 109.4 14.8 322.1 114.3 13.8 297.5 120.0 12.8 272.5 126.9 11.7 248.5 135.0 10.7
114 375.7 120.5 16.1 350.1 126.3 15.0 322.4 132.8 13.8 294.9 141.2 12.7 269.5 150.5 11.6
125 407.6 132.2 17.5 387.7 142.6 16.6 370.0 153.5 15.9 352.0 167.7 15.1 318.0 182.6 13.6
135 445.9 142.6 19.1 423.0 154.0 18.2 403.9 165.6 17.3 384.7 181.2 16.5 364.1 198.7 15.6
150 487.5 157.7 20.9 466.4 169.8 20.0 445.3 182.8 19.1 425.0 198.8 18.2 403.5 217.6 17.3
160 531.8 172.9 22.8 505.6 186.4 21.7 484.4 200.1 20.8 462.1 218.8 19.8 438.4 239.1 18.8
174 575.5 190.2 24.7 554.9 203.5 23.8 529.7 219.1 22.7 506.5 237.1 21.7 468.1 259.0 20.1
204 671.9 217.9 28.8 639.3 235.2 27.4 611.0 252.9 26.2 582.7 275.7 25.0 552.5 301.5 23.7
225 732.3 238.7 31.4 697.8 256.6 30.0 668.8 276.5 28.7 637.1 301.8 27.3 583.4 330.1 25.0
5.00 249 817.2 267.5 35.1 782.2 287.7 33.6 748.3 310.2 32.1 713.9 337.5 30.6 655.9 368.2 28.2
264 860.1 280.5 36.9 820.5 301.2 35.2 787.3 324.4 33.8 750.7 353.7 32.2 686.3 385.2 29.5
281 924.2 297.8 39.7 889.9 320.7 38.2 846.6 346.0 36.3 809.7 374.6 34.8 769.6 410.4 33.0
301 1000.9 324.1 43.0 955.9 349.2 41.0 913.5 375.6 39.2 872.2 408.9 37.4 828.4 447.0 35.6
325 1082.5 352.8 46.5 1030.8 379.7 44.2 988.9 408.4 42.5 944.0 446.4 40.5 896.0 488.6 38.5
350 1166.6 394.8 50.1 1118.2 423.4 48.0 1072.1 458.3 46.0 1022.2 499.0 43.9 868.4 548.9 37.3
370 1249.0 400.5 53.7 1193.4 431.0 51.4 1141.3 464.1 49.1 1089.0 504.7 46.8 978.3 546.9 42.1
390 1329.1 425.8 57.1 1264.4 458.5 54.3 1212.4 492.9 52.2 1156.3 538.6 49.7 1046.1 582.9 44.9
415 1423.7 457.8 61.3 1355.4 492.3 58.3 1300.8 528.8 55.9 1241.4 577.1 53.4 1117.1 623.9 48.1
450 1503.4 482.6 64.6 1436.3 519.2 61.8 1374.8 559.5 59.1 1311.0 608.8 56.3 1160.6 659.6 49.9
475 1588.4 510.8 68.3 1519.2 550.1 65.3 1453.6 592.8 62.5 1386.9 644.8 59.7 1248.4 699.5 53.6
500 1674.0 539.8 72.0 1603.0 581.2 68.9 1532.7 626.3 65.9 1463.2 680.3 62.9 1325.0 738.2 56.9
525 1763.6 566.4 75.8 1682.4 608.8 72.3 1613.4 655.0 69.3 1539.8 713.5 66.2 1374.3 770.9 59.0
080 289.2 88.4 12.4 270.0 92.9 11.6 249.3 97.4 10.7 228.0 102.5 9.8 207.1 109.1 8.9
090 316.8 100.3 13.6 295.4 104.9 12.7 272.5 109.9 11.7 249.3 116.3 10.7 227.8 123.7 9.8
106 371.0 113.5 15.9 347.5 118.5 14.9 321.0 123.9 13.8 294.5 130.7 12.7 269.2 138.4 11.6
114 403.7 124.9 17.4 377.7 130.8 16.2 349.2 136.9 15.0 319.5 144.8 13.7 291.3 153.9 12.5
125 432.4 135.4 18.6 412.4 146.3 17.7 392.3 157.2 16.9 373.4 170.4 16.0 328.2 183.8 14.1
135 471.8 145.9 20.3 451.5 157.6 19.4 429.0 169.7 18.4 408.3 184.0 17.5 373.3 199.4 16.0
150 515.6 161.3 22.2 496.8 173.6 21.4 472.6 187.4 20.3 451.1 202.3 19.4 428.3 221.0 18.4
160 563.6 177.3 24.2 538.4 190.8 23.1 513.5 205.3 22.1 490.1 222.5 21.1 455.4 241.6 19.6
174 610.8 194.5 26.3 588.4 208.7 25.3 564.1 223.9 24.2 537.9 242.3 23.1 483.2 260.8 20.8
204 710.4 223.5 30.5 682.0 240.7 29.3 648.4 259.4 27.9 618.7 280.2 26.6 586.6 306.7 25.2
225 777.6 244.9 33.4 742.2 263.3 31.9 709.2 283.1 30.5 676.1 307.6 29.1 583.2 329.7 25.1
7.00 249 867.9 273.6 37.3 831.1 294.5 35.7 794.0 317.1 34.1 757.4 343.9 32.6 672.9 369.9 28.9
264 915.0 287.0 39.3 870.9 308.9 37.4 834.5 331.6 35.9 796.3 360.7 34.2 686.2 385.1 29.5
281 978.5 304.3 42.1 949.0 327.1 40.8 900.7 353.6 38.7 860.2 381.3 37.0 818.1 416.8 35.2
301 1058.5 331.8 45.5 1019.1 356.6 43.8 969.0 384.5 41.6 926.2 415.0 39.8 879.8 454.2 37.8
325 1150.4 360.8 49.4 1097.1 389.2 47.2 1048.7 418.1 45.1 1001.0 454.1 43.0 912.6 492.3 39.2
350 1240.9 404.1 53.3 1184.1 434.2 50.9 1136.4 466.8 48.8 1083.9 508.4 46.6 870.2 549.1 37.4
370 1321.9 410.3 56.9 1268.6 441.4 54.6 1209.2 474.9 52.1 1154.6 513.6 49.7 1004.5 549.5 43.2
390 1409.7 436.3 60.7 1345.6 470.3 57.9 1284.7 505.4 55.3 1225.7 547.9 52.8 1055.6 584.0 45.4
415 1509.5 468.7 65.0 1441.8 504.4 62.1 1377.4 542.0 59.3 1315.4 587.1 56.6 1141.2 626.4 49.1
450 1594.0 494.8 68.6 1525.4 532.2 65.7 1456.2 572.8 62.7 1389.5 620.0 59.8 1161.2 658.9 50.1
475 1683.1 523.7 72.4 1613.3 563.6 69.4 1541.3 606.8 66.3 1469.8 657.2 63.3 1259.3 700.7 54.2
500 1773.0 552.9 76.3 1701.2 595.3 73.2 1625.7 640.6 69.9 1550.9 693.2 66.8 1346.7 740.5 57.9
525 1870.0 580.3 80.4 1785.5 623.8 76.8 1708.5 670.2 73.5 1631.2 726.7 70.2 1377.6 770.8 59.3
080 308.8 92.1 13.3 289.0 96.4 12.4 267.9 100.9 11.5 245.6 105.4 10.6 222.9 111.6 9.6
090 338.6 104.2 14.6 316.2 109.0 13.6 292.6 113.8 12.6 268.1 119.8 11.5 244.3 127.0 10.5
106 398.2 117.6 17.1 373.1 123.0 16.0 346.6 128.5 14.9 318.8 134.8 13.7 290.7 142.0 12.5
114 434.0 129.5 18.7 406.2 135.4 17.5 376.9 141.8 16.2 345.7 149.0 14.9 314.8 157.7 13.5
125 456.1 138.9 19.6 438.4 149.8 18.9 415.4 161.3 17.9 395.2 173.6 17.0 331.1 184.3 14.2
135 497.9 149.3 21.4 480.5 161.1 20.7 454.7 174.0 19.6 432.8 186.8 18.6 380.0 200.0 16.3
150 544.6 165.1 23.4 526.6 177.6 22.7 501.4 191.7 21.6 478.0 206.2 20.6 445.5 223.4 19.2
160 595.0 181.7 25.6 572.4 195.5 24.6 543.8 210.4 23.4 519.2 226.1 22.3 457.1 241.7 19.7
174 646.7 199.0 27.8 623.7 213.8 26.8 599.2 229.2 25.8 570.1 247.6 24.5 498.6 262.6 21.5
204 750.4 228.8 32.3 725.6 246.2 31.2 687.3 266.0 29.6 655.6 285.6 28.2 596.9 308.0 25.7
225 822.9 250.9 35.4 788.3 269.9 33.9 750.8 290.3 32.3 716.0 313.4 30.8 579.6 329.6 24.9
9.00 249 917.8 280.5 39.5 881.9 302.3 37.9 841.7 325.3 36.2 802.2 350.8 34.5 683.3 371.4 29.4
264 967.7 294.7 41.6 926.0 316.7 39.8 883.0 340.3 38.0 843.0 367.2 36.3 689.3 385.3 29.7
281 1033.8 310.9 44.5 1004.1 334.8 43.2 960.0 361.3 41.3 912.2 390.1 39.2 867.9 422.7 37.3
301 1118.2 339.2 48.1 1084.0 363.9 46.6 1029.1 393.3 44.3 981.5 423.3 42.2 932.2 460.7 40.1
325 1214.3 370.0 52.2 1166.5 398.2 50.2 1110.2 428.5 47.8 1060.2 461.1 45.6 907.2 490.5 39.0
350 1317.5 413.5 56.7 1254.9 445.3 54.0 1202.0 477.3 51.7 1146.6 517.6 49.3 865.2 549.4 37.2
370 1396.1 419.9 60.2 1346.2 451.5 58.0 1281.0 487.0 55.1 1221.5 524.1 52.6 1019.4 551.8 43.9
390 1487.6 447.6 64.1 1429.7 481.6 61.6 1359.2 518.1 58.6 1297.6 557.5 55.9 1062.3 585.0 45.7
415 1593.2 481.1 68.6 1531.0 516.5 66.0 1456.3 556.2 62.8 1392.0 597.7 60.0 1146.7 626.6 49.4
450 1684.1 507.5 72.5 1617.9 545.4 69.6 1541.3 587.0 66.4 1458.8 631.2 62.8 1161.2 659.1 50.0
475 1777.7 537.4 76.6 1710.0 577.5 73.7 1631.1 621.7 70.2 1555.4 670.1 67.1 1279.7 703.0 55.1
500 1872.9 566.9 80.6 1804.1 609.8 77.8 1721.2 657.0 74.2 1641.5 707.7 70.7 1369.1 743.7 59.0
525 1975.9 595.5 85.1 1895.8 639.4 81.6 1805.7 687.7 77.9 1725.8 740.5 74.3 1370.2 770.4 59.1
50
COOLING CAPACITIES — 60 Hz, SI (cont)
HIGH-EFFICIENCY UNITS
CONDENSER ENTERING AIR TEMPERATURE (C)
UNIT 30 35 40 45 50
LCWT SIZE
(C) Cooler Cooler Cooler Cooler Cooler
30GXN,R Cap. Input Cap. Input Cap. Input Cap. Input Cap. Input
Flow Flow Flow Flow Flow
kW kW kW kW kW kW kW kW kW kW
Rate Rate Rate Rate Rate
083 272.4 82.8 11.7 255.1 86.5 10.9 236.9 91.0 10.2 216.9 95.7 9.3 196.1 101.8 8.4
093 301.0 91.7 12.9 282.3 96.0 12.1 262.6 101.0 11.3 241.1 106.2 10.4 218.9 113.1 9.4
108 338.4 103.8 14.5 327.8 112.5 14.1 310.9 121.8 13.3 295.6 131.5 12.7 280.0 144.1 12.0
118 365.5 111.3 15.7 355.8 120.5 15.3 341.0 130.5 14.6 323.1 141.0 13.9 307.2 153.4 13.2
128 399.8 122.8 17.2 388.9 132.7 16.7 369.7 143.6 15.9 351.9 154.6 15.1 334.7 169.1 14.4
138 439.2 136.4 18.9 426.3 147.1 18.3 403.5 159.0 17.3 385.1 171.2 16.5 366.0 187.8 15.7
153 486.2 151.3 20.9 471.0 162.2 20.2 446.9 174.5 19.2 428.0 187.4 18.4 407.2 204.8 17.5
163 526.8 164.1 22.6 512.2 175.8 22.0 488.1 189.1 21.0 466.6 203.1 20.0 444.9 221.1 19.1
178 580.7 182.2 24.9 561.6 194.6 24.1 533.8 208.8 22.9 511.8 224.2 22.0 487.6 244.3 20.9
208 688.6 209.8 29.6 671.2 226.1 28.8 638.0 244.2 27.4 608.7 262.5 26.1 580.0 286.7 24.9
228 723.7 224.0 31.1 701.5 240.8 30.1 667.5 259.2 28.7 638.3 278.8 27.4 608.2 304.4 26.1
5.00 253 827.8 258.2 35.5 805.0 277.2 34.6 765.6 299.1 32.9 732.7 322.1 31.5 698.9 352.4 30.0
268 874.9 276.5 37.6 845.3 296.3 36.3 807.4 318.8 34.7 772.5 344.7 33.2 736.6 376.2 31.6
283 946.5 289.7 40.7 918.8 311.8 39.5 874.6 336.0 37.6 834.1 361.9 35.9 794.3 394.7 34.2
303 989.3 303.2 42.5 961.2 326.1 41.4 918.6 351.3 39.5 875.4 378.4 37.7 834.3 411.5 35.9
328 1091.8 336.6 46.9 1058.6 360.2 45.6 1009.0 387.1 43.4 964.9 416.2 41.5 920.0 452.6 39.6
353 1191.5 367.9 51.3 1154.7 393.2 49.6 1101.9 422.0 47.4 1054.4 453.5 45.4 1006.0 492.6 43.3
373 1293.4 397.8 55.6 1257.0 428.2 54.1 1199.2 462.0 51.6 1144.2 498.4 49.2 1091.2 543.7 47.0
393 1325.6 409.1 57.0 1285.0 438.4 55.2 1224.2 471.2 52.7 1171.2 506.3 50.3 1117.0 551.1 48.0
418 1387.5 431.3 59.7 1341.4 463.0 57.7 1283.7 497.7 55.2 1226.5 537.6 52.7 1165.7 584.5 50.2
453 1479.4 451.8 63.6 1436.0 485.9 61.8 1370.8 523.3 59.0 1308.9 563.3 56.3 1247.9 613.1 53.6
478 1585.4 486.4 68.1 1540.0 523.1 66.2 1472.5 563.2 63.3 1405.4 607.4 60.5 1341.1 661.2 57.7
503 1692.1 469.8 72.8 1646.3 559.9 70.8 1573.0 603.5 67.6 1502.7 650.7 64.6 1434.8 709.4 61.7
528 1789.0 558.1 76.9 1730.4 598.7 74.4 1657.9 644.0 71.3 1584.3 696.3 68.1 1500.7 756.4 64.5
083 292.6 85.2 12.6 274.3 89.4 11.8 255.3 93.9 11.0 235.2 98.6 10.1 213.4 103.9 9.2
093 322.6 94.6 13.9 303.3 99.1 13.0 282.8 104.2 12.2 260.7 109.3 11.2 237.7 115.4 10.2
108 358.4 106.0 15.4 348.0 114.8 15.0 332.7 124.3 14.3 314.8 134.4 13.5 298.5 145.9 12.8
118 387.5 113.6 16.7 377.1 122.8 16.2 365.1 132.9 15.7 345.0 144.2 14.8 327.8 155.8 14.1
128 423.6 125.5 18.2 412.3 135.8 17.7 396.5 146.8 17.0 375.2 158.6 16.1 356.8 171.5 15.3
138 465.3 139.3 20.0 452.6 150.7 19.5 432.3 162.9 18.6 410.2 175.6 17.6 390.0 190.6 16.8
153 515.0 154.2 22.1 500.7 165.5 21.5 478.0 178.1 20.5 455.4 191.4 19.6 433.7 207.6 18.6
163 558.1 167.7 24.0 543.5 179.8 23.4 523.1 193.3 22.5 496.9 208.1 21.4 474.1 224.4 20.4
178 615.8 186.4 26.5 598.5 199.1 25.7 571.2 213.8 24.6 545.1 229.6 23.4 520.1 248.7 22.4
208 729.3 214.5 31.3 710.6 231.2 30.5 683.5 249.5 29.4 648.3 269.2 27.9 617.6 290.8 26.5
228 766.8 229.1 33.0 746.2 246.3 32.1 713.9 265.4 30.7 679.5 285.6 29.2 647.7 309.6 27.8
7.00 253 876.6 264.1 37.7 853.8 284.0 36.7 819.8 306.1 35.2 779.8 330.4 33.5 744.5 358.1 32.0
268 926.6 283.2 39.8 896.7 304.3 38.5 860.8 326.8 37.0 820.5 353.2 35.3 767.6 380.5 33.0
283 1001.1 295.8 43.1 975.2 318.6 41.9 934.6 343.2 40.3 887.2 370.1 38.2 845.4 400.2 36.4
303 1046.6 309.5 45.1 1020.2 333.4 43.9 981.4 359.2 42.2 932.3 387.4 40.2 888.1 418.8 38.3
328 1155.5 343.5 49.7 1125.1 368.3 48.4 1078.0 395.4 46.4 1026.3 425.4 44.2 979.4 459.9 42.1
353 1261.2 376.3 54.2 1227.7 402.4 52.8 1177.2 431.6 50.6 1121.9 464.1 48.3 1071.2 501.2 46.2
373 1367.9 406.5 58.9 1333.8 438.2 57.4 1282.5 472.3 55.2 1217.4 510.5 52.4 1161.6 552.2 50.0
393 1402.5 417.6 60.4 1366.3 448.2 58.8 1308.5 481.8 56.3 1245.9 517.9 53.6 1189.2 559.3 51.3
418 1467.7 440.9 63.2 1425.3 473.7 61.4 1367.8 509.2 58.9 1303.0 549.5 56.1 1223.5 591.8 52.7
453 1565.2 462.4 67.3 1524.4 497.0 65.7 1464.0 535.4 63.0 1392.6 576.8 60.0 1327.7 623.5 57.1
478 1677.1 497.2 72.2 1635.3 534.8 70.4 1573.3 575.9 67.7 1495.3 621.9 64.4 1426.9 672.7 61.5
503 1790.1 532.3 77.0 1745.6 572.9 75.1 1682.1 617.1 72.4 1599.0 667.1 68.8 1526.6 721.9 65.8
528 1892.1 571.4 81.4 1834.4 614.0 78.9 1765.4 659.3 76.0 1682.4 713.2 72.4 1570.1 766.7 67.5
083 313.1 87.7 13.5 294.1 92.4 12.7 274.4 96.7 11.8 253.9 101.5 10.9 231.3 106.4 10.0
093 345.3 97.5 14.9 324.8 102.5 14.0 303.6 107.3 13.1 281.3 112.6 12.1 257.0 118.2 11.1
108 379.0 108.3 16.3 368.1 117.2 15.8 354.7 126.9 15.3 335.2 137.5 14.4 317.4 148.4 13.7
118 410.6 115.6 17.7 399.3 125.4 17.2 387.3 135.8 16.7 369.5 147.1 15.9 349.0 159.4 15.0
128 448.6 128.3 19.3 436.5 138.7 18.8 422.8 150.1 18.2 400.4 162.5 17.2 379.8 174.9 16.3
138 492.4 142.8 21.2 478.9 154.1 20.6 462.4 166.4 19.9 436.7 180.0 18.8 415.0 193.7 17.9
153 544.1 157.3 23.4 530.1 168.9 22.8 510.9 181.3 22.0 483.8 195.5 20.8 461.5 210.1 19.9
163 590.1 171.2 25.4 575.7 183.8 24.8 557.4 197.5 24.0 529.8 213.0 22.8 504.5 229.0 21.7
178 650.8 190.6 28.0 634.3 204.2 27.3 610.8 218.6 26.3 579.5 235.3 24.9 553.5 252.7 23.8
208 771.4 219.2 33.2 751.5 235.9 32.3 729.8 254.6 31.4 691.0 275.5 29.7 656.9 296.1 28.3
228 810.6 234.5 34.9 789.6 252.1 34.0 762.0 271.5 32.8 723.1 292.9 31.1 688.7 315.1 29.6
9.00 253 926.4 269.8 39.9 904.1 290.5 38.9 875.5 312.7 37.7 829.9 338.5 35.7 791.8 364.7 34.1
268 978.2 290.2 42.1 950.6 312.0 40.9 916.0 334.8 39.4 871.2 361.6 37.5 799.6 385.4 34.4
283 1057.5 302.0 45.6 1030.6 325.4 44.4 996.2 350.5 42.9 944.6 378.6 40.7 898.1 407.7 38.7
303 1106.1 316.2 47.6 1078.6 340.9 46.5 1043.5 367.6 45.0 993.6 396.9 42.8 943.5 427.5 40.7
328 1219.6 350.6 52.5 1190.2 376.6 51.3 1148.6 404.2 49.6 1091.6 435.3 47.1 1040.6 468.3 44.8
353 1332.0 384.2 57.3 1299.9 412.3 55.9 1254.6 441.8 54.1 1188.2 474.9 51.2 1133.8 510.6 48.8
373 1445.2 415.3 62.3 1410.5 448.1 60.8 1365.1 483.6 58.8 1297.7 522.9 55.9 1233.8 564.1 53.2
393 1480.9 426.8 63.8 1445.3 458.7 62.3 1395.5 492.2 60.1 1325.9 530.4 57.1 1263.7 570.3 54.4
418 1548.7 450.8 66.7 1508.3 485.0 65.0 1452.8 521.5 62.6 1385.2 561.9 59.7 1282.8 601.1 55.2
453 1653.6 472.7 71.2 1611.9 508.7 69.4 1558.8 547.9 67.3 1482.6 591.3 63.9 1410.3 636.7 60.8
478 1771.5 507.7 76.3 1729.3 547.2 74.5 1673.0 589.9 72.1 1593.5 637.0 68.6 1515.8 687.2 65.3
503 1890.3 543.3 81.4 1846.5 585.9 79.6 1788.9 631.2 77.0 1703.1 683.1 73.4 1621.7 736.9 69.8
528 1996.5 584.8 86.0 1941.7 629.4 83.6 1871.8 676.5 80.6 1786.8 729.8 76.9 1633.1 777.8 70.3
LEGEND
Cap. — Capacity of Refrigeration Tons (kW)
kW — Compressor Motor Input Power of Rated Voltage
LCWT — Leaving Chilled Water Temperature
51
Performance data (cont)
30GXN,R080-281,301,325,350, 30GXN,R283,303,328,353-528,
COOLER PRESSURE DROP — ENGLISH COOLER PRESSURE DROP — ENGLISH
53
8 8 3
-1 22 26
5, 9-
37
8 5
11 12 22 24 70, 78
100.0 ,3 -4
353 418 450 28
3 8, 3, 5 0, 0-5
30 32 39 41 39 50
100.0
PRESSURE DROP (FT WG)
350
2 5,
,3
93 114 4 8 01
0 17 20 1,
3
0- 6- 0- 8-
08 10 16 17 28
3
28
10.0
1.0
100 1000 10000
COOLER FLOW (GPM)
1.0
100 1000 10000
COOLER FLOW (GPM)
30GXN,R080-281,301,325,350, 30GXN,R283,303,328,353-528,
COOLER PRESSURE DROP — SI COOLER PRESSURE DROP — SI
3 8 8 8 73
-15 78-20 25-22 49-26 ,3
118 125 2 2 70
COOLER PRESSURE DROP (kpa)
1 3 78
1000 ,
53 8 0-4 8
3 8 , 3 3, 41 5 0,45 -52
30 32 39 41 39 500
1000
COOLER PRESSURE DROP (kpa)
0
3 4 4 , 35
-09 06-11 60-
17 25
080 1 1 1, 3
100 , 30
281
3
28
100
10
10 100
COOLER FLOW (1/SEC)
10
10 100 1000
52
Electrical data
REDUCED AMBIENT 115 F DATA
UNIT VOLTAGE POWER STANDARD CONDENSER FAN CONTROL CIRCUIT
UNIT
V-Hz Supplied SUPPLY # Power Supply ICF Rec Fuse Size V-Hz
30GXN,R MCA MOCP MCA and MOCP
(3 Ph) Min Max QTY. REQD Conductors XL WD XL WD (Single Ph)
208/230-60 187 253 1 3 356.5 500 † 527.9 † 400 115-60 30
230-60 207 253 1 3 324.5 450 † 515.1 † 400 115-60 30
080 460-60 414 506 1 3 160.9 225 652.6 255.6 200 200 115-60 30
575-60 518 633 1 3 129.0 175 542.4 205.4 150 150 115-60 30
380-60 342 418 1 3 195.6 250 729.3 291.3 225 225 230-60 15
208/230-60 187 253 1 3 353.7 500 † 534.5 † 400 115-60 30
230-60 207 253 1 3 324.4 450 † 522.9 † 400 115-60 30
083 460-60 414 506 1 3 160.1 225 655.8 258.8 200 200 115-60 30
575-60 518 633 1 3 128.0 175 544.6 207.6 150 150 115-60 30
380-60 342 418 1 3 193.7 250 732.7 294.7 225 225 230-60 15
208/230-60 187 253 1 6 406.1 600 † 593.9 † 500 115-60 30
230-60 207 253 1 3 369.3 500 † 581.1 † 450 115-60 30
090 460-60 414 506 1 3 183.2 250 757.6 288.6 225 225 115-60 30
575-60 518 633 1 3 148.1 200 606.4 231.4 175 175 115-60 30
380-60 342 418 1 3 222.9 300 845.3 327.3 250 250 230-60 15
208/230-60 187 253 1 6 389.1 500 † 600.5 † 450 115-60 30
230-60 207 253 1 3 356.4 500 † 588.9 † 400 115-60 30
093 460-60 414 506 1 3 176.1 250 760.8 291.8 200 200 115-60 30
575-60 518 633 1 3 140.8 200 608.6 233.6 175 175 115-60 30
380-60 342 418 1 3 213.0 300 848.7 330.7 250 250 230-60 15
208/230-60 187 253 1 6 482.0 700 † 693.9 † 600 115-60 30
230-60 207 253 1 6 438.9 600 † 681.1 † 500 115-60 30
106 460-60 414 506 1 3 217.3 300 899.4 338.4 250 250 115-60 30
575-60 518 633 1 3 174.4 250 719.8 270.8 200 200 115-60 30
380-60 342 418 1 3 264.9 350 1002.5 382.5 300 300 230-60 15
208/230-60 187 253 1 6 445.8 600 † 705.2 † 500 115-60 30
230-60 207 253 1 6 407.7 500 † 691.7 † 500 115-60 30
108 460-60 414 506 1 3 201.7 250 904.7 343.7 250 250 115-60 30
575-60 518 633 1 3 161.4 225 723.8 274.8 200 200 115-60 30
380-60 342 418 1 3 244.1 350 1008.5 388.5 300 300 230-60 15
208/230-60 187 253 1 6 507.7 700 † 719.6 † 600 115-60 30
230-60 207 253 1 6 462.0 600 † 704.2 † 600 115-60 30
114 460-60 414 506 1 3 228.9 300 911.0 350.0 300 300 115-60 30
575-60 518 633 1 3 183.4 250 728.8 279.8 225 225 115-60 30
380-60 342 418 1 3 279.0 400 1016.6 396.6 350 350 230-60 15
208/230-60 187 253 1 6 486.0 600 † 745.5 † 600 115-60 30
230-60 207 253 1 6 445.6 600 † 729.6 † 500 115-60 30
118 460-60 414 506 1 3 219.9 300 922.9 361.9 250 250 115-60 30
575-60 518 633 1 3 175.9 250 738.3 289.3 200 200 115-60 30
380-60 342 418 1 3 266.1 350 1030.5 410.5 300 300 230-60 15
208/230-60 187 253 1 6 576.6 800 † 814.6 † 700 115-60 30
230-60 207 253 1 6 525.4 700 † 795.4 † 600 115-60 30
125 460-60 414 506 1 3 260.6 350 1025.1 396.1 300 300 115-60 30
575-60 518 633 1 3 207.8 300 820.3 317.3 250 250 115-60 30
380-60 342 418 1 3 316.1 450 1145.6 449.6 400 400 230-60 15
208/230-60 187 253 1 6 527.7 700 † 808.5 † 600 115-60 30
230-60 207 253 1 6 483.3 700 † 792.6 † 600 115-60 30
128 460-60 414 506 1 3 238.8 300 1022.9 393.9 300 300 115-60 30
575-60 518 633 1 3 191.0 250 818.3 315.3 225 225 115-60 30
380-60 342 418 1 3 288.9 400 1141.5 445.5 350 350 230-60 15
208/230-60 187 253 1 6 567.3 800 † 848.0 † 700 115-60 30
138, 230-60 207 253 1 6 519.1 700 † 828.4 † 600 115-60 30
283B, 303B, 460-60 414 506 1 3 256.7 350 1040.8 411.8 300 300 115-60 30
373B 575-60 518 633 1 3 205.3 250 832.6 329.6 250 250 115-60 30
380-60 342 418 1 3 310.6 400 1163.2 467.2 350 350 230-60 15
208/230-60 187 253 2 9 453.7/259* 700/450* † 818.2/518.0* † 600/350* 115-60 30
153, 230-60 207 253 1 6 604.9 800 † 1005.4 † 700 115-60 30
283A, 328B, 460-60 414 506 1 3 298.9 400 1302.6 498.6 350 350 115-60 30
393B, 418B 575-60 518 633 1 3 239.1 300 1042.1 399.1 300 300 115-60 30
380-60 342 418 1 3 361.6 500 1453.4 564.4 450 450 230-60 15
208/230-60 187 253 2 9 468.7/300* 700/500* † 833.2/581.0* † 600/400* 115-60 30
163, 230-60 207 253 2 9 432.7/272* 700/450* † 833.2/581.0* † 600/350* 115-60 30
303A 460-60 414 506 1 3 320.8 450 1324.5 520.5 400 400 115-60 30
575-60 518 633 1 3 256.6 350 1059.6 416.6 300 300 115-60 30
380-60 342 418 1 6 388.1 500 1479.9 590.9 450 450 230-60 15
208/230-60 187 253 2 9 468.7/378* 700/600* † 833.2/743.0* † 600/500* 115-60 30
178, 230-60 207 253 2 9 432.7/343* 700/600* † 833.2/743.0* † 600/450* 115-60 30
328A, 353A, 460-60 414 506 1 3 349.1 450 1352.8 548.8 400 400* 115-60 30
353B 575-60 518 633 1 3 279.2 350 1082.2 439.2 350 350 115-60 30
380-60 342 418 1 6 422.4 500 1514.2 625.2 500 500 230-60 15
208/230-60 187 253 2 9 541/350* 700/500* † 821.2/609.0* † 600/400* 115-60 30
230-60 207 253 2 9 489/325* 700/500* † 798.4/609.0* † 450 115-60 30
208 460-60 414 506 1 6 383 450 1167.1 538.1 450 450 115-60 30
575-60 518 633 1 3 306 350 932.8 429.8 350 350 115-60 30
380-60 342 418 1 6 467 500 1319.4 623.4 500 500 230-60 15
208/230-60 187 253 2 9 619/350* 800/500* † 983.2/609.0* † 700/400* 115-60 30
228, 230-60 207 253 2 9 560/325* 800/500 † 960.4/609.0* † 500 115-60 30
453A, 453B, 460-60 414 506 1 6 418 500* 1422.1 618.1 500 500 115-60 30
478B 575-60 518 633 1 3 334 400 1136.8 493.8 400 400 115-60 30
380-60 342 418 1 6 510 600 1601.4 712.4 600 600 230-60 15
208/230-60 187 253 2 12 681/404* 800/600* † 1045.8/685.0* † 700/450* 115-60 30
253, 230-60 207 253 2 9 617/350* 800/500* † 1017.0/659.0* † 600 115-60 30
373A, 393A, 460-60 414 506 1 6 468 600 1471.9 667.9 600 600 115-60 30
478A, 503A, 503B 575-60 518 633 1 3 374 450 1176.6 533.6 450 450 115-60 30
380-60 342 418 1 6 570 700 1662.1 773.1 700 700 230-60 15
208/230-60 187 253 2 12 681/482* 800/700* † 1045.8/847.0* † 700/600* 115-60 30
268, 230-60 207 253 2 12 617/447* 800/700* † 1017.0/847.0* † 600 115-60 30
418A, 528A, 460-60 414 506 1 6 496 600 1500.2 696.2 600 600 115-60 30
528B 575-60 518 633 1 6 396 500 1199.2 556.2 450 450 115-60 30
380-60 342 418 1 6 605 700 1696.4 807.4 700 700 230-60 15
53
Electrical data (cont)
REDUCED AMBIENT 115 F DATA (cont)
UNIT VOLTAGE HIGH-STATIC CONDENSER FAN CONTROL CIRCUIT
POWER
UNIT Supplied # Power ICF Rec Fuse Size
V-Hz SUPPLY V-Hz MCA and
30GXN,R Supply MCA MOCP
(3 Ph) Min Max QTY. REQD XL WD XL WD (Single Ph) MOCP
Conductors
208/230-60 187 253 1 6 384.8 500 † 556.2 † 450 115-60 30
230-60 207 253 1 3 352.8 450 † 543.4 † 400 115-60 30
080 460-60 414 506 1 3 172.5 225 664.2 267.2 200 200 115-60 30
575-60 518 633 1 3 138.9 175 552.3 215.3 175 175 115-60 30
380-60 342 418 1 3 208.8 250 742.4 304.4 250 250 230-60 15
208/230-60 187 253 1 6 396.2 500 † 577.0 † 450 115-60 30
230-60 207 253 1 3 366.9 500 † 565.4 † 450 115-60 30
083 460-60 414 506 1 3 177.5 225 673.2 276.2 200 200 115-60 30
575-60 518 633 1 3 142.9 175 559.5 222.5 175 175 115-60 30
380-60 342 418 1 3 213.4 250 752.4 314.4 250 250 230-60 15
208/230-60 187 253 1 6 434.5 600 † 622.2 † 500 115-60 30
230-60 207 253 1 6 397.7 500 † 609.4 † 450 115-60 30
090 460-60 414 506 1 3 194.8 250 769.2 300.2 225 225 115-60 30
575-60 518 633 1 3 158.1 225 616.3 241.3 200 200 115-60 30
380-60 342 418 1 3 236.0 300 858.4 340.4 300 300 230-60 15
208/230-60 187 253 1 6 431.6 600 † 643.0 † 500 115-60 30
230-60 207 253 1 6 398.9 500 † 631.4 † 450 115-60 30
093 460-60 414 506 1 3 193.5 250 778.2 309.2 225 225 115-60 30
575-60 518 633 1 3 155.7 200 623.5 248.5 175 175 115-60 30
380-60 342 418 1 3 232.7 300 868.4 350.4 300 300 230-60 15
208/230-60 187 253 1 6 524.5 700 † 736.4 † 600 115-60 30
230-60 207 253 1 6 481.4 700 † 723.6 † 600 115-60 30
106 460-60 414 506 1 3 234.7 300 916.8 355.8 300 300 115-60 30
575-60 518 633 1 3 189.3 250 734.7 285.7 225 250 115-60 30
380-60 342 418 1 3 284.6 400 1022.2 402.2 350 350 230-60 15
208/230-60 187 253 1 6 488.3 600 † 747.7 † 600 115-60 30
230-60 207 253 1 6 450.2 600 † 734.2 † 500 115-60 30
108 460-60 414 506 1 3 263.8 350 1028.2 408.2 300 300 230-60 15
575-60 518 633 1 3 459.7 600 † 691.4 † 600 230-50 15
380-60 342 418 1 3 277.1 350 1084.2 427.2 350 350 230-50 15
208/230-60 187 253 1 6 550.2 700 † 762.1 † 700 115-60 30
230-60 207 253 1 6 504.5 700 † 746.7 † 600 115-60 30
114 460-60 414 506 1 3 246.3 350 928.4 367.4 300 300 115-60 30
575-60 518 633 1 3 198.3 250 743.7 294.7 225 225 115-60 30
380-60 342 418 1 3 298.7 400 1036.3 416.3 350 350 230-60 15
208/230-60 187 253 1 6 542.7 700 † 802.1 † 600 115-60 30
230-60 207 253 1 6 502.2 600 † 786.2 † 600 115-60 30
118 460-60 414 506 1 3 243.1 300 946.1 385.1 300 300 115-60 30
575-60 518 633 1 3 195.8 250 758.2 309.2 225 225 115-60 30
380-60 342 418 1 3 292.4 400 1056.8 436.8 350 350 230-60 15
208/230-60 187 253 1 6 619.1 800 † 857.1 † 700 115-60 30
230-60 207 253 1 6 567.9 800 † 837.9 † 700 115-60 30
125 460-60 414 506 1 3 278.0 400 1042.5 413.5 350 350 115-60 30
575-60 518 633 1 3 222.7 300 835.2 332.2 250 250 115-60 30
380-60 342 418 1 3 335.8 450 1165.3 469.3 400 400 230-60 15
208/230-60 187 253 1 6 584.4 800 † 865.1 † 700 115-60 30
230-60 207 253 1 6 540.0 700 † 849.2 † 600 115-60 30
128 460-60 414 506 1 3 262.0 350 1046.1 417.1 300 300 115-60 30
575-60 518 633 1 3 210.9 250 838.2 335.2 250 250 115-60 30
380-60 342 418 1 3 315.2 400 1167.8 471.8 350 350 230-60 15
208/230-60 187 253 1 6 623.9 800 † 904.7 † 700 115-60 30
138, 230-60 207 253 1 6 575.8 700 † 885.0 † 700 115-60 30
283B, 303B, 460-60 414 506 1 3 279.9 350 1064.0 435.0 350 350 115-60 30
373B 575-60 518 633 1 3 225.2 300 852.5 349.5 250 250 115-60 30
380-60 342 418 1 3 336.9 450 1189.5 493.5 400 400 230-60 15
208/230-60 187 253 2 9 524.5/259* 800/450* † 889.0/518.0* † 700/350* 115-60 30
153, 230-60 207 253 1 6 675.7 800 † 1076.2 † 800 115-60 30
283A, 328B, 460-60 414 506 1 3 327.9 450 1331.6 527.6 400 400 115-60 30
393B, 418B 575-60 518 633 1 3 263.9 350 1066.9 423.9 300 300 115-60 30
380-60 342 418 1 6 394.5 500 1486.3 597.3 450 450 230-60 15
208/230-60 187 253 2 9 553.7/300* 800/500* † 918.2/581.0* † 700/400* 115-60 30
163, 230-60 207 253 2 9 517.7/272* 700/450* † 918.2/581.0* † 600/350* 115-60 30
303A 460-60 414 506 1 3 355.6 450 1359.3 555.3 400 400 115-60 30
575-60 518 633 1 3 286.4 350 1089.4 446.4 350 350 115-60 30
380-60 342 418 1 6 427.5 500 1519.3 630.3 500 500 230-60 15
208/230-60 187 253 2 9 553.7/378* 800/600* † 918.2/743.0* † 700/500* 115-60 30
178, 230-60 207 253 2 9 517.7/343* 700/600* † 918.2/743.0* † 600/450* 115-60 30
328A, 353A, 460-60 414 506 1 6 383.9 500 1387.6 583.6 450 450 115-60 30
353B 575-60 518 633 1 3 309.0 400 1112.0 469.0 350 350 115-60 30
380-60 342 418 1 6 461.8 600 1553.6 664.6 600 600 230-60 15
208/230-60 187 253 2 12 541/463* 700/600* † 821.2/722.4* † 600/500* 115-60 30
230-60 207 253 2 12 489/443* 700/600* † 798.4/705.2* † 500 115-60 30
208 460-60 414 506 1 6 426 500 1210.5 581.5 500 500 115-60 30
575-60 518 633 1 3 343 400 970.6 467.6 400 400 115-60 30
380-60 342 418 1 6 513 600 1365.4 669.4 600 600 230-60 15
208/230-60 187 253 2 12 619/463* 800/600* † 983.2/722.4* † 700/500* 115-60 30
228, 230-60 207 253 2 12 560/443* 800/600* † 960.4/705.2* † 500 115-60 30
453A, 453B, 460-60 414 506 1 6 462 500 1465.5 661.5 500 500 115-60 30
478B 575-60 518 633 1 3 372 450 1174.6 531.6 400 400 115-60 30
380-60 342 418 1 6 556 700 164*7.4 758.4 600 600 230-60 15
253, 208/230-60 187 253 2 12 681/534* 800/700* † 1045.8/814.6* † 700/600* 115-60 30
373A, 393A, 230-60 207 253 2 12 617/509* 800/700* † 1017.0/798.4* † 600 115-60 30
478A, 503A, 460-60 414 506 1 6 518 600 1521.5 717.5 600 600 115-60 30
503B 575-60 518 633 1 6 417 500 1219.8 576.8 450 450 115-60 30
380-60 342 418 1 6 623 700 1714.7 825.7 700 700 230-60 15
208/230-60 187 253 2 12 681/612* 800/800* † 1045.8/976.6* † 700/700* 115-60 30
268, 230-60 207 253 2 12 617/576* 800/800* † 1017.0/976.6* † 600 115-60 30
418A, 528A, 460-60 414 506 1 6 546 600 1549.8 745.8 600 600 115-60 30
528B 575-60 518 633 1 6 439 500 1242.4 599.4 500 500 115-60 30
380-60 342 418 1 6 657 800 1748.9 859.9 700 700 230-60 15
54
HIGH AMBIENT 125 F DATA — STANDARD CONDENSER FAN
UNIT VOLTAGE POWER STANDARD CONDENSER FAN CONTROL CIRCUIT
UNIT
V-Hz Supplied SUPPLY # Power Supply ICF Rec Fuse Size V-Hz MCA and
30GXN,R MCA MOCP
(3 Ph) Min Max QTY. REQ’D Conductors XL WD XL WD (Single Ph) MOCP**
208/230-60 187 253 1 3 374.0 500 † 534.3 † 450 115-60 30
230-60 207 253 1 3 339.2 450 † 520.2 † 400 115-60 30
080 460-60 414 506 1 3 168.2 225 655.2 258.2 200 200 115-60 30
575-60 518 633 1 3 136.3 175 544.9 207.9 175 175 115-60 30
380-60 342 418 1 3 206.0 250 733.2 295.2 250 250 230-60 15
208/230-60 187 253 1 3 357.6 500 † 536.8 † 400 115-60 30
230-60 207 253 1 3 327.9 450 † 524.9 † 400 115-60 30
083 460-60 414 506 1 3 161.8 225 656.8 259.8 200 200 115-60 30
575-60 518 633 1 3 129.4 175 545.4 208.4 150 150 115-60 30
380-60 342 418 1 3 195.8 250 733.9 295.9 225 225 230-60 15
208/230-60 187 253 1 6 418.9 600 † 600.3 † 500 115-60 30
230-60 207 253 1 6 384.1 500 † 586.2 † 450 115-60 30
090 460-60 414 506 1 3 190.7 250 760.2 291.2 225 225 115-60 30
575-60 518 633 1 3 153.9 225 608.9 233.9 175 175 115-60 30
380-60 342 418 1 3 233.3 300 849.2 331.2 300 300 230-60 15
208/230-60 187 253 1 6 400.2 500 † 602.8 † 450 115-60 30
230-60 207 253 1 3 366.4 500 † 590.9 † 450 115-60 30
093 460-60 414 506 1 3 181.1 250 761.8 292.8 225 225 115-60 30
575-60 518 633 1 3 144.8 200 609.4 234.4 175 175 115-60 30
380-60 342 418 1 3 219.1 300 849.9 331.9 250 250 230-60 15
208/230-60 187 253 1 6 490.1 700 † 700.3 † 600 115-60 30
230-60 207 253 1 6 447.1 600 † 686.2 † 600 115-60 30
106 460-60 414 506 1 3 221.5 300 902.0 341.0 250 250 115-60 30
575-60 518 633 1 3 178.6 250 722.3 273.3 225 225 115-60 30
380-60 342 418 1 3 270.3 400 1006.4 386.4 350 350 230-60 15
208/230-60 187 253 1 6 484.6 700 † 719.1 † 600 115-60 30
230-60 207 253 1 6 442.8 600 † 704.3 † 500 115-60 30
108 460-60 414 506 1 3 219.3 300 911.0 350.0 250 250 115-60 30
575-60 518 633 1 3 175.4 250 728.8 279.8 200 200 115-60 30
380-60 342 418 1 3 265.3 350 1016.1 396.1 300 300 230-60 15
208/230-60 187 253 1 6 518.3 700 † 728.5 † 600 115-60 30
230-60 207 253 1 6 472.8 600 † 711.9 † 600 115-60 30
114 460-60 414 506 1 3 234.3 300 914.8 353.8 300 300 115-60 30
575-60 518 633 1 3 188.9 250 732.6 283.6 225 225 115-60 30
380-60 342 418 1 3 285.7 400 1021.8 401.8 350 350 230-60 15
208/230-60 187 253 1 6 527.7 700 † 762.2 † 600 115-60 30
230-60 207 253 1 6 483.3 600 † 744.8 † 600 115-60 30
118 460-60 414 506 1 3 238.8 300 930.5 369.5 300 300 115-60 30
575-60 518 633 1 3 191.0 250 744.4 295.4 225 225 115-60 30
380-60 342 418 1 3 288.9 400 1039.7 419.7 350 350 230-60 15
208/230-60 187 253 1 6 579.2 800 † 817.2 † 700 115-60 30
230-60 207 253 1 6 527.9 700 † 797.9 † 600 115-60 30
125 460-60 414 506 1 3 261.8 350 1026.3 397.3 300 300 115-60 30
575-60 518 633 1 3 209.1 300 821.6 318.6 250 250 115-60 30
380-60 342 418 1 3 317.4 450 1146.9 450.9 400 400 230-60 15
208/230-60 187 253 1 6 587.9 800 † 825.2 † 700 115-60 30
230-60 207 253 1 6 537.8 700 † 807.8 † 600 115-60 30
128 460-60 414 506 1 3 266.0 350 1030.5 401.5 300 300 115-60 30
575-60 518 633 1 3 212.8 300 824.4 321.4 250 250 115-60 30
380-60 342 418 1 3 321.9 450 1150.7 454.7 400 400 230-60 15
208/230-60 187 253 1 6 615.1 800 † 853.1 † 700 115-60 30
230-60 207 253 1 6 561.3 800 † 831.3 † 700 115-60 30
135 460-60 414 506 1 3 278.5 400 1043.0 414.0 350 350 115-60 30
575-60 518 633 1 3 221.9 300 834.4 331.4 250 250 115-60 30
380-60 342 418 1 3 336.6 450 1166.1 470.1 400 400 230-60 15
208/230-60 187 253 1 6 630.6 800 † 867.9 † 700 115-60 30
230-60 207 253 1 6 576.4 800 † 846.4 † 700 115-60 30
138 460-60 414 506 1 3 285.3 400 1049.8 420.8 350 350 115-60 30
575-60 518 633 1 3 228.2 300 839.8 336.8 300 300 115-60 30
380-60 342 418 1 3 345.2 450 1174.1 478.1 400 400 230-60 15
208/230-60 187 253 2 9 343.9/418.4* 500/700* † 578.2/743.0* † 450/600* 115-60 30
230-60 207 253 1 6 643.6 800 † 1008.4 † 800 115-60 30
150 460-60 414 506 1 3 318.9 450 1034.8 500.8 400 400 115-60 30
575-60 518 633 1 3 254.6 350 1043.9 400.9 300 300 115-60 30
380-60 342 418 1 6 386.6 500 1456.3 567.3 450 450 230-60 15
208/230-60 187 253 2 9 493.2/283* 800/500* † 818.2/518.0* † 600/350* 115-60 30
230-60 207 253 1 6 658.6 800 † 1023.4 † 800 115-60 30
153 460-60 414 506 1 3 325.7 450 1311.6 507.6 400 400 115-60 30
575-60 518 633 1 3 260.6 350 1049.3 406.3 300 300 115-60 30
380-60 342 418 1 6 394.1 500 1464.3 575.3 450 450 230-60 15
208/230-60 187 253 2 12 403.2/418.4* 600/700* † 641.2/743.0* † 500/600* 115-60 30
230-60 207 253 1 6 687.2 800 † 1052.0 † 800 115-60 30
160 460-60 414 506 1 3 340.7 450 1326.6 522.6 400 400 115-60 30
575-60 518 633 1 3 271.3 350 1060.6 417.6 350 350 115-60 30
380-60 342 418 1 6 412.2 500 1481.9 592.9 500 500 230-60 15
208/230-60 187 253 2 9 508.2/344* 800/600* † 833.2/581.0* † 600/450* 115-60 30
230-60 207 253 2 9 468.5/311* 700/500* † 833.2/581.0* † 600/400* 115-60 30
163 460-60 414 506 1 3 354.3 500 1340.2 536.2 400 400 115-60 30
575-60 518 633 1 3 283.5 400 1072.2 429.2 350 350 115-60 30
380-60 342 418 1 6 428.8 600 1498.9 609.9 500 500 230-60 15
See Legend and Notes on page 56.
55
Electrical data (cont)
HIGH AMBIENT 125 F DATA — STANDARD CONDENSER FAN (cont)
UNIT VOLTAGE POWER STANDARD CONDENSER FAN CONTROL CIRCUIT
UNIT
V-Hz Supplied SUPPLY # Power Supply ICF Rec Fuse Size V-Hz MCA and
30GXN,R MCA MOCP
(3 Ph) Min Max QTY. REQ’D Conductors XL WD XL WD (Single Ph) MOCP**
208/230-60 187 253 2 12 493.6/418.4* 800/700* † 818.2/743.0* † 600/600* 115-60 30
230-60 207 253 2 9 453.4/378.3* 700/600* † 818.2/743.0* † 600/500* 115-60 30
174 460-60 414 506 1 3 374.4 500 1360.3 556.3 450 450 115-60 30
575-60 518 633 1 3 298.6 400 1087.8 444.8 350 350 115-60 30
380-60 342 418 1 6 453.8 600 1523.6 634.6 500 500 230-60 15
208/230-60 187 253 2 12 508.2/418* 800/700* † 833.2/743.0* † 600/600* 115-60 30
230-60 207 253 2 9 468.5/378* 700/600* † 833.2/743.0* † 600/500* 115-60 30
178 460-60 414 506 1 3 381.2 500 1367.1 563.1 450 450 115-60 30
575-60 518 633 1 3 305.0 400 1093.7 450.7 350 350 115-60 30
380-60 342 418 1 6 461.3 600 1531.5 642.5 600 600 230-60 15
208/230-60 187 253 2 12 580/408* 800/600* † 904.6/646.0* † 700/450* 115-60 30 (50)
230-60 207 253 2 9 524/376* 800/600* † 889.2/646.0* † 500 115-60 30 (50)
204 460-60 414 506 1 6 419 500 1404.5 600.5 500 500 115-60 30 (50)
575-60 518 633 1 3 332 450 1121.5 478.5 400 400 115-60 30 (50)
380-60 342 418 1 6 508 600 1577.4 688.4 600 600 230-60 15 (25)
208/230-60 187 253 2 12 619/374* 800/600* † 855.9/609.0* † 700/400* 115-60 30
230-60 207 253 2 9 560/348* 800/600* † 829.8/609.0* † 500 115-60 30
208 460-60 414 506 1 6 427 500 1191.8 562.8 500 500 115-60 30
575-60 518 633 1 3 341 400 952.6 449.6 400 400 115-60 30
380-60 342 418 1 6 520 600 1349.3 653.3 600 600 230-60 15
208/230-60 187 253 2 12 609/483* 800/800* † 934.1/808.0* † 700/600* 115-60 30 (50)
230-60 207 253 2 12 550/443* 800/700* † 914.8/808.0* † 500 115-60 30 (50)
225 460-60 414 506 1 6 458 600 1444.2 640.2 500 500 115-60 30 (50)
575-60 518 633 1 3 366 450 1154.9 511.9 400 400 115-60 30 (50)
380-60 342 418 1 6 559 700 1628.8 739.8 700 700 230-60 15 (25)
208/230-60 187 253 2 12 693/374* 1000/600* † 1017.9/609.0* † 800/350* 115-60 30
230-60 207 253 2 12 627/296* 800/500* † 991.8/557.0* † 500 115-60 30
228 460-60 414 506 1 6 461 600 1446.8 642.8 500 500 115-60 30
575-60 518 633 1 3 368 450 1156.6 513.6 400 400 115-60 30
380-60 342 418 1 6 561 700 1631.3 742.3 700 700 230-60 15
208/230-60 187 253 2 12 753/421* 1000/600* † 1077.7/659.0* † 800/500* 115-60 30 (50)
230-60 207 253 2 12 681/389* 800/600* † 1045.6/659.0* † 600 115-60 30 (50)
249 460-60 414 506 1 6 503 600 1489.1 685.1 600 600 115-60 30 (50)
575-60 518 633 1 6 400 500 1189.4 546.4 450 450 115-60 30 (50)
380-60 342 418 1 6 612 700 1681.8 792.8 700 700 230-60 15 (25)
208/230-60 187 253 2 12 752/448* 1000/700* † 1077.4/685.0* † 800/500* 115-60 30
230-60 207 253 2 12 681/389* 800/600* † 1045.6/659.0* † 600 115-60 30
253 460-60 414 506 1 6 516 600 1501.9 697.9 600 600 115-60 30
575-60 518 633 1 6 412 500 1200.6 557.6 450 450 115-60 30
380-60 342 418 1 6 628 800 1698.4 809.4 700 700 230-60 15
208/230-60 187 253 2 12 753/496* 1000/800* † 1077.7/821.0* † 800/600* 115-60 30 (50)
230-60 207 253 2 12 681/456* 800/700* † 1045.6/821.0* † 600 115-60 30 (50)
264 460-60 414 506 1 6 530 600 1516.0 712.0 600 600 115-60 30 (50)
575-60 518 633 1 6 422 500 1211.2 568.2 500 500 115-60 30 (50)
380-60 342 418 1 6 645 800 1715.2 826.2 700 700 230-60 15 (25)
208/230-60 187 253 2 12 752/522* 1000/800* † 1077.4/847.0* † 800/600* 115-60 30
230-60 207 253 2 12 681/482* 800/700* † 1045.6/847.0* † 600 115-60 30
268 460-60 414 506 1 6 543 600 1528.8 724.8 600 600 115-60 30
575-60 518 633 1 6 433 500 1222.1 579.1 500 500 115-60 30
380-60 342 418 1 6 661 800 1731.0 842.0 800 800 230-60 15
460-60 414 506 1 6 563 700 1549.3 745.3 700 700 115-60 30 (50)
281 575-60 518 633 1 6 450 500 1239.2 596.2 500 500 115-50 30 (50)
380-60 342 418 1 6 689 800 1758.7 869.7 800 800 230-60 15 (25)
460-60 414 506 1 6 597 700 1582.7 778.7 700 700 115-60 30 (50)
301 575-60 518 633 1 6 476 500 1264.8 621.8 600 600 115-60 30 (50)
380-60 342 418 2 9 354/420* 500/600* 1423.4/1489.3* 534.4/600.3* 400/500* 400/500* 230-60 15 (25)
460-60 414 506 1 6 640 700 1626.3 822.3 700 700 115-60 30 (50)
325 575-60 518 633 1 6 509 600 1298.2 655.2 600 600 115-50 30 (50)
380-60 342 418 2 9 379/445* 500/600* 1449.0/1514.9* 560.0/625.9* 450/500* 450/500* 230-60 15 (25)
460-60 414 506 1 6 694 800 1680.1 876.1 800 800 115-60 30 (50)
350 575-60 518 633 1 6 553 600 1341.8 698.8 600 600 115-60 30 (50)
380-60 342 418 2 12 413/479* 500/600* 1482.4/1548.3* 593.4/659.3* 500/600* 500/600* 230-60 15 (25)
56
HIGH AMBIENT 125 F DATA — DUPLEX UNITS — STANDARD CONDENSER FAN
UNIT VOLTAGE POWER STANDARD CONDENSER FAN CONTROL CIRCUIT
UNIT
V-Hz Supplied SUPPLY # Power Supply ICF Rec Fuse Size V-Hz MCA and
30GXN,R MCA MOCP
(3 Ph) Min Max QTY. REQ’D Conductors XL WD XL WD (Single Ph) MOCP**
208/230-60 187 253 2 12 403.2/418.4* 600/700* † 641.2/743.0* † 500/600* 115-60 30
230-60 207 253 1 6 687.2 800 † 1052.0 † 800 115-60 30
415B 460-60 414 506 1 3 340.7 450 1326.6 522.6 400 400 115-60 30
575-60 518 633 1 3 271.3 350 1060.6 417.6 350 350 115-60 30
380-60 342 418 1 6 412.2 500 1481.9 592.9 500 500 230-60 15
208/230-60 187 253 1 6 630.6 800 † 867.9 † 700 115-60 30
283B 230-60 207 253 1 6 576.4 800 † 846.4 † 700 115-60 30
303B 460-60 414 506 1 3 285.3 400 1049.8 420.8 350 350 115-60 30
373B 575-60 518 633 1 3 228.2 300 839.8 336.8 300 300 115-60 30
390B 380-60 342 418 1 3 345.2 450 1174.1 478.1 400 400 230-60 15
283A 208/230-60 187 253 2 9 493.2/283* 800/500* † 818.2/518.0* † 600/350* 115-60 30
328B 230-60 207 253 1 6 658.6 800 † 1023.4 † 800 115-60 30
393B 460-60 414 506 1 3 325.7 450 1311.6 507.6 400 400 115-60 30
418B 575-60 518 633 1 3 260.6 350 1049.3 406.3 300 300 115-60 30
380-60 342 418 1 6 394.1 500 1464.3 575.3 450 450 230-60 15
208/230-60 187 253 2 9 508.2/344* 800/600* † 833.2/581.0* † 600/450* 115-60 30
230-60 207 253 2 9 468.5/311* 700/500* † 833.2/581.0* † 600/400* 115-60 30
303A 460-60 414 506 1 3 354.3 500 1340.2 536.2 400 400 115-60 30
575-60 518 633 1 3 283.5 400 1072.2 429.2 350 350 115-60 30
380-60 342 418 1 6 428.8 600 1498.9 609.9 500 500 230-60 15
208/230-60 187 253 2 12 508.2/418* 800/700* † 833.2/743.0* † 600/600* 115-60 30
328A 230-60 207 253 2 9 468.5/378* 700/600* † 833.2/743.0* † 600/500* 115-60 30
353A 460-60 414 506 1 3 381.2 500 1367.1 563.1 450 450 115-60 30
353B 575-60 518 633 1 3 305.0 400 1093.7 450.7 350 350 115-60 30
380-60 342 418 1 6 461.3 600 1531.5 642.5 600 600 230-60 15
208/230-60 187 253 2 9 343.9/418.4* 500/700* † 578.2/743.0* † 450/600* 115-60 30
230-60 207 253 1 6 643.6 800 † 1008.4 † 800 115-60 30
370B 460-60 414 506 1 3 318.9 450 1034.8 500.8 400 400 115-60 30
575-60 518 633 1 3 254.6 350 1043.9 400.9 300 300 115-60 30
380-60 342 418 1 6 386.6 500 1456.3 567.3 450 450 230-60 15
208/230-60 187 253 2 12 609/483* 800/800* † 934.1/808.0* † 700/600* 115-60 30 (50)
370A 230-60 207 253 2 12 550/443* 800/700* † 914.8/808.0* † 500 115-60 30 (50)
450A/B 460-60 414 506 1 6 458 600 1444.2 640.2 500 500 115-60 30 (50)
475B 575-60 518 633 1 3 366 450 1154.9 511.9 400 400 115-60 30 (50)
380-60 342 418 1 6 559 700 1628.8 739.8 700 700 230-60 15 (25)
208/230-60 187 253 2 12 753/496* 1000/800* † 1077.7/821.0* † 800/600* 115-60 30 (50)
390A 230-60 207 253 2 12 681/456* 800/700* † 1045.6/821.0* † 600 115-60 30 (50)
415A 460-60 414 506 1 6 530 600 1516.0 712.0 600 600 115-60 30 (50)
525A/B 575-60 518 633 1 6 422 500 1211.2 568.2 500 500 115-60 30 (50)
380-60 342 418 1 6 645 800 1715.2 826.2 700 700 230-60 15 (25)
208/230-60 187 253 2 12 693/374* 1000/600* † 1017.9/609.0* † 800/350* 115-60 30
453A 230-60 207 253 2 12 627/296* 800/500* † 991.8/557.0* † 500 115-60 30
453B 460-60 414 506 1 6 461 600 1446.8 642.8 500 500 115-60 30
478B 575-60 518 633 1 3 368 450 1156.6 513.6 400 400 115-60 30
380-60 342 418 1 6 561 700 1631.3 742.3 700 700 230-60 15
373A 208/230-60 187 253 2 12 752/448* 100/700* † 1077.4/685.0* † 800/500* 115-60 30
393A 230-60 207 253 2 12 681/389* 800/600* † 1045.6/659.0* † 600 115-60 30
478A 460-60 414 506 1 6 516 600 1501.9 697.9 600 600 115-60 30
503A 575-60 518 633 1 6 412 500 1200.6 557.6 450 450 115-60 30
503B 380-60 342 418 1 6 628 800 1698.4 809.4 700 700 230-60 15
208/230-60 187 253 2 12 752/522* 1000/800* † 1077.4/847.0* † 800/600* 115-60 30
418A 230-60 207 253 2 12 681/482* 800/700* † 1045.6/847.0* † 600 115-60 30
528A 460-60 414 506 1 6 543 600 1528.8 724.8 600 600 115-60 30
528B 575-60 518 633 1 6 433 500 1222.1 579.1 500 500 115-60 30
380-60 342 418 1 6 661 800 1731.0 842.0 800 800 230-60 15
208/230-60 187 253 2 12 753/421* 1000/600* † 1077.7/659.0* † 800/500* 115-60 30 (50)
230-60 207 253 2 12 681/389* 800/600* † 1045.6/659.0* † 600 115-60 30 (50)
475A 460-60 414 506 1 6 503 600 1489.1 685.1 600 600 115-60 30 (50)
500A/B 575-60 518 633 1 6 400 500 1189.4 546.4 450 450 115-60 30 (50)
380-60 342 418 1 6 612 700 1681.8 792.8 700 700 230-60 15 (25)
57
Electrical data (cont)
HIGH AMBIENT 125 F DATA — HIGH-STATIC CONDENSER FAN
UNIT VOLTAGE POWER HIGH-STATIC CONDENSER FAN CONTROL CIRCUIT
UNIT
V-Hz Supplied SUPPLY # Power Supply ICF Rec Fuse Size V-Hz MCA and
30GXN,R MCA MOCP
(3 Ph) Min Max QTY. REQD Conductors XL WD XL WD (Single Ph) MOCP**
208/230-60 187 253 1 6 402.4 500 † 562.6 † 450 115-60 30
230-60 207 253 1 3 367.5 500 † 548.5 † 450 115-60 30
080 460-60 414 506 1 3 179.8 250 666.8 269.8 200 200 115-60 30
575-60 518 633 1 3 146.2 200 554.8 217.8 175 175 115-60 30
380-60 342 418 1 3 219.2 300 746.3 308.3 250 250 230-60 15
208/230-60 187 253 1 6 400.1 500 † 579.2 † 450 115-60 30
230-60 207 253 1 3 370.4 500 † 567.4 † 450 115-60 30
083 460-60 414 506 1 3 179.2 225 674.2 277.2 200 200 115-60 30
575-60 518 633 1 3 144.3 175 560.3 223.3 175 175 115-60 30
380-60 342 418 1 3 215.5 250 753.6 315.6 250 250 230-60 15
208/230-60 187 253 1 6 447.2 600 † 628.6 † 500 115-60 30
230-60 207 253 1 6 412.4 500 † 614.5 † 500 115-60 30
090 460-60 414 506 1 3 202.3 250 771.8 302.8 250 250 115-60 30
575-60 518 633 1 3 163.8 225 618.8 243.8 200 200 115-60 30
380-60 342 418 1 3 246.4 350 862.3 344.3 300 300 230-60 15
208/230-60 187 253 1 6 442.6 600 † 645.2 † 500 115-60 30
230-60 207 253 1 6 408.9 500 † 633.4 † 500 115-60 30
093 460-60 414 506 1 3 198.5 250 779.2 310.2 225 225 115-60 30
575-60 518 633 1 3 159.7 225 624.3 249.3 200 200 115-60 30
380-60 342 418 1 3 238.8 300 869.6 351.6 300 300 230-60 15
208/230-60 187 253 1 6 532.6 700 † 742.8 † 600 115-60 30
230-60 207 253 1 6 489.6 700 † 728.7 † 600 115-60 30
106 460-60 414 506 1 3 238.9 350 919.4 358.4 300 300 115-60 30
575-60 518 633 1 3 193.5 250 737.2 288.2 225 225 115-60 30
380-60 342 418 1 3 290.0 400 1026.1 406.1 350 350 230-60 15
208/230-60 187 253 1 6 527.1 700 † 761.6 † 600 115-60 30
230-60 207 253 1 6 485.3 600 † 746.8 † 600 115-60 30
108 460-60 414 506 1 3 236.7 300 928.4 367.4 300 300 115-60 30
575-60 518 633 1 3 190.3 250 743.7 294.7 225 225 115-60 30
380-60 342 418 1 3 285.0 400 1035.8 415.8 350 350 230-60 15
208/230-60 187 253 1 6 560.8 800 † 771.0 † 700 115-60 30
230-60 207 253 1 6 515.3 700 † 754.4 † 600 115-60 30
114 460-60 414 506 1 3 251.7 350 932.2 371.2 300 300 115-60 30
575-60 518 633 1 3 203.8 250 747.5 298.5 250 250 115-60 30
380-60 342 418 1 3 350.4 400 1041.5 421.5 350 350 230-60 15
208/230-60 187 253 1 6 584.3 800 † 818.9 † 700 115-60 30
230-60 207 253 1 6 539.9 700 † 801.4 † 600 115-60 30
118 460-60 414 506 1 3 262.0 350 953.7 392.7 300 300 115-60 30
575-60 518 633 1 3 210.8 250 764.2 315.2 250 250 115-60 30
380-60 342 418 1 3 315.2 400 1066.0 446.0 350 350 230-60 15
208/230-60 187 253 1 6 621.7 800 † 859.7 † 700 115-60 30
230-60 207 253 1 6 570.4 800 † 840.4 † 700 115-60 30
125 460-60 414 506 1 3 279.2 400 1043.7 414.7 350 350 115-60 30
575-60 518 633 1 3 224.0 300 836.5 333.5 250 250 115-60 30
380-60 342 418 1 3 337.1 450 1166.6 470.5 400 400 230-60 15
208/230-60 187 253 1 6 644.5 800 † 881.9 † 800 115-60 30
230-60 207 253 1 6 594.4 800 † 864.4 † 700 115-60 30
128 460-60 414 506 1 3 289.2 400 1053.7 424.7 350 350 115-60 30
575-60 518 633 1 3 232.6 300 844.2 341.2 300 300 115-60 30
380-60 342 418 1 3 348.1 450 1177.0 481.0 400 400 230-60 15
208/230-60 187 253 1 6 657.6 800 † 895.6 † 800 115-60 30
230-60 207 253 1 6 603.8 800 † 873.8 † 700 115-60 30
135 460-60 414 506 1 3 295.9 400 1060.4 431.4 350 350 115-60 30
575-60 518 633 1 3 236.8 300 849.3 346.3 300 300 115-60 30
380-60 342 418 1 3 356.3 500 1185.8 489.8 400 400 230-60 15
208/230-60 187 253 1 6 687.2 800 † 924.5 † 800 115-60 30
230-60 207 253 1 6 633.0 800 † 903.0 † 700 115-60 30
138 460-60 414 506 1 3 308.5 400 1073.0 444.0 350 350 115-60 30
575-60 518 633 1 3 248.1 300 859.7 356.7 300 300 115-60 30
380-60 342 418 1 3 371.5 500 1200.3 504.3 450 450 230-60 15
208/230-60 187 253 2 12 400.6/418* 600/700* † 634.8/743.0* † 500/600* 115-60 30
230-60 207 253 1 6 700.3 1000 † 1065.0 † 800 115-60 30
150 460-60 414 506 1 3 342.1 450 1328.0 524.0 400 400 115-60 30
575-60 518 633 1 3 274.5 350 1063.7 420.7 350 350 115-60 30
380-60 342 418 1 6 412.9 500 1482.6 593.6 500 500 230-60 15
208/230-60 187 253 2 9 564.0/283* 800/500* † 889.0/518.0* † 700/350* 115-60 30
230-60 207 253 1 6 729.5 1000 † 1094.2 † 1000 115-60 30
153 460-60 414 506 1 3 354.7 500 1340.6 536.6 400 400 115-60 30
575-60 518 633 1 3 285.4 400 1074.1 431.1 350 350 115-60 30
380-60 342 418 1 6 427.0 600 1497.1 608.1 500 500 230-60 15
208/230-60 187 253 2 12 459.8/418* 700/700* † 697.8/743.0* † 600/600* 115-60 30
230-60 207 253 1 6 743.9 1000 † 1108.6 † 1000 115-60 30
160 460-60 414 506 1 3 363.9 500 1349.8 545.8 450 450 115-60 30
575-60 518 633 1 3 291.2 400 1080.4 437.4 350 350 115-60 30
380-60 342 418 1 6 438.5 600 1508.2 619.2 500 500 230-60 15
208/230-60 187 253 2 9 593.2/344* 800/600* † 918.2/581.0* † 700/450* 115-60 30
230-60 207 253 2 9 553.5/311* 800/500* † 918.2/581.0* † 700/400* 115-60 30
163 460-60 414 506 1 6 389.1 500 1375.0 571.0 450 450 115-60 30
575-60 518 633 1 3 313.2 400 1101.9 458.9 350 350 115-60 30
380-60 342 418 1 6 468.2 600 1538.3 649.3 600 600 230-60 15
58
HIGH AMBIENT 125 F DATA — HIGH-STATIC CONDENSER FAN (cont)
UNIT VOLTAGE POWER HIGH-STATIC CONDENSER FAN CONTROL CIRCUIT
UNIT
V-Hz Supplied SUPPLY # Power Supply ICF Rec Fuse Size V-Hz MCA and
30GXN,R MCA MOCP
(3 Ph) Min Max QTY. REQD Conductors XL WD XL WD (Single Ph) MOCP**
208/230-60 187 253 2 12 564.4/418* 800/700* † 889.0/743.0* † 700/600* 115-60 30
230-60 207 253 2 9 524.3/378* 800/600* † 889.0/743.0* † 600/500* 115-60 30
174 460-60 414 506 1 6 403.4 500 1389.3 585.3 450 450 115-60 30
575-60 518 633 1 3 323.4 400 1112.6 469.6 400 400 115-60 30
380-60 342 418 1 6 486.7 600 1556.4 667.4 600 600 230-60 15
208/230-60 187 253 2 12 593.2/418* 800/700* † 918.2/743.0* † 700/600* 115-60 30
230-60 207 253 2 9 553.5/378* 800/600* † 918.2/743.0* † 700/500* 115-60 30
178 460-60 414 506 1 6 416.0 500 1401.9 597.9 500 500 115-60 30
575-60 518 633 1 3 334.7 450 1123.4 480.4 400 400 115-60 30
380-60 342 418 1 6 500.7 600 1570.9 681.9 600 600 230-60 15
208/230-60 187 253 2 12 580/489* 800/700* † 904.6/727.0* † 700/600* 115-60 30 (50)
230-60 207 253 2 12 524/457* 800/700* † 889.2/727.0* † 500 115-60 30 (50)
204 460-60 414 506 1 6 450 600 1435.5 631.5 500 500 115-60 30 (50)
575-60 518 633 1 3 359 450 1148.5 505.5 400 400 115-60 30 (50)
380-60 342 418 1 6 540 700 1610.2 721.2 600 600 230-60 15 (25)
208/230-60 187 253 2 12 619/488* 800/700* † 855.9/722.4* † 700/600* 115-60 30
230-60 207 253 2 12 560/461* 800/600* † 829.8/722.4* † 600 115-60 30
208 460-60 414 506 1 6 471 500 1235.2 606.2 600 600 115-60 30
575-60 518 633 1 3 379 450 990.4 487.4 450 450 115-60 30
380-60 342 418 1 6 566 700 1395.3 699.3 700 700 230-60 15
208/230-60 187 253 2 12 609/564* 800/800* † 934.1/889.0* † 700/600* 115-60 30 (50)
230-60 207 253 2 12 550/524* 800/800* † 914.8/889.0* † 600 115-60 30 (50)
225 460-60 414 506 1 6 489 600 1475.2 671.2 600 600 115-60 30 (50)
575-60 518 633 1 6 393 500 1181.9 538.9 450 450 115-60 30 (50)
380-60 342 418 1 6 592 700 1661.6 772.6 700 700 230-60 15 (25)
208/230-60 187 253 2 12 693/488* 1000/700* † 1017.9/722.4* † 800/600* 115-60 30
230-60 207 253 2 12 627/461* 800/600* † 991.8/722.4* † 600 115-60 30
228 460-60 414 506 1 6 504 600 1490.2 686.2 600 600 115-60 30
575-60 518 633 1 6 406 500 1194.4 551.4 450 450 115-60 30
380-60 342 418 1 6 607 700 1677.3 788.3 700 700 230-60 15
208/230-60 187 253 2 12 753/518* 1000/700* † 1077.7/756.2* † 800/600* 115-60 30 (50)
230-60 207 253 2 12 681/486* 800/700* † 1045.6/756.2* † 600 115-60 30 (50)
249 460-60 414 506 1 6 540 600 1526.3 722.3 600 600 115-60 30 (50)
575-60 518 633 1 6 433 500 1221.8 578.8 500 500 115-60 30 (50)
380-60 342 418 1 6 651 800 1721.2 832.2 700 700 230-60 15 (25)
208/230-60 187 253 2 12 752/577* 1000/800* † 1077.4/814.6* † 800/700* 115-60 30
230-60 207 253 2 12 681/545* 800/700* † 1045.6/814.6* † 700 115-60 30
253 460-60 414 506 1 6 566 700 1551.5 747.5 700 700 115-60 30
575-60 518 633 1 6 455 500 1243.8 600.8 500 500 115-60 30
380-60 342 418 1 6 681 800 1751.0 862.0 800 800 230-60 15
208/230-60 187 253 2 12 753/594* 1000/800* † 1077.7/918.2* † 800/700* 115-60 30 (50)
230-60 207 253 2 12 681/553* 800/800* † 1045.6/918.2* † 700 115-60 30 (50)
264 460-60 414 506 1 6 567 700 1553.2 749.2 700 700 115-60 30 (50)
575-60 518 633 1 6 454 500 1243.6 600.6 500 500 115-60 30 (50)
380-60 342 418 1 6 685 800 1754.6 865.6 800 800 230-60 15 (25)
208/230-60 187 253 2 12 752/652* 1000/800* † 1077.4/814.6* † 800/700* 115-60 30
230-60 207 253 2 12 681/612* 800/800* † 1045.6/814.6* † 700 115-60 30
268 460-60 414 506 1 6 593 700 1578.4 774.4 700 700 115-60 30
575-60 518 633 1 6 477 500 1265.3 622.3 600 600 115-60 30
380-60 342 418 1 6 713 800 1783.5 894.5 800 800 230-60 15
460-60 414 506 1 6 613 700 1598.9 794.9 700 700 115-60 30 (50)
281 575-60 518 633 1 6 493 600 1282.4 639.4 600 600 115-60 30 (50)
380-60 342 418 1 6 741 800 1811.2 922.2 800 800 230-60 15 (25)
460-60 414 506 1 6 646 700 1632.3 828.3 700 700 115-60 30 (50)
301 575-60 518 633 1 6 519 600 1308.0 665.0 600 600 115-60 30 (50)
380-60 342 418 2 9 354/472* 500/600* 1423.4/1541.8* 534.4/652.8* 400/600* 400/600* 230-60 15 (25)
460-60 414 506 1 6 539 600 1675.9 871.9 600 600 115-60 30 (50)
325 575-60 518 633 1 6 432 500 1341.4 698.4 500 500 115-60 30 (50)
380-60 342 418 2 9 379/498* 500/600* 1449.0/1567.4* 560.0/678.4* 450/600* 450/600* 230-60 15 (25)
460-60 414 506 1 6 744 800 1729.7 925.7 800 800 115-60 30 (50)
350 575-60 518 633 1 6 596 700 1385.0 742.0 700 700 115-60 30 (50)
380-60 342 418 2 12 413/531* 500/700* 1482.4/1600.8* 593.4/711.8* 500/600* 500/600* 230-60 15 (25)
59
Electrical data (cont)
HIGH AMBIENT 125 F DATA — DUPLEX UNITS — HIGH-STATIC CONDENSER FAN
UNIT VOLTAGE HIGH-STATIC CONDENSER FAN CONTROL CIRCUIT
POWER
UNIT
V-Hz Supplied SUPPLY # Power Supply ICF Rec Fuse Size V-Hz MCA and
30GXN,R MCA MOCP
(3 Ph) QTY. REQD Conductors (Single Ph) MOCP**
Min Max XL WD XL WD
208/230-60 187 253 1 6 657.6 800 † 895.6 † 800 115-60 30
230-60 207 253 1 6 603.8 800 † 873.8 † 700 115-60 30
390B 460-60 414 506 1 3 295.9 400 1060.4 431.4 350 350 115-60 30
575-60 518 633 1 3 236.8 300 849.3 346.3 300 300 115-60 30
380-60 342 418 1 3 356.3 500 1185.8 489.8 400 400 230-60 15
208/230-60 187 253 1 6 687.2 800 † 924.5 † 800 115-60 30
283B 230-60 207 253 1 6 633.0 800 † 903.0 † 700 115-60 30
303B 460-60 414 506 1 3 308.5 400 1073.0 444.0 350 350 115-60 30
373B 575-60 518 633 1 3 248.1 300 859.7 356.7 300 300 115-60 30
380-60 342 418 1 3 371.5 500 1200.3 504.3 450 450 230-60 15
208/230-60 187 253 2 9 564.0/283* 800/500* † 889.0/518.0* † 700/350* 115-60 30
283A 230-60 207 253 1 6 729.5 1000 † 1094.2 † 1000 115-60 30
328B 460-60 414 506 1 3 354.7 500 1340.6 536.6 400 400 115-60 30
393B
418B 575-60 518 633 1 3 285.4 400 1074.1 431.1 350 350 115-60 30
380-60 342 418 1 6 427.0 600 1497.1 608.1 500 500 230-60 15
208/230-60 187 253 2 9 593.2/344* 800/600* † 918.2/581.0* † 700/450* 115-60 30
230-60 207 253 2 9 553.5/311* 800/500* † 918.2/581.0* † 700/400* 115-60 30
303A 460-60 414 506 1 6 389.1 500 1375.0 571.0 450 450 115-60 30
575-60 518 633 1 3 313.2 400 1101.9 458.9 350 350 115-60 30
380-60 342 418 1 6 468.2 600 1538.3 649.3 600 600 230-60 15
208/230-60 187 253 2 12 593.2/418* 800/700* † 918.2/743.0* † 700/600* 115-60 30
328A 230-60 207 253 2 9 553.5/378* 800/600* † 918.2/743.0* † 700/500* 115-60 30
353A 460-60 414 506 1 6 416.0 500 1401.9 597.9 500 500 115-60 30
353B 575-60 518 633 1 3 334.7 450 1123.4 480.4 400 400 115-60 30
380-60 342 418 1 6 500.7 600 1570.9 681.9 600 600 230-60 15
208/230-60 187 253 2 12 400.6/418* 600/500* † 634.8/743.0* † 500/600* 115-60 30
230-60 207 253 1 6 700.3 1000 † 1065.0 † 800 115-60 30
370B 460-60 414 506 1 3 342.1 450 1328.0 524.0 400 400 115-60 30
575-60 518 633 1 3 274.5 350 1063.7 420.7 350 350 115-60 30
380-60 342 418 1 6 412.9 500 1482.6 593.6 500 500 230-60 15
208/230-60 187 253 2 12 609/564* 800/800* † 934.1/889.0* † 700/600* 115-60 30 (50)
370A 230-60 207 253 2 12 550/524* 800/800* † 914.8/889.0* † 600 115-60 30 (50)
415B 460-60 414 506 1 6 489 600 1475.2 671.2 600 600 115-60 30 (50)
450A/B
525A/B 575-60 518 633 1 6 393 500 1181.9 538.9 450 450 115-60 30 (50)
380-60 342 418 1 6 592 700 1661.6 772.6 700 700 230-60 15 (25)
208/230-60 187 253 2 12 753/594* 1000/800* † 1077.7/918.2* † 800/700* 115-60 30 (50)
230-60 207 253 2 12 681/553* 800/800* † 1045.6/918.2* † 700 115-60 30 (50)
390A 460-60 414 506 1 6 567 700 1553.2 749.2 700 700 115-60 30 (50)
415A
575-60 518 633 1 6 454 500 1243.6 600.6 500 500 115-60 30 (50)
380-60 342 418 1 6 685 800 1754.6 865.6 800 800 230-60 15 (25)
208/230-60 187 253 2 12 693/488* 1000/700* † 1017.9/722.4* † 800/600* 115-60 30
453A 230-60 207 253 2 12 627/461* 800/600* † 991.8/722.4* † 600 115-60 30
453B 460-60 414 506 1 6 504 600 1490.2 686.2 600 600 115-60 30
478B 575-60 518 633 1 3 406 500 1194.4 551.4 450 450 115-60 30
380-60 342 418 1 6 607 700 1677.3 788.3 700 700 230-60 15
373A 208/230-60 187 253 2 12 752/577* 1000/800* † 1077.4/814.6* † 800/700* 115-60 30
393A 230-60 207 253 2 12 681/545* 800/700* † 1045.6/814.6* † 700 115-60 30
478A 460-60 414 506 1 6 566 700 1551.5 747.5 700 700 115-60 30
503A 575-60 518 633 1 6 455 500 1243.8 600.8 500 500 115-60 30
503B 380-60 342 418 1 6 681 800 1751.0 862.0 800 800 230-60 15
208/230-60 187 253 2 12 752/652* 1000/800* † 1077.4/976.6* † 800/700* 115-60 30
418A 230-60 207 253 2 12 681/612* 800/800* † 1045.6/976.6* † 700 115-60 30
528A 460-60 414 506 1 6 593 700 1578.4 774.4 700 700 115-60 30
528B 575-60 518 633 1 6 477 500 1265.3 622.3 600 600 115-60 30
380-60 342 418 1 6 713 800 1783.5 894.5 800 800 230-60 15
60
HIGH AMBIENT 125 F DATA — DUPLEX UNITS — HIGH-STATIC CONDENSER FAN (cont)
UNIT VOLTAGE HIGH-STATIC CONDENSER FAN CONTROL CIRCUIT
POWER
UNIT
V-Hz Supplied SUPPLY # Power Supply ICF Rec Fuse Size V-Hz MCA and
30GXN,R MCA MOCP
(3 Ph) QTY. REQD Conductors (Single Ph) MOCP**
Min Max XL WD XL WD
208/230-60 187 253 2 12 609/564* 800/800* † 934.1/889.0* † 700/600* 115-60 30 (50)
230-60 207 253 2 12 550/524* 800/800* † 914.8/889.0* † 600 115-60 30 (50)
475B 460-60 414 506 1 6 489 600 1475.2 671.2 600 600 115-60 30 (50)
575-60 518 633 1 6 393 500 1181.9 538.9 450 450 115-60 30 (50)
380-60 342 418 1 6 592 700 1661.6 772.6 700 700 230-60 15 (25)
208/230-60 187 253 2 12 753/518* 1000/700* † 1077.7/756.2* † 800/600* 115-60 30 (50)
230-60 207 253 2 12 681/486* 800/700* † 1045.6/756.2* † 600 115-60 30 (50)
475A 460-60 414 506 1 6 540 600 1526.3 722.3 600 600 115-60 30 (50)
500A/B
575-60 518 633 1 6 433 500 1221.8 578.8 500 500 115-60 30 (50)
380-60 342 418 1 6 651 800 1721.2 832.2 700 700 230-60 15 (25)
208/230-60 187 253 2 12 753/594* 1000/800* † 1077.7/918.2* † 800/700* 115-60 30 (50)
230-60 207 253 2 12 681/553* 800/800* † 1045.6/918.2* † 700 115-60 30 (50)
525A/B 460-60 414 506 1 6 567 700 1553.2 749.2 700 700 115-60 30 (50)
575-60 518 633 1 6 454 500 1243.6 600.6 500 500 115-60 30 (50)
380-60 342 418 1 6 685 800 1754.6 865.6 800 800 230-60 15 (25)
61
Controls
The standard microprocessor-based control in the If the entering fluid temperature is 85 F (29 C) or higher
30GXN,R units provides the following functions: and the saturated suction temperature is 50 F (10 C) or
• leaving fluid temperature control (using both entering higher, the maximum operating pressure (MOP) feature
and leaving fluid sensors) limits the suction to keep the chiller on line.
• 7-day time sequence of both pump and chiller Normal operation — The entering fluid temperature
• temperature reset from return fluid (standard) or from sensor senses changes in entering fluid temperature to
outdoor ambient, occupied space temperature, 4 to anticipate changes in the cooling load. Based on leaving
20 mA signal, or via the optional Carrier Comfort Net- fluid temperature, the control will add or delete capacity to
work (CCN). maintain a constant leaving fluid temperature.
• automatic compressor lead-lag switching based on com- Transition to off — The chiller unloads once the “time-
pressor accumulated run times and number of cycles. to-stop” signal has been given. This signal can be either
• automatic temperature range across the cooler internal or external (remote).
adjustment
Safeties — The 30GXN,R control as shipped from the
• fully automatic control of the chiller components
factory automatically deenergizes any active compressor
A 4-line, 20-character per line display is used to accom- that experiences any of the following:
plish the following (see figure below):
• electrical overload
• perform service test procedures • thermal overload protection
• set schedules and set points • high pressure
• identify operating mode and run status conditions • low oil pressure
• display current temperatures and pressures being used • loss of refrigerant charge
by the control for internal calculations • loss of phase protection
• identify abnormal (alarm or alert) conditions • reverse rotation (control prevents compressor start)
• configure unit operation • current imbalance
Sequence of operation • ground current fault
• low chilled fluid temperature
The control has a 44.0 F (6.2 C) leaving fluid temperature • loss of chilled water flow
(LWT) set point as shipped from the factory. If temperature
reset or demand limiting is in effect, this set point may Additional information
change. Detailed information on controls and operation is available
Start-up — The chiller starts when the circulating pump is in the Controls, Start-Up, Operation and Troubleshooting
energized and the flow has been proven. The compressor guide included with each unit. Packaged Service Training
starts unloaded. programs are also available. Contact your Carrier repre-
NOTE: The starting compressor is determined by the auto- sentative for more information.
matic lead/lag feature. Dual chiller control — The ComfortLink™ controller
allows 2 chillers (piped in series or parallel) to operate as a
NAVIGATOR DISPLAY MODULE — STANDARD single chilled water plant with standard control functions
coordinated through the master chiller controller. This
Com
standard ComfortLink feature requires a communication
fort
NA
VIG
ATO
Lin
R™
k link between the 2 chillers and an additional thermistor for
L e a vi
ng W
a te r
parallel operation.
ECOLOGIC™ and ECOLOGIC η™ control — ECO-
4 4 . 0 Te m p e
°F ra tu
re
ENT
ER
starts the chiller in the unloaded state to eliminate the
potential of compressor overload due to high head pres-
sure or low suction pressure. The controller will equalize
run time on each circuit through the lead/lag feature. If a
circuit becomes disabled, the control will automatically set
the active circuit to lead, keeping the chiller online at a
reduced capacity.
62
Typical control wiring schematic
NOTES:
1. Factory wiring is in accordance with National Electrical Code (NEC). Field modifications or addi-
LEGEND tions must be in compliance with all applicable codes.
A — Alarm 2. Wiring for main field power supply must be rated 75° C minimum. Use copper conductors for all
CWP — Chilled Water Pump units. Maximum incoming wire size for each terminal block is 500 kcmil.
CWPI — Chilled Water Pump Interlock 3. Power for control circuit should be supplied from a separate source (except 380-v units) through a
EMM — Energy Management Module field-supplied disconnect with 30-amp maximum protection for 115-volt control circuits and 15-
FIOP — Factory-Installed Option amp maximum protection for 230-volt control circuit. Connect control circuit power to terminals 1
LWT — Leaving Water Thermistor and 2 of TB4. Control circuit conductors for all units must be copper only. Control circuit power is
OAT — Outdoor-Air Thermistor factory wired for 380-v units.
SPT — Space Temperature Thermistor 4. Terminals 13 and 14 of TB5 are for field external connection for remote on-off. The contacts must
TB — Terminal Block be rated for dry circuit application capable of handling a 24-vac load up to 50 mA.
Field Wiring 5. Terminals 1 and 2 of TB5 are for Chilled Water Pump Interlock (CWPI) functions. If added, chilled
Field Control Wiring water pump interlock contacts must be wired in series with flow switch contacts. The contacts must
Factory-Installed Wiring be rated for dry circuit application capable of handling a 24-vac load up to 50 mA load. Chilled
Water Flow Switch (CWFS) is factory installed.
6. Terminals 10 and 12 of TB5 are for control of chilled water pump starter. The maximum load
allowed for the chilled water pump relay is 75-va sealed, 360-va inrush at 115 or 230 volt. Field
power supply is not required.
7. Terminals 11 and 12 of TB5 are for alarm relay. The maximum load allowed for the alarm relay is
75-va sealed, 360-va inrush at 115 or 230 volt. Field power supply is not required.
8. Make appropriate connections to TB6 as shown for energy management board options. The con-
tacts for Demand Limit and Ice Done options must be rated for dry circuit application capable of
handling a 24-vac load up to 50 mA.
63
Application data
UNIT OPERATING RANGE*
ITEM MAX MIN NOMINAL
Cooler Leaving Fluid Temperature† 60 F (15 C) 40 F (4.4 C) —
Cooler Entering Fluid Temperature** 70 F (21.1 C) 45 F (7.2 C) —
Max Cooler Temp Reference Nominal
Number of Difference Min Flow Rate Flow Rate
Cooler Flow Rates 30GXN,R Cooler
Passes
F C Gpm L/s Gpm L/s
minus 1 pass 2 13 7.4 136 8.6
080, 083 std 3 20 11.1 91 5.7 182 11.5
plus 1 pass 4 27 14.8 68 4.3
minus 1 pass 2 13 7.4 149 9.4
090, 093 std 3 20 11.1 100 6.3 199 12.6
plus 1 pass 4 27 14.8 75 4.7
minus 1 pass 2 13 7.4 176 11.1
106, 108 std 3 20 11.1 117 7.4 234 14.8
plus 1 pass 4 27 14.8 88 5.5
minus 1 pass 2 13 7.4 191 12.0
114 std 3 20 11.1 127 8.0 254 16.1
plus 1 pass 4 27 14.8 95 6.0
minus 1 pass 1 10 5.6 254 16.1
118 std 2 20 11.1 127 8.0 254 16.1
plus 1 pass 3 30 16.7 85 5.4
minus 1 pass 2 13 7.4 209 13.2
125 std 3 20 11.1 139 8.8 278 17.6
plus 1 pass 4 27 14.8 104 6.6
minus 1 pass 1 10 5.6 278 17.6
128 std 2 20 11.1 139 8.8 278 17.6
plus 1 pass 3 30 16.7 93 5.9
minus 1 pass 2 13 7.4 229 14.4
135 std 3 20 11.1 152 9.6 305 19.2
plus 1 pass 4 27 14.8 114 7.2
minus 1 pass 1 10 5.6 305 19.2
138 std 2 20 11.1 152 9.6 305 19.2
plus 1 pass 3 30 16.7 102 6.4
minus 1 pass 1 10 5.6 336 21.2
150, 153 std 2 20 11.1 168 10.6 336 21.2
plus 1 pass 3 30 16.7 112 7.1
minus 1 pass 1 10 5.6 364 23.0
160, 163 std 2 20 11.1 182 11.5 364 23.0
plus 1 pass 3 30 16.7 121 7.7
minus 1 pass 1 10 5.6 401 25.3
174, 178†† std 2 20 11.1 200 12.6 401 25.3
plus 1 pass 3 30 16.7 134 8.4
minus 1 pass 1 10 5.6 461 29.1
204, 208†† std 2 20 11.1 230 14.5 461 29.1
plus 1 pass 3 30 16.7 154 9.7
minus 1 pass 1 10 5.6 502 31.6
225, 228†† std 2 20 11.1 251 15.8 502 31.6
plus 1 pass 3 30 16.7 167 10.5
minus 1 pass 1 10 5.6 562 35.4
249, 253†† std 2 20 11.1 281 17.7 562 35.4
plus 1 pass 3 30 16.7 187 11.8
minus 1 pass 1 10 5.6 588 37.1
264, 268†† std 2 20 11.1 294 18.6 588 37.1
plus 1 pass 3 30 16.7 196 12.4
minus 1 pass 1 10 5.6 641 40.5
281†† std 2 20 11.1 321 20.2 641 40.5
plus 1 pass 3 30 16.7 214 13.5
minus 1 pass 1 10 5.6 689 43.4
301†† std 2 20 11.1 344 21.7 689 43.4
plus 1 pass 3 30 16.7 230 14.5
minus 1 pass 1 10 5.6 741 46.8
325†† std 2 20 11.1 371 23.4 741 46.8
plus 1 pass 3 30 16.7 247 15.6
minus 1 pass 1 10 5.6 801 50.5
350†† std 2 20 11.1 401 25.3 801 50.5
plus 1 pass 3 30 16.7 267 16.8
*Maximum ambient temperature and percent of unit capacity will vary based on unit NOTES:
load and return water temperature. All models are qualified for use at 125 F (46 C). 1. The 30GXN,R units will start with loop temperatures up to 95 F (35 C).
Some models may require the high ambient fan option. Contact your local Carrier rep- 2. Nominal flow rates required at ARI conditions 44 F (7 C) leaving fluid temperature,
resentative to obtain performance data using the Carrier electronic catalog. 54 F (12 C) entering water temperature, 95 F (35 C) ambient. Fouling factor
†For applications requiring cooler leaving water temperature operation at less than 0.00010 ft2-hr-F/Btu (0.000018 m2-K/kW).
40 F (4.4 C), the units require the use of antifreeze and application may require one 3. To obtain proper temperature control, cooler loop fluid volume must be at least 3 gal/
of the special order brine option. Contact your local Carrier representative for more ton (3.23 L/kW) of chiller nominal capacity for air conditioning and at least 6 gal/ton
information. (6.5 L/kW) for process applications or systems that must operate in low ambient tem-
**For applications requiring cooler entering water temperature operation at less than peratures (below 32 F [0° C]).
45 F (7.2 C), contact your local Carrier representative for unit selection using the 4. Where winds of 5 mph (2.2 m/s) or greater are anticipated at outdoor ambient temper-
Carrier electronic catalog. atures below 32 F (0° C), wind baffles are required.
††Requires optional or accessory low ambient kit for operation below 15 F (–9 C). All
other models require the low ambient control for operation below 0° F (–17.8 C).
64
DUPLEX UNIT OPERATING RANGE
MAX. COOLER TEMPERATURE REFERENCE NOMINAL
NO. OF DIFFERENCE MIN FLOW RATE FLOW RATE
30GXN,R COOLER PASSES
F C Gpm L/s Gpm L/s
283 STD 1 20 11.1 329 20.8 658 41.5
303 STD 1 20 11.1 347 21.9 694 43.8
328 STD 1 20 11.1 382 24.1 764 48.2
353 STD 1 20 11.1 420 26.5 839 53.0
370 STD 1 20 11.1 502 31.7 879 55.5
373 STD 1 20 11.1 444 28.0 889 56.1
390 STD 1 20 11.1 588 37.1 909 57.3
393 STD 1 20 11.1 461 29.1 921 58.1
415 STD 1 20 11.1 588 37.1 974 61.4
418 STD 1 20 11.1 475 30.0 950 59.9
450 STD 1 20 11.1 502 31.7 1031 65.0
453 STD 1 20 11.1 512 32.3 1025 64.7
475 STD 1 20 11.1 542 34.2 1085 68.4
478 STD 1 20 11.1 546 34.4 1091 68.8
500 STD 1 20 11.1 571 36.0 1141 72.0
503 STD 1 20 11.1 579 36.5 1158 73.0
525 STD 1 20 11.1 601 37.9 1202 75.8
528 STD 1 20 11.1 607 38.3 1214 76.6
65
Application data (cont)
Minimum cooler flow — Flow (maximum cooler tem- Chilled fluid loop volume — The chilled fluid loop
perature rise) for standard units is shown in the Unit Oper- volume in circulation must equal or exceed 3 gal per nomi-
ating Ranges table. Maximum change in temperature is nal ton of cooling (3.23 L per kW) for temperature stability
20° F (11.1° C). When flow rate required is lower (or rise is and accuracy in normal air conditioning applications.
higher), follow recommendations below: For example, a 30GXN,R106 with a nominal capacity of
• Multiple smaller chillers can be applied in series, each 97.5 tons (342.8 kW) would require 292.5 gal (1106 L) in
providing a portion of the design temperature rise. circulation in the system loop.
• Some chilled fluid can be recirculated through the cooler For process jobs where accuracy is vital, or for operation
to raise flow rate. However, mixed temperature entering at ambient temperatures below 32 F (0° C) with low unit
cooler must be maintained at a minimum of at least 5° F loading conditions, there should be from 6 to 10 gal. per
(2.8° C) above the leaving chilled fluid temperature. ton (6.5 to 10.8 L per kW). To achieve this volume, it is of-
• Special reduced pass or multiple pass heads cooler can ten necessary to install a tank in the loop. Tank should be
be used. Contact your Carrier representative for further baffled to ensure there is no stratification, and that water
information. (or brine) entering tank is adequately mixed with liquid in
the tank. See below.
NOTE: Recirculation flow is shown below.
TANK INSTALLATION
RECIRCULATION FLOW
66
Wind baffles (field-installed accessory) — Baffles Series chillers
must be added to all units for operation below 32 F (0° C) Where a large temperature drop (greater than 20 F
if wind velocity is anticipated to be greater than 5 mph [11.1 C]) is desired or where chiller capacities greater than
(8 km/h). can be supplied by a single 30GXN,R chiller are required
Cooler freeze protection — If chiller refrigerant or fluid or where stand-by capability is required, chillers may be
lines are in an area where ambient conditions fall below installed in series. The leaving fluid temperature sensors
32 F (0° C), it is required that an antifreeze solution be need not be relocated. However, the cooler minimum
added to protect the unit and fluid piping to a temperature entering fluid temperature limitations should be considered
15° F (8.3° C) below the lowest anticipated temperature. for the chillers located downstream of other chillers. Use of
For corrections to performance, refer to the chiller pro- reduced pass heads may be required to keep waterside
gram in the electronic catalog. pressure drop at an acceptable level.
Use only antifreeze solutions approved for heat ex- Minimum clearances
changer duty. Use of automotive antifreezes is not recom-
mended because of the fouling that can occur once their The recommended minimum clearance to ensure proper
airflow through the condenser coils and to allow fan main-
relatively short-lived inhibitors break down.
tenance is as shown below.
Select concentration based on either Burst or Freeze
Protection as dictated by application. Additional freeze Acceptable clearance between the chiller and a single
wall may be reduced to 3 ft on one side or end opposite the
protection is available through the use of the low ambient
control panel without sacrificing performance. Clearances
protection option. Since power is sometimes lost for ex-
tended periods during winter storms (particularly in subur- between chillers in dual chiller applications, may be reduced
to 6 ft on one side without sacrificing performance.
ban and rural areas) freeze protection will only be effective
if back-up power supply can be assured for the unit’s con-
MULTIPLE UNIT SEPARATION
trol circuit, heater and cooler pump.
If not protected with an antifreeze solution, draining 6 ft (1.8 m)
MINIMUM
cooler and outdoor piping is recommended if system will
not be used during freezing weather conditions.
10 ft
Oversizing chillers (3 m)
MINIMUM
Oversizing chillers by more than 15% at design conditions
must be avoided as the system operating efficiency will be
adversely affected (resulting in greater and/or excessive
ALIGNED SIDE BY SIDE
electrical demand and cycling of compressors). When
future expansion of equipment is anticipated, install a sin-
gle chiller to meet present load requirements, and install a
second chiller to meet the additional load demand. Energy management
It is also recommended that the installation of 2 smaller Demand limiting and load shedding are popular techniques
chillers be considered where operation at minimum load is used to reduce peak electric demands typically experienced
critical. The operation of 2 small chillers at higher loading during hot summer days when air conditioning loads are
is preferred to operating a single chiller at or near its mini- highest. When utility electricity demands exceed a certain
mum recommended value. level, electrical loads are turned off to keep the peak
The minimum load control accessory should not be used demands below a prescribed maximum limit. Compressor
as a means to allow oversizing chillers. Minimum load con- unloading reduces electrical demand while allowing the
trol should be given consideration where substantial operat- chiller to operate under part-load capacity and to maintain
ing time is anticipated below the minimum unloading step. partial chilled fluid cooling.
Electrical demand can be limited by unloading the chiller
Parallel chillers to a predetermined percentage of the load. One stage of
Where chiller capacities greater than can be supplied by a unloading can be initiated by a remote signal to significant-
single 30GXN,R chiller are required, or where stand-by ly reduce the chiller power consumption. This power re-
capability is desired, chillers may be installed in parallel. duction applies to the full load power at nominal condi-
Units may be of the same or different sizes. However, tions. The demand limit control should not be cycled less
cooler flow rates must be balanced to ensure proper flow than 10 minutes on and 5 minutes off.
to each chiller. The accessory Chillervisor System Manager
can be used to ensure proper staging sequence of up to 8
chillers. Isolated valves on individual chiller pumps are rec-
ommended for parallel chiller arrangements. Refer to the
accessory Chillervisor System Manager installation instruc-
tions for further details.
67
Application data (cont)
Duty cycling due to potential attack from sulfur, sulfur oxide, nitrogen
Duty cycling will cycle the electrical load in an installation oxides, carbon and several other industrial airborne contam-
(building, factory, etc.) at regular intervals to control the inants. In moderate seacoast environments, copper-fin coils
electrical demand. This reduces the electrical demand, have extended life compared to standard or pre-coated
thereby lowering demand charges, by cycling the operating aluminum-fin coils.
electrical equipment off and on. However, duty cycling is E-coated aluminum-fin coils have a extremely flexible
NOT allowed since constant cycling will cause increased and durable epoxy coating uniformly applied to all coil sur-
stress and damage to the motor windings, bearings, and faces. Unlikely brittle phenolic dip and bake coatings,
controls. If demand must be controlled the Demand Limit E-coat provides superior protection with unmatched flexi-
sequence in the 30GXN,R control system is recom- bility, edge coverage, metal adhesion, thermal perfor-
mended. For detailed information refer to the Controls, mance and most importantly, corrosion resistance.
Start-Up, Operation, Service, and Troubleshooting guide E-coated coils provide this protection since all coil surfaces
included with the unit. are completely encapsulated from environmental contami-
nation. Specify E-coated aluminum-fin coils for industrial
Ice duty environments with high levels of air pollution. This option
ComfortLink™ controls have the capability of reduced also provides better protection compared to standard or
leaving fluid temperature operation for thermal storage, or pre-coated aluminum-fin coils in industrial environments.
ice duty. The optional energy management module
E-coated copper-fin coils have the same flexible and
includes input contacts for the “ice done” signal generated
durable epoxy coating as E-coated aluminum-fin coils.
by the thermal storage control system. The ice duty feature However, this option combines the natural salt and envi-
may be configured to start on an external input command
ronment resistance of all-copper construction with the
or by the ComfortLink standard internal scheduling func-
highest level of corrosion protection. Specify E-coated
tion. The ice duty function requires brine modification for copper-fin coils in the harshest combination of coastal and
leaving fluid temperatures below 40 F (4.4 C). Ice Duty
industrial environments.
may be used in combination with any other standard fea-
tures offered by the Energy Management Module and Operating cost analysis
ComfortLink controls. ECOLOGIC η™ chiller cost payback analysis for high
Wye-delta start efficiency chillers. Chiller full load operating efficiency is
directly related to the annual operating cost of the
Wye-delta start is standard on all 30GXR units and machine. The simple example given below details how the
optional on all 30GXN units (except 208/230-v units).
increase in chiller efficiency can have a very dramatic
This feature is not always required on 30GX units due to
impact on annual operating expense.
the use of multiple compressors that allow small electrical
load increments, but is available if required. Maximum Annual operating cost can be defined as a function of
instantaneous current flow (see ICF in Electrical Data tables chiller capacity, chiller efficiency, chiller run time and utility
on pages 53-61) should be used in determining need. cost (including demand charges).
For full load evaluation, the equation is:
Vibration isolation
Annual operating cost difference = [Chiller Capaci-
External 1/4-in. neoprene vibration-absorbent pads are
ty (tons) x Utility Cost ($/kWhr) x Time at Full Load
available as field-installed accessories. (hrs) x Difference in Chiller Efficiency (12/EERchiller 1
Strainers – 12/EERchiller 2)] + [Chiller Capacity (tons) x Demand
A strainer with a minimum screen size of 20 mesh must be Charge ($/kW) x Months at Peak Demand x Difference
installed in the entering cooler fluid line, 10 ft (3.3 m) in Chiller Efficiency (12/EERchiller 1 – 12/EERchiller 2)]
ahead of the cooler. Example
Condenser coil corrosion protection Assume a school in Orlando, Florida with two 210 ton
(Enviro-Shield™) chillers, in operation for 2000 hours per year, 4 months of
Pre-coated aluminum-fin coils have a durable epoxy- $10/kW demand charges and $0.10/kWhr utility costs.
phenolic coating applied to the fin prior to the fin stamping Assuming that one chiller will be at full load nearly all the
process to provide protection in mildly corrosive coastal time, the comparison between the standard efficiency
environments. Pre-coated coils have an inert barrier 30GXN225 with EER of 9.56, and the High Efficiency
between the aluminum fin and copper tube. This barrier ECOLOGIC η 30GXN228 with EER of 10.40 yields:
electrically disconnects the dissimilar metals to minimize Annual cost savings =
the potential for galvanic corrosion. This economical [210 tons x $0.10/kWhr x 2000 hours x (12/10.40 EER
option provides substantial corrosion protection beyond –12/9.56 EER)] + [210 tons x $10.00/kWhr x 4 months
the standard uncoated coil construction. x (12/10.40 EER –12/9.56 EER)]
Copper-fin coils provide increased corrosion resistance in Annual cost savings = $5,100
moderate coastal environments where industrial air pollu-
This simplistic example details the dramatic impact the
tion is not present. All copper coils eliminate bi-metallic con- High Efficiency 30GXN,R chiller can have on the life cycle
struction to eliminate the potential for galvanic corrosion.
cost of the chiller plant.
Application in industrial environments is not recommended
68
Typical piping and wiring
NOTES: LEGEND
1. Chiller must be installed levelly to maintain proper compressor oil return and hydraulics. AUX — Auxiliary
2. Wiring and piping shown are general points-of-connection guides only and are not intended CKT — Circuit
for a specific installation. Wiring and piping shown are for a quick overview of system and FD — Field-Supplied Disconnect
are not in accordance with recognized standards. ST — Starter
3. All wiring must comply with applicable local and national codes.
4. All piping must follow standard piping techniques. Refer to Carrier System Design Manual or Airflow Through Condenser
appropriate ASHRAE (American Society of Heating, Refrigeration, and Air Conditioning
Engineers) handbook for details. Airflow Through Air-Handling
Unit
Power Wiring
Chilled Water Piping
69
Typical piping and wiring — duplex units
NOTES: LEGEND
1. Chiller must be installed levelly to maintain proper compressor oil return and hydraulics. AUX — Auxiliary
2. Wiring and piping shown are general points-of-connection guides only and are not intended CKT — Circuit
for a specific installation. Wiring and piping shown are for a quick overview of system and FD — Field-Supplied Disconnect
are not in accordance with recognized standards. ST — Starter
3. All wiring must comply with applicable local and national codes.
4. All piping must follow standard piping techniques. Refer to Carrier System Design Manual or Airflow Through Condenser
appropriate ASHRAE (American Society of Heating, Refrigeration, and Air Conditioning
Engineers) handbook for details. Airflow Through Air-Handling
Unit
Power Wiring
Chilled Water Piping
70
Guide specifications
Air-Cooled Liquid Chiller E. Compressors:
1. Unit shall have semi-hermetic twin-screw, gear-
HVAC Guide Specifications driven compressors with internal muffler and
Size Range: 80 to 525 Tons check valve.
(267 to 1750 kW) Nominal 2. Each compressor shall be equipped with a dis-
charge shutoff valve.
Carrier Model Number: 30GXN, GXR
3. Capacity control shall be provided by pilot-
Part 1 — General operated solenoid valve, capable of reducing
1.01 SYSTEM DESCRIPTION unit capacity to 10% of full load. Compressor
Microprocessor controlled, air-cooled liquid chiller shall start in unloaded condition.
utilizing HFC-134a, screw compressors, and elec- 4. Motor cooling shall be provided by direct liquid
tronic expansion devices. injection and protected internal overload
1.02 QUALITY ASSURANCE thermistor.
A. Unit shall be rated in accordance with ARI Standard 5. Lube oil system shall include pre-filter and inter-
550/590, latest revision (U.S.A.). nal filter capable of filtration to 2 microns.
B. Unit construction shall comply with ASHRAE 15 6. Rubber-in-shear isolation.
Safety Code, NEC, and ASME applicable codes F. Cooler:
(U.S.A. codes). 1. Cooler shall be tested and stamped in accor-
C. Unit shall be manufactured in a facility registered to dance with ASME code (U.S.A.) for a refrigerant
ISO 9001:2000 Manufacturing Quality Standard. working-side pressure of 220 psig (1517 kPa)
D. Unit shall be full load run tested at the factory. and shall be tested for a maximum fluid-side
pressure of 300 psig (2068 kPa) (in Canada,
1.03 DELIVERY, STORAGE AND HANDLING 250 psig [1724 kPa] per Canadian National
A. Unit controls shall be capable of withstanding Registry requirements).
150 F (66 C) storage temperatures in the control 2. Shall be mechanically cleanable shell-and-tube
compartment. type with removable heads.
B. Unit shall be stored and handled per unit manufac- 3. Tubes shall be internally-enhanced, seamless-
turer's recommendations. copper type, and shall be rolled into tube sheets.
Part 2 — Products 4. Shall be equipped with mechanical grooved
2.01 EQUIPMENT Victaulic-type fluid connections.
A. General: 5. Shell shall be insulated with 3/4-in. (19 mm)
Factory assembled, single-piece or factory config- closed-cell, polyvinyl-chloride foam with a maxi-
ured duplex chassis, air-cooled liquid chiller. Con- mum K factor of 0.28.
tained within the unit cabinet shall be all factory 6. Shall incorporate 2 independent refrigerant
wiring, piping, controls, refrigerant charge circuits.
(HFC-134a), and special features required prior to 7. Shall have a cooler drain and vent.
field start-up.
8. Shall incorporate a refrigerant level sensing
B. Efficiency: device.
Chiller shall have a minimum full load operating effi- 9. Low Ambient Protection: Unit shall have factory-
ciency of _____ EER as rated in accordance with installed head-mounted cooler heater, liquid line
and certified per ARI 550/590-98. solenoid vales and pumpout cycle to protect
C. Unit Cabinet: cooler from ambient temperature freeze down to
1. Frame shall be of heavy-gage galvanized steel. 0° F (–17 C).
2. Cabinet shall be galvanized steel casing with a G. Condenser:
pre-painted finish. 1. Coil shall be air-cooled with integral subcooler,
3. Cabinet shall be capable of withstanding and shall be constructed of aluminum fins
500-hour salt spray test in accordance with the mechanically bonded to seamless copper tubes.
ASTM (U.S.A.) B-117 standard. The tubes are then cleaned, dehydrated, and
sealed.
D. Fans:
2. Condenser coils shall be leak tested and shall be
1. Condenser fans shall be direct-driven, 11-blade pressure tested at 450 psig (3103 kPa).
airfoil cross-section, reinforced polymer con-
struction, shrouded-axial type, and shall be stat- 3. Refrigeration Components: Refrigerant circuit
ically and dynamically balanced with inherent components shall include oil separator, high
corrosion resistance. Air shall be discharged and low side pressure relief device, discharge
vertically upward. and liquid line shutoff valves, filter drier, mois-
ture indicating sight glass, electronic expansion
2. Fans shall be protected by coated steel wire device, refrigerant economizer (size 105-525
safety guards. units), and complete operating charge of both
refrigerant HFC-134a and compressor oil.
71
Guide specifications (cont)
4. The chiller shall include the ability to isolate the in outdoor environments. Display shall have
refrigerant charge in either the cooler or the back light and contrast adjustment for easy
condenser. viewing in bright sunlight or night condi-
H. Controls, Safeties, and Diagnostics: tions. The display module shall have raised
surface buttons with positive tactile
1. Controls: response.
a. Unit controls shall include the following min- d. The chiller controller shall include multiple
imum components: connection ports for communicating with
1) Microprocessor with non-volatile mem- the local equipment network, the Carrier
ory. Battery backup system shall not be Comfort Network (CCN) and the ability to
accepted. access all chiller control functions from any
1) Power and control circuit terminal point on the chiller.
blocks. e. The control system shall allow software up-
1) ON/OFF control switch. grade without the need for new hardware
1) Replaceable solid-state relay panels. modules.
1) Thermistor installed to measure satu-
rated condensing temperature, cooler 2. Safeties:
saturation temperature, compressor a. Unit shall be equipped with thermistors and
return gas temperature, and cooler all necessary components in conjunction
entering and leaving fluid temperatures. with the control system to provide the unit
b. Unit controls shall include the following with the following protections:
functions as standard: 1) Loss of refrigerant charge.
1) Automatic circuit lead/lag. 1) Reverse rotation.
1) Capacity control based on leaving 1) Low chilled fluid temperature.
chilled fluid temperature and compen- 1) Low oil pressure (each compressor
sated by rate of change of return-fluid circuit).
temperature with temperature set point 1) Voltage imbalance.
accuracy to 0.1° F (0.06° C). 1) Ground current fault.
1) Limiting the chilled fluid temperature 1) Thermal overload.
pull-down rate at start-up to an adjust- 1) High pressure.
able range of 0.2° F to 2° F (0.11° C to 1) Electrical overload.
1.1° C) per minute to prevent excessive 1) Loss of phase.
demand spikes at start-up. 1) Current imbalance.
1) Seven-day time schedule. 1) Loss of chilled water flow.
1) Leaving chilled fluid temperature reset b. Fan motors shall have inherent overcurrent
from return fluid, outdoor-air tempera- protection.
ture, space temperature, or 4 to 20 mA 3. Diagnostics:
input.
1) Demand limit control with 2-stage con- a. The display module shall be capable of indi-
trol (0 to 100% each) or through 4 to cating the safety lockout condition by dis-
20 mA input (0 to 100%). playing the information in clear language at
1) Chilled water pump start/stop control. the display. Information displayed shall
1) Dual chiller control for series chiller include:
applications without addition of hard- 1) Compressor lockout.
ware modules or additional thermistors. 1) Loss of charge.
1) Amperage readout per compressor with 1) Low fluid flow.
%MTA per compressor. 1) Low oil pressure.
1) Auto-restart after power failure. 1) Cooler freeze protection.
c. The control panel shall include, as standard, 1) High or low suction superheat.
a portable hand held display module with a 1) Thermistor malfunction.
minimum of 4 lines and 20 characters per 1) Entering and leaving-fluid temperature.
line, of clear English, Spanish, Portuguese or 1) Evaporator and condenser pressure.
French language. Display menus shall pro- 1) Electronic expansion valve positions.
vide clear language descriptions of all menu 1) All set points.
items, operating modes, configuration 1) Time of day.
points and alarm diagnostics. Reference to b. Display module, in conjunction with the
factory codes shall not be accepted. An microprocessor, must also be capable of dis-
industrial grade coiled extension cord shall playing the output results of a service test.
allow the display module to be moved Service test shall verify operation of every
around the chiller. Magnets shall hold the switch, thermistor, fan, and compressor
display module to any sheet metal panel to before chiller is started. User shall be able to
allow hands-free operation. Display module force each output device.
shall have NEMA 4x housing suitable for use
72
c. Diagnostics shall include the ability to review 4. Non-Fused Disconnect:
a list of the 20 most recent alarms with clear Unit shall be supplied with factory-installed,
language descriptions of the alarm event. non-fused electrical disconnect for main power
Display of alarm codes without the ability supply.
for clear language descriptions shall be
prohibited. 5. Loss-of-Flow Protection:
d. An alarm history buffer shall allow the user Unit shall be supplied with factory-installed
to store no less than 20 alarm events with thermal dispersion type proof-of-flow sensing
clear language descriptions, time and date switch.
stamp event entry. 6. Optional Condenser Coil Materials:
I. Operating Characteristics: a. Pre-coated aluminum-fin coils:
1. Unit shall be capable of starting and running at Shall have a durable epoxy-phenolic coating
outdoor ambient temperatures from 0° F to to provide protection in mildly corrosive
125 F (–18 to 52 C) 080-150,160 units and coastal environments. Coating shall be
15 F to 125 F (–9 to 52 C) 153,174-528 units. applied to the aluminum fin stock prior to
2. Unit shall be capable of starting up with 95 F the fin stamping process to create an inert
(35 C) entering fluid temperature to the cooler. barrier between the aluminum fin and cop-
J. Motors: per tube. Epoxy-phenolic barrier shall mini-
mize galvanic action between dissimilar
Condenser-fan motors shall be totally enclosed metals.
3-phase type with permanently lubricated bearings
and Class F insulation. b. Copper-fin coils:
K. Electrical Requirements: Shall be constructed of copper fins mechani-
cally bonded to copper tubes and copper
1. Unit primary electrical power supply shall enter tube sheets. Galvanized steel tube sheets
the unit at a single location (some units have shall not be acceptable. A polymer strip shall
multiple poles). prevent coil assembly from contacting sheet
2. Primary electrical power supply shall be rated to metal coil pan to minimize potential for gal-
withstand 115 F (46 C) operating ambient as vanic corrosion between the coil and pan.
standard or 125 F (52 C) optional. All copper construction shall provide protec-
3. Unit shall operate on 3-phase power at the volt- tion in moderate coastal environments.
age shown in the equipment schedule. c. E-Coat aluminum-fin coils:
4. Control voltage shall be 115-v or 230-v, single- Shall have a flexible epoxy polymer coating
phase, separate power supply. uniformly applied to all coil surface areas
5. Unit shall be shipped with factory control and without material bridging between fins.
power wiring installed. Coating process shall ensure complete coil
encapsulation. Color shall be high gloss
L. Special Features: black with gloss - 60° of 65-90% per ASTM
Certain standard features are not applicable when ID523-89. Uniform dry film thickness from
the features designed by * are specified. For assis- 0.8 to 1.2 mil on all surface areas including
tance in amending the specifications, contact your fin edges. Superior hardness characteristics
Carrier Sales office. of 2H per ASTM D3363-92A and cross
1. Wye-Delta Starter: hatch adhesion of 4B-5B per ASTM
Unit shall have a factory-installed, wye-delta D3359-93. Impact resistance shall be up to
start to minimize electrical inrush current. 160 in./lb (ASTM D2794-93). Humidity
and water immersion resistance shall be up
* 2. Low-Ambient Operation: to minimum 1000 and 250 hours respec-
a. Unit shall be capable of starting and running tively (ASTM D2247-92 and ASTM D870-
at outdoor ambient temperatures down to 92). Corrosion durability shall be confirmed
–20 F (–29 C) with the addition of antifreeze through testing to no less than 3000 hours
in the cooler circuit, wind baffles, and field- salt spray per ASTM B117-90. Coil con-
installed or factory-installed low-ambient kit. struction shall be aluminum fins mechanically
b. Factory-mounted or field-supplied low ambient bonded to copper tubes.
head pressure control shall be accomplished d. E-Coat copper-fin coils:
via electronic variable speed condenser fan Shall have a flexible epoxy polymer coating
motor drive system. uniformly applied to all coil surface areas
3. Control Power Transformer: without material bridging between fins. Coat-
Unit shall be supplied with a field (or factory) ing process shall ensure complete coil encap-
installed transformer that will allow supply con- sulation. Color shall be high gloss black
with gloss - 60° of 65-90% per ASTM
trol circuit power from the main unit power
D523-89. Uniform dry film thickness from
supply. 0.8 to 1.2 mil on all surface areas including
fin edges. Superior hardness characteristics
73
Guide specifications (cont)
of 2H per ASTM D3363-92A and cross 14. Sound Reduction Enclosures/Hail Guards/
hatch adhesion of 4B-5B per ASTM D3359- Wind Baffles:
93. Impact resistance shall be up to Field-installed accessory kit shall include sheet
160 in./lb (ASTM D2794-93). Humidity and metal hoods with sound absorbing panels
water immersion resistance shall be up to designed to reduce sound levels, protect coils
minimum 1000 and 250 hours respectively from hail damage and baffle the wind for low
(ASTM D2247-92 and ASTM D870-92).
ambient operation.
Corrosion durability shall be confirmed
through testing to no less than 3000 hours 15. Vibration Isolation:
salt spray per ASTM B117-90. Coil con- Vibration isolation pads shall be supplied for
struction shall be copper-fins mechanically field installation at unit mounting points. Pads
bonded to copper tubes with copper tube shall help to reduce vibration transmission into
sheets. Galvanized steel tube sheets shall not the occupied space.
be acceptable. A polymer strip shall prevent
coil assembly from contacting sheet metal 16. GFI Convenience Outlet:
coil pan to maintain coating integrity and Shall be factory or field-installed and mounted
minimize corrosion potential between the with easily accessible 115-v female receptacle.
coil and pan. Shall include 15 amp GFI receptacle with inde-
7. Remote Enhanced Display: pendent fuse protection. Voltage required to
operate convenience outlet shall be provided by
Unit shall be supplied with indoor-mounted,
field-installed step-down transformer.
remote, 40-character per line, 16-line display
panel for field installation. 17. Alternate Cooler Heads:
8. Medium Temperature Brine: a. Plus-one-pass — Unit shall be equipped with
plus-one-pass cooler heads to be used with
Unit shall be factory modified to start and oper- low temperature brine options.
ate at leaving chilled fluid temperatures between
15 F (–9 C) and 40 F (40 C). b. Minus-one-pass — Unit shall be equipped
with minus-one-pass cooler heads with
9. Chiller System Manager Multi-Unit Control: reduced water-side pressure drop for series
Field-installed control shall sequence between 2 flow duplex models or high chilled water
and 8 chillers in parallel or 2 chillers in series in flow applications.
a single system. System shall control chilled and 18. Control Display Access Door:
condenser water pumps. Unit shall be provided with a transparent con-
10. Minimum Load Control: trol box door that allows see-through viewing of
Unit shall be equipped with factory (or field) control display without opening the control
installed, microprocessor-controlled, minimum- box.
load control that shall permit unit operation 19. Cooler Head Insulation:
below 10% capacity. Unit shall be supplied with field-installed cooler
11. Energy Management Control Module: insulation that shall cover the cooler heads.
A factory or field-installed module shall provide 20. Suction Isolation Valves:
the following energy management capabilities:
Unit shall be supplied with factory-installed suc-
4 to 20 mA signals for leaving fluid temperature tion isolation valves.
reset, cooling set point reset or demand limit
control; 2-point demand limit control (from 0 to 21. Remote Service Port:
100%) activated by a remote contact closure; Unit shall be supplied with factory or field-
and discrete input for “Ice Done” indication for installed remote connection port for hand held
ice storage system interface. display device connectivity. Port shall be female
12. Security Guards: RJ-14 receptacle housed in cast aluminum,
weatherproof enclosure with spring loaded
Unit shall be supplied with factory (or field)
weather-sealed hinged door. Remote service
installed, PVC-coated grilles to protect the con-
port shall be located adjacent to mechanical
denser, cooler, and compressor. components to allow convenient access to diag-
*13. High-Static/High Ambient Condenser Fans: nostic and operational information while stand-
Unit shall have factory-installed condenser fans ing next to the mechanical component.
capable of generating 0.4 in. wg (100 Pa) or
0.8 in. wg (200 Pa) external static pressure at
nominal condenser airflow. The 0.4 in. wg
(100 Pa) shall provide additional condenser air
flow and additional capacity up to 125 F (52 C).
74
Carrier Corporation • Syracuse, New York 13221 1203 11-02
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Book 2 New Book 3 Pg 76 Catalog No. 523-073 Printed in U.S.A. PC 903 Form 30GXN-4PD
Tab 5c Tab SC3 Replaces: 30GXN-3PD