Product Data and Installation Sheet Elt10 E L T S: Mergency Ighting EST Witch D O

The ELT10 emergency lighting test switch is designed to test emergency luminaires by interrupting power for a preset time period to avoid draining batteries. It has three test intervals: 10 minutes, 1 hour, and 3 hours. It is installed by connecting it between the main power supply and load in accordance with wiring regulations.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
100 views2 pages

Product Data and Installation Sheet Elt10 E L T S: Mergency Ighting EST Witch D O

The ELT10 emergency lighting test switch is designed to test emergency luminaires by interrupting power for a preset time period to avoid draining batteries. It has three test intervals: 10 minutes, 1 hour, and 3 hours. It is installed by connecting it between the main power supply and load in accordance with wiring regulations.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 2

PRODUCT DATA AND INSTALLATION SHEET

ELT10 EMERGENCY LIGHTING DESCRIPTION AND OPERATION


TEST SWITCH The ELT10 emergency lighting test switch is designed to test the function
of emergency luminaires. A key switch is used to interrupt the supply to
the luminaires for a pre-programmed period of time. At the end of the
time period the supply to the luminaires is automatically re-instated. The
result is that there is no risk of depleting the batteries in the emergency
fitting.

Three pre-programmed test intervals are available:


• 10 minutes
• 1 hour
• 3 hours

The unit will power up with the SUPPLY ON lamp illuminated—the supply
will be connected to the output.

Turn and release the key switch to select the 10 minute test interval. Turn
and release again to select the next test interval—the supply will be dis-
connected from the output for the duration of the test.

To cancel a test, turn and release the keyswitch until the SUPPLY ON
lamp illuminates.

INSTALLATION
Warning. This device works at mains potential. Be sure to take care when working with electricity.
1. Make sure the load is connected and in working order.

2. Isolate the mains supply to the circuit at the main distribution board.

3. Wire the ELT10 as in the diagram above.

4. Connect the controller via the terminal block. Live supply to the L terminal, Neutral supply to the N terminal and the load to the NC terminal.
When using the ELT-REL relay unit, connect to the NO terminal.

5. Screw unit to the wall and switch the mains supply on.

6. The SUPPLY ON lamp will light up (see below).

Ref: %WD004 Issue 2


SPECIFICATION
LOAD

10 Amp incandescent lighting


6 Amp fluorescent lighting
3 Amp compact fluorescent lighting
3 Amp low energy lighting
3 Amp low voltage lighting (switch primary of transformer)
Fluorescent lighting (max 6 fittings recommended)
For fluorescent lighting total power factor correction capacitance must not exceed 40 F
SUPPLY VOLTAGE 220-240 Volts AC 50 Hz
TIMING PERIOD 10 minutes, 1 hour, 3 hours
FIXING METHOD Surface fixing 25mm deep plastic surface mount moulded box.
Flush fixing 25mm steel wall box or 32mm deep cavity wall box.
TERMINAL CAPACITY 2.5mm2
MATERIAL Flame retardant ABS
TYPE Class 2
TEMPERATURE -10°C to 35°C
CONFORMITY EMC-89/336/EEC
LVD-73/23/EEC

C.P. Electronics Ltd


Unit 2 Abbey Manufacturing Estate
Mount Pleasant, Wembley
Middlesex. HA0 1RR

Tel: + 44 (0) 20 8900 0671


IMPORTANT NOTICE! Due to our policy of continual
Fax: + 44 (0) 20 8900 0674
product i mprovement CP
This device should be installed by a qualified electrician Electronics reserves the right to www.cpelectronics.co.uk
in accordance with the latest edition of the IEE wiring alter the specification of this enquiry@cpelectronics.co.uk
regulations. product without prior notice.

Ref: %WD004 Issue 2

You might also like