Pulser Guide
Supported Pulsers & Wiring
FuelCloud, Inc.
100 S. Elliott Rd.
Newberg, OR97132
Change Log V1
A. Initial release.
B. Updated Veeder-Root pulser information.
©2017 FuelCloud Inc. Manual 1 Rev. A 2
Supported Pulser Listing
Brand Model Type Pulses Per Unit
Balcrank Impulse Contact 10
GPI Conditioned Digital 700*
Output Module
ICS MR1 Contact 10
MidCom MCR-90 Digital 10/100
OPW 500 Contact 10/100
OPW 800-f Contact 10
PMP Rapid-Fire Contact 10
Sotera 825P / 850P Digital 10/100
Veeder-Root 7697/1871/7671 Digital 100
Veeder-Root Contact 10
*Note: Pulse rate subject to change based on manufactures
calibration. Check pulser for exact pulse rate.
©2017 FuelCloud Inc. Manual 1 Rev. A 3
Unsupported Pulsers / Dispenser
Brand Model Type Pulses Per Unit
Gilbarco 2 Wire Dispenser Digital NA
Wayne Dispenser Digital NA
Tokheim Dispenser Digital NA
Note: This list is subject to change as FuelCloud is constantly
working to add support for 3rd party equipment.
Manual 1 Rev. A 4
Balcrank
CloudBox / CloudLink Balcrank Impulse
PWR
ENC / FILL Red
GND Black
• The Balcrank Impulse meter is a 2 wire contact pulser that
connects to ENC/ FILL and GND. The polarity of the wires
does not matter.
• In order to receive accurate pulses from the Balcrank meter,
the CloudBox firmware needs to be on V2.138 or higher.
©2017 FuelCloud Inc. Manual 1 Rev. A 5
GPI
CloudBox / CloudLink GPI Conditioned Output
PWR Red
ENC / FILL White
GND Black
• The GPI conditioned output module is a 3 wire digital pulser.
©2017 FuelCloud Inc. Manual 1 Rev. A 6
ICS MR1
The ICS MR1 is compatible
with:
• Fill Rite 800 & 900 registers.
• Dresser Wayne 700R
• GPI MR-5-30
CloudBox / CloudLink ICS MR1
PWR
ENC / FILL Red / Blue*
GND Red / Blue*
Power ICS MR1
110VAC Line Black
Neutral White
Earth Ground Green
• The ICS MR1 is a 2 wire contact pulser
• *Note: If there are blue wires, then the pulser is a dual output variant. These
wires do not need to be plugged into FuelCloud unless the second output is
needed.
• The ICS MR1 requires power (AC or DC depending on the model) that the
CloudBox and CloudLink do not provide.
• For installation into registers see page 14, 15, or 16.
©2017 FuelCloud Inc. Manual 1 Rev. A 7
MidCom
©2017 FuelCloud Inc. Manual 1 Rev. A 8
OPW 500
The OPW 500 is compatible
with:
• Fill Rite 800 & 900 registers.
• Dresser Wayne 700R
• GPI MR-5-30
CloudBox / CloudLink OPW 500
PWR
ENC / FILL Red / Blue*
GND Red / Blue*
Power OPW 500
110VAC Line Black
Neutral White
Earth Ground Green
• The OPW 500 is a 2 wire contact pulser
• *Note: If there are blue wires, then the pulser is a dual output variant. These
wires do not need to be plugged into FuelCloud unless the second output is
needed.
• The ICS MR1 requires power (AC or DC depending on the model) that the
CloudBox and CloudLink do not provide.
• For installation into registers see page 14, 15, or 16.
©2017 FuelCloud Inc. Manual 1 Rev. A 9
OPW 500 Continued
• The OPW 500 is configurable to output 10 or 100 pulses per
gallon. The diagram above shows the jumper position for the
desired output.
©2017 FuelCloud Inc. Manual 1 Rev. A 10
OPW 800-f
The OPW 800-f is compatible
with:
• Fill Rite 800 & 900 registers.
• Dresser Wayne 700R
• GPI MR-5-30
CloudBox / CloudLink OPW 800-f
PWR
ENC / FILL Red / Blue*
GND Red / Blue*
Power OPW 800-f
110VAC Line Black
Neutral White
Earth Ground Green
• The OPW 800-f is a 2 wire contact pulser
• *Note: If there are blue wires, then the pulser is a dual output variant. These
wires do not need to be plugged into FuelCloud unless the second output is
needed.
• The ICS MR1 requires power (AC or DC depending on the model) that the
CloudBox and CloudLink do not provide.
• For installation into registers see page 14, 15, or 16.
©2017 FuelCloud Inc. Manual 1 Rev. A 11
PMP Rapid-Fire
The PMP Rapid-Fire is
compatible with:
• Fill Rite 800 & 900 registers.
• Dresser Wayne 700R
• GPI MR-5-30
CloudBox / CloudLink PMP Rapid Fire
PWR
ENC / FILL Red / Blue*
GND Red / Blue*
Power PMP Rapid Fire
110VAC Line Black
Neutral White
Earth Ground Green
• The PMP Rapid-Fire is a 2 wire contact pulser
• *Note: If there are blue wires, then the pulser is a dual output variant. These
wires do not need to be plugged into FuelCloud unless the second output is
needed.
• The ICS MR1 requires power (AC or DC depending on the model) that the
CloudBox and CloudLink do not provide.
• For installation into registers see page 14, 15, or 16.
©2017 FuelCloud Inc. Manual 1 Rev. A 12
Sotera 825P / 850P
CloudBox / CloudLink Sotera 825P / 850P
PWR Red
ENC / FILL White
GND Black
• The Sotera 825P/ 850P is a 3 wire digital pulser.
• The Sotera output includes 6 wires, but the CloudBox and
CloudLink only require 3.
©2017 FuelCloud Inc. Manual 1 Rev. A 13
Sotera 825P / 850P Continued
CloudBox / CloudLink Sotera 825P / 850P
PWR Red
ENC / FILL White
GND Black
• To adjust the pulse rate see the Sotera 825P / 850P manual.
The default setting is 10 pulses per unit.
©2017 FuelCloud Inc. Manual 1 Rev. A 14
Veeder-Root 7697, 7671
CloudBox / CloudLink 7697, 7671
PWR Red
ENC / FILL Black
GND White
• The 7697 and 7671 Veeder-Root pulsers are 3 wire digital
pulsers.
©2017 FuelCloud Inc. Manual 1 Rev. A 15
Veeder-Root 7671
CloudBox / CloudLink 1871
PWR
ENC / FILL Black
GND Black
• The Veeder-Root 7671 pulser is a 2 wire contact pulser that
connects to ENC/ FILL and GND. The polarity of the wires
does not matter.
• In order to receive accurate pulses from the 7671 pulser, the
CloudBox firmware needs to be on V2.138 or higher.
©2017 FuelCloud Inc. Manual 1 Rev. A 16
Fill Rite 800 & 900 Installation
• http://www.intconsys.com/pdf/MR1_FR%20INSTALLATION%20110VAC.pdf
©2017 FuelCloud Inc. Manual 1 Rev. A 17
Dresser Wayne Installation
• http://www.intconsys.com/pdf/MR1_DW%20INSTALLATION%20110VAC.pdf
©2017 FuelCloud Inc. Manual 1 Rev. A 18
GPI MR 5-30 Installation
• http://www.intconsys.com/pdf/MR1_GPI%20INSTALLATION%20110VAC.pdf
©2017 FuelCloud Inc. Manual 1 Rev. A 19
Sources Cited
• MR1 Pulser Link. N.p., n.d. Web. 02 June 2017.
<http://www.intconsys.com/index.php/mr1-pulser-link>.
• "Sotera Operation and Safety Manual." Sotera Systems. N.p., n.d. Web. 2 June 2017.
<https://www.fillrite.com/dam/4060.pdf>.
• "Switchable PMP Rapid-Fire™ Pulser Installation Instructions." PMP Corperation. N.p.,
n.d. Web. 2 June 2017. <http://www.pmp-corp.com/customer-
content/www/cms/files/143_Switchable_Rapid_Fire_Installation_Instructions_48503_7
_9_2014.pdf>.
• "Model 800-F Pulser." OPW Fuel Management Systems. N.p., n.d. Web. 2 June 2017.
<http://www.opwglobal.com/docs/libraries/manuals/electronic-systems/opw-fms-
manuals/M00-4000800F_Model_800F_Pulser_Installation_Guide.pdf?sfvrsn=4>.
• "Model 500 Pulser." OPW Fuel Management Systems. N.p., n.d. Web. 2 June 2017.
<http://www.opwglobal.com/docs/libraries/manuals/electronic-systems/opw-fms-
manuals/M00-4000500_Model_500_Pulser_Installation_Guide.pdf?sfvrsn=4>.
©2017 FuelCloud Inc. Manual 1 Rev. A 20