Pulser Guide

Supported Pulsers & Wiring

FuelCloud, Inc.
100 S. Elliott Rd.
Newberg, OR97132
Change Log V1
A. Initial release.
B. Updated Veeder-Root pulser information.

©2017 FuelCloud Inc. Manual 1 Rev. A 2


Supported Pulser Listing

Brand Model Type Pulses Per Unit

Balcrank Impulse Contact 10

GPI Conditioned Digital 700*


Output Module
ICS MR1 Contact 10

MidCom MCR-90 Digital 10/100

OPW 500 Contact 10/100

OPW 800-f Contact 10

PMP Rapid-Fire Contact 10

Sotera 825P / 850P Digital 10/100

Veeder-Root 7697/1871/7671 Digital 100

Veeder-Root Contact 10

*Note: Pulse rate subject to change based on manufactures


calibration. Check pulser for exact pulse rate.

©2017 FuelCloud Inc. Manual 1 Rev. A 3


Unsupported Pulsers / Dispenser

Brand Model Type Pulses Per Unit

Gilbarco 2 Wire Dispenser Digital NA

Wayne Dispenser Digital NA

Tokheim Dispenser Digital NA

Note: This list is subject to change as FuelCloud is constantly


working to add support for 3rd party equipment.

Manual 1 Rev. A 4
Balcrank

CloudBox / CloudLink Balcrank Impulse


PWR
ENC / FILL Red
GND Black

• The Balcrank Impulse meter is a 2 wire contact pulser that


connects to ENC/ FILL and GND. The polarity of the wires
does not matter.
• In order to receive accurate pulses from the Balcrank meter,
the CloudBox firmware needs to be on V2.138 or higher.

©2017 FuelCloud Inc. Manual 1 Rev. A 5


GPI

CloudBox / CloudLink GPI Conditioned Output


PWR Red
ENC / FILL White
GND Black

• The GPI conditioned output module is a 3 wire digital pulser.

©2017 FuelCloud Inc. Manual 1 Rev. A 6


ICS MR1

The ICS MR1 is compatible


with:
• Fill Rite 800 & 900 registers.
• Dresser Wayne 700R
• GPI MR-5-30

CloudBox / CloudLink ICS MR1


PWR
ENC / FILL Red / Blue*
GND Red / Blue*
Power ICS MR1
110VAC Line Black
Neutral White
Earth Ground Green
• The ICS MR1 is a 2 wire contact pulser
• *Note: If there are blue wires, then the pulser is a dual output variant. These
wires do not need to be plugged into FuelCloud unless the second output is
needed.
• The ICS MR1 requires power (AC or DC depending on the model) that the
CloudBox and CloudLink do not provide.
• For installation into registers see page 14, 15, or 16.
©2017 FuelCloud Inc. Manual 1 Rev. A 7
MidCom

©2017 FuelCloud Inc. Manual 1 Rev. A 8


OPW 500

The OPW 500 is compatible


with:
• Fill Rite 800 & 900 registers.
• Dresser Wayne 700R
• GPI MR-5-30

CloudBox / CloudLink OPW 500


PWR
ENC / FILL Red / Blue*
GND Red / Blue*
Power OPW 500
110VAC Line Black
Neutral White
Earth Ground Green
• The OPW 500 is a 2 wire contact pulser
• *Note: If there are blue wires, then the pulser is a dual output variant. These
wires do not need to be plugged into FuelCloud unless the second output is
needed.
• The ICS MR1 requires power (AC or DC depending on the model) that the
CloudBox and CloudLink do not provide.
• For installation into registers see page 14, 15, or 16.
©2017 FuelCloud Inc. Manual 1 Rev. A 9
OPW 500 Continued

• The OPW 500 is configurable to output 10 or 100 pulses per


gallon. The diagram above shows the jumper position for the
desired output.

©2017 FuelCloud Inc. Manual 1 Rev. A 10


OPW 800-f

The OPW 800-f is compatible


with:
• Fill Rite 800 & 900 registers.
• Dresser Wayne 700R
• GPI MR-5-30

CloudBox / CloudLink OPW 800-f


PWR
ENC / FILL Red / Blue*
GND Red / Blue*
Power OPW 800-f
110VAC Line Black
Neutral White
Earth Ground Green
• The OPW 800-f is a 2 wire contact pulser
• *Note: If there are blue wires, then the pulser is a dual output variant. These
wires do not need to be plugged into FuelCloud unless the second output is
needed.
• The ICS MR1 requires power (AC or DC depending on the model) that the
CloudBox and CloudLink do not provide.
• For installation into registers see page 14, 15, or 16.
©2017 FuelCloud Inc. Manual 1 Rev. A 11
PMP Rapid-Fire

The PMP Rapid-Fire is


compatible with:
• Fill Rite 800 & 900 registers.
• Dresser Wayne 700R
• GPI MR-5-30

CloudBox / CloudLink PMP Rapid Fire


PWR
ENC / FILL Red / Blue*
GND Red / Blue*
Power PMP Rapid Fire
110VAC Line Black
Neutral White
Earth Ground Green
• The PMP Rapid-Fire is a 2 wire contact pulser
• *Note: If there are blue wires, then the pulser is a dual output variant. These
wires do not need to be plugged into FuelCloud unless the second output is
needed.
• The ICS MR1 requires power (AC or DC depending on the model) that the
CloudBox and CloudLink do not provide.
• For installation into registers see page 14, 15, or 16.
©2017 FuelCloud Inc. Manual 1 Rev. A 12
Sotera 825P / 850P

CloudBox / CloudLink Sotera 825P / 850P


PWR Red
ENC / FILL White
GND Black

• The Sotera 825P/ 850P is a 3 wire digital pulser.


• The Sotera output includes 6 wires, but the CloudBox and
CloudLink only require 3.

©2017 FuelCloud Inc. Manual 1 Rev. A 13


Sotera 825P / 850P Continued

CloudBox / CloudLink Sotera 825P / 850P


PWR Red
ENC / FILL White
GND Black

• To adjust the pulse rate see the Sotera 825P / 850P manual.
The default setting is 10 pulses per unit.

©2017 FuelCloud Inc. Manual 1 Rev. A 14


Veeder-Root 7697, 7671

CloudBox / CloudLink 7697, 7671


PWR Red
ENC / FILL Black
GND White

• The 7697 and 7671 Veeder-Root pulsers are 3 wire digital


pulsers.

©2017 FuelCloud Inc. Manual 1 Rev. A 15


Veeder-Root 7671

CloudBox / CloudLink 1871


PWR
ENC / FILL Black
GND Black

• The Veeder-Root 7671 pulser is a 2 wire contact pulser that


connects to ENC/ FILL and GND. The polarity of the wires
does not matter.
• In order to receive accurate pulses from the 7671 pulser, the
CloudBox firmware needs to be on V2.138 or higher.

©2017 FuelCloud Inc. Manual 1 Rev. A 16


Fill Rite 800 & 900 Installation
• http://www.intconsys.com/pdf/MR1_FR%20INSTALLATION%20110VAC.pdf

©2017 FuelCloud Inc. Manual 1 Rev. A 17


Dresser Wayne Installation
• http://www.intconsys.com/pdf/MR1_DW%20INSTALLATION%20110VAC.pdf

©2017 FuelCloud Inc. Manual 1 Rev. A 18


GPI MR 5-30 Installation
• http://www.intconsys.com/pdf/MR1_GPI%20INSTALLATION%20110VAC.pdf

©2017 FuelCloud Inc. Manual 1 Rev. A 19


Sources Cited

• MR1 Pulser Link. N.p., n.d. Web. 02 June 2017.


<http://www.intconsys.com/index.php/mr1-pulser-link>.
• "Sotera Operation and Safety Manual." Sotera Systems. N.p., n.d. Web. 2 June 2017.
<https://www.fillrite.com/dam/4060.pdf>.
• "Switchable PMP Rapid-Fire™ Pulser Installation Instructions." PMP Corperation. N.p.,
n.d. Web. 2 June 2017. <http://www.pmp-corp.com/customer-
content/www/cms/files/143_Switchable_Rapid_Fire_Installation_Instructions_48503_7
_9_2014.pdf>.
• "Model 800-F Pulser." OPW Fuel Management Systems. N.p., n.d. Web. 2 June 2017.
<http://www.opwglobal.com/docs/libraries/manuals/electronic-systems/opw-fms-
manuals/M00-4000800F_Model_800F_Pulser_Installation_Guide.pdf?sfvrsn=4>.
• "Model 500 Pulser." OPW Fuel Management Systems. N.p., n.d. Web. 2 June 2017.
<http://www.opwglobal.com/docs/libraries/manuals/electronic-systems/opw-fms-
manuals/M00-4000500_Model_500_Pulser_Installation_Guide.pdf?sfvrsn=4>.

©2017 FuelCloud Inc. Manual 1 Rev. A 20

You might also like