100% found this document useful (1 vote)
136 views5 pages

ADVR-2200M: Universal Hybrid Analog-Digital Voltage Regulator Operation Manual

This document is an operation manual for the ADVR-2200M universal hybrid analog-digital voltage regulator. It provides specifications for the regulator's sensing inputs, power inputs, excitation output, adjustments, and installation instructions. The regulator can be used for 1 or 3 phase generators from 3.5 to 7 amps and includes protections such as under frequency, over excitation, and soft start ramp time.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
100% found this document useful (1 vote)
136 views5 pages

ADVR-2200M: Universal Hybrid Analog-Digital Voltage Regulator Operation Manual

This document is an operation manual for the ADVR-2200M universal hybrid analog-digital voltage regulator. It provides specifications for the regulator's sensing inputs, power inputs, excitation output, adjustments, and installation instructions. The regulator can be used for 1 or 3 phase generators from 3.5 to 7 amps and includes protections such as under frequency, over excitation, and soft start ramp time.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 5

ADVR-2200M

Universal Hybrid Analog-Digital


Voltage Regulator Operation Manual

Hybrid Universal Analog / Digital 1 or 3 Phase 3.5 Amp Self Excited,


Shunt, Auxiliary Winding, Harmonic Power or PMG Automatic
Voltage Regulator Easy to Set-Up and Program Install Manual

Use with KUTAI IVT-1260 / IVT-2460 add-on module can boost


generator motor starting capacity.

KUTAI ELECTRONICS INDUSTRY CO., LTD.


TEL : +886-7-8121771 FAX : +886-7-8121775 Website : www.kutai.com.tw
Headquarters : No.3, Ln. 201, Qianfu St., Qianzhen Dist., Kaohsiung City 80664, Taiwan
SECTION 1 : SPECIFICATION
Sensing Input (E1, E2, E3) Average Reading Static Power Dissipation
Voltage 220  600 Vac, 1 phase / 3 phase Max. 12 watts
DIP switch setting
180  280 Vac @ 220 Vac Burden in SHUNT & PMG Wiring
330  515 Vac @ 380 / 440 Vac 550 VA @ power input 110 Vac
420  660 Vac @ 480 / 600 Vac 1100 VA @ power input 220 Vac
Frequency 50/60 Hz, DIP switch setting
Quadrature Droop Input (C1, C2)
Power Input (P1, P2) CT 1A or 5A greater than 5VA (DIP switch setting)
Voltage 60  300 Vac, 1 phase 2 wire Sensitivity +/- 7% @ PF +/- 0.5 (Droop adjustable)
Frequency 50  500 Hz
Analogue Voltage Input (A1, A2)
Auxiliary Input (P3, P4) Input resistance greater than 2K ohms
Voltage 40  300 Vac, 1 phase 2 wire Max. Input +/- 5 Vdc or +10 Vdc
Frequency 40  500 Hz Sensitivity 1 Vdc for 2.5% Generator Volts (adjustable)

Excitation Output (F+, F-) Under Frequency Protection (Factory Presets)


110V 1 phase Continuous 63 Vdc 3.5A 50 Hz system presets knee point at 45 Hz
Max. 90 Vdc 7A for 10 secs. 60 Hz system presets knee point at 55 Hz
220V 1 phase Continuous 125 Vdc 3.5A
Max. 180 Vdc 7A for 10 secs. Over Excitation Protection
220V 3 phase Continuous 150 Vdc 3.5A Set point 125 Vdc +/- 4 % @ power input 220 Vac
Max. 215 Vdc 7A for 10 secs. Inverse-time curve. This function can be turned off.
Resistance ≧ 18 ohms @ power input 110 Vac
≧ 36 ohms @ power input 220 Vac Voltage Thermal Drift
Max. 100 ohms Less than 3% at temperature range -40 to +70 ˚C
Fuse Spec. Slow blow 5 x 20 mm S505-5A
Under-Frequency Knee Point Thermal Drift
External Voltage Adjustment (VR1, VR2) Less than +/- 0.1 Hz at -40 to +70 ˚C
Max. +/- 5% @ 500 ohms 1 watt potentiometer
Max. +/- 10% @ 1K ohm 1 watt potentiometer Environment
Operating Temperature -40 to +60 ˚C
Voltage Regulation Storage Temperature -40 to +85 ˚C
Less than +/- 0.5% ( with 4% engine governing ) Relative Humidity Max. 95%
Vibration 5.5 Gs @ 60 Hz
Build Up Voltage
5 Vac 25 Hz residual volts at power input terminal Dimensions
150.0 (L) x 135.0 (W) x 55.5 (H) mm
Soft Start Ramp Time 5.91 (L) x 5.31 (W) x 2.19 (H) inch
4 seconds +/- 10%
Weight
Typical System Response 470 g +/- 2%
Less than 20 milliseconds 1.04 lb +/- 2%

EMI Suppression
Internal electromagnetic interference filtering

___________________________________________________________________________________________
2 ADVR-2200M
SECTION 2 : OUTLINE / SIZE / INSTALLATION REFERENCE

Unit : mm

Figure 1 Outline Drawing

ATTENTION
1. AVR can be mounted directly on the engine, genset, switchgear, control panel, or any position that will
not affect operation. For dimension reference, please see Figure 1.
2. All voltage readings are to be taken with an average-reading voltmeter Meggers and high-potential test
equipment must not be used. Use of such equipment could damage the AVR.
3. Terminal:“Fast-On” terminals 6.35 mm (1/4 inch).
4. Improper setting of under-frequency protection could cause the output voltage of the unit to drop or
become unstable under with changes in load. Avoid making any changes to the U/F setting unless
necessary.
5. Turn off O/E in AVR when paralleling.

SECTION 3 : DIP SWITCH PROGRAMMING

ON ON SW1
SW1 SW2 SW1-1 & SW1-2 Sets the Generators Sensing Voltage
1 2 1 2 3 4 5 6
SW2
SW2-1 Set Sensing Voltage for 1 or 3 Phase
SW2-2 Set Generator Frequency
SW2-3 Set Over Excitation Protection ON or OFF
SW2-4 & 5 Sets Generator Capacity
SW2-6 Sets Capacity of Droop CT

___________________________________________________________________________________________
ADVR-2200M 3
SECTION 4 : ADJUSTMENTS
U/F Under Frequency Protection
Adjustment When generator s p e e d falls LED Indicator lit up when the generator is
below the knee point, the under frequency in U/F (Under Frequency Protection) and
protection circuit will activate and the O/E (Over Excitation Protection).
voltage and frequency begin to decrease
in linear descend.
Select frequency 50 or 60 Hz according to
the generator in use. DROOP Droop Adjustment
When paralleling, the AVR increase or
DIP U/F Dip Adjustment decrease its voltage output, when
When U/F protection is activated, the phase current leads or lag the voltage.
voltage droop ratio can be adjusted via The increase and decrease range can
this DIP (POT). The adjustable range is be preset by the DROOP adjustment.
310 V/Hz.

STAB Stability Adjustment TRIM Trim Adjustment


Correct stability adjustment must be When terminal A1 and A2 are biased
conducted while the generator is with a DC voltage (010V), the TRIM is
operating without load. First adjust the then used to adjust the influence on the
STAB potentiometer (POT) anti- output voltage of the AVR. If the TRIM
clockwise until the voltage becomes VOLT Voltage Adjustment (POT) is adjusted fully counter-
unstable, and then slightly adjust it Generator rated output voltage clockwise, any bias voltage will not
clockwise (About1/5 turn). When the adjustment. cause any influence. On the contrary if
voltage just reaches the critical point the TRIM is adjusted fully clockwise,
Must be in accordance with the then any signal will produce a maximum
(Knee point) of stabilization, where the DIP Switch SW1-1 & 2 voltage
voltage is stable yet very close to 10% effect.
range setting.
becoming unstable.
Figure 2

SECTION 5 : WIRING CONNECTIONS

ON ON ON ON

P3 P4 Aux. Power Input C1 C1

P4 and P1 are C2 Set the DIP SW Correctly C2 Set the DIP SW Correctly
concurrent P3
P3
(internal short circuit)
P4 P4

VR1 & VR2 are VR1 ADVR-2200M VR1 ADVR-2200M


VR2 VR2
Normally Bridged
and Voltage is A1 A1

Adjusted on the A2 A2
PCB
1K Ohm 1W

0 to 10 Vdc
Analog lnput
Only use when Paralleling
E1 E2 E3 P2 P1 F+ F- E1 E2 E3 P2 P1 F+ F-
to Correct (PF)

CT is only used
CT. CT.
when paralleling
T T
Exciter

Exciter

S S
R R
N N
Stator Wires Stator Wires
Generator PMG Generator

Figure 3 PMG Connection Figure 4 Shunt Connection (220V)

___________________________________________________________________________________________
4 ADVR-2200M
ON ON

C1

C2 Set the DIP SW Correctly

P3

P4

VR1 ADVR-2200M
VR2

A1

A2

E1 E2 E3 P2 P1 F+ F-

(Harmonic)
AUX. wires
CT.
T

Exciter
S
R
N
Stator Wires
Generator

Figure 5 Auxiliary Winding (AUX.) Connection

Shunt with IVT wiring diagram

ON ON

C1

C2 Set the DIP SW Correctly

P3

P4

VR1 ADVR-2200M
VR2

A1
S2

S1

OUT2

OUT1

A2
Droop
%

Time
ON

Test
IVT
Fuse
Output
Ready

Test
Batt-Volt
B B+ E1 E2 E3 P2 P1 F+ F-
OVLD

CT.
T
Exciter

S
+ R
N
Stator Wires

Generator

Figure 6 ADVR-2200M & IVT-1260 / IVT-2460 Wiring Connection

ATTENTION
1. All AC voltage readings are average value only.
2. Use a remote 500 ohms 1 watt external VR for +/- 5% adjustment range. (keep shorted if not used)
3. Use a remote 1K ohm 1 watt external VR for +/- 10% adjustment range.
4. Sensing Voltage can be set from 220 – 600 Vac Program SW1-1 & 2 correctly.
5. For single phase sensing bridge E2 & E3 and move SW2-1 to OFF.
6. If your PMG is not working you can also power the AVR in shunt using terminals P1 & P2 connected to
the output of the generator as long as it’s less than 277 Vac.

※ Use only the replacement fuses specified in this user manual.


※ Appearance and specifications of products are subject to change for improvement without prior notice.

___________________________________________________________________________________________
ADVR-2200M 5

You might also like