Triconex                 TM
Technical Application Note #48, Rev. 10
Subject: Triconex Safety System Boundary and Reviewed Devices
Affected Products
Triconex™ Tricon™, Tricon CX, Trident™, and Triconex General Purpose (Tri-GP) controllers
Introduction
This Technical Application Note (TAN) provides a summary of third-party products tested by, or with oversight
from, Schneider Electric® to show interoperability with Triconex products. The list of third-party products is
exemplary and is not intended to be all inclusive of hardware that is interoperable with Triconex products. The
scope of third-party products reviewed for interoperability includes those within the TÜV-approved safety
boundary as well as those outside the TÜV-approved safety boundary.
Triconex safety systems maximize the TÜV-approved safety boundary when used with TÜV-approved
Triconex External Termination Panels (ETPs) and Interface Cables. The use of non-Triconex-approved
cables and/or ETPs limits the TÜV safety certification boundary and potentially limits the ability of the logic
solver to respond to safety demands. Networking equipment is a black channel and outside the TÜV-
approved safety boundary.
Background
IEC 61508 and IEC 61511 define a programmable electronic Safety Instrumented System (SIS) as consisting
of sensors, logic solvers, and final control elements, as shown in this figure.
                                           Logic                         Final
    Sensors
                                           Solver                      Elements
Figure 1 – Simplified SIS
Together, these elements implement Safety Instrumented Functions (SIF) of the target Safety Integrity Level
(SIL). To implement a safety-certified SIF, the system designer must choose safety-certified loop elements,
including sensors, final elements, logic solvers, and other interconnecting components.
Global Customer Support (GCS) Center
https://pasupport.schneider-electric.com
Part No. 9791005-048, Rev 10
March 22, 2022
                                                     Public
                                                                                                             2 of 11
In addition to the components shown in Figure 1, a typical SIS consists of other components such as cables
and external termination panels. Figure 2 shows the SIS including these components, which are used to
connect the sensors and final elements to the logic solvers.
Certifications
    •    TÜV approves the use of Triconex ETPs and interconnecting cables with the Tricon, Tricon CX,
         Trident, and Tri-GP Safety Logic Solvers within the boundary of the TÜV-Certified Safety System.
    •    TÜV certifies the use of the Tricon, Tricon CX, and Trident Safety Logic Solvers in up to SIL 3
         applications with the TÜV-approved ETPs and interconnecting cables in accordance with IEC 61508.
    •    TÜV certifies the use of the Tri-GP Safety Logic Solver in up to SIL 2 applications with the TÜV-
         approved ETPs and interconnecting cables in accordance with IEC 61508.
    •    Triconex ETPs are certified for electrical safety in full compliance with international standards by the
         Canadian Standards Association (CSA). They are qualified for general use in North America and
         other jurisdictions requiring compliance with these standards, as well as the European CE mark as
         per the Low Voltage Directive.
    •    Triconex ETPs and interconnecting cables comply with the applicable IEC EMC standard (IEC 61326-
         3-1, 2) which includes the European CE mark per the EMC directive.
    •    Tricon, Tricon CX, Trident, and Tri-GP ETPs that are approved for hazardous locations comply with
         North American Class I, Division 2 and European ATEX Zone 2 requirements. Additionally, Tricon CX
         ETPs that are approved for hazardous locations also comply with IECEx Zone 2 requirements.
The boundary of the TÜV-Certified Safety System extends up to the ETPs, including the Interface Cables, as
shown in Figure 2 below. The use of non-Triconex ETPs or cables, even those with some form of TÜV
approval which are not part of this certified system, may reduce the TÜV-Certified Safety System boundary.
                                         Approved external
                                                                              Approved external
                                         termination panel
                                                                              termination panel
                                         and cable
                                                                              and cable
                     End-user
                     installed                                                               End-user
                     field wiring                                                            installed
                                                                                             field wiring
                                 External                Logic         External
                                                                                                    Final
   Sensors                      Termination              Solver       Termination
                                                                                                  Elements
                                   Panel                (Tricon)         Panel
Boundary with use of non                                                              Boundary of
Triconex external                                                                     TÜV-Certified
termination panels or cables                                                          Safety System
Figure 2 – Safety System Boundary
Approved ETPs and Interface Cables are listed in the Field Termination Guide for Tricon Systems, the
Planning and Installation Guide for Trident Systems, the Planning and Installation Guide for Tri-GP Systems,
and the Tricon CX Addendum to Tricon User Guides which are available on the Global Customer Support
(GCS) website.
Schneider Electric in Lake Forest, California controls the design, configuration management, supply chain
management, and quality assurance for Triconex ETPs and cable assemblies, as well as sourcing of
approved ETPs and Interface Cables.
Technical Application Note 48                        March 22, 2022                      Part No. 9791005-048, Rev 10
                                                             Public
                                                                                                           3 of 11
Use of Unapproved Components
System component selection and safety standards compliance are the responsibility of the system integrator.
The use of non-Triconex cables and ETPs can potentially have a negative impact on compliance with the
applicable safety standards and the availability of the safety system. The use of non-Triconex-approved
equipment should be carefully evaluated before use.
See Appendix A for a list of devices that have been reviewed by the company and may be appropriate for
some applications.
Conclusion
The boundary of the safety system includes the ETPs and Interface Cables. To maximize the TÜV-approved
boundary, approved ETPs and cables must be used with the Tricon, Tricon CX, Trident, or Tri-GP Safety
Logic Solver. Non-Triconex ETPs and cables may be appropriate in some installations. Networking equipment
is outside the TÜV-approved safety boundary.
If you have any questions regarding this Technical Application Note, contact your regional support office or
the Global Customer Support (GCS) Center.
Appendix A – Reviewed Devices within Safety Boundary
After review and interoperability testing, the following third-party products used within the TÜV-approved
safety boundary were deemed compatible with Triconex products.
Refer to the manufacturer’s website for detailed product information, and installation and operation guidance.
External Termination Panels / Pluggable Conditioning Modules / Multiplexers
 GM International (GMI) External Termination Panels (ETPs) Used with GMI Pluggable Conditioning
 Modules (PCMs) and Tricon CX I/O Modules
 I/O Module           GMI ETP Model            ETP Details                Supported PCMs
 3506X DI             TBE-D5016-TRI-012        SIL3, HazLoc, 16 PCMs      D6001S, D5031S, D5032S, D5037S,
                                                                          D5038SA, D5039SA, D5093S,
                                                                          D5038XA, D5039XA
 3626X DO             TBE-D5016-TRI-007        SIL3, HazLoc, 16 PCMs      D6001S, D5040S, D5048S, D5049S,
                                                                          D5090S, D5091S, D5096S, D5097S,
                                                                          D5098S
 3722X AI,            TBE-D5016-TRI-011        SIL3, HazLoc, 16 PCMs      D5011S, D5014S, D5015SS,
 3723X AI                                                                 D5072S, D6001S, D6017SS
 3809X/AX AO          TB-D5016-TRI-010         SIL3, HazLoc, 16 PCMs      D5020S, D6001S
 3902X/AX UIO         TB-D5016-TRI-010         SIL3, HazLoc, 16 PCMs      D6001S, D6004S, D5031S, D5032S,
                                                                          D5037S, D5093S, D5038SB,
                                                                          D5039SB, D5049S, D5090S-102,
                                                                          D5091S-103, D5096S-106, D5097S-
                                                                          107, D5014S, D5015SK, D6017SK,
                                                                          D5072S-099, D5020S
 GMI PCMs Used with Tricon CX I/O Modules
 GMI PCM          I/O                                                                        Compatible I/O
 Model            Type          PCM Type   Details                                           Modules
Technical Application Note 48                        March 22, 2022                    Part No. 9791005-048, Rev 10
                                                          Public
                                                                                                            4 of 11
 GM International (GMI) External Termination Panels (ETPs) Used with GMI Pluggable Conditioning
 Modules (PCMs) and Tricon CX I/O Modules
 I/O Module   GMI ETP Model                ETP Details                  Supported PCMs
 Pass-Through
 D6001S           ANY           NIS1   SIL 3, Pass-Through, 2-Wire, 1 Channel                 3506X, 3626X,
                                                                                              3722X, 3723X,
                                                                                              3809X/AX,
                                                                                              3902X/AX
 D6004S           ANY           NIS    SIL 3, Pass-Through, 2- or 3-Wire, 1 Channel,          3902X/AX
                                       Power Terminals
 Digital Input (DI)
 D5093S         DI              NIS    SIL 3, 24 to 220 VAC/VDC Switch, Transistor            3506X, 3902X/AX
                                       Out, 1 Channel
 D5031S           DI            IS2    SIL 3, Switch/Proximity, Transistor Out, LFD3,         3506X, 3902X/AX
                                       1 Channel
 D5032S           DI            IS     SIL 3, Switch/Proximity, Relay Out, LFD,               3506X, 3902X/AX
                                       1 Channel
 D5037S           DI            IS     SIL 2, Switch/Proximity, Transistor Out, LFD,          3506X, 3902X/AX
                                       1 Channel
 D5038SA          SDI           IS     SIL 3, Switch/Proximity, Line Monitor Out, LFD,        3506X
 D5038XA                               FM4, 1 Channel
 D5038SB          SDI           IS     SIL 3, Switch/Proximity, Line Monitor Out, LFD,        3902X/AX
                                       FM4, 1 Channel
 D5039SA          SDI           IS     SIL 2, Switch/Proximity, Line Monitor Out, LFD,        3506X
 D5039XA                               FM4, 1 Channel
 D5039SB          SDI           IS     SIL 2, Switch/Proximity, Line Monitor Out, LFD,        3902X/AX
                                       FM4, 1 Channel
 Digital Output (DO)
 D5040S       DO                IS     SIL 3, Loop Powered, NE5 Load, 1 Channel               3626X
 D5048S           SDO           IS     SIL 3, Loop Powered, NE5 Load, LFD, FM,                3626X
                                       1 Channel
 D5049S           SDO           IS     SIL 3, Bus Powered, NE5 Load, LFD, FM,                 3626X, 3902X/AX
                                       1 Channel
 Relay Output
 D5090S7      DO                NIS    SIL 3, Relay Output, NE Load, 1 Channel                3626X, 3902X/AX
 D5090S-          DO            NIS    SIL 3, Relay Output, NE Load, 1 Channel                3902X/AX
 1027
 D5091S7          DO            NIS    SIL 3, Relay Output, ND6 Load, 1 Channel               3626X
 D5091S-          DO            NIS    SIL 3, Relay Output, ND Load, 1 Channel
                                                               6
                                                                                              3902X/AX
 1037
 D5096S7          SDO           NIS    SIL 3, Relay Output, NO8 Contact, NE or                3626X
                                       F&G9/ND Load, LFD, FM, 1 Channel
Technical Application Note 48                 March 22, 2022                            Part No. 9791005-048, Rev 10
                                                   Public
                                                                                                                    5 of 11
 GM International (GMI) External Termination Panels (ETPs) Used with GMI Pluggable Conditioning
 Modules (PCMs) and Tricon CX I/O Modules
 I/O Module             GMI ETP Model        ETP Details                        Supported PCMs
 D5096S-           SDO          NIS      SIL 3, Relay Output, NO Contact, NE or
                                                                     8
                                                                                                       3902X/AX
 1067                                    F&G9/ND Load, LFD, FM, 1 Channel
 D5097S7           SDO          NIS      SIL 3, Relay Output, NC10 Contact, NE or                      3626X
                                         F&G/ND Load, LFD, FM, 1 Channel
 D5097S-           SDO          NIS      SIL 3, Relay Output, NC10 Contact, NE or                      3902X/AX
 1077                                    F&G/ND Load, LFD, FM, 1 Channel
 D5098S            DO           NIS      SIL 3, Relay Output, NE Load, 1 Channel                       3626X
 Analog Input (AI)
 D5011S            AIH          IS       SIL 3, 2-Wire Passive, 4-20 mA, HART,                         3722X, 3723X
                                         1 Channel
 D5014S            AIH          IS       SIL 3, 2/4-Wire Active/Passive 4-20 mA, HART,                 3722X, 3723X,
                                         1 Channel                                                     3902X/AX
 D5015SK           AIH          IS       SIL 2, 2/4-Wire Active/Passive, 4-20 mA, HART,                3902X/AX
                                         1 Channel
 D5015SS           AIH          IS       SIL 2, 2/4-Wire Active/Passive, 4-20 mA, HART,                3722X, 3723X
                                         1 Channel
 D5072S            AI           IS       SIL 2, TC/RTD, Temperature Converter                    4-    3722X, 3723X,
 D5072S-                                 20 mA, 1 Channel                                              3902X/AX
 099
 D6017SK           AIH          NIS      SIL 3, 3/4-Wire Active 4-20 mA, 200 mA                        3902X/AX
                                         Transmitter Power, HART, 1 Channel
 D6017SS           AIH          NIS      SIL 3, 3/4-Wire Active 4-20 mA, 200 mA                        3722X, 3723X
                                         Transmitter Power, HART, 1 Channel
 Analog Output (AO)
 D5020S            AOH          IS       SIL 2, 4-20 mA, HART, LFD, 1 Channel                          3809X/AX,
                                                                                                       3902X/AX
 1
   NIS = not intrinsically safe                                 6
                                                                  ND = normally de-energized
 2
   IS = intrinsically safe                                      7
                                                                  Operational field voltage of 22.3 to 32 VDC
 3
   LFD = line and load fault detection                          8
                                                                  NO = normally open
 4
   FM = fault mirroring                                         9
                                                                  F&G = fire and gas
 5
   NE = normally energized                                      10
                                                                   NC = normally closed
Technical Application Note 48                  March 22, 2022                                   Part No. 9791005-048, Rev 10
                                                    Public
                                                                                                                                 6 of 11
 MTL Instruments
 Part or Model Number
 MTL4850-TR HART Multiplexer
 HCU3700/3703E HART Interface
 HCU3704E FTA + HART Interface
 HCU3805E HART Interface
 BPM32+Adapter (DI, DO, AI, AO) Motherboard
 BPM16U+Adapter (DI, DO, AI)
 Isolators
 MTL4015                              MTL4016                             MTL4024                        MTL4041B
 MTL4073                              MTL4045C                            MTL4061
P
 Pepperl+Fuchs (P+F) External Termination Panels (ETPs) Used with P+F Pluggable Conditioning
 Modules (PCMs) and Tricon CX I/O Modules
 I/O Module              P+F ETP Model1                  ETP Details                        Supported PCMs
 3506X DI                HiCTB16-TRX-RAC-                SIL3, HazLoc, 16 PCMs              HiC2821, HiC2841
                         PL-DI16
 3626X DO                HiCTB16-TRX-RAC-                SIL3, HazLoc, 16 PCMs              HiC2873, HiC2883, HiC5861,
                         PL-DO16                                                            HiC5863
 3722X AI,               HiCTB16-TRX-RAC-                SIL3, HazLoc, 16 PCMs              HiC2025, HiC2025A, HiC2025ES,
 3723X AI                PL-AI16                                                            HiC2025Y1, HiC2081
 3809X/AX AO             HiCTB16-TRX-RAC-                SIL3, HazLoc, 16 PCMs              HiC2031, HiC2031ES
                         PL-IO16
 3902X/AX UIO            HiCTB16-TRX-RAC-                SIL3, HazLoc, 16 PCMs              DI: HiC2821, HiC2841, HiC2853R4
                         PL-IO16                                                            DO: HiC2873, HiC2883, HiC5861,
                                                                                            HiC5863
                                                                                            AI: HiC2025, HiC2025A,
                                                                                            HiC2025ES, HiC2025Y1, HiC2081
                                                                                            AO: HiC2031, HiC2031ES
                                                                                            UIO: HiC2441
 1
     See the “Tricon CX Field Termination Specifications” section of the Tricon CX Addendum to Tricon User Guides for information on
     Triconex I/O Interface Cables.
Technical Application Note 48                              March 22, 2022                                  Part No. 9791005-048, Rev 10
                                                                 Public
                                                                                                                    7 of 11
 P+F PCMs Used with Tricon CX I/O Modules
 P+F PCM         I/O            PCM                                                                Compatible I/O
 Model           Type           Type           Details                                             Modules
 Digital Input (DI)
 HiC2821             SDI        IS             SIL 2, NAMUR or Dry Contact Input, Relay            3506X, 3902X/AX
                                               Output and LFD1, 1 Channel
 HiC2841             SDI        IS             SIL 2, NAMUR or Dry Contact Input, Passive          3506X, 3902X/AX
                                               Transistor Output and LFD1, 1 Channel
 HiC2853R4           SDI        IS             SIL 3, Input for Approved Dry Contacts or           3902X/AX
                                               SN/S1n Sensors, Passive Transistor Output
                                               (Resistive) and LFD1, 1 Channel
 Digital Output (DO)
 HiC2873             SDO        IS             SIL 32, Bus or Loop Powered, Output 40mA at         3626X, 3902X/AX
                                               12 VDC, LFD1, 1 Channel
 HiC2883             SDO        IS             SIL 3, Bus or Loop Powered, Output 45mA at          3626X, 3902X/AX
                                               12 VDC, LFD, 1 Channel
 Relay Output
 HiC5861      DO                NIS            SIL 3, Signal Conditioner (non-EX), Relay           3626X, 3902X/AX
                                               Contact Output for De-Energized to Safe
                                               Function, Test Pulse Immunity, 1 Channel
 HiC5863             DO         NIS            SIL 3, Signal Conditioner (non-EX), Relay           3626X, 3902X/AX
                                               Contact Output for Energized to Safe Function,
                                               Test Pulse Immunity, 1 Channel
 Analog Input (AI)
 HiC2025        AIH             IS             SIL 2, 2-Wire Active/Passive, 4-20 mA or 1V-        3722X, 3723X,
                                               5V, HART, 1 Channel                                 3902X/AX
 HiC2025A            AIH        IS             SIL 2, 2-Wire Active/Passive, 4-20 mA or 1V-        3722X, 3723X,
                                               5V, HART, Reduced Intrinsically Safe                3902X/AX
                                               Parameters, 1 Channel
 HiC2025ES           AIH        IS             SIL 3, 2-Wire Active/Passive, 4-20 mA or 1V-        3722X, 3723X,
                                               5V, HART, 1 Channel                                 3902X/AX
 HiC2025Y1           AIH        IS             SIL 2, 2-Wire Passive, 4-20 mA or 1V-5V,            3722X, 3723X,
                                               HART, 1 Channel                                     3902X/AX
 HiC2081             AI         IS             SIL 2, TC/RTD/Potentiometer or Voltage Input,       3722X, 3723X,
                                               4-20 mA Linearized Output, LFD, 1 Channel           3902X/AX
 Analog Output (AO)
 HiC2031      AOH               IS             SIL 2, 4-20 mA, HART, 1 Channel                     3809X/AX, 3902X/AX
 HiC2031ES           AOH        IS             SIL 3, 4-20 mA, HART, LFD, 1 Channel                3809X/AX, 3902X/AX
 Universal Input Output (UIO)
 HiC2441             UIO        IS             SIL 2, Auto Configuring Analog Input, Digital       3902X/AX
                                               Input3, Analog Output, Digital Output, HART,
                                               1 Channel
 1
   Line and load fault detection (LFD) is not propagated to the I/O Module, Field Alarm LED.
 2
   SIL 3 in loop powered mode only.
 3
   Special conditions of use for Digital Input use case.
Technical Application Note 48                             March 22, 2022                        Part No. 9791005-048, Rev 10
                                                                Public
                                                                                                       8 of 11
 P+F PCMs Used with Tricon I/O Modules
 P+F Models
 Termination Boards
 HiSHPTB/32/TR-AI-01                                     HiSHPTB/32/TR-AO-01
 HiSHPTB/32/TR-AI-01-Y1                                  HiSHPTB/32/TR-AI-03
 HiSHPTB/32/TR-AI-02                                     HiCTB16-TRI-DOISS-EL-PL-Y1
 HiDTB08-TRI-DOISD-EL-PL-Y1                              HiCTB32-TRI-DOISS-EL-PL-Y1
 HiDTB16-TRI-DOISD-EL-PL-Y2                              HiDTB16-TRI-AIISS-EL-PL
 HiDTB08-TRI-AIISD-EL-SC                                 HiDTB16-TRI-AIISD-EL-PL
 HiDTB08-TRI-AIISD-EL-PL                                 HiCTB16-TRI-DIISS-EL-PL
 HiCTB16-TRI-AIISS-EL-PL                                 HiCTB32-TRI-DIISS-EL-PL
 HiDTB16-TRI-DIISD-EL-PL                                 HiDTB08-TRI-DIISQ-EL-SC
 HiCTB16-TRI-DIISD-EL-PL                                 HiDTB08-TRI-AOISD-EL-PL
 HiDTB16-TRI-DIISQ-EL-SC                                 HiCTB08-TRI-AOISS-EL-PL
 Modules
 HiC2821                        HiC2822                  HiC2871                   HiC2025
 HiC2031                        HiC2873                  HiC2877                   HiD2872
 HiD2876                        HiD2082                  HiD2081                   HiD2026
 HiD2029                        HiD2030                  HiD2031                   HiD2822
 HiD2842                        HiD2844                  KFD2
 Motherboards
 MB-DI-TR                       MB-DO-TR                 MB-AI-TR                  MB-AO-TR
 HART Interface
 FI-PFH-TR-AI-370X-GP
 Phoenix Contact
 Part or Model Number
 Termination Boards
 VIP-TRICONEX-CX-ETP-16CH - 2908788
 Modules
 IOA FEED-THRU/EX - 2906598                              IOA-PSR-PS22 - 2702971
Technical Application Note 48              March 22, 2022                          Part No. 9791005-048, Rev 10
                                                Public
                                                                                                          9 of 11
 STAHL
 Part or Model Number
 Modules
 9161/DI-TR                     9161/DO-TR                   9161/GA-TR
 Isolators
 9103                           9118                         9123                    9124
 9150                           9151
 Weidmuller
 Part or Model Number
 Safety Relays
 SCS 24VDC P1SIL3DS I, mat. no. 2500980000
Appendix B – Reviewed Devices outside of Safety Boundary
After review and interoperability testing, the following third-party products used outside of the TÜV-approved
safety boundary were deemed compatible with Triconex products.
Refer to the manufacturer’s website for detailed product information, and installation and operation guidance.
Network Switches and Small Form-Factor Pluggables (SFPs)
Networking equipment is a black channel and outside the TÜV-approved safety boundary.
Refer to the Tricon CX Addendum to Tricon User Guides and Triconex System Security Reference Guide for
information on selecting and using networking equipment.
Network switch guidelines include:
    •    Switch Type: Managed
    •    Data Capacity: Average of 0.5Gbps per controller
    •    Virtual Local Area Network: VLAN support
    •    Ethernet Ports and Media: Chosen based on network architecture
    •    Certifications: IEC 62443-4-2 and hazardous locations, as required
For SFP modules, see the “Small Form-Factor Pluggable (SFP) Requirements” section of the Tricon CX
Addendum to Tricon User Guides.
Network equipment used with Triconex products is to have similar or better performance to that of the
equipment summarized below, which has been reviewed and tested for interoperability.
Technical Application Note 48                  March 22, 2022                         Part No. 9791005-048, Rev 10
                                                    Public
                                                                                                                                10 of 11
 Network Switches Used with Tricon CX Communication Modules1
 Switch Model Tested                              Switch Type
 Cisco SG300-10SFP                                10-Port Gigabit SFP Managed Switch
 Extreme Networks C5G124-48P2                     48-Port Gigabit SFP Managed Switch
 Extreme Networks C5K175-24                       24-Port Gigabit SFP Managed Switch
 1
     Network switches listed in this table have been reviewed and found to be compatible with the following Tricon CX products: 4355X and
     4610X.
 Network Switches Used with Tricon CX I/O Bus1
 Switch Model Tested                               Switch Type
 Cisco SG300-28SFP                                 28-Port Gigabit SFP Managed Switch
 Extreme Networks C5K175-24                        24-Port Gigabit SFP Managed Switch
 1
     Network switches listed in this table have been reviewed and found to be compatible with the following Tricon CX products: 3009X and
     4703X.
 Small Form-Factor Pluggable (SFP) Transceivers Used with Tricon CX Communication Modules1
 SFP Model Tested                                          Speed                    Fiber Type
 Cisco MFEFX1                                              100BASE-FX               multi-mode fiber (MMF)
 Cisco MFELX1                                              100BASE-LX               single-mode fiber (SMF)
 Cisco GLC-LX-SM-RGD                                       1000BASE-                single-mode fiber (SMF) or multi-mode
                                                           LX/LH                    fiber (MMF)
 Extreme Networks 1000BASE-BX-D SFP                        1000BASE-BX-D            single-mode fiber (SMF)
 Extreme Networks 1000BASE-BX-U SFP                        1000BASE-BX-U            single-mode fiber (SMF)
 Proline GLC-SX-MM-RGD-CDW                                 1000BASE-SX              multi-mode fiber (MMF)
 Proline GLC-ZX-SM-RGD-PRO                                 1000BASE-ZX              single-mode fiber (SMF)
 1
     SFPs listed in this table have been reviewed and found to be compatible with the following Tricon CX products: 4355X and 4610X.
 Small Form-Factor Pluggable (SFP) Transceivers Used with Tricon CX I/O Bus1
 SFP Model Tested                                       Max. Distance             Fiber Type
 Cisco GLC-LX-SM-RGD                                    1800 ft (550 m)           multi-mode fiber (MMF), or
                                                        6.2 mi (10 km)            single-mode fiber (SMF)
 Cisco GLC-SX-MM-RGD                                    1800 ft (550 m)           multi-mode fiber (MMF)
 Cisco GLC-ZX-SM-RGD                                    43.5 mi (70 km)           single-mode fiber (SMF)
 Perle PSFP-1000D-S1LC10D-XT                            6.2 mi (10 km)            single-mode fiber (SMF)
 Perle PSFP-1000D-S1LC10U-XT                            6.2 mi (10 km)            single-mode fiber (SMF)
 Proline GLC-ZX-SM-RGD-PRO                              43.5 mi (70 km)           single-mode fiber (SMF)
 Transition Networks TN-SFP-GE-S-C2                     1800 ft (550 m)           multi-mode fiber (MMF)
Technical Application Note 48                              March 22, 2022                                  Part No. 9791005-048, Rev 10
                                                                 Public
                                                                                                                                                                               11 of 11
 Small Form-Factor Pluggable (SFP) Transceivers Used with Tricon CX I/O Bus1
 SFP Model Tested                                                          Max. Distance                       Fiber Type
 Transition Networks TN-SFP-GE-L-C                               2
                                                                           6.2 mi (10 km)                      single-mode fiber (SMF)
 Transition Networks TN-SFP-GE-Z-C2                                        43.5 mi (70 km)                     single-mode fiber (SMF)
 1
     SFPs listed in this table have been reviewed and found to be compatible with the following Tricon CX products: 3009X and 4703X.
 2
     Conformal coated. We recommend the use of conformal coated SFPs in Safety Intelligent Enclosures (SIEs) and other outdoor
     installations.
©2008–2022 Schneider Electric Systems USA, Inc. All rights reserved.
The Schneider Electric brand and any trademarks of Schneider Electric SE and its subsidiaries referred to in this guide are the property of Schneider Electric SE or its
subsidiaries. All other brands may be trademarks of their respective owners.
This guide and its content are protected under applicable copyright laws and furnished for informational use only. No part of this guide may be reproduced or transmitted in
any form or by any means (electronic, mechanical, photocopying, recording, or otherwise), for any purpose, without the prior written permission of Schneider Electric.
Schneider Electric does not grant any right or license for commercial use of the guide or its content, except for a non-exclusive and personal license to consult it on an "as is"
basis. Schneider Electric products and equipment should be installed, operated, serviced, and maintained only by qualified personnel.
As standards, specifications, and designs change from time to time, information contained in this guide may be subject to change without notice. To the extent permitted by
applicable law, no responsibility or liability is assumed by Schneider Electric and its subsidiaries for any errors or omissions in the informational content of this material or
consequences arising out of or resulting from the use of the information contained herein.
Changes from Previous Release (Rev 9)
      Section                                   Description
      Introduction                              •      Added overview and purpose of TAN 48
      Conclusion                                •      Describes third-party products that are within and outside of the TÜV approved safety
                                                       boundary
      Appendix A                                •      Renamed the appendix and added to the overview
                                                •      Added compatible Pepperl+Fuchs external termination panels and pluggable
                                                       conditioning modules
      Appendix B                                •      New section added to identify “Reviewed Devices outside of Safety Boundary”
                                                •      Added reference and network switch guidelines to the “Network Switches and Small
                                                       Form-Factor Pluggables (SFPs)” sub-section
Global Customer Support (GCS) Contact Information
      Location                Americas GCS                                Asia Pacific GCS                           EURA GCS
                              Foxboro, MA, United States                  Shanghai                                   Baarn, Netherlands
      Contact                 +1-866-746-6477
      Information                                                         +86-21-37180086                            +31-3554-84125
                              International:
                              +1-508-549-2424
Technical Application Note 48                                                  March 22, 2022                                                     Part No. 9791005-048, Rev 10
                                                                                       Public