Contractor:
Consultant:
THIRD SAUDI EXPANSION OF THE HOLY
MOSQUE & SURROUNDING AREAS
Project Ref:
WIRES INSULATION RESISTANCE TEST (WITST)
Sub. Project Name : HARAM BUILDING
Date of Test :
DATE:
Subcontractor Name : IBLEC WIR No: Rev.
Zone: Area: Floor: Panel Name:
Meggering Result ( Giga Ohms )
Sr# Circuit No. Wire Size Breaker Home Run Circuit Length
Continuity Length Remarks
rating (M) (M)
L-L L-N L-E E-N
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
MEGGER MODEL / SERIAL NO. FLUKE 1555 MEGGER TEST VOLTAGE (VOLTS) 500 VDC
CALIBRATION VALIDITY DATE 30-Mar-20 DURATION (SECONDS) 60
AS THE PROJECT SPECIFICATION SECTION 16120 PART 3.5 (C )
THE INSULATION RESISTANCE VALUE SHALL BE GREATER THAN 1 Mohm AS PER BS 7671:2018, TABLE 64.
Approved by: Site Eng. Approved by: SBG QC Eng. Approved by: DAR Eng.
Name: NIJIN ALI Name: TAMER ISSA Name:
Sign: Sign: Sign:
Date: Date: Date:
Contractor:
Cons ul tant:
THIRD SAUDI EXPANSION OF THE HOLY
MOSQUE & SURROUNDING AREAS
Project Ref:
CABLES INSULATION RESISTANCE TEST (CITST) Date of Test : / /
DATE:
Sub. Project Name:
Subcontractor Name : WIR No: Rev.
Zone: Area: Floor:
Cables Description Cables Size Meggering Result ( Mega Ohms ) Continuty Cable
Sr# Length Remarks
From To Phase & Neutral Earth R-Y R-B Y-B R-N Y-N B-N N-E R Y B N E (M)
10
MEGGER MODEL / SERIAL NO. MEGGER TEST VOLTAGE (VOLTS)
CALIBRATION VALIDITY DATE DURATION (SECONDS)
AS THE PROJECT SPECIFICATION SECTION 16120 PART 3.5 (C )
THE INSULATION RESISTANCE VALUE SHALL BE GREATER THAN 1 Mohm AS PER BS 7671:2018, TABLE 64.
Approved by: Site Eng. Approved by: SBG QC Eng. Approved by: DAR Eng.
Name: Name: Name:
Sign: Sign: Sign:
Date: Date: Date: