COMPRESSOR DATA SHEET
In Accordance with Federal Uniform Test Method for Certain Lubricated Air Compressors
Rotary Compressor: Variable Frequency Drive
MODEL DATA - FOR COMPRESSED AIR
1 Manufacturer: Ingersoll Rand
Model Number R160NE-A145 Date: 8/18/2020
2 X Air-cooled Water-cooled Type: Screw C:\Users\nnbabu
# of Stages: 2
3* Full Load Operating Pressure b 100 psigb
4 Drive Motor Nominal Rating 200 hp
5 Drive Motor Nominal Efficiency 96.1 percent
6 Fan Motor Nominal Rating (if applicable) 5.4 hp
7 Fan Motor Nominal Efficiency 89.5 percent
Specific Power
Input Power (kW) Capacity (acfm) a,d
(kW/100 acfm)d
185.3 1060.0 17.48
160.0 935.5 17.10
8* 136.5 811.3 16.82
114.6 686.7 16.69
93.8 562.0 16.69
73.6 437.2 16.83
53.8 313.0 17.19
9* Total Package Input Power at Zero Flow c, d 0.0 kW
10 Isentropic Efficiency 78.4 percent
35
30
(kW/100ACFM)
Specific Power
25
20
11
15
10
0 200 400 600 800 1000 1200
Capacity (ACFM)
Note: Graph is only a visual representation of the data in section 8
Note: Y-axis scale 10 to 35, +5kW/100acfm increments if necessary above 35
X-Axis Scale, 0 to 25% over maximum capacity
* For models that are tested in the CAGI Performance Verification Program, these are the items verified by the third party program administrator
Consult CAGI website for a list of participants in the third party verificationwww.cagi.org
program:
NOTES: a. Measured at the discharge terminal point of the compressor package in accordance with ISO 1217, Annex C; ACFM is actual cubic feet per minute at
inlet conditions.
b. The operating pressure at which the Capacity (item 8) and Electrical Consumption (item 8) were measured
for this data sheet.
c. No Load Power. In accordance with ISO 1217, Annex E, if measurement of no load power equals less than 1%, manufacturer may state “not
significant” or “0” on the test report.
d Tolerance is specified in ISO 1217, Annex C, as shown in table below.
NOTE: The terms "power" and "energy" are synonymous for purposes of this document.
Volume Flow Rate Specific Energy No Load / Zero
Member at specified conditions Volume Flow Rate Consumption Flow Power
3
m / min ft3 / min % % %
Below 0.5 Below 17.6 +/- 7 +/- 8
0.5 to 1.5 17.6 to 53 +/- 6 +/- 7 +/- 10%
ROT 031.1 1.5 to 15 53 to 529.7 +/- 5 +/- 6
Above 15 Above 529.7 +/- 4 +/- 5
12/19 Rev 3 This form was developed by the Compressed Air and Gas Institute for the use of its members participating in the PVP. CAGI has not independently verified the reported data.