Series 3730 Electropneumatic Positioner Type 3730-2 and Type 3730-3 with HART communication
Application Single-acting or double-acting positioner for attachment to pneumatic control valves. Self-calibrating, automatic adaptation to valve and actuator. Reference variable 4 to 20 mA Travels 3.6 to 200 mm Opening angles 24 to 100
The positioner ensures a predetermined assignment of the valve stem position (controlled variable x) to the electric input signal (reference variable w). It compares the control signal received from a controller to the travel or opening angle of the control valve and issues a corresponding output signal pressure (output variable y). Special features Simple attachment to common linear and rotary actuators with SAMSON direct attachment interface (Fig. 1), NAMUR rib (Fig. 2), valves with rod-type yokes acc. to IEC 60534-6-1 or rotary actuators acc. to VDI/VDE 3845 (Fig. 3) Any desired mounting position Simple one-knob, menu-driven operation LCD easy to read in any mounting position due to selectable reading direction Configurable with a PC over the SSP interface using the TROVIS-VIEW software Variable, automatic start-up with four different initialization modes Preset parameters only values deviating from the standard need to be adjusted Calibrated travel sensor without gears susceptible to wear "Sub" initialization mode (substitution) allows the positioner to be started up in case of emergency whilst the plant is running without the valve moving through the whole travel range All parameters saved in EEPROM (protection against power failure) Two-wire system with a small electrical load between 300 and 410 depending on the version (see Table 1) Adjustable output pressure limitation Tight-closing function can be activated Continuous monitoring of zero point Integrated temperature sensor and operating hours counter Two standard configurable position alarms Self-diagnostics; alarms as condensed state conforming to NAMUR Recommendation NE 107, issued over a fault alarm contact or optional analog position transmitter Integrated EXPERTplus diagnostics (see T 8388 EN), suitable for valves for throttling and on/off service with additional partial stroke test for valves in safety-related applications Certified according to IEC 61508/SIL
Fig. 1 Type 3730, direct attachment to Type 3277 Pneumatic Actuator
Fig. 2 Type 3730, attachment to NAMUR rib
Fig. 3 Type 3730, attachment according to VDI/VDE 3845
Fig. 4 Type 3730, external position sensor with Type 3510 Micro-flow Valve
Versions Type 3730-2 Electropneumatic positioner with LCD, operable on site, local communication using SSP interface, EXPERTplus diagnostics Type 3730-3 Positioner as above, additionally with HART communication Type 3731 Ex d Positioner As above, additionally with HART communication See Data Sheet T 8387-3 EN
Associated Information Sheet
T 8350 EN
Edition December 2009
Data Sheet
T 8384-2/3 EN
Additional options Inductive limit switch with proximity switch Analog position transmitter with two-wire transmitter Forced venting function with solenoid valve Binary input External position sensor (Fig. 4) Stainless steel housing Principle of operation The electropneumatic positioner is attached to pneumatic control valves. It is used to assign the valve stem position (controlled variable x) to the input signal (reference variable w). The input signal received from a control system is compared to the travel or opening angle of the control valve and an output signal pressure (output variable y) is produced. The positioner consists of an electric travel sensor system (2), an analog i/p converter with a downstream booster and the electronics unit with microcontroller (5). When a deviation occurs, the actuator is pressurized or vented. If required, the changes in the signal pressure can be slowed down by a volume restriction. The signal pressure to the actuator can be limited by software to 1.4, 2.4 or 3.7 bar. A constant air stream to the atmosphere is created by the flow regulator (9) with a fixed set point. The air stream is used to purge the inside of the case as well as to optimize the air capacity booster. The i/p module (6) is supplied with a constant upstream pressure by the pressure regulator (8) to make it independent of the supply air pressure.
Operation The positioner is operated with a user-friendly rotary pushbutton. The parameters are selected by turning the knob, pushing it activates the required settings. In the menu, all parameters are listed in one level, meaning there is no need to search through submenus. All parameters can be checked and changed on site. All values are displayed on the LCD. The reading direction of the LCD can be rotated by 180 at the push of a button. The closing direction of the control valve is indicated to the positioner by the slide switch "Air to open/Air to close". It assigns the CLOSED position of the control valve to the 0 % reading. The INIT key activates initialization, which is started according to (pre)set parameters (autotune). After initialization has been completed, the positioner immediately starts control operation. To configure the positioner with SAMSONs TROVIS-VIEW configuration software, the positioner is equipped with an additional digital interface to be connected to the RS-232 interface of a PC. Additionally, all parameters of the Type 3730-3 Positioner can be accessed using HART communication.
22 20 Serial Interface
BE
16 13
mm
21 FSK
S
A3 15 19 A2 14 A1 14
Legend 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 Control valve Travel sensor Controller A/D converter Microcontroller i/p module Pneumatic booster Pressure regulator Flow regulator Volume restriction Inductive limit switch (optional) Solenoid valve (optional) Position transmitter or binary input (optional) Software limit switches Fault alarm output LCD Control of solenoid valve Galvanic isolation (optional) D/A converter Communication interface HART connection (Type 3730-3 only) Binary input BE (optional)
24V DC
PD
x 17 12 6 9 18 3
11
8 7 Q 10
1 x
Fig. 5 Functional diagram of Type 3730-2/-3 Positioner
T 8384-2/3 EN
Table 1 Technical data for Type 3730 Positioner
Common data for Type 3730-... Positioner Travel, adjustable Direct attachment to Type 3277 Actuator: Attachment acc. to IEC 60 534-6-1: Attachment to rotary actuators: 3.6 to 30 mm 3.6 to 200 mm 24 to 100 opening angle
Travel range Reference variable w
Adjustable Signal range Static destruction limit Supply pressure Air quality acc. to ISO 8573-1 (2001)
Within the initialized travel/opening angle Can be restricted to maximally 1/5 4 to 20 mA Two-wire device with reverse polarity protection Minimum span 4 mA 100 mA 3.6 mA for display 3.8 mA for operation 1.4 to 7 bar (20 to 105 psi) Max. particle size and density: Class 4 Oil content: Class 3 Pressure dew point: Class 3 or at least 10 K below the lowest ambient temperature to be expected 0 bar up to the capacity of the supply pressure Can be limited to 1.4 bar/2.4 bar/3.7 bar 0.2 bar using software Linear/equal percentage/reverse equal percentage User-defined (over operating software and communication) Butterfly valve, rotary plug valve and segmented ball valve: Linear/equal percentage 1 % 0.3 % 0.1 % Up to 240 s separately adjustable for exhaust and supply air via software Reversible Independent of supply air approx. 110 ln/h At p = 6 bar: 8.5 mn3/h At p = 1.4 bar: 3.0 mn3/h KVmax (20 C) = 0.09 At p = 6 bar: 14.0 mn3/h At p = 1.4 bar: 4.5 mn3/h KVmax (20 C) = 0.15 20 to +80 C 45 to +80 C with metal cable gland The limits in the EC Type Examination Certificate additionally apply for explosion-protected devices. 0.15 %/10 K None 0.25 % up to 2000 Hz and 4 g acc. to IEC 770 Complies with EN 61000-6-2, EN 61000-6-3 and NAMUR Recommendation NE 21 requirements One M20x1.5 cable gland for 6 to 12 mm clamping range Second M20x1.5 threaded connection additionally available Screw terminals for 0.2 to 2.5 mm wire cross-sections IP 66 / NEMA 4X Suitable for use in safety-relevant applications up to SIL 2 (single device) and SIL 3 (with redundant configuration), safety shutdown at a reference variable of 0 mA. See summary of explosion protection certificates
Minimum current Supply air
Signal pressure (output) Characteristics Adjustable
Deviation Hysteresis Sensitivity Transit time Direction of action Air consumption, steady-state Air output capacity Actuator pressurized Actuator vented
Permissible ambient temperature Influences Temperature Supply air Vibrations Electromagnetic compatibility Electrical connections Degree of protection Use in safety instrumented systems in compliance with IEC 61508 Explosion protection ATEX, IECEx, FM/CSA etc. Binary contacts
Two software limit switches with reverse polarity protection, configurable switching behavior, default settings according to table below Signal status Version No response Response One fault alarm contact Signal status Version No alarm Alarm To be connected to Without explosion protection Conductive (R = 348 ) Effectively non-conducting Binary input of a PLC acc. to EN 61131, Pmax = 400 mW or for connection to NAMUR switching amplifier acc. to EN 60947-5-6 With explosion protection 2.1 mA 1.2 mA NAMUR switching amplifier acc. to EN 60947-5-6 Without explosion protection Effectively non-conducting Conductive (R = 348 ) With explosion protection 1.2 mA 2.1 mA
T 8384-2/3 EN
Materials Housing External parts Cable gland Weight Additional data for Type 3730-2 Load impedance Communication (local) Software requirements (SSP) Additional data for Type 3730-3 Load impedance Communication (local) Software requirements (SSP) Communication (HART) Software requirements (HART) 8.2 V (corresponds to 410 at 20 mA) SAMSON SSP interface and serial interface adapter TROVIS-VIEW with database module 3730-3 HART field communication protocol Impedance in HART frequency range: Receiving 350 to 450 Sending approx. 115 DTM file acc. to Specification 1.2, suitable for integrating the positioner into frame applications that support the FDT/DTM concept (e.g. PACTware); other integration options (e.g. AMS, PDM) available Without explosion protection: 6 V (corresponds to 300 at 20 mA) SAMSON SSP interface and serial interface adapter TROVIS-VIEW with database module 3730-2 With explosion protection: 7 V (corresponds to 350 at 20 mA) Die-cast aluminum EN AC-AlSi12(Fe) (EN AC-44300) acc. to DIN EN 1706 Chromated and powder paint coated Special version in stainless steel 1.4581 Stainless steel 1.4571 and 1.4301 Polyamide, black, M20 x 1.5 Approx. 1.0 kg
Handheld communicator Device description for Type 3730-3
PC
Table 1a Options for Type 3730-2 and Type 3730-3 Positioners
Solenoid valve Approval acc. to IEC 61508/SIL Input 24 V DC Electrical isolation and reverse polarity protection Static destruction limit 40 V U 5.7 V Current consumption I = (corresponds to 4.8 mA at 24 V/114 mW) 3840 15 V > 19 V > 5 x 106 switching cycles Same as positioner pneumatics Two-wire transmitter Electrical isolation 12 to 30 V DC Reverse polarity protection Static destruction limit 40 V 4 to 20 mA Reversible 10 to +114 % Linear Same as positioner Same as positioner Same as positioner Issued as status current 2.4 0.1mA or 21.6 0.1mA For connection to switching amplifier acc. to EN 60947-5-6. Can be used in combination with a software limit switch. Same as Type 3730 Positioner 10 m Flexible and durable With M12x1 connector Flame-retardant acc. to VDE 0472 Resistant to oils, lubricants and coolants as well as other aggressive media 60 to +105 C The limits in the EC Type Examination Certificate additionally apply for explosion-protected devices. Up to 10 g in the range of 10 to 2000 Hz IP 67
Signal 0 no pick-up Signal 1 safe pick-up Service life Use in safety-related systems in compliance with IEC 61508/SIL Analog position transmitter Power supply Output signal Direction of action Operating range Characteristic Hysteresis High-frequency influence Other influences Fault alarm Inductive limit switch SJ-2SN proximity switch External position sensor Travel Cable Permissible ambient temperature Immunity to vibration Degree of protection
T 8384-2/3 EN
Binary input Electrical isolation Switching behavior configured over software (e.g. TROVIS-VIEW, DTM) Active switching behavior (default setting) Connection Electrical data Contact For external switch (floating contact) or relay contact Open-circuit voltage when contact is open: 10 V Pulsed DC current reaching peak value of 100 mA and RMS value of 0.01 mA when contact is closed Closed, R < 50 On switching state (default setting) Open, R > 400 Off switching state (default setting) For externally applied DC voltage, reverse polarity protection 3 to 30 V, destruction limit 40 V, current draw 3.7 mA at 24 V > 6 V On switching state (default setting) < 1 V Off switching state (default setting)
Passive switching behavior Connection Electrical data Voltage
Summary of explosion protection certificates
Type of approval Type 3730-2 Positioner EC Type Examination Certificate First Addendum Second Addendum Third Addendum Fourth Addendum Statement of Conformity First Addendum Second Addendum IECEx GOST approval FM approval IECEx PTB 05.0007 B02637 ID 3012394 PTB 03 ATEX 2016 X PTB 00 ATEX 2158 2001-03-01 2002-03-01 2004-02-16 2007-08-24 2008-11-06 2003-03-07 2005-05-03 2008-11-06 2005-02-21 2009-02-26 2002-10-30 II 2 G EEx ia IIC T6 Position transmitter II 2 D IP 65 T 80 C, Zone 21 dust, device index .01 Electrical data for forced venting altered Electrical data, structure-borne sound sensor and binary input added II 3 G EEx nA II T6; Zone 2; Type 3730-28 II 3 G EEx nL IIC T6; II 3 D IP 54/IP 65 T 80 C Electrical data, structure-borne sound sensor and binary input added Ex ia IIC T6/T5/T4; IP 54 and IP 65 T 80 C; Type 3730-21.9... 0 Ex ia IIC T6 X, valid until 2012-02-26; Type 3730-21 Intrinsically safe, Class I, II, III; Div. 1, Group A, B, C, D, E, F, G; Class I, Zone 0, AEx ia IIC T6; Non-incendive, Class I, Div. 2, Group A, B, C, D; NEMA Type 4; Type 3730-23 Div. 2 Gr. F and G Ex ia IIC T6, Cl. I, Zone 0; Intrinsically safe, Class I, Group A, B, C, D; Class II, Group E, F, G; Non-incendive, Class I, Div. 2, Group A, B, C, D; Type 4 Enclosure; Type 3730-23 Class II, Div. 2, Group E, F, G Ex ia IIC T6; Type 3730-27 Ex ia IIC T6; valid until 2010-12-15; Type 3730-21 Test report by TV Rheinland for Series 3730, valid until November 2012 II 2 G EEx ia IIC T6; without position transmitter Forced fail-safe venting function II 2 D IP 65 T 80 C, Zone 21 dust, model index .01 Binary input. Electrical data for forced venting altered Ex ia IIC T6/T5/T4; IP 54 and IP 65 T 80 C; Type 3730-31.9... 0 Ex ia IIC T6 X; 2 Ex nA/nL; valid until 2011-01-15 Ex ia IIC T4...T6; Type 3730-31 Ex nA II T4...T6; Ex nL IIC T4...T6; Type 3730-38 2003-09-30 2005-04-26 2007-09-10 2008-12-10 II 3 G EEx nA II T6; Zone 2; Type 3730-38 II 3 G EEx nL IIC T6; II 3 D IP 65 T 80 C; Zone 22 Electrical data, structure-borne sound sensor and binary input added Permissible ambient temperature range extended Certificate number Date Type of protection/Comments
Revision CSA approval 1330129
2004-02-04 2003-03-17
Revision to 1330129 JIS approval KOSHA SIL 4 acc. to IEC 61508/ SIL 3 acc. to IEC 61511 Type 3730-3 Positioner EC Type Examination Certificate First Addendum Second Addendum Third Addendum IECEx GOST approval NEPSI approval Statement of Conformity First Addendum Second Addendum Third Addendum
1500997 C16679 2005-2359-Q1 V 60 2007 C4
2004-03-05 2003-11-25 2005-12-16 2008-01-07
PTB 02 ATEX 2174
2002-11-15 2003-06-18 2004-02-16 2007-09-10
IECEx PTB 05.0008 B00885 GYJ071189 GYJ071190X PTB 03 ATEX 2180 X
2005-02-21 2008-01-15 2007-07-26
T 8384-2/3 EN
Type of approval EC Type Examination Certificate FM approval Model index 01 and higher
Certificate number PTB 03 ATEX 2211 X 3018702
Date 2003-10-22 2004-02-02
Type of protection/Comments II 2 G EEx d ia IIC T6; Type 3730-39 with Type 3770-1 Field Barrier Intrinsically safe; Class I, II, III; Div. 1, Group A, B, C, D, E, F, G; Class I, Zone 0, AEx ia IIC T6; NEMA Type 4 Non incendive, Class I; Div. 2, Group A, B, C, D; Class II, Div. 2, Group F, G; Type 3730-33 Ex ia IIC T6; Cl. I, Zone 0 Intrinsically safe, Class I, Group A, B, C, D; Type 4 Enclosure Class II, Gr. E, F, G; Non-incendive, Class I, Div. 2, Group A, B, C, D Class II, Div. 2, Gr. E, F, G; Type 3730-33 Ex ia IIC T6; valid until 2010-12-15; Type 3730-31 Test report by TV Rheinland for Series 3730, valid until November 2012
CSA approval Model index 01 and higher
1508990
2004-03-05
KOSHA SIL 4 acc. to IEC 61508/ SIL 3 acc. to IEC 61511
2005-2360-Q1 V 60 2007 C4
2005-12-16 2008-01-07
The test certificates are included in the mounting and operating instructions or are available on request. Refer to Data Sheet T 8379 EN for EEx d certificates for the Type 3770 Field Barrier.
Positioner attachment The Type 3730 Electropneumatic Positioner can be attached directly to the Type 3277 Actuator over a connection block. In actuators with fail-safe action Actuator stem extends and Type 3277-5 Actuator (120 cm), the signal pressure is routed over an internal bore in the actuator yoke to the actuator. In actuators with fail-safe action Actuator stem retracts and in actuators with effective diaphragm areas of 240 cm or larger, the signal pressure is routed to the actuator over ready-made external piping. Dimensions in mm
Using a bracket, the positioner can also be attached according to IEC 60534-6-1 (NAMUR recommendation). The positioner can be mounted on any side of the control valve. A pair of universal brackets is used for the attachment to Type 3278 Rotary Actuators or other rotary actuators according to VDI/VDE 3845. The rotary motion of the actuator is transferred to the positioner over a coupling wheel.
Direct attachment
210
M 20x1.5
34
58 164 Output (38)
Supply (9)
External position sensor
28
86
70
Schild
70
T 8384-2/3 EN
14
40
28
80
NAMUR attachment
Pressure gauge bracket G or NPT or connecting plate Lever S = 17 mm M = 50 mm L = 100 mm XL = 200 mm
58 15 46
70
34
Attachment to rotary actuators VDI/VDE 3865 Fixing level 2
Output A1 50 Supply (9)
A1
76
A2
79 59 49
Connecting plate G or NPT
50
58
Reversing amplifier
80 130 150 Output A2
Mounting unit CrNiMo steel bracket
Connecting plate
164
15
Mounting unit for rotary actuators Heavy-duty version
Output A1 50 Supply (9)
A1
76
A2
86
Connecting plate G or NPT
56
Reversing amplifier
80 130 166
Output A2
30 86 101
Connecting plate
164
15
T 8384-2/3 EN
Article code
Positioner With LCD and autotune, 4 to 20 mA reference variable 2 software limit switches, one fault alarm contact With LCD and autotune, HART communication, 4 to 20 mA, 2 software limit switches, one fault alarm contact Explosion protection Without II 2 G EEx ia IIC T6 and II 2 D IP 65 T 80 C acc. to ATEX CSA/FM intrinsically safe/non incendive II 3 G EEx nA/nL II T6 and Additional equipment Inductive limit switch Without Type SJ2-SN Solenoid valve Without With, 24 V DC Position transmitter Without With External position sensor Without With Binary input Without With Diagnostics EXPERTplus Housing material Aluminum (standard) Stainless steel 1.4581 Special application None Device completely free of paint-impairing substances Exhaust air connection with -18 NPT thread, back of housing sealed Special version None IECEx GOST approval Ex ia GOST approval Ex nA/nL 1 1 8 0 1 1 2 0 2 4 0 0 1 2 0 0 1 4 0 0 2 0 0 1 0 0 1 0 0 4 0 1 II 3D IP 65 T 80 C 1 3 8 0 Type 3730- x 2 3 x x x x x 0 x x 0 x 0 0 x 0 x x
Ordering text Type 3730-x... Positioner Without pneumatic connecting rail (only for direct attachment to Type 3277 Actuator) With pneumatic connecting rail ISO 228/1-G With pneumatic connecting rail -18 NPT Without/with pressure gauge up to max. 6 bar Additional cover plate with list of parameters and operating instructions in English/Spanish or English/French (standard version in German/English) Attachment to Type 3277 Actuator (120 to 700 cm) Attachment according to IEC 60534-6-1 (NAMUR) Travel: ... mm; if applicable, stem diameter: ... mm
Attachment to Type 3278 Rotary Actuator (160/320 cm), mounting unit with CrNiMo steel bracket or heavy-duty attachment Attachment according to rotary actuators acc. to VDI/VDE 3845, mounting unit with CrNiMo steel bracket or heavy-duty attachment Pneumatic reversing amplifier for double-acting actuators with connection acc. to ISO 228/1 - G or -18 NPT Adapter M20 x 1.5 to NPT Metal cable gland Special version with CrNiMo steel housing
SAMSON AG MESS- UND REGELTECHNIK Weismllerstrae 3 60314 Frankfurt am Main Germany Phone: +49 69 4009-0 Fax. +49 069 4009-1507 Internet: http://www.samson.de
T 8384-2/3 EN