0 ratings0% found this document useful (0 votes) 396 views4 pagesNfpa 780
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content,
claim it here.
Available Formats
Download as PDF or read online on Scribd
A: 06 m (2) or 7.6 m (26 ft) maximum spacing
B: Air terminals are located within 0.6m (21)
of ends of ridges
FIGURE 4.8.2 Air Terminals on Pitched Roof.
4.8.2.1 Strike termination devices shall be placed on ridges of pitched roofs and around the
perimeter of flat or gently sloping roofs at intervals not exceeding 6 m (20 fi.
4.8.2.2. Strike termination devices 600 mm (24 in.) or more above the object or area to be
protected shall be permitted to be placed at intervals not exceeding 7.6 m (25 fi)
4.8.2.3 Pitched Roof Area.
(A) A pitched roof with eave heights of 15 m (50 ft) or less above grade shall require
protection for the ridge only where there is no horizontal portion of the building that
extends beyond the eaves, other than a gutter.
(B) Pitched roofs with eave heights more than 15 m (50 ff) shall have strike termination
devices located according to the 46 m (150 ft) geometric model. [See Figure 4.7.3.1(B) and
Figure 4.7.3.3.)
4.8.2.4 Flat or Gently Sloping Roof Area. Flat or gently sloping roofs that exceed 15 m
(50 #) in width or length shall have additional strike termination devices located at intervals
not to exceed 15 m (50 ft) on the flat or gently sloping areas, as shown in Figure 4.8.2.4(a)
and Figure 4.8.2.4(b), or such area can also be protected using taller air terminals that create
|zones of protection using the rolling sphere model so the sphere does not contact the flat
roof area.
Copyright NFPAA: 15 m {80 ft) maximum spacing between air terminals
B: 45 m (150 ft) maximum length of cross run conductor permitted
without a connection from the eross run conductor to the main
perimeter or down conductor
©: 8 m (20 tt) oF 7.6 m (25 ft) maximum spacings botwoon air
terminals along edge
FIGURE 4.8.2.4(a) Air Terminals on Flat Roof.
As 15 m (59 ft) maximurn spacing
8: 6m (20 ft) oF 7.6 m (25-11) maximum spacing
Copyright NFPAFIGURE 4.8.2.4(b) Air Terminals on Gently Sloping Roof.
4.8.3* Dormers.
4.8.3.1 Dormers as high or higher than the main roof shall be protected with strike
termination devices, conductors, and grounds, where required.
4.8.3.2. Dormers and projections below the main ridge shall require protection only on
those areas extending outside a zone of protection,
4.8.4 Roofs with Intermediate Ridges. Strike termination devices shall be located along
the outermost ridges of buildings that have a series of intermediate ridges at the same
intervals as required by 4.8.2.
4.8.4.1. Strike termination devices shall be located on the intermediate ridges in accordance
with the requirements for the spacing of strike termination devices on flat or gently sloping
roofs.
4.8.4.2 If any intermediate ridge is higher than the outermost ridges, it shall be treated as @
‘main ridge and protected according to 4.8.2.
4.8.5 Flat or Gently Sloping Roofs with Irregular Perimeters. Structures that have
exterior wall designs that result in irregular roof perimeters shall be treated on an individual
bi
4.8.5.1. The outermost projections form an imaginary roof edge that shall be used to locate
the strike termination devices in accordance with 4.8.2.
4.8.5.2 Inall cases, however, strike termination devices shall be located in accordance with
Section 4.8, as shown in Figure 4.8.5.2.
Copyright NFPAA: Aie terminals within 0.6 m (2 tt) of ee)
Outemost projection of roof edge
FIGURE 48.5.2 Flat or Gently Sloping Roof with Irregular Perimeter.
4.8.5.3 Strike termination devices installed on vertical roof members shall be permitted to
use a single main-size cable to connect to a main roof conductor.
4.8.5.4 The main roof conductor shall be run adjacent to the vertical roof members so that
the single cable from the strike termination device is as short as possible and in no case
longer than 4.9 m (16 ft)
4.8.5.5 The connection of the single cable to the down conductor shall be made with a tee
splice, as shown in Figure 4.8.5.5
Copyright NFPA