0 ratings0% found this document useful (0 votes) 115 views10 pagesTransformer Lecture Notes 2
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content,
claim it here.
Available Formats
Download as PDF or read online on Scribd
2 TRANSFORMERS
2.1. Introduction
Basic transformer principles were covered in
Electromechanics [1], and the main results are
given below. Figure 2-1 is a schematic
representation of a single-phase transformer with
two coils on a magnetic core, where the magnetic
coupling is assumed to be perfect: the same flux ¢
passes through each turn of each coil,
@ ¢
‘N, tums: NN, turns
Figure 2-1: Transformer with source and load
Voltage relationships
Kirchhoff’s voltage law applied to the two
windings gives:
a9
yet Rian, 2eR OL
tf 21)
1p;
yy) =@-Ri=N,% Ri, 22)
=~ Ron = Na Roi (2-2)
If the resistances Ry and R; are negligible, then
equations 2-1 and 2-2 become:
ds
nent on
do
nent a
dt en
Dividing these equations gives the important result
eM
v2 Ne
5)
Sinusoldal operation
If the voltage source is sinusoidal, then the core
flux will also be sinusoidal, so we may put:
=
Substituting this expression in equation 2-3 gives:
SINE (2-6)
¥=N, B= No, coser=Vigcosor (2-7)
Thus the maximum primary voltage is:
Vig = NO, = 2 FN YDy, = 2 FNAB, (2-8)
where A is the cross-sectional area of the core and
Bw is the maximum flux density in the core. A
typical value for By is 1.4 T for the silicon ste!
characteristic in figure 2-2.
2
18
16
14
12
1
os
06
o4
oz
0
Flux density 8, T
0 2 4 6 8 10 12 14 16 18 20
Magnetic intensity H, kA‘
Figure 2-2: Silicon transformer steel.
Current relationships
‘The relationship between the primary and
secondary currents can be found by considering the
‘magnetic circuit of the transformer. From the basic
‘magnetic circuit equation, we have:
F = Ni Noy = RO 29)
In a well-designed transformer, the reluctance Nis
small, so equation 2-9 becomes:
yi Nai =0 (2-10)
This gives the counterpart of equation 2-5 for
voltage:
= (11)
2 Electrical Machines and Systems Course NotesIf sinusoidal voltages and currents are represented
by phasors, the corresponding forms for the basic
voltage and current equations are:
N,
Me 212)
V."N2
Lh (2-13)
LN
Transformer rating
‘The maximum voltage at the primary terminals of a
transformer is determined by equation 2-8, and is.
independent of the current. The maximum primary
current is determined by the FR power loss in the
resistance of the transformer windings, which
‘generates heat in the transformer. This power loss
is independent of the applied voltage.
Consequently, for a given design of transformer,
there is a maximum value for the product Vil: at
the primary terminals. To a first approximation,
this is also equal to the product Vahs at the
secondary terminals. This maximum value does not
depend on the phase angle between the voltage and
the current. Transformer ratings therefore specify
the apparent power VI (volt-amperes, VA) rather
than the real power VI cos ¢ (watts, W).
2.2 Types of power transformer
In addition to the ordinary single-phase power
transformer, two other types are in common use:
auto-wound transformers, and 3-phase
transformers,
Auto-wound transformers
‘A transformer can have a single coil with an output
taken from a portion of the coil, as shown in figure
2.3. This is known as an auto-wound transformer
‘or auto-transformer.
Vs
Figure 2-3: Auto-wound transformer.
Unlike the normal transformer with two windings,
known as a double-wound transformer, the auto-
wound transformer does not provide electrical
isolation between the primary and the secondary,
However, an auto-wound transformer can have a
much larger apparent power rating than a double-
wound transformer of the same physical size.
Let N be the number of turns on the upper part
of the winding in figure 2-3, and NV, the number of
turns on the lower part. The conventional
transformer equations 2-12 and 2-13 apply to these
parts of the winding, since they are equivalent to
two separate windings with a common connection.
Applying Kirchhoff’ law to this circuit gives:
Vs =Vy4Vy (2414)
1-14, (2-15)
As an example, suppose that Nj = No. Ifthe
transformer is regarded as ideal (see section 2.3),
then I = Ip and V; = V2, Equations 2-14 and 2-15,
give:
Vs-Vi+
y= 2V)=2V, (2-16)
= 2, = 2s an
‘where Vz is the voltage across the load and Is is the
ccurrent supplied by the source. This auto-wound
‘transformer behaves as a step-down transformer
with a ratio of 2:1, and the current in each winding
is equal to half of the load current.
‘An elegant application of the auto-wound
transformer principle is the variable transformer,
which has a single-layer coil wound on a toroidal
core, The output is taken from a carbon brush that
makes contact with the surface of the coil; the
brush can be moved smoothly from one end of the
coil to the other, thus varying the output voltage.
Examples of variable transformers are shown in
figure 2-4
Transformers 3Figure 2-4: Variable transformers.
(RS Components Ltd)
‘phase transformers
In 3-phase systems (see section 4.1), itis common
practice to use sets of three single-phase
transformers. It is also possible, however, to make
3.phase transformers with three sets of windings
on three limbs of a core, as shown in figure 2-5
Figure 2-5: 3-phase transformer model.
‘The corresponding fluxes are shown in figure 2-6.
Ga de Ge
Figure 2-6: 3-phase transformer flux.
In a balanced system with sinusoidal phase
voltages, the fluxes will be given by:
6, =0,,cosot
$5 = @y,cos(or—120") (218)
6, =, cos(@t 240°) = ©, cost +120°)
Figure 2-7 shows flux plots for the transformer at
the instants when cx = 0, 120° and 240°.
{b)
Figure 2-7: 3-phase transformer flux plots:
(a) 0°, (b) 120°, (c) 240",
There is no requirement for another limb to form a
flux return path, because the fluxes fy, gy and J.
sum to zero in a balanced 3-phase system. The
proof is as follows. From equation 2-18, the sum is
given by:
ba* +e
Om
-0s01 + cos(@ot —120°) +cos(@t +120°) (2-19)
= coset + 2cosertcos120°
0st coset = 0
Because the fluxes in the three limbs sum to zero at
all instants of time, there is no leakage of flux from,
the core, as the flux plots in figure 2-7
demonstrate
4 Electrical Machines and Systems Course Notes2,3 Ideal transformer properties
If the primary and secondary windings have zero
resistance, and the magnetic core has zero
reluctance, then the approximate equalities in
‘equations 2-12 and 2-13 become exact equalities.
This leads to the concept of an ideal transformer
‘element, to accompany the other ideal elements of
circuit theory. Figure 2-8 shows a circuit symbol
for the ideal transformer element.
Figure 2-8: Ideal transformer element
The voltage and current relationships in the time
and frequency domains are given in table 2-1,
Table 2-1: Ideal transformer relationships.
ye domain Frequency domain
V2 No 2-20)
YOM
4M, bi, ew
i, My LM
‘The following properties of the ideal transformer
may be deduced from equations 2-16 and 2-17:
* The voltage transformation is independent of
the current, and vice versa.
+ Ifthe secondary is short-circuited, so that
v2 = 0, the primary terminals appear to be
short-circuited since v; = 0
+ Ifthe secondary is open-circuited, so that
in= 0, the primary terminals appear to be open-
circuited since i; = 0.
+ The output power is equal to the input power,
so there is no power loss in the element.
Impedance transformation
‘The ideal transformer has the important property of
transforming impedance values in a circuit.
Consider an ideal transformer with an impedance
Z, connected to its secondary terminals, as shown
in figure 2-9,
Nu
Figure 2-9: Ideal transformer with a load,
‘The secondary impedance is given by:
(2-22)
At the primary terminals, the circuit presents an
impedance given by:
(2.23)
(
Thus the combination of an ideal transformer of
ration and an impedance Z;, can be replaced by an
‘equivalent impedance Z,,/
Referred impedances
Figure 2-10(a) shows an ideal transformer with a
load impedance Z, connected to the secondary.
Another impedance Z is in series with Z,. The
input impedance of this circuit is:
~hath,
Es
Z, (224)
‘The input impedance of the circuit in figure 2-
10(b) is:
Z,
ZL, - 0,4
in Lt
(2.25)
‘The two expressions for Z,, will be identical if:
2
n
(2-26)
Transformers 5°
Zin g Lh
°
NNa @)
Za
Zin ; é | Z
NaN (b)
Figure 2-10: Referred impedance ~ 1.
The impedance Z's is termed the secondary
impedance Zp referred to the primary.
Ina similar way, a primary impedance Z) can
be referred to the secondary, as shown in figure
2-11. In this case, the referred impedance is given
by:
ZLi=wZ, (2-27)
Zs
°
Bn 3 hi
°
NiNy @
°
NiNy )
Figure 2-11: Referred impedance ~ 2.
‘The concept of referred impedance is often a useful
device for simplifying circuits containing
transformers, as will be shown in the next section,
It is conventional to use a single prime (’) to denote
quantities referred to the primary side, and a
double prime (") to denote quantities referred to
the secondary side.
2.4 Circuit model of a transformer
Ina practical transformer, the winding resistances
and the core reluctance are not zero. In addition,
there will be some power loss in the core because
of eddy currents and hysteresis in the magnetic
‘material, All of these effects can be represented by
the equivalent circuit (3, 4] shown in figure 2-12.
MN
Figure 2-12: Transformer equivalent circuit
This circuit is based on the ideal transformer
clement, with additional circuit elements to
represent the imperfections. The resistances Ry and
Ry represent the physical resistances of the
windings, and R. represents the power lost in the
core. The reactance X,, known as the magnetising
reactance, allows for the current required to
‘magnetise the core when the reluctance is not zero.
Reactances x, and x, known as leakage
reactances, represent the leakage flux that exists
‘when the magnetic coupling between the primary
and the secondary is not perfect. Figure 2-13 shows,
the leakage flux when the core has an artificially
ow relative permeability of 10, and one winding at
atime is energised. In practice, the leakage is much
less than this, so the leakage reactances are
normally very much smaller than the magnetising,
reactance Xr
(a)
6 Electrical Machines and Systems Course NotesRit dR
nn sen.
| 4) x 3
b) Nas
Figure 2-13: Transformer leakage flux:
(a) eft coil energised, (b) right coll energised.
In the circuit of figure 2-12, the current I's is ®
the effective value of the secondary current as seen no om ies
from the primary side of the transformer. Itis also
nen. fren.
known as the secondary current referred to the
primary.
The current Iy is the no-load current,whichis jx, [Ip 3 g
the current taken by the primary when there is no
load connected to the secondary. It has a
‘component Ion, known as the magnetising current,
which represents the current required to set up the WisNy
‘magnetic flux in the core. The current Io is the
ccore loss component of the no-load current. )
ite
Bin
Approximate equivalent circuit
For power transformers with ratings above
100 VA, the values of the series elements Ry and x Rnd [IR
are gencrally much smaller than the shunt elements
R_ and X». Under normal working conditions, the
voltage drop in Ry + x; is much smaller than the °
applied voltage Vj. Similarly, the no-load current /y NisNa
is much smaller than the load current f. It follows
that the shunt elements can be moved to the input
terminals, as shown in figure 2-14(a), with very Figure 2-14: Approximate equivalent circuit
litte loss of accuracy.
The secondary elements Ry and jr; can be
replaced by equivalent elements = R:/rand 2.5 Parameter determination
= ™m/ 7 on the primary side (see section 2.3),
giving the circuit shown in figure 2-14(b), Finally, The parameters of the approximate equivalent
the series elements can be combined to give an circuit (igure 2-14) can be determined
cfective esistance R, and leakage reactance x, as experimentally from two tests
shown in figure 2-14(c), where the values are + An open-cireuit test, where the secondary is
left unconnected and the normal rated voltage
R=R, +h, x= +22 228) is applied to the primary.
” " + A short-circuit test, where the secondary
terminals are short-circuited and a low voltage
is applied to the primary, sufficient to circulate
the normal full-load current,
Transformers 7Open-circuit test
With the secondary unconnected, I; = 0, so the
equivalent circuit reduces to the form shown in
figure 2-15.
Troe
oS
+
Vow Xe 3 []R
o—_
Figure 2-15: Open-circult test,
‘Toa very close approximation, the current Ig.
supplied to the primary is equal to the no-load.
current Ip in figure 2-12. The values of the
elements R, and X,,can be determined from
‘measurements of the input voltage Vj, current Ii
and power Pcs follows. The input power is
entirely dissipated in the resistance R,, giving:
Va
R (2:29)
v, L
Z, ae 2.30)
a (230)
Xm
In terms of magnitudes, equation 2-30 becomes:
¥, 1
toe = ——= (231)
Toe | 1 ’ 1
VRE Xn
Re-arranging equation 2-31 gives the value of Xx
(2:32)
From figure 2-14(¢), it follows that the turns ratio
is given by:
(2:33)
Short-circuit test
If the secondary terminals are short-circuited, the
ideal transformer in figure 2-14 can be replaced by
a short circuit, so the equivalent circuit takes the
form shown in figure 2-16(a). In a typical power
transformer, the shunt elements R. and Xj. are at
Teast 100 times larger than the series elements Re
and x,. Consequently, the shunt elements can be
neglected, and the circuit reduces to the form
shown in figure 2-16(b).
R. Ske.
Xm
(a)
Tne RP
+
Vive
(b)
: Short-circuit test.
The values of the elements R, and x, can be
determined from measurements of the input voltage
Vigq Current /\,- and power P,.as follows. The
input power is entirely dissipated in the resistance
R,, giving:
(2:34)
8 Electrical Machines and Systems Course NotesRe-arranging equation 2-36 gives the value of x:
237)
In practice, the open-circuit testis usually
made on the low-voltage side of the transformer to
minimise the value of V,,, and the short-circuit test
is made on the high-voltage side to minimise the
value of [,.. The resulting parameter values are then
referred to the primary side of the transformer.
2.6 Transformer performance
Consider a transformer with an impedance Z
connected to the secondary. With the approximate
equivalent circuit, this may be represented by the
circuit diagram of figure 2-17.
MN
Figure 2-17: Transformer with a load.
‘The load impedance can be referred to the primary
side of the ideal transformer element, giving the
circuit shown in figure 2-18,
Jeep, nk:
1 R
Figure 2-18: Circuit with referred impedance.
solved for the currents Ip and
1’, The referred secondary voltage is given by
V2= Zil's, and the secondary terminal quantities
are given by V2= nV'2, = V2 n.
Voltage regulation and efficiency
When a load is connected to the secondary of a
transformer, there will be a voltage drop in the
series elements R, and x,, so the secondary terminal
voltage will change. The voltage regulation is
defined as:
Vani =
(2-38)
V;
where Vaqris the magnitude of the no-load
secondary terminal voltage, and Vaq is the
corresponding full-load voltage.
Power is lost as heat in the windings and core
of the transformer, represented by the resistance
elements R, and R-in the equivalent circuit. The
efficiency is defined in the usual way as:
Pp.
oe (239)
P. )
where P, is the power input to the primary and Phar
is the power output from the secondary. The power
lost as heat in the transformer is:
Pog = Ping — Poe
(2-40)
so we have the following alternative forms of
equation 2-39:
P,
ut + Poss
Large transformers are very efficient. Even a
2 KVA transformer can have an efficiency of about
95%, Above 25 kVA, the efficiency usually
exceeds 99%, It is very difficult to make an
accurate measurement of efficiency by direct
measurement of Pay and Py, since this would
require an accuracy of measurement of the order of
0.01%, Instead, the normal practice is to determine
the losses from measurements, and calculate the
efficiency from one of the alternative expressions
in equation 2-41. The losses can be calculated with
high accuracy from the equivalent-circuit
parameters determined from tests on the
transformer.
Maximum efficiency
‘The power loss in a transformer has two
components: the core loss, given by Vi / Rand
Transformers 9the PR loss, given by /°R,. The core loss will be
constant if the primary voltage V; is constant, but
the FR loss will vary with the secondary current.
‘When the current is low, the output power will be
ow, but the core loss remains at the normal value,
Consequently, the efficiency of the transformer
will be low under these conditions. It may be
shown that the efficiency is a maximum when the
secondary current is such that the variable FR loss
is equal to the fixed core loss. This result also
applies to other devices where the losses have
fixed and variable components. Transformers are
usually designed to have maximum efficiency at
the normal operating value of secondary current,
which may be less than the maximum rated current
Power relationships
When calculating the transformer performance, the
following power relationships can be useful. The
complex power S is given by [2]
S=P+jQ=vIr (2-42)
where V is the voltage phasor, I* is the complex
conjugate of the current, P is the real power, and Q
is the reactive power. If gis the phase angle, then:
P=Scos =Vicos$=Re(VI*) (2-43)
Q=Ssing =Vising =Im(VI*) (2-44)
|e? <0!
If the voltage phasor V is chosen as the reference
quantity, and defined to be purely real (V = V+j0),
then the power relationships take a simple form:
P=Vicos$=VRe(I) (2-46)
S= (2-45)
Q=Vising=-VIm) 2-47)
Worked example 2-1
A2KVA, 50 Hz, power transformer has the
following equivalent-circuit parameter values
referred to the primary:
R.= 0.682 Q, x,= 0.173 2, R,
X= 657 2, Nz / Ny = 0.472,
If the primary is connected to 230 V 50 Hz supply,
and a load impedance (6.0 + j2.5) is connected
to the secondary, determine:
(a) the secondary current magnitude,
1080.9,
(b) the secondary terminal voltage magnitude,
(©) the primary current magnitude,
(@ the voltage regulation,
(©) the efficiency of the transformer.
(a) Secondary current
The load impedance referred to the primary is:
Z, _6.0+ j25
nn (0.472)?
26.9 + j.22
The secondary current referred to the primary is:
ye
Z.+2,
230+ j0
~ (0.682 + j0.173) + (26.9 + j11.2)
230. jo
27.64 jll4
= [7.12 - j2.94]=7.70 A
=7.12- j294A
The secondary current magnitude is:
I, 7.70 _
n 0472
6.34
(b) Secondary voltage
The secondary voltage magnitude is:
Vp =fyZz =16.3|6.0+ 2.5]
=16.3x6.5=106.0V
(c) Primary current
The no-load current is:
Vi, Vi _ 230+ j0 | 230+ j0
RX» 1080” j657
=0.213— j0.350A
The primary current is:
=h+h
= (0.213 = 0.350) + (7.12 = j2.94)
33 j3.29A
33— j3.29|=8.03 A
h
(d) Voltage regulation
On no load, the secondary voltage is:
V, = nV, = 0.472 x 230 = 108.6 V
10 Electrical Machines and Systems Course Notes‘The voltage regulation is therefore:
¢ Vani ~ Vo _ 108.6-106.0
1 108.6
2.33%
(c) Efficiency
‘The output power is:
Pay = BR, = (16:31)? 6.0 =1597 W
‘The power loss is:
We
Pay = + IPR,
oss
_ 230.0)?
1080
=894W
(7.699)? «0.682
‘The input power is therefore:
P, + Py, = 1597 + 89.4 = 1686 W
Alternatively, from equation 2-46 the input power
B,, = V, Re(I,) = 230.0 x7.330 = 1686 W
The efficiency is therefore:
Pow
P.
2.7 Current transformers
‘The use of transformers for measuring current has.
been introduced in Electromechanics (1], where
the danger of open-circuiting the secondary has
been explained, This section introduces the
important topic of measurement errors.
Current transformer errors
Ina well-designed current transformer, the core
‘lux density is low and the core is made from a
high-quality magnetic material. Under normal
‘operating conditions, the core loss will be
negligibly small, so the core loss resistance R-can
bbe omitted from the equivalent circuit. A circuit
‘model for a current transformer connected to a load
therefore takes the form shown in figure 2-19.
Lor,
NuNy
Figure 2-19: Current transformer circuit model.
Only the relationship between currents is of
interest, so the primary impedance (R; + jx:) can be
disregarded. It is now convenient to refer the
primary quantities to the secondary side, giving the
circuit model shown in figure 2-20.
iy
Figure 2-20: Modified circuit model.
‘The circuit acts as a current divider, where the
current in the secondary branch is given by:
IX nM
L
at Dt Xm
(2-48)
where I”; is the primary current referred to the
secondary, and Z2 = R: + jr. Ina well-designed
transformer, the secondary impedance Zais very
small in comparison with the referred magnetising
reactance X"q, $0 this term introduces very little
error. Equation 2-48 shows that itis desirable to
keep the load impedance Z, as small as possible if
the error is to be minimised.
In practice, current transformers are designed
for a specified maximum secondary voltage at the
rated secondary current. This defines a maximum,
apparent power for the secondary load, or burden.
‘Typically, a small current transformer will have a
rated secondary burden of 5 VA. With the usual
secondary current rating of 5 A, this implies that
the maximum secondary voltage is | V, and the
maximum impedance magnitude is 0.2.9.
Transformers 11