Nema Ics 10.1-2005
Nema Ics 10.1-2005
INDUSTRIAL CONTROL
AND SYSTEMS
PART 1:
ELECTROMECHANICAL
AC TRANSFER SWITCH
EQUIPMENT
NEMA Standards Publication ICS 10-2005
Published by:
www.nema.org
© Copyright 2005 by the National Electrical Manufacturers Association. All rights including
translation into other languages, reserved under the Universal Copyright Convention, the Berne
Convention for the Protection of Literary and Artistic Works, and the International and Pan
American Copyright Conventions.
NOTICE AND DISCLAIMER
The information in this publication was considered technically sound by the consensus of
persons engaged in the development and approval of the document at the time it was
developed. Consensus does not necessarily mean that there is unanimous agreement among
every person participating in the development of this document.
The National Electrical Manufacturers Association (NEMA) standards and guideline publications,
of which the document contained herein is one, are developed through a voluntary consensus
standards development process. This process brings together volunteers and/or seeks out the
views of persons who have an interest in the topic covered by this publication. While NEMA
administers the process and establishes rules to promote fairness in the development of
consensus, it does not write the document and it does not independently test, evaluate, or verify
the accuracy or completeness of any information or the soundness of any judgments contained
in its standards and guideline publications.
NEMA disclaims liability for any personal injury, property, or other damages of any nature
whatsoever, whether special, indirect, consequential, or compensatory, directly or indirectly
resulting from the publication, use of, application, or reliance on this document. NEMA disclaims
and makes no guaranty or warranty, express or implied, as to the accuracy or completeness of
any information published herein, and disclaims and makes no warranty that the information in
this document will fulfill any of your particular purposes or needs. NEMA does not undertake to
guarantee the performance of any individual manufacturer or seller’s products or services by
virtue of this standard or guide.
In publishing and making this document available, NEMA is not undertaking to render
professional or other services for or on behalf of any person or entity, nor is NEMA undertaking
to perform any duty owed by any person or entity to someone else. Anyone using this document
should rely on his or her own independent judgment or, as appropriate, seek the advice of a
competent professional in determining the exercise of reasonable care in any given
circumstances. Information and other standards on the topic covered by this publication may be
available from other sources, which the user may wish to consult for additional views or
information not covered by this publication.
NEMA has no power, nor does it undertake to police or enforce compliance with the contents of
this document. NEMA does not certify, test, or inspect products, designs, or installations for
safety or health purposes. Any certification or other statement of compliance with any health or
safety–related information in this document shall not be attributable to NEMA and is solely the
responsibility of the certifier or maker of the statement.
ICS 10-2005, Part 1 AC Transfer Switch Equipment
Page i
CONTENTS
Page
Foreword
This Standards Publication was prepared by a technical committee of the NEMA Industrial
Automation Control Products and Systems Section. It was approved in accordance with the
bylaws of NEMA and supersedes the indicated NEMA Standards Publication. This Standards
Publication supersedes ICS 10-1993. Information on static transfer switches can be found in
ICS 10-1999 Part 2: Static AC Transfer Switch Equipment.
This Standards Publication provides practical information concerning ratings, construction, test,
performance and manufacture of industrial control equipment. These standards are used by the
electrical industry to provide guidelines for the manufacture and proper application of reliable
products and equipment and to promote the benefits of repetitive manufacturing and widespread
product availability.
NEMA Standards represent the result of many years of research, investigation and experience
by the members of NEMA, its predecessors, its Sections and Committees. They have been
developed through continuing consultation among manufacturers, users and national
engineering societies and have resulted in improved serviceability of electrical products with
economies to manufacturers and users.
One of the primary purposes of this Standards Publication is to encourage the production of
reliable control equipment which, in itself, functions in accordance with these accepted
standards. Some portions of these standards, such as electrical spacings and interrupting
ratings, have a direct bearing on safety; almost all of the items in this publication, when applied
properly, contribute to safety in one way or another.
Properly constructed industrial control equipment is, however, only one factor in minimizing the
hazards which may be associated with the use of electricity. The reduction of hazard involves
the joint efforts of the various equipment manufacturers, the system designer, the installer and
the user. Information is provided herein to assist users and others in the proper selection of
control equipment.
The industrial control manufacturer has limited or no control over the following factors which are
vital to a safe installation:
a. Environmental conditions
b. System design
c. Equipment selection and application
d. Installation
e. Operating practices
f. Maintenance
This publication is not intended to instruct the user of control equipment with regard to these
factors except insofar as suitable equipment to meet needs can be recognized in this publication
and some application guidance is given.
This Standards Publication is necessarily confined to defining the construction requirements for
industrial control equipment and to providing recommendations for proper selection for use
under normal or certain specific conditions. Since any piece of industrial control equipment can
be installed, operated and maintained in such a manner that hazardous conditions may result,
conformance with this publication does not by itself assure a safe installation. When, however,
equipment conforming with these standards is properly selected and is installed in accordance
with the National Electrical Code and properly maintained, the hazards to persons and property
will be reduced.
To continue to serve the best interests of users of Industrial Control and Systems equipment,
the Industrial Automation Control Products and Systems Section is actively cooperating with
other standardization organizations in the development of simple and more universal metrology
practices. In this publication, the U.S. customary units are gradually being supplemented by
those of the modernized metric system known as the International Systems of Units (SI). This
transition involves no changes in standard dimensions, tolerances, or performance
specifications.
NEMA Standards Publications are subject to periodic review. They are revised frequently to
reflect user input and to meet changing conditions and technical progress. Proposed revisions to
this Standards Publication should be submitted to:
Vice President, Technical Services
National Electrical Manufacturers Association
1300 North 17th Street, Suite 1847
Rosslyn, Virginia 22209
This standards publication was developed by the Industrial Automation Control Products and
Systems Section. Section Approval of the standard does not necessarily imply that all section
members voted for its approval or participated in its development. At the time it was approved,
the Section was composed of the following members:
Part 1
AC TRANSFER SWITCH EQUIPMENT
1 GENERAL
The definitions and standards of ICS 1, except for clause 7 pertaining to spacings as indicated,
also apply to this standard.
Emergency systems are those that meet the requirements of Articles 517 and 700 of NFPA 70
(NEC) and NFPA 99. Emergency systems are those legally required to automatically supply
alternate power within 10 seconds of power interruption to a number of prescribed functions
essential for safety to human life.
Legally required standby systems are those that meet the requirements of Article 701 of NFPA
70 (NEC). These systems are intended to automatically supply power to selected loads (other
than those classed as emergency systems) in the event of failure of the normal source.
Optional standby systems are those that meet the requirements of Article 702 of NFPA 70
(NEC). These systems are intended to supply power either automatically or non-automatically to
selected loads other than those classed as Emergency or Legally Required Standby.
ICS 1.3-1986 (R2001) Preventive Maintenance of Industrial Control and Systems Equipment
1.2 Scope
The standards in this section apply to electromechanical automatic and nonautomatic transfer
switches and bypass isolation switches rated 600 volts AC or less, 60 Hertz, for use on
single-phase and polyphase AC circuits.
2 DEFINITIONS
For the purposes of this NEMA Standards Publication, the following definitions apply.
automatic transfer switch: Self-acting equipment for transferring one or more load conductor
connections from one power source to another.
An automatic transfer switch may be supplied with or without a bypass isolation switch. An
automatic transfer switch may include logic to inhibit automatic operation in either or both
directions provided the switch reverts to automatic operation upon loss of power to the load.
bypass isolation switch: A manually operated device used in conjunction with a transfer
switch to provide a means of directly connecting load conductors to a power source and of
disconnecting the transfer switch.
A bypass isolation switch may be supplied with an automatic or nonautomatic transfer switch.
dual source bypass isolation switch: provides a means of maintaining power to the building
load during transfer switch service or repair. It also provides means to manually connect the
building load to the alternate source in the event the source feeding the load fails while the
transfer switch is disabled.
nonautomatic transfer switch: A device, operated by direct manpower or electrical remote
manual control, for transferring one or more load conductor connections from one power source
to another.
A nonautomatic transfer switch may be supplied with or without a bypass isolation switch.
transfer switch: A device for transferring one or more load conductor connections from one
power source to another.
A transfer switch may be automatic or nonautomatic.
conditional short-circuit rating: The prospective current that a transfer switch can
satisfactorily withstand for a total operating time of the overcurrent protective device under
specified conditions of use and behavior.
contact transfer time: The time measured from the parting of one set of main contacts to the
closing of a second set of main contacts on an alternate power source.
monitored source deviation: A variation in the power source being monitored that signals the
transfer switch to operate.
For clarification of terms:
a. Typical variations that can be detected are changes in voltage and frequency.
b. “Normal Source Failure” is a term often used to describe the loss or reduction of voltage
supplied by the normal power source. It is one type of monitored source deviation.
c. “Transfer Signal” is a term used to describe the signal that is initiated by the monitored
source deviation and that signals the transfer switch to operate.
operating transfer time: The time measured from the instant of the monitored source deviation
to the closing of main contacts on an available alternate power source exclusive of any
purposely introduced time delay.
total system transfer time: The time measured from the instant of the monitored source
deviation in one power source to the closing of main contacts on another power source,
including any purposely introduced time delays and engine-generator start-up time. “Total
System Transfer Time” is a parameter of the total system and not solely of the automatic
transfer switch.
3 CLASSIFICATIONS
Type A (PC*): A transfer switch that is not intended to provide required overcurrent (overload
and short-circuit) protection.
Type B (CB*): A transfer switch that is intended to automatically provide required overcurrent
(overload and short-circuit) protection.
*International Electrotechnical Commission (IEC)
4.1 Rated and Limiting Values for the Main (Power) Circuit
a. Total system load consisting of any combination of motors, electric discharge lamps,
electric heating (resistive) loads, and tungsten lamp loads, provided the latter does not
exceed 30 percent of the continuous current rating of the transfer switch equipment
b. Tungsten lamp load consisting entirely of tungsten lamps
c. Electric discharge lamp load consisting entirely of electric discharge lamps, including
fluorescent lamps
d. Resistive load consisting of heater and other noninductive loads in which the inrush
current does not exceed 150 percent of the continuous current rating of the switch
The withstand and closing current rating shall be one of the values specified in Column 1 of
Table 4–1.
Standard withstand and closing ratings are based on transfer switch equipment testing
conducted at maximum allowable test circuit power factors and corresponding minimum X/R
ratios specified in Table 4–1. When applying transfer switch equipment, consideration should be
given to both available fault current and circuit X/R ratio at the point of application.
5.1 Markings
See NEMA Standards Publication ICS 1.3 for preventive maintenance instructions.
7 CONSTRUCTION
7.1 Spacings
Except as otherwise specified in the following paragraphs, spacings in automatic transfer
switches and bypass isolation switches shall be not less than those shown in Table 7-1.
The spacings on printed wiring assemblies may be as small as 0.031 inch (0.8 mm) where the
power to the printed wiring assembly is limited and transient voltages are controlled as specified
in ICS 1, Clause 7.
The spacings given in Table 7–1 do not apply to snap switches, lampholders and similar wiring
devices that are used as a part of transfer switch equipment.
In a circuit involving potentials of not more than 50 VAC, the spacings at field-wiring terminals
may be 0.125 inch (3.2 mm) through air and 0.250 inch (6.4 mm) over the surface, and the other
spacings may be 0.053 inch (1.4 mm) through air and over the surface, provided that insulation
and clearances between the low-potential circuit and any high-potential circuit are in accordance
with the requirements that are applicable to the high-potential circuit.
7.2 Test Switch
An external test switch or terminals for connection to an external test switch shall be provided.
Such a test switch shall be connected so that operation of the test switch simulates a failure of
the normal power source.
7.3 Interlock
f. The control circuit shall have short-circuit protection and a disconnecting means suitable
for the available current of the supply, where the control circuit is located ahead of the
service disconnecting means. See 7.5 for fire pump control.
g. Be provided with overcurrent protection either immediately adjacent to, or as part of, the
transfer switch disconnecting means
7.5 Fire Pump Circuit Service
Where a transfer switch is used in a fire pump circuit, the requirements of NFPA 20 shall apply.
Table 7-1
SPACINGS
Minimum Spacings (inches)
Nominal Operating Voltage
51-150 151-300 301-600
Volts Volts Volts
1. Power Circuits Rated Not more Than 400 Amperes and Control Circuits
a. Between any uninsulated live part and (1) an uninsulated live part through air 0.125 0.250 0.375
of the opposite polarity and (2) an exposed metal part.* or oil (3.2 mm) (6.4 mm) (9.5 mm)
b. Between any uninsulated live part and the walls of a metal shortest 0.500 0.500 0.500
enclosure, including fittings for conduit or armored cable** distance (12.7mm) (12.7mm) (12.7 mm)
a. Between any uninsulated live part and an uninsulated live part of through air 0.500 0.750 1.000*
the opposite polarity. or oil (12.7mm) (19.1mm) (25.4 mm)
b. Between any uninsulated live part and an uninsulated grounded through air 0.500 0.500 1.000†
part, exposed metal part, or the walls of a metal enclosure, or oil (12.7mm) (12.7mm) (25.4 mm)
including fittings for conduit or armored cable.**
* The spacing between wiring terminals of opposite polarity and the spacing between a wiring terminal and a ground part shall be
not less than 0.250 inch (6.4 mm) if short-circuiting of grounding of such terminals may result from projecting strands of wire.
** For the purpose of this requirement, a metal piece attached to the enclosure is considered to be a part of the enclosure if
deformation of the enclosure is likely to reduce spacings between the metal piece and uninsulated live parts.
† The through-air spacing may be not less than 0.500 inch (12.7 mm) at the main terminals and also between grounded dead metal
and the neutral of a 277/480-VAC, 3-phase, 4-wire transfer switch.
Table 7-2
SIZE OF GROUNDING CONDUCTORS
Size of Largest Service Conductor or Equivalent Size of Grounding Conductor
Size of Multiple-conductor Cables*
*The equivalent size for multiple conductor cables shall be the sum of the circular-mil areas of the individual conductors.
Voltage critical loads may require adjustable voltage-monitoring and control means.
8.2.1 General
Transfer switch and bypass isolation switches shall be capable of meeting performance tests as
specified in UL 1008.
a. Type A transfer switches for which the manufacturer has not assigned a conditional
short-circuit rating shall withstand the level and duration of available short-circuit current
for which they are rated.
b. Type A transfer switches for which the manufacturer has assigned a conditional
short-circuit rating shall withstand the available short-circuit current for which they are
rated until the protective device clears the short circuit.
c. Type B transfer switches shall be capable of automatically interrupting the available
short-circuit current for which they are rated.
8.2.2.10 Repeated Dielectric Test
Verify the ability of the switch to withstand a reduced dielectric test after the withstand and
circuit closing tests.
A previously untested sample shall be permitted to be used for the withstand, circuit closing and
repeated dielectric tests.
Where transfer switch equipment is rated for multiple specific loads, as listed in 4.1.3, additional
samples shall be permitted to be used.
9 APPLICATIONS
For a fuller treatment of motor transfer, see the section on bus transfer or reclosing in MG 1.
a. Voltage
b. Number of phases
c. Number of wires
d. Frequency
e. Number of switched poles
f. Type of load as defined in 4.1.3
g. Continuous current or horsepower, or both, requirements of the load
h. Available fault current
i. Whether the switch is intended for emergency or standby service
j. Whether it is necessary to disconnect the load from both power sources simultaneously
k. Whether the switch is to be suitable for use as service equipment
l. Whether the switch is to include integral overcurrent protection
m. Whether it is necessary to provide a bypass isolation switch in conjunction with the
transfer switch. Where a bypass isolation switch is provided, it should be compatible
with the transfer switch.
9.3 Features for Particular Applications
Some conditions or requirements of particular applications may make additional features
necessary. These may include the following:
a. Time delay to override monitored source deviation—A fixed or adjustable time delay
which delays all signals for operation. This time delay prevents starting of the engine or
the transfer of the load from the normal power source to the alternate power source
during momentary voltage dips or disturbances of the normal power source.
b. Time delay before transfer to alternate power source—A fixed or adjustable time delay
which delays the transfer of the load to an available alternate power source. This delay
g. Alternate system exerciser—A programmable time switch to initiate the starting of the
engine-generator and to transfer the load from the normal to the alternate power source
for a preset period of time at preset intervals. The load is transferred back to the normal
power source at the end of the exercise period.*
Provision should be made for the initiation of immediate retransfer to the normal source
in the event of an engine generator failure during the exercise period.
h. Auxiliary contact—A contact, other than the power circuit contacts, that is part of transfer
switch and is available for connection by the user. The number of auxiliary contacts,
mode of operation and function of each contact should be specified.
i. Engine start contact—A contact that initiates cranking of the engine generator set when
the normal power source fails.*
j. Alternate source monitor—A device(s) that monitors voltage or frequency, or both, of the
alternate power source, and inhibits transfer to the alternate source until the monitored
parameters reach specified levels.
k. Test switch—A switch to simulate failure of the normal power source, causing transfer of
the load to the alternate power source.
l. Close-differential protection—A device(s) that monitors all lines of the normal power
source and initiates transfer of the load from the normal power source to the alternate
power source when any line of the normal power source drops below a predetermined
value of voltage. It initiates transfer of the load back to the normal power source when all
lines of the normal power source return to within specified limits. This feature is
generally used for installations where only a limited reduction in voltage can be tolerated.
m. Time-delay-bypass switch—A momentary contact switch that initiates immediate transfer
of the load back to the normal power source, bypassing any optional time delays.
n. Manual return-to-normal switch—A momentary contact switch that initiates transfer from
the alternate to the normal power source where automatic transfer is not desired.
Annex A
Short Time Rating
Section 4.1.6 of ICS 10 outlines withstand and closing ratings for transfer switch equipment. As
noted, the requirement parallels those of UL Standard 1008. With the introduction of circuit
breakers with electronic trips, the requirements for withstand and closing capability of transfer
switch equipment (TSE) is more complex. UL 1008 addresses this issue by providing the option
for “short time ratings.”
Traditional thought said that the transfer switch is a piece of wire, and that it was protected by
the common thermal/magnetic circuit breaker. When protected by a circuit breaker with the
familiar I 2 T (thermal) trip, and instantaneous trip, the transfer switch merely had to be able to
“withstand” a short-circuit fault long enough to allow the upstream device to clear the fault.
However, with a short time trip element, it is possible that the upstream breaker may not trip
during a fault. This means the transfer switch contacts must survive this event as defined by UL
1008.
The worst case condition is determined by the Instantaneous pickup and Short Time Delay
setting on the Upstream Protective Device. The Transfer Switch must “survive” a current that is
just below the instantaneous pickup until the short time delay expires. If the TSE contacts fail to
survive, and the upstream device does not trip, then loss of power to the load results.
In electrical systems it is highly desirable to make sure that a fault is cleared by the upstream
protective device that is closest to the fault. To achieve this, the application for a “short time” trip
rating on upstream circuit breakers has become a necessity. The short time trip characteristic
gives the user the ability to program the trip curve of a particular circuit breaker so that it will
intentionally wait for a downstream device to clear the fault. This means that a transfer switch
applied between this upstream breaker and a downstream device must then truly withstand the
fault current seen while the protective devices react. Failure to do so will make the transfer
switch the weak link in the system.
The short-time characteristic is usually a “flat response” type. This means that a timer in the
circuit breaker is started when the fault current exceeds the short time pickup setting. If the
current remains above the pickup point and the timer times out, then the circuit breaker will trip.
The designer should be aware that there may be I 2 T short time characteristics available in
certain trip units, and these offer some increased coordination possibilities.
In either case it is important to note that should the fault current continue to increase, and reach
the instantaneous pickup point for the trip, that the breaker would then trip instantaneously.
Therefore, the worst case scenario for the transfer switch is the case where the fault current
rises to just below the instantaneous pickup, and the short time has to time out. This is the
particular point the user must be aware of, and allow for in the application of the transfer switch.
In other words, it is important to make sure that the transfer switch will truly withstand a current
equal to the instantaneous current pickup for the maximum time of the short time delay. It is also
important to realize that the instantaneous pickup point, and the maximum interrupt rating of the
breaker are not synonymous.
Let us use a generic example that may explain the application. We will deal with a 3000A circuit
breaker having an adjustable short-time pick up settable between 2 and 6 times the nominal
rating, and an instantaneous pickup settable between 2 and 10 times the nominal rating. The
maximum short time delay setting is 0.5 seconds, or 30 cycles on a 60 Hz system. Given this
example, proper application of a transfer switch would require a short time rating (for the
transfer switch) of 30 kA for 0.5 seconds. This relates to setting both the instantaneous pickup
and the short time delay of the upstream breaker at their maximums. Since various circuit
breakers offer different options relating to pickups and time ranges, responsibility to properly
apply the transfer switch must fall on the designer.
The designer should understand that the short time rating of a transfer switch is much different
than the short-circuit rating . The short-circuit rating is based on tripping of the upstream device
and the need to transfer to the alternate source. The short time rating deals with a non-tripping
condition of the upstream device for a period of time, and the fact that the primary source of
power will not be interrupted. The transfer switch will not see a need to transfer, and must
therefore remain in a state to handle load current from the uninterrupted source during, and after
the fault is cleared by the downstream device.
When applying a transfer switch with a short time rating, the designer should always apply the
transfer switch having short-time current ratings equal to or greater than the selected
instantaneous pickup setting and short time delay setting of the properly coordinated upstream
breaker.
Annex B
Neutral Conductors in Power Transfer Systems
Many transfer switching systems involve three phase AC power sources with a neutral conductor
(normally referred to as “4-wire distribution”) or single-phase sources with neutral. Single-phase
sources can be either 2-wire (line-neutral) or 3-wire (line-neutral-line) circuits. The application
of transfer systems for switching neutral connected loads between such power sources requires
consideration of several issues to achieve satisfactory operation, including compliance with the
National Electrical Code and preserving the functionality of ground fault monitoring equipment.
The National Electrical Code defines when power sources are required to be grounded and also
addresses the required grounding practices. In broad terms there are two types of sources,
those that are “separately derived” and those that are “non-separately derived.” Separately
derived sources are those with no direct connection (including a neutral conductor) to another
source. A non-separately derived source is directly connected to another power source,
typically through solidly connected neutral conductors. The determination as to whether a
source is to be separately derived or non-separately derived is typically made by the system
designer and/or authority having jurisdiction.
If it is determined that a power system consists of separately derived sources, each neutral must
be bonded to ground at its respective source. When transfer equipment is used in this type
system the neutral conductor must be switched along with the phase (line) conductors to prevent
multiple connections between neutral and ground within the system. Multiple connections
between neutral and ground can result in current flow through the grounding system, violating
the requirement that the ground system is never allowed to carry current, except in the case of a
fault. Multiple connections may also defeat or cause false operation of ground fault detection by
allowing ground fault currents to bypass monitoring equipment, or by allowing normal neutral
currents to appear as fault currents.
When switching the neutral conductor, timing of the opening and closing of the phase (line) and
neutral poles is important. If the phase conductors are connected without connection of the
neutral conductors a transient over-voltage can occur at the load.
The current rating of the neutral pole in transfer equipment is another consideration.
Unbalanced loads can result in high neutral currents. Also, nonlinear electronic loads
connected to transfer equipment can create current harmonics that add in the neutral conductors
that might make it necessary to over size the neutral current capacity to prevent overheating of
conductors or the switch poles. Depending on the nature of loads, the neutral rating may need
to be up to 200% of the phase rating.
For systems consisting of non-separately derived sources it is not appropriate to switch the
neutral conductors. If a power system consists of non-separately derived sources, the neutral
conductors from the sources must be solidly connected together. This “shared neutral” must be
bonded to ground at only one source. There must not be any switching device between the
neutral conductors of the sources. This technique allows the neutral conductor of each source to
carry its respective neutral current, and the ground conductors to carry only ground fault current.
By not switching the neutral conductors the possibility of transient overvoltage from neutral
switching delays or failures is eliminated.