100% found this document useful (1 vote)
336 views27 pages

Nema Ics 10.1-2005

Uploaded by

Achintya Samanta
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
100% found this document useful (1 vote)
336 views27 pages

Nema Ics 10.1-2005

Uploaded by

Achintya Samanta
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 27

NEMA ICS 10

INDUSTRIAL CONTROL
AND SYSTEMS
PART 1:
ELECTROMECHANICAL
AC TRANSFER SWITCH
EQUIPMENT
NEMA Standards Publication ICS 10-2005

Industrial Control and Systems


Part 1: Electromechanical AC Transfer Switch Equipment

Published by:

National Electrical Manufacturers Association


1300 North 17th Street
Rosslyn, Virginia 22209

www.nema.org

© Copyright 2005 by the National Electrical Manufacturers Association. All rights including
translation into other languages, reserved under the Universal Copyright Convention, the Berne
Convention for the Protection of Literary and Artistic Works, and the International and Pan
American Copyright Conventions.
NOTICE AND DISCLAIMER

The information in this publication was considered technically sound by the consensus of
persons engaged in the development and approval of the document at the time it was
developed. Consensus does not necessarily mean that there is unanimous agreement among
every person participating in the development of this document.

The National Electrical Manufacturers Association (NEMA) standards and guideline publications,
of which the document contained herein is one, are developed through a voluntary consensus
standards development process. This process brings together volunteers and/or seeks out the
views of persons who have an interest in the topic covered by this publication. While NEMA
administers the process and establishes rules to promote fairness in the development of
consensus, it does not write the document and it does not independently test, evaluate, or verify
the accuracy or completeness of any information or the soundness of any judgments contained
in its standards and guideline publications.

NEMA disclaims liability for any personal injury, property, or other damages of any nature
whatsoever, whether special, indirect, consequential, or compensatory, directly or indirectly
resulting from the publication, use of, application, or reliance on this document. NEMA disclaims
and makes no guaranty or warranty, express or implied, as to the accuracy or completeness of
any information published herein, and disclaims and makes no warranty that the information in
this document will fulfill any of your particular purposes or needs. NEMA does not undertake to
guarantee the performance of any individual manufacturer or seller’s products or services by
virtue of this standard or guide.

In publishing and making this document available, NEMA is not undertaking to render
professional or other services for or on behalf of any person or entity, nor is NEMA undertaking
to perform any duty owed by any person or entity to someone else. Anyone using this document
should rely on his or her own independent judgment or, as appropriate, seek the advice of a
competent professional in determining the exercise of reasonable care in any given
circumstances. Information and other standards on the topic covered by this publication may be
available from other sources, which the user may wish to consult for additional views or
information not covered by this publication.

NEMA has no power, nor does it undertake to police or enforce compliance with the contents of
this document. NEMA does not certify, test, or inspect products, designs, or installations for
safety or health purposes. Any certification or other statement of compliance with any health or
safety–related information in this document shall not be attributable to NEMA and is solely the
responsibility of the certifier or maker of the statement.
ICS 10-2005, Part 1 AC Transfer Switch Equipment
Page i

CONTENTS
Page

Part 1 AC TRANSFER SWITCH EQUIPMENT ....................................................................... 1


1 GENERAL...................................................................................................................... 1
1.1 Referenced Standards........................................................................................... 1
1.2 Scope ................................................................................................................... 2
2 DEFINITIONS ................................................................................................................ 2
2.1 Switching Devices ................................................................................................. 2
2.2 Operation of AC Transfer Switch Equipment .......................................................... 2
3 CLASSIFICATIONS........................................................................................................ 3
4 CHARACTERISTICS AND RATINGS .............................................................................. 3
4.1 Rated and Limiting Values for the Main (Power) Circuit.......................................... 3
4.1.1 System Voltage Ratings............................................................................. 3
4.1.2 Continuous Current Rating ........................................................................ 3
4.1.3 Rating Based on Load Characteristics ....................................................... 3
4.1.4 Interrupting Rating..................................................................................... 4
4.1.5 Motor Starter Rating .................................................................................. 4
4.1.6 Withstand and Closing Ratings .................................................................. 4
4.1.7 Overcurrent Protection .............................................................................. 4
5 PRODUCT MARKING, INSTALLATION, AND MAINTENANCE INFORMATION................ 5
5.1 Markings ............................................................................................................... 5
5.1.1 Transfer Switches...................................................................................... 5
5.1.2 Bypass Isolation Switch Equipment ............................................................ 5
5.1.3 Control Circuits ......................................................................................... 5
5.1.4 Maintenance of Transfer Switch Equipment ........................................................... 5
6 SERVICE AND STORAGE CONDITIONS ....................................................................... 5
7 CONSTRUCTION........................................................................................................... 6
7.1 Spacings............................................................................................................... 6
7.2 Test Switch ........................................................................................................... 6
7.3 Interlock................................................................................................................ 6
7.3.1 Protection from Cross-Connection ............................................................. 6
7.3.2 Bypass Isolation Switch Interlock ............................................................... 6
7.4 Service Equipment ................................................................................................ 6
7.5 Fire Pump Circuit Service ...................................................................................... 7
7.6 Emergency Power Circuit Service.......................................................................... 7
7.7 Control Circuits ..................................................................................................... 7
8 PERFORMANCE REQUIREMENTS AND TESTS ............................................................ 9
8.1 Performance Requirements ................................................................................... 9
8.1.1 Control Circuits ......................................................................................... 9
8.1.2 Ground-Fault Protection ............................................................................ 9
8.1.3 Undervoltage Monitoring Characteristics .................................................... 9
8.2 Design Tests ......................................................................................................... 9

© Copyright 2005 by the National Electrical Manufacturers Association.


ICS 10-2005, Part 1 AC Transfer Switch Equipment
Page ii

8.2.1 General ..................................................................................................... 9


8.2.2 Test Sequence .......................................................................................... 9
8.2.3 Test Samples ......................................................................................... 10
9 APPLICATIONS ........................................................................................................... 11
9.1 Motor Transfer .................................................................................................... 11
9.2 AC Transfer Switch Equipment Specification ....................................................... 11
9.3 Features for Particular Applications ..................................................................... 11
Annex A Short Time Rating ................................................................................................ 14
Annex B Neutral Conductors in Power Transfer Systems ...................................................... 16

© Copyright 2005 by the National Electrical Manufacturers Association.


ICS 10-2005, Part 1 AC Transfer Switch Equipment
Page iii

Foreword

This Standards Publication was prepared by a technical committee of the NEMA Industrial
Automation Control Products and Systems Section. It was approved in accordance with the
bylaws of NEMA and supersedes the indicated NEMA Standards Publication. This Standards
Publication supersedes ICS 10-1993. Information on static transfer switches can be found in
ICS 10-1999 Part 2: Static AC Transfer Switch Equipment.

This Standards Publication provides practical information concerning ratings, construction, test,
performance and manufacture of industrial control equipment. These standards are used by the
electrical industry to provide guidelines for the manufacture and proper application of reliable
products and equipment and to promote the benefits of repetitive manufacturing and widespread
product availability.

NEMA Standards represent the result of many years of research, investigation and experience
by the members of NEMA, its predecessors, its Sections and Committees. They have been
developed through continuing consultation among manufacturers, users and national
engineering societies and have resulted in improved serviceability of electrical products with
economies to manufacturers and users.

One of the primary purposes of this Standards Publication is to encourage the production of
reliable control equipment which, in itself, functions in accordance with these accepted
standards. Some portions of these standards, such as electrical spacings and interrupting
ratings, have a direct bearing on safety; almost all of the items in this publication, when applied
properly, contribute to safety in one way or another.

Properly constructed industrial control equipment is, however, only one factor in minimizing the
hazards which may be associated with the use of electricity. The reduction of hazard involves
the joint efforts of the various equipment manufacturers, the system designer, the installer and
the user. Information is provided herein to assist users and others in the proper selection of
control equipment.

The industrial control manufacturer has limited or no control over the following factors which are
vital to a safe installation:

a. Environmental conditions
b. System design
c. Equipment selection and application
d. Installation
e. Operating practices
f. Maintenance
This publication is not intended to instruct the user of control equipment with regard to these
factors except insofar as suitable equipment to meet needs can be recognized in this publication
and some application guidance is given.

This Standards Publication is necessarily confined to defining the construction requirements for
industrial control equipment and to providing recommendations for proper selection for use
under normal or certain specific conditions. Since any piece of industrial control equipment can
be installed, operated and maintained in such a manner that hazardous conditions may result,
conformance with this publication does not by itself assure a safe installation. When, however,
equipment conforming with these standards is properly selected and is installed in accordance

© Copyright 2005 by the National Electrical Manufacturers Association.


ICS 10-2005, Part 1 AC Transfer Switch Equipment
Page iv

with the National Electrical Code and properly maintained, the hazards to persons and property
will be reduced.

To continue to serve the best interests of users of Industrial Control and Systems equipment,
the Industrial Automation Control Products and Systems Section is actively cooperating with
other standardization organizations in the development of simple and more universal metrology
practices. In this publication, the U.S. customary units are gradually being supplemented by
those of the modernized metric system known as the International Systems of Units (SI). This
transition involves no changes in standard dimensions, tolerances, or performance
specifications.

NEMA Standards Publications are subject to periodic review. They are revised frequently to
reflect user input and to meet changing conditions and technical progress. Proposed revisions to
this Standards Publication should be submitted to:
Vice President, Technical Services
National Electrical Manufacturers Association
1300 North 17th Street, Suite 1847
Rosslyn, Virginia 22209

This standards publication was developed by the Industrial Automation Control Products and
Systems Section. Section Approval of the standard does not necessarily imply that all section
members voted for its approval or participated in its development. At the time it was approved,
the Section was composed of the following members:

ABB Control, Inc.—Wichita Falls, TX


ABB Automation Technologies – Raleigh, NC
ASCO Power Technologies—Florham Park, NJ
Automatic Switch Company – Florham Park, NJ
c3controls—Beaver, PA
California Linear Devices – Carlsbad, CA
CARLO GAVAZZI, INC.—Buffalo Grove, IL
Cooper Bussman – St. Louis, MO
Cummins, Inc.—Minneapolis, MN
Eaton Electrical, Inc.—Milwaukee, WI
Electro Switch Corporation—Weymouth, MA
Emerson Process Management—Austin, TX
GE Consumer & Industrial—Charlottesville, VA
Hubbell Incorporated—Wadsworth, OH
Hubbell Industrial Controls, Inc.—Archdale, NC
Joslyn Clark Controls, Inc.—Lancaster, SC
L-3 Communications/SPD Technologies – Anaheim, CA
Master Controls Systems, Inc.—Lake Bluff, IL
Metron, Inc.—Denver, CO
Mitsubishi Electric Automation, Inc.—Vernon Hills, IL
Moeller Electric Corporation—Houston, TX
Omron Electronics LLC—Schaumburg, IL
Peerless Electric—Warren, OH
Phoenix Contact, Inc.—Harrisburg, PA
Post Glover Resistors, Inc.—Erlanger, KY
Reliance Controls Corporation—Racine, WI
Rockwell Automation—Milwaukee, WI
Russelectric, Inc.—Hinngham, MA
Schneider Automation, Inc.—North Andover, MA
Schneider Electric North America/Square D Company—Raleigh, NC

© Copyright 2005 by the National Electrical Manufacturers Association.


ICS 10-2005, Part 1 AC Transfer Switch Equipment
Page v

Schneider North American Operation Division—Lexington, KY


SEW-Eurodrive, Inc.—Lyman, SC
Siemens Corporate Research—Princeton, NJ
Siemens Energy & Automation, Inc.—Norcross, GA
Siemens Shared Services LLC—Duluth, GA
Square D Company—Raleigh, NC
Torna Tech Inc.—Saint-Laurent, Canada
Toshiba International Corporation—Houston, TX
Total Control Products, Inc.—Terrace Park, OH
Tyco Electronics/AMP—Harrisburg, PA
WAGO Corporation—Germantown, WI
Weidmuller Inc.—Richmond, VA
Yaskawa Electric America, Inc.—Waukegan, IL

© Copyright 2005 by the National Electrical Manufacturers Association.


ICS 10-2005, Part 1 AC Transfer Switch Equipment
Page vi

<This page is intentionally left blank.>

© Copyright 2005 by the National Electrical Manufacturers Association.


ICS 10-2005, Part 1 AC Transfer Switch Equipment
Page 1

Part 1
AC TRANSFER SWITCH EQUIPMENT

1 GENERAL

The definitions and standards of ICS 1, except for clause 7 pertaining to spacings as indicated,
also apply to this standard.

Emergency systems are those that meet the requirements of Articles 517 and 700 of NFPA 70
(NEC) and NFPA 99. Emergency systems are those legally required to automatically supply
alternate power within 10 seconds of power interruption to a number of prescribed functions
essential for safety to human life.

Legally required standby systems are those that meet the requirements of Article 701 of NFPA
70 (NEC). These systems are intended to automatically supply power to selected loads (other
than those classed as emergency systems) in the event of failure of the normal source.

Optional standby systems are those that meet the requirements of Article 702 of NFPA 70
(NEC). These systems are intended to supply power either automatically or non-automatically to
selected loads other than those classed as Emergency or Legally Required Standby.

1.1 Referenced Standards


In this NEMA Standards Publication reference is made to the following standards listed below.
Copies are available from the indicated sources.

National Electrical Manufacturers Association


1300 North 17th Street
Rosslyn, VA 22209

ICS 1-2000 Industrial Control and Systems, General Requirements

ICS 1.3-1986 (R2001) Preventive Maintenance of Industrial Control and Systems Equipment

MG 1-1999 Motors and Generators

Underwriters Laboratories Inc.


333 Pfingsten Road
Northbrook, IL 60062

UL 1008-1996 Automatic Transfer Switches

National Fire Protection Association


Batterymarch Park
Quincy, MA 02269

NFPA 20-1999 Installation of Centrifugal Fire Pumps

NFPA 70-1999 National Electrical Code (NEC)

NFPA 99-1999 Health Care Facilities

© Copyright 2005 by the National Electrical Manufacturers Association.


ICS 10-2005, Part 1 AC Transfer Switch Equipment
Page 2

1.2 Scope
The standards in this section apply to electromechanical automatic and nonautomatic transfer
switches and bypass isolation switches rated 600 volts AC or less, 60 Hertz, for use on
single-phase and polyphase AC circuits.

2 DEFINITIONS

For the purposes of this NEMA Standards Publication, the following definitions apply.

2.1 Switching Devices

automatic transfer switch: Self-acting equipment for transferring one or more load conductor
connections from one power source to another.
An automatic transfer switch may be supplied with or without a bypass isolation switch. An
automatic transfer switch may include logic to inhibit automatic operation in either or both
directions provided the switch reverts to automatic operation upon loss of power to the load.
bypass isolation switch: A manually operated device used in conjunction with a transfer
switch to provide a means of directly connecting load conductors to a power source and of
disconnecting the transfer switch.
A bypass isolation switch may be supplied with an automatic or nonautomatic transfer switch.
dual source bypass isolation switch: provides a means of maintaining power to the building
load during transfer switch service or repair. It also provides means to manually connect the
building load to the alternate source in the event the source feeding the load fails while the
transfer switch is disabled.
nonautomatic transfer switch: A device, operated by direct manpower or electrical remote
manual control, for transferring one or more load conductor connections from one power source
to another.
A nonautomatic transfer switch may be supplied with or without a bypass isolation switch.

transfer switch: A device for transferring one or more load conductor connections from one
power source to another.
A transfer switch may be automatic or nonautomatic.

2.2 Operation of AC Transfer Switch Equipment

conditional short-circuit rating: The prospective current that a transfer switch can
satisfactorily withstand for a total operating time of the overcurrent protective device under
specified conditions of use and behavior.
contact transfer time: The time measured from the parting of one set of main contacts to the
closing of a second set of main contacts on an alternate power source.
monitored source deviation: A variation in the power source being monitored that signals the
transfer switch to operate.
For clarification of terms:
a. Typical variations that can be detected are changes in voltage and frequency.
b. “Normal Source Failure” is a term often used to describe the loss or reduction of voltage
supplied by the normal power source. It is one type of monitored source deviation.

© Copyright 2005 by the National Electrical Manufacturers Association.


ICS 10-2005, Part 1 AC Transfer Switch Equipment
Page 3

c. “Transfer Signal” is a term used to describe the signal that is initiated by the monitored
source deviation and that signals the transfer switch to operate.

operating transfer time: The time measured from the instant of the monitored source deviation
to the closing of main contacts on an available alternate power source exclusive of any
purposely introduced time delay.
total system transfer time: The time measured from the instant of the monitored source
deviation in one power source to the closing of main contacts on another power source,
including any purposely introduced time delays and engine-generator start-up time. “Total
System Transfer Time” is a parameter of the total system and not solely of the automatic
transfer switch.

3 CLASSIFICATIONS

Transfer switches are classified Type A or Type B as follows:

Type A (PC*): A transfer switch that is not intended to provide required overcurrent (overload
and short-circuit) protection.
Type B (CB*): A transfer switch that is intended to automatically provide required overcurrent
(overload and short-circuit) protection.
*International Electrotechnical Commission (IEC)

4 CHARACTERISTICS AND RATINGS


Transfer switch equipment is marked with electrical ratings and shall be applied in accordance
with those ratings.

4.1 Rated and Limiting Values for the Main (Power) Circuit

4.1.1 System Voltage Ratings


The system voltage rating of transfer switch equipment shall be 120, 208, 240, 480, or 600 VAC,
single phase or polyphase.

4.1.2 Continuous Current Rating


The continuous current rating of transfer switch equipment shall be in the range of 30 to 4000
amps, based on an ambient temperature of 40°C.

4.1.3 Rating Based on Load Characteristics


Transfer switch equipment shall be rated for one or more of the following types of loads:

a. Total system load consisting of any combination of motors, electric discharge lamps,
electric heating (resistive) loads, and tungsten lamp loads, provided the latter does not
exceed 30 percent of the continuous current rating of the transfer switch equipment
b. Tungsten lamp load consisting entirely of tungsten lamps
c. Electric discharge lamp load consisting entirely of electric discharge lamps, including
fluorescent lamps
d. Resistive load consisting of heater and other noninductive loads in which the inrush
current does not exceed 150 percent of the continuous current rating of the switch

© Copyright 2005 by the National Electrical Manufacturers Association.


ICS 10-2005, Part 1 AC Transfer Switch Equipment
Page 4

4.1.4 Interrupting Rating


Current interrupting ratings shall be expressed in rms symmetrical amperes.

4.1.5 Motor Starter Rating


Transfer switch equipment intended for a load consisting of a single motor may include overload
relays and may be rated in horsepower or in full-load and locked-rotor current.

4.1.6 Withstand and Closing Ratings


Transfer switch equipment shall have withstand and closing ratings, expressed in maximum
available fault current (rms symmetrical amperes) at maximum rated voltage, and marked in
accordance with UL 1008 and this standard. The type and rating of any associated protective
devices necessary to meet the requirements of UL 1008 shall also be marked on the transfer
switch equipment.

The withstand and closing current rating shall be one of the values specified in Column 1 of
Table 4–1.

Standard withstand and closing ratings are based on transfer switch equipment testing
conducted at maximum allowable test circuit power factors and corresponding minimum X/R
ratios specified in Table 4–1. When applying transfer switch equipment, consideration should be
given to both available fault current and circuit X/R ratio at the point of application.

4.1.7 Overcurrent Protection


Each service, feeder, and branch circuit should have the appropriate short-circuit, ground-fault
and overload protection, provided either externally or as an integral part of the transfer switch
equipment.
Table 4–1
AVAILABLE FAULT CURRENTS AND RESPECTIVE TEST POWER FACTORS
AND CORRESPONDING X/R RATIOS
Withstand and Closing Maximum Test Minimum
Rating Power Factor Corresponding
(rms symetrical amperes) X/R Ratio
5,000 0.50 1.73
7,500 0.50 1.73
10,000 0.50 1.73
14,000 0.30 3.18
18,000 0.30 3.18
22,000 0.20 4.90
25,000 0.20 4.90
30,000 0.20 4.90
35,000 0.20 4.90
42,000 0.20 4.90
50,000 0.20 4.90
65,000 0.20 4.90
85,000 0.20 4.90
100,000 0.20 4.90
125,000 0.20 4.90
150,000 0.20 4.90
200,000 0.20 4.90

© Copyright 2005 by the National Electrical Manufacturers Association.


ICS 10-2005, Part 1 AC Transfer Switch Equipment
Page 5

5 PRODUCT MARKING, INSTALLATION, AND MAINTENANCE INFORMATION

5.1 Markings

5.1.1 Transfer Switches


The nameplate markings for transfer switches shall include:

a. Name of manufacturer and catalog number, or the equivalent serial number


b. Voltage and frequency ratings
c. Continuous current rating
Additional markings shall be those required by UL 1008 and shall include the following, where
applicable:

d. Suitability for emergency or standby service as defined by the NEC


e. Suitability for specific loads. See 4.3.5 of UL 1008
f. Suitability for use as service equipment
g. Interrupting or short-circuit ratings
1. For Type A: Short-circuit rating or conditional short-circuit rating with the type and
rating of the additionally required short-circuit protective device
2. For Type B: Interrupting rating
h. Cautions or warnings, or both
i. Automatic or nonautomatic
5.1.2 Bypass Isolation Switch Equipment
The nameplate markings for bypass/isolation switches shall include:

a. Name of manufacturer and catalog number, or the equivalent serial number


b. Voltage and frequency ratings
c. Continuous current rating
5.1.3 Control Circuits
Transfer switch equipment control circuits shall meet the marking requirements of UL 1008.

5.1.4 Maintenance of Transfer Switch Equipment


A maintenance program and schedule should be established for each particular installation to
assure minimum down time. The program should include periodic testing, tightening of
connections, inspection for evidence of overheating and excessive contact erosion, removal of
dust and dirt, and replacement of contacts when required.

See NEMA Standards Publication ICS 1.3 for preventive maintenance instructions.

6 SERVICE AND STORAGE CONDITIONS

ICS 1, Clause 6 applies.

© Copyright 2005 by the National Electrical Manufacturers Association.


ICS 10-2005, Part 1 AC Transfer Switch Equipment
Page 6

7 CONSTRUCTION

7.1 Spacings
Except as otherwise specified in the following paragraphs, spacings in automatic transfer
switches and bypass isolation switches shall be not less than those shown in Table 7-1.

The spacings on printed wiring assemblies may be as small as 0.031 inch (0.8 mm) where the
power to the printed wiring assembly is limited and transient voltages are controlled as specified
in ICS 1, Clause 7.
The spacings given in Table 7–1 do not apply to snap switches, lampholders and similar wiring
devices that are used as a part of transfer switch equipment.

In a circuit involving potentials of not more than 50 VAC, the spacings at field-wiring terminals
may be 0.125 inch (3.2 mm) through air and 0.250 inch (6.4 mm) over the surface, and the other
spacings may be 0.053 inch (1.4 mm) through air and over the surface, provided that insulation
and clearances between the low-potential circuit and any high-potential circuit are in accordance
with the requirements that are applicable to the high-potential circuit.
7.2 Test Switch
An external test switch or terminals for connection to an external test switch shall be provided.
Such a test switch shall be connected so that operation of the test switch simulates a failure of
the normal power source.

7.3 Interlock

7.3.1 Protection from Cross-Connection


The operating mechanism of a transfer switch shall have a mechanical or electromechanical
interlock to prevent simultaneous connection of the load to both the normal and alternate power
sources.

7.3.2 Bypass Isolation Switch Interlock


Bypass isolation switches shall be provided with necessary interlocks to prevent the
unintentional simultaneous connection of two power sources. In addition, bypass isolation
switches provided with overlapping contacts shall be provided with a means of interlocking to
prevent the opening of nonload-break contacts under load.

7.4 Service Equipment


Transfer switches which are designed to be suitable for use as service equipment shall:

a. Have spacings in accordance with Table 7-1, Item 2


b. Have accessible independent disconnecting means for both the normal and alternate
power sources
c. Be marked “suitable for use as service equipment”
d. Where provided with a neutral, have provision for connection of the service grounding
conductor to the neutral terminal in accordance with Table 7-2
e. Be provided with ground-fault protection where applied on solidly grounded wye
electrical services of more than 150 VAC to ground, but not exceeding 600 VAC
phase-to-phase for each service disconnect rated 1000 amperes or more. See 7.5 for fire
pump control and 8.6 for emergency power circuits.

© Copyright 2005 by the National Electrical Manufacturers Association.


ICS 10-2005, Part 1 AC Transfer Switch Equipment
Page 7

f. The control circuit shall have short-circuit protection and a disconnecting means suitable
for the available current of the supply, where the control circuit is located ahead of the
service disconnecting means. See 7.5 for fire pump control.
g. Be provided with overcurrent protection either immediately adjacent to, or as part of, the
transfer switch disconnecting means
7.5 Fire Pump Circuit Service
Where a transfer switch is used in a fire pump circuit, the requirements of NFPA 20 shall apply.

7.6 Emergency Power Circuit Service


The alternate source for emergency systems shall not be required to have ground-fault
protection of equipment.

7.7 Control Circuits


Transfer switch equipment shall be exempted from the motor control circuit overcurrent
protection requirements of ICS 1, Clause 7.

© Copyright 2005 by the National Electrical Manufacturers Association.


ICS 10-2005, Part 1 AC Transfer Switch Equipment
Page 8

Table 7-1
SPACINGS
Minimum Spacings (inches)
Nominal Operating Voltage
51-150 151-300 301-600
Volts Volts Volts

1. Power Circuits Rated Not more Than 400 Amperes and Control Circuits

a. Between any uninsulated live part and (1) an uninsulated live part through air 0.125 0.250 0.375
of the opposite polarity and (2) an exposed metal part.* or oil (3.2 mm) (6.4 mm) (9.5 mm)

over 0.250 0.375 0.500


surface (6.4 mm) (9.5 mm) (12.7 mm)

b. Between any uninsulated live part and the walls of a metal shortest 0.500 0.500 0.500
enclosure, including fittings for conduit or armored cable** distance (12.7mm) (12.7mm) (12.7 mm)

2. Power Circuits Rated Over 400 amperes and Service Equipment.

a. Between any uninsulated live part and an uninsulated live part of through air 0.500 0.750 1.000*
the opposite polarity. or oil (12.7mm) (19.1mm) (25.4 mm)

over 0.750 1.250 2.000


surface (19.1mm) (31.8mm) (50.8 mm)

b. Between any uninsulated live part and an uninsulated grounded through air 0.500 0.500 1.000†
part, exposed metal part, or the walls of a metal enclosure, or oil (12.7mm) (12.7mm) (25.4 mm)
including fittings for conduit or armored cable.**

* The spacing between wiring terminals of opposite polarity and the spacing between a wiring terminal and a ground part shall be
not less than 0.250 inch (6.4 mm) if short-circuiting of grounding of such terminals may result from projecting strands of wire.
** For the purpose of this requirement, a metal piece attached to the enclosure is considered to be a part of the enclosure if
deformation of the enclosure is likely to reduce spacings between the metal piece and uninsulated live parts.
† The through-air spacing may be not less than 0.500 inch (12.7 mm) at the main terminals and also between grounded dead metal
and the neutral of a 277/480-VAC, 3-phase, 4-wire transfer switch.

Table 7-2
SIZE OF GROUNDING CONDUCTORS
Size of Largest Service Conductor or Equivalent Size of Grounding Conductor
Size of Multiple-conductor Cables*

Copper Aluminum Copper Aluminum

2 AWG or smaller 0 AWG or smaller 8 AWG 6 AWG


1 or 2 AWG 2/0 or 3/0 AWG 6 AWG 4 AWG
2/0 or 3/0 AWG 4/0 AWG or 250 kcmil 4 AWG 2 AWG
Over 3/0 AWG to 350 kcmil Over 250 to 500 kcmil 2 AWG 0 AWG
Over 350 to 600 kcmil Over 500 to 900 kcmil 0 AWG 3/0 AWG
Over 600 to 1100 kcmil Over 900 to 1750 kcmil 2/0 AWG 4/0 AWG
Over 1100 kcmil Over 1750 kcmil 3/0 AWG 250 kcmil

*The equivalent size for multiple conductor cables shall be the sum of the circular-mil areas of the individual conductors.

© Copyright 2005 by the National Electrical Manufacturers Association.


ICS 10-2005, Part 1 AC Transfer Switch Equipment
Page 9

8 PERFORMANCE REQUIREMENTS AND TESTS

8.1 Performance Requirements

8.1.1 Control Circuits


Transfer switch equipment control circuits shall meet the overcurrent and mechanical protection
requirements of UL 1008.

8.1.2 Ground-Fault Protection


Where ground-fault protection is provided, the performance requirements are as follows:

a. The maximum setting of the ground-fault protection shall be 1200 amperes.


b. The maximum time delay shall be 1 second for ground-fault currents equal to or greater
than 3000 amperes.
c. In health care facilities, the ground-fault protection on the service disconnect must be
coordinated with the ground-fault protection on the next downstream feeder to ensure
100 percent selectivity such that the feeder device and not the service disconnect shall
open on ground faults on the load side of the feeder device. There shall be a minimum
time separation of six cycles between tripping bands.
8.1.3 Undervoltage Monitoring Characteristics
Unless otherwise specified, transfer switch equipment shall have provision for initiating the
transfer of load conductor connections to an alternate power source when the voltage on any
phase of the normal power source falls below 70 percent of rated voltage. Provision shall also
be made for transferring the connections back to the normal power source when the voltage on
all phases of the normal power source returns to at least 90 percent of rated voltage.

Voltage critical loads may require adjustable voltage-monitoring and control means.

8.2 Design Tests

8.2.1 General
Transfer switch and bypass isolation switches shall be capable of meeting performance tests as
specified in UL 1008.

8.2.2 Test Sequence


The following design tests conducted on enclosed transfer switch equipment are usually
performed in the sequence shown below.

8.2.2.1 Normal Operation Test


Verify the correct functioning of controls for automatic and test operation.

8.2.2.2 Overvoltage Test


Verify the ability of coils to withstand 110 percent of rated voltage for the maximum time during
which they are normally energized.

© Copyright 2005 by the National Electrical Manufacturers Association.


ICS 10-2005, Part 1 AC Transfer Switch Equipment
Page 10

8.2.2.3 Undervoltage Test


Verify the ability of phase-voltage-sensing relay coils to withstand 95 percent of rated pull-in
voltage with the relay armatures open.

8.2.2.4 Overload Test


Verify the ability of the switch to interrupt specified loads at rated voltage.

8.2.2.5 Temperature test


Verify the ability of the switch to carry rated current. (As an alternative, this test may be run
after the endurance test.)

8.2.2.6 Endurance Test


Verify the ability of the switch to operate for a prescribed number of operations under specified
conditions. The endurance test requirements for switches used in standby systems are less
severe than those for switches used in emergency systems.

8.2.2.7 Dielectric Test


Verify the ability of the switch to withstand the prescribed dielectric test.

8.2.2.8 Withstand Test


Verify the ability of the switch, with the contact initially closed, to withstand the prescribed level
and duration of available short-circuit current.

8.2.2.9 Circuit-Closing Test


Verify the ability of the switch to close onto and withstand the prescribed level and duration of
available short-circuit current.

a. Type A transfer switches for which the manufacturer has not assigned a conditional
short-circuit rating shall withstand the level and duration of available short-circuit current
for which they are rated.
b. Type A transfer switches for which the manufacturer has assigned a conditional
short-circuit rating shall withstand the available short-circuit current for which they are
rated until the protective device clears the short circuit.
c. Type B transfer switches shall be capable of automatically interrupting the available
short-circuit current for which they are rated.
8.2.2.10 Repeated Dielectric Test
Verify the ability of the switch to withstand a reduced dielectric test after the withstand and
circuit closing tests.

8.2.3 Test Samples


One sample shall be used to complete the overload, temperature, endurance, and dielectric
tests.

A previously untested sample shall be permitted to be used for the withstand, circuit closing and
repeated dielectric tests.

© Copyright 2005 by the National Electrical Manufacturers Association.


ICS 10-2005, Part 1 AC Transfer Switch Equipment
Page 11

Where transfer switch equipment is rated for multiple specific loads, as listed in 4.1.3, additional
samples shall be permitted to be used.

9 APPLICATIONS

9.1 Motor Transfer


Motors rated approximately 50 horsepower and greater are susceptible to damage when, in an
ON-OFF-ON operation, they are switched before the residual motor voltage has decayed to a
safe level. The high abnormal currents that may result from the out-of-phase relationship
between the motor's residual voltage and the voltage of the reconnected power source may also
trip overcurrent protective devices and, therefore, should be avoided. Consideration should be
given to include controls in AC transfer switch equipment to minimize these abnormal currents.

For a fuller treatment of motor transfer, see the section on bus transfer or reclosing in MG 1.

9.2 AC Transfer Switch Equipment Specification


The following characteristics of normal and alternate power sources should be specified in order
to properly match the transfer switch equipment to the system:

a. Voltage
b. Number of phases
c. Number of wires
d. Frequency
e. Number of switched poles
f. Type of load as defined in 4.1.3
g. Continuous current or horsepower, or both, requirements of the load
h. Available fault current
i. Whether the switch is intended for emergency or standby service
j. Whether it is necessary to disconnect the load from both power sources simultaneously
k. Whether the switch is to be suitable for use as service equipment
l. Whether the switch is to include integral overcurrent protection
m. Whether it is necessary to provide a bypass isolation switch in conjunction with the
transfer switch. Where a bypass isolation switch is provided, it should be compatible
with the transfer switch.
9.3 Features for Particular Applications
Some conditions or requirements of particular applications may make additional features
necessary. These may include the following:

a. Time delay to override monitored source deviation—A fixed or adjustable time delay
which delays all signals for operation. This time delay prevents starting of the engine or
the transfer of the load from the normal power source to the alternate power source
during momentary voltage dips or disturbances of the normal power source.
b. Time delay before transfer to alternate power source—A fixed or adjustable time delay
which delays the transfer of the load to an available alternate power source. This delay

© Copyright 2005 by the National Electrical Manufacturers Association.


ICS 10-2005, Part 1 AC Transfer Switch Equipment
Page 12

allows an engine-generator time to stabilize at rated voltage and frequency before


accepting the load.*
c. Time delay before transfer to normal power source—An adjustable time delay which
inhibits transfer of the load back to the normal power source. This delay allows the
normal power source time to stabilize before accepting the load. The time delay may be
automatically nullified if the alternate power source fails and power is available at the
normal power source.
d. Time delay before engine shutdown—A fixed or adjustable time delay which delays the
shutdown of the engine-generator (alternate power source) after the load is transferred
back to the normal power source. This delay allows the engine to run at no load and
thereby minimizes the possibility of shutdown due to an increase in the temperature of
the cooling water. It also permits the immediate transfer of the load back to the
engine-generator in the event that the normal power source has not fully stabilized.*
e. Time delay to limit cranking—A fixed or adjustable time delay to limit the cranking time of
the engine-generator if the engine fails to start when the normal power source fails.*
f. Engine exerciser—A programmable time switch to initiate the starting of the
engine-generator for a preset period of time at preset intervals without transferring the
load from the normal to the alternate power source.*
Caution: No load operation may be detrimental to the engine, and the engine generator
manufacturer should be consulted. Paragraph g would be considered.

g. Alternate system exerciser—A programmable time switch to initiate the starting of the
engine-generator and to transfer the load from the normal to the alternate power source
for a preset period of time at preset intervals. The load is transferred back to the normal
power source at the end of the exercise period.*
Provision should be made for the initiation of immediate retransfer to the normal source
in the event of an engine generator failure during the exercise period.
h. Auxiliary contact—A contact, other than the power circuit contacts, that is part of transfer
switch and is available for connection by the user. The number of auxiliary contacts,
mode of operation and function of each contact should be specified.
i. Engine start contact—A contact that initiates cranking of the engine generator set when
the normal power source fails.*
j. Alternate source monitor—A device(s) that monitors voltage or frequency, or both, of the
alternate power source, and inhibits transfer to the alternate source until the monitored
parameters reach specified levels.
k. Test switch—A switch to simulate failure of the normal power source, causing transfer of
the load to the alternate power source.
l. Close-differential protection—A device(s) that monitors all lines of the normal power
source and initiates transfer of the load from the normal power source to the alternate
power source when any line of the normal power source drops below a predetermined
value of voltage. It initiates transfer of the load back to the normal power source when all
lines of the normal power source return to within specified limits. This feature is
generally used for installations where only a limited reduction in voltage can be tolerated.
m. Time-delay-bypass switch—A momentary contact switch that initiates immediate transfer
of the load back to the normal power source, bypassing any optional time delays.
n. Manual return-to-normal switch—A momentary contact switch that initiates transfer from
the alternate to the normal power source where automatic transfer is not desired.

© Copyright 2005 by the National Electrical Manufacturers Association.


ICS 10-2005, Part 1 AC Transfer Switch Equipment
Page 13

o. Overcurrent protection—The addition of elements to permit the transfer switch equipment


to provide running overcurrent protection for a single motor.
p. Service equipment—See 7.4.
q. In-phase monitor—A device that monitors the relative voltage and phase angle between
the power source to be transferred to and the power from which the transfer is to be
made, and initiates transfer when acceptable values of voltage and phase angle are
present. Such a device may function on the transfer from either power source.
r. Delayed transition—Provides a timed disconnection of the load from the power sources
during transfer, primarily to allow decay of motor residual voltage.
s. Load disconnect device—A device that initiates opening of a pilot contact prior to
transfer from either source and then provides a timed closure after transfer. It is used
primarily to allow decay of motor voltage without affecting the speed of transfer.
t. Closed transition switch—Transfer switch equipment providing momentary paralleling of
both power sources during transfer in either direction. The closed transition is possible
only when the sources are properly interfaced and synchronized.
u. Bypass isolation switch—A switch that may provide any of the following features or
functions:
1. Load-break contacts
2. Overlapping contacts
3. Combination of 1 and 2
4. Single-source bypass
5. Dual source bypass
6. Total isolation of the transfer switch for purpose of maintenance, testing,
modification, or repair. A bypass isolation switch can function as an independent
nonautomatic transfer switch.
*Applicable to installations where the alternate power source is an engine-generator set.

© Copyright 2005 by the National Electrical Manufacturers Association.


ICS 10-2005, Part 1 AC Transfer Switch Equipment
Page 14

Annex A
Short Time Rating

Section 4.1.6 of ICS 10 outlines withstand and closing ratings for transfer switch equipment. As
noted, the requirement parallels those of UL Standard 1008. With the introduction of circuit
breakers with electronic trips, the requirements for withstand and closing capability of transfer
switch equipment (TSE) is more complex. UL 1008 addresses this issue by providing the option
for “short time ratings.”

Traditional thought said that the transfer switch is a piece of wire, and that it was protected by
the common thermal/magnetic circuit breaker. When protected by a circuit breaker with the
familiar I 2 T (thermal) trip, and instantaneous trip, the transfer switch merely had to be able to
“withstand” a short-circuit fault long enough to allow the upstream device to clear the fault.
However, with a short time trip element, it is possible that the upstream breaker may not trip
during a fault. This means the transfer switch contacts must survive this event as defined by UL
1008.

The worst case condition is determined by the Instantaneous pickup and Short Time Delay
setting on the Upstream Protective Device. The Transfer Switch must “survive” a current that is
just below the instantaneous pickup until the short time delay expires. If the TSE contacts fail to
survive, and the upstream device does not trip, then loss of power to the load results.

In electrical systems it is highly desirable to make sure that a fault is cleared by the upstream
protective device that is closest to the fault. To achieve this, the application for a “short time” trip
rating on upstream circuit breakers has become a necessity. The short time trip characteristic
gives the user the ability to program the trip curve of a particular circuit breaker so that it will
intentionally wait for a downstream device to clear the fault. This means that a transfer switch
applied between this upstream breaker and a downstream device must then truly withstand the
fault current seen while the protective devices react. Failure to do so will make the transfer
switch the weak link in the system.

The short-time characteristic is usually a “flat response” type. This means that a timer in the
circuit breaker is started when the fault current exceeds the short time pickup setting. If the
current remains above the pickup point and the timer times out, then the circuit breaker will trip.
The designer should be aware that there may be I 2 T short time characteristics available in
certain trip units, and these offer some increased coordination possibilities.

In either case it is important to note that should the fault current continue to increase, and reach
the instantaneous pickup point for the trip, that the breaker would then trip instantaneously.
Therefore, the worst case scenario for the transfer switch is the case where the fault current
rises to just below the instantaneous pickup, and the short time has to time out. This is the
particular point the user must be aware of, and allow for in the application of the transfer switch.
In other words, it is important to make sure that the transfer switch will truly withstand a current
equal to the instantaneous current pickup for the maximum time of the short time delay. It is also
important to realize that the instantaneous pickup point, and the maximum interrupt rating of the
breaker are not synonymous.

Let us use a generic example that may explain the application. We will deal with a 3000A circuit
breaker having an adjustable short-time pick up settable between 2 and 6 times the nominal
rating, and an instantaneous pickup settable between 2 and 10 times the nominal rating. The
maximum short time delay setting is 0.5 seconds, or 30 cycles on a 60 Hz system. Given this
example, proper application of a transfer switch would require a short time rating (for the
transfer switch) of 30 kA for 0.5 seconds. This relates to setting both the instantaneous pickup

© Copyright 2005 by the National Electrical Manufacturers Association.


ICS 10-2005, Part 1 AC Transfer Switch Equipment
Page 15

and the short time delay of the upstream breaker at their maximums. Since various circuit
breakers offer different options relating to pickups and time ranges, responsibility to properly
apply the transfer switch must fall on the designer.

The designer should understand that the short time rating of a transfer switch is much different
than the short-circuit rating . The short-circuit rating is based on tripping of the upstream device
and the need to transfer to the alternate source. The short time rating deals with a non-tripping
condition of the upstream device for a period of time, and the fact that the primary source of
power will not be interrupted. The transfer switch will not see a need to transfer, and must
therefore remain in a state to handle load current from the uninterrupted source during, and after
the fault is cleared by the downstream device.

When applying a transfer switch with a short time rating, the designer should always apply the
transfer switch having short-time current ratings equal to or greater than the selected
instantaneous pickup setting and short time delay setting of the properly coordinated upstream
breaker.

© Copyright 2005 by the National Electrical Manufacturers Association.


ICS 10-2005, Part 1 AC Transfer Switch Equipment
Page 16

Annex B
Neutral Conductors in Power Transfer Systems

Many transfer switching systems involve three phase AC power sources with a neutral conductor
(normally referred to as “4-wire distribution”) or single-phase sources with neutral. Single-phase
sources can be either 2-wire (line-neutral) or 3-wire (line-neutral-line) circuits. The application
of transfer systems for switching neutral connected loads between such power sources requires
consideration of several issues to achieve satisfactory operation, including compliance with the
National Electrical Code and preserving the functionality of ground fault monitoring equipment.

The National Electrical Code defines when power sources are required to be grounded and also
addresses the required grounding practices. In broad terms there are two types of sources,
those that are “separately derived” and those that are “non-separately derived.” Separately
derived sources are those with no direct connection (including a neutral conductor) to another
source. A non-separately derived source is directly connected to another power source,
typically through solidly connected neutral conductors. The determination as to whether a
source is to be separately derived or non-separately derived is typically made by the system
designer and/or authority having jurisdiction.

Separately Derived Sources

If it is determined that a power system consists of separately derived sources, each neutral must
be bonded to ground at its respective source. When transfer equipment is used in this type
system the neutral conductor must be switched along with the phase (line) conductors to prevent
multiple connections between neutral and ground within the system. Multiple connections
between neutral and ground can result in current flow through the grounding system, violating
the requirement that the ground system is never allowed to carry current, except in the case of a
fault. Multiple connections may also defeat or cause false operation of ground fault detection by
allowing ground fault currents to bypass monitoring equipment, or by allowing normal neutral
currents to appear as fault currents.

When switching the neutral conductor, timing of the opening and closing of the phase (line) and
neutral poles is important. If the phase conductors are connected without connection of the
neutral conductors a transient over-voltage can occur at the load.

The current rating of the neutral pole in transfer equipment is another consideration.
Unbalanced loads can result in high neutral currents. Also, nonlinear electronic loads
connected to transfer equipment can create current harmonics that add in the neutral conductors
that might make it necessary to over size the neutral current capacity to prevent overheating of
conductors or the switch poles. Depending on the nature of loads, the neutral rating may need
to be up to 200% of the phase rating.

Non-Separately Derived Sources

For systems consisting of non-separately derived sources it is not appropriate to switch the
neutral conductors. If a power system consists of non-separately derived sources, the neutral
conductors from the sources must be solidly connected together. This “shared neutral” must be
bonded to ground at only one source. There must not be any switching device between the
neutral conductors of the sources. This technique allows the neutral conductor of each source to
carry its respective neutral current, and the ground conductors to carry only ground fault current.
By not switching the neutral conductors the possibility of transient overvoltage from neutral
switching delays or failures is eliminated.

© Copyright 2005 by the National Electrical Manufacturers Association.


ICS 10-2005, Part 1 AC Transfer Switch Equipment
Page 17

© Copyright 2005 by the National Electrical Manufacturers Association.

You might also like