DATA SHEET
EXPLOSION PROOF THERMAL DETECTORS
THERMOTECH®
DESCRIPTION
The Thermotech thermal detectors are normally open devices designed especially
for fire detection and alarm systems. The detectors are a rate anticipation type that
operate immediately whenever the ambient area temperature reaches the preset
temperature setting of the detector, regardless of how fast or slow the temperature
rises. When the temperature drops back down below the set-point, the detector will
reset itself.
Under rapid heat increase situations, the rate anticipation feature allows the detector
to respond one to three degrees ahead of the set-point. However, the detector does
not respond to momentary fluctuations of temperatures below that of the alarm
setting, thus eliminating false alarms.
APPLICATION
The Thermotech explosion-proof thermal detectors are used to detect the
presence of heat beyond the detector’s temperature set-point for the purpose of
activating a fire alarm and/or automatic suppression system. The detectors are
explosion rated for Class I and Class II hazardous environments. The maximum
area coverage for each detector is rated at 40 ft. x 40 ft. in accordance with the        APPROVALS:
manufacturer’s specified limitations.
                                                                                          •   UL Listed
                                                                                          •   FM Approved
                                                                                          •   CSFM
SPECIFICATIONS                                                                            •   City of New York
Part Numbers:              60-008 135°F Ex-Proof Thermal
                           60-009 194°F Ex-Proof Thermal
Electric Rating:           6-125 VAC 5 amps
                           6-25 VDC 1 amp
                           125 VDC 0.5 amp
Area Coverage:             40 ft. x 40 ft. max.
www.Fike.com                                                                                    Form No. E.1.15.01-2, December, 2016
                                                                                                                             1 of 2
 This document is only intended to be a guideline and is not applicable to
 all situations. Information subject to full disclaimer at
 http://www.fike.com/disclaimer
 DETECT-A-FIRE®
 DESCRIPTION
 The Detect-A-Fire thermal detectors are normally open devices designed especially
 for fire detection and alarm systems. The detectors come in a range of temperature
 settings from 190°F to 450°F. Each is color coded to visually indicate its temperature
 setting. (Refer to the table below)
 The detectors are rate compensation type that operate immediately whenever the
 ambient area temperature reaches the preset temperature setting of the detector,
 regardless of how fast or slow the temperature rises. When the temperature drops
 back down below the set-point, the detector will reset itself. However, the detector
 does not respond to momentary fluctuations of temperatures below that of the
 alarm setting, thus eliminating false alarms.
 APPLICATION
 The Detect-A-Fire explosion-proof thermal detectors are used to detect the presence
 of heat beyond the detector’s set-point for the purpose of activating a fire alarm
 and/or automatic suppression system. The detectors are explosion rated for Class I,
 Groups B, C and D and Class II, Groups E, F and G hazardous environments. The
 maximum spacing for each detector is shown in the table below.
                                                                                                APPROVALS:
 SPECIFICATION                                                                                   • UL Listed
                                                                                                 • FM Approved
 Part Numbers:           60-021 190°F Ex-Proof Thermal                                           • ULC Listed
                         60-018 225°F Ex-Proof Thermal
                         60-038 275°F Ex-Proof Thermal
                         60-022 325°F Ex-Proof Thermal
                         C60-007 450°F Ex-Proof Thermal
 Electric Rating:        125 VAC 5 amps
                         125 VDC 0.5 amp
          °F Setting and        Color           Spacing (feet)
            Tolerance          Coating     UL         FM         ULC
           190 + 7/-8           White      50         50         25
           225 + 7/-8           White      25         50         25
               275 ±10           Blue      25         50         25
               325 ±10           Red       50         50         25
               450 ±15          Green      25         50         25
www.Fike.com                                                                              Form No. E.1.15.01-2, December, 2016
                                                                                                                        2 of 2