35TMAN
35TMAN
COMPAC-US-01
3AUA489002B4894 R0101 Rev. B
Effective: 9/1/00
Supersedes: Rev. A
3
Product Overview
ACS 100
● 1/6 - 3 HP, 200 - 240 V both Single and Three Phase
● Protected Chassis Standard with Optional NEMA 1 Enclosure Kit Available
● Operator Panel Standard
● Flange, Wall or DIN Rail Mounting
● Heatsinkless Models
ACS 140
● 1/6 - 3 HP, 200 - 240 V both Single and Three Phase
● 1/2 - 3 HP, 380 - 480 V
● Protected Chassis Standard with Optional NEMA 1 Enclosure Kit Available
● Operator Panel Standard
● Flange, Wall or DIN Rail Mounting
● Heatsinkless Models
● RS232 Modbus Serial Communications
● PID Setpoint Control Standard
ACS 400
● 3 - 40 HP, 200 - 240 V
● 3 - 50 HP, 380 - 480 V
● NEMA 1 Enclosure Standard with Optional NEMA 4 and NEMA 12
Enclosures Available
● RS485 Modbus Serial Communication Standard
● PID Setpoint Control standard
The ACS 100, ACS 140 and ACS 400 are microprocessor-based pulse width modulated (PWM) adjustable
frequency AC drives. These drives take advantage of sophisticated microprocessor control and advanced
IGBT power switching technology to deliver excellent performance control of AC motors for a wide
range of applications.
4
Standard Features
5
Specifications
Input Connection
Voltage (VIN): 230 V Units (ACS 100/140 1/6 - 3 HP) - 1 Phase 200 - 240 V ±10%
230 V Units (ACS 100/140 1/6 - 3 HP) - 3 Phase 200 - 240 V ±10%
230 V Units (ACS 400 3 - 40 HP) - 3 Phase 200 - 240 V ±10%
480 V Units (ACS 140 1/2 - 3 HP, ACS 400 3 - 40 HP) - 3 Phase 380 - 480 V ±10 %
Frequency: 48 to 63 Hz
Power Factor (for Fundamental): 0.98
Motor connection
Voltage: 3-phase, from 0 to VIN(VMAX at Field Weakening Point)
Output Frequency: 0 to 250 Hz (ACS 100/140 - 300 Hz)
Frequency Resolution: 0.1 Hz Digital, 10 bit Analog Input 1 & 2
Switching Frequency fS: 4.0, 8.0 or 16.0 kHz
Continuous Output Current:
Constant Torque: Rated IN (IN: Rated Current), fs = 4kHz
Overload Capacity:
Constant Torque: 1.5 X IN, for 1 minute every 10 minutes
Field Weakening Point: (ACS 400) 30 to 250 Hz, (ACS 100/140) 300 Hz
Acceleration Time: 0.1 to 1800 seconds
Deceleration Time: 0.1 to 1800 seconds
Enclosure: (ACS400) NEMA Type 1, NEMA Type 12 and NEMA Type 4,
(ACS100/140) Protected Chassis
Environmental Limits:
Ambient Operating Temperature (fS = 4 kHz):
Variable Torque (NEMA Type 1 & NEMA Type 12):
32 to 104 °F (0 to 40 °C)
Storage Temperature: 4 to 158 °F (-20 to 70 °C)
Cooling Method: (ACS 400) Integral Fan(s), (ACS 100/140) Natural Convection up to 1.5 HP
Relative Humidity: max 95%, no condensation allowed
Altitude Maximum: 3300 ft. (1000 m) above sea level (100% load) 1 % derating every 330 ft. above 3300 ft.
Agency Approval: UL, cUL, CE
External Control Connections
Two Programmable Analog Inputs (ACS 140/400):
Voltage Reference: 0 (2) to 10 V, 200 kΩ, Single Ended
Current Reference: 0 (4) to 20 mA, 500 Ω, Single Ended
Potentiometer: 10 VDC, 10 mA (1k to 10 kΩ)
Auxiliary Voltage: (ACS 400) 24 VDC, max 250 mA, (ACS 100/140) 12 VDC, max 100 mA
Five Programmable Digital Inputs: (ACS 400) 24 VDC, (ACS 100/140) 12 VDC
Response Delay: < 8 ms
One Programmable Analog Output: (ACS 140/400) 0 (4) to 20 mA, 500 Ω max.
Two Programmable Relay (Form C) Outputs:
(ACS 100) One Fault Relay Output
Max. Switching Voltage: 30 VDC / 250 VAC
Max. Switching Current: 8 A / 24 VDC, 8 A / 250 VAC
Max. Switching Power: 2000 VA / 250 VAC
Max. Continuous Current: 2 A
Response Delay: < 10 ms
Protections:
Overcurrent Trip Limit: 3.5 x IN instantaneous (ACS 100 1.5 x IN, ACS 140 2.25 x IN)
Adjustable Current Regulation Limit:
1.1 x IN (RMS) max
Overvoltage Trip Limit: 1.35 x VR
Undervoltage Trip Limit: 0.65 x VN
Overtemperature (Heatsink): 203 °F (95 °C) (ACS 100/140: 194 °F (90 °C))
Auxiliary Voltage: Short Circuit Protected
Ground Fault: Protected
Short Circuit: Protected
Microprocessor Fault: Protected
Motor Stall Protection: Protected
Motor Overtemperature Protection (I2t):
Protected
Input Power Loss of Phase: Protected
Loss of Reference: Protected
Short Circuit Current Rating: 65,000 RMS Symmetrical Amperes (ACS 400 ONLY)
Input Line Impedance: 3% with Standard Internal Reactors (ACS 400 ONLY)
6
Parameters, Macros and Protection
Functions
Start; normal/flying/torque boost
Start; premagnetizing
IR compensation
Stop; ramp/coasting
Stop; DC brake
DC hold
U/f -ratio; linear/square
Acceleration/deceleration 1 (s) 0.1 … 1800 0.1 … 1800 0.1 … 1800
Acceleration/deceleration 2 (s) 0.1 … 1800 0.1 … 1800
S-ramp; fast/medium/slow
Preset speeds 1 7 7
Critical frequencies 2 2
Slip compensation
Application Macros
Factory
ABB Standard
3-wire
Alternate
Motor potentiometer
Hand/Auto Control
PID Control (process)
Premagnetize
Pump and Fan Control (PFC)
Protection, fault functions
Overload protection
Stall protection
Output overcurrent
Output short circuit
Ground fault, motor cable
Under load
Network failure
Low input signal level (AI<min)
Panel fault
Over voltage
Under voltage
External fault
Automatic fault reset, under voltage
Automatic fault reset, over voltage, over current, AI<min
Fault history 1 3 3
Supervision functions (programmable) 1)
Speed
Current
Torque
Output power
Reference setpoint
1)
Many other signals can also be monitored, please refer to the appropriate user's manual.
7
Technical Data
1-phase Supply Voltage 200 - 240 V ± 10 %
Standard series
Nominal ratings Over- Power losses
Order Nominal Frame Input Output Max. Over- temp. Line Power Control
code motor size/ current current output current (heat fuse2) circuit circuit
ACS 101- P N 3) weight current (peak) sink)
ACS 141- HP lbs. A A A4) A oC A W W
K18-1 0.16 A/1.98 2.7 1.0 1.5 3.2 90 6 7 8
K25-1 0.25 A/1.98 4.4 1.4 2.1 4.5 90 6 10 10
K37-1 0.33 A/1.98 5.4 1.7 2.6 5.5 90 10 12 12
K75-1 0.5 A/1.98 3.2 2.2 3.3 7.1 90 10 13 14
1K1-1 0.75 A/1.98 9.0 3.0 4.5 9.7 90 10 19 16
1K6-1 1.0 B/2.64 10.8 4.3 6.5 13.8 90 16 27 17
2K1-1 1.5 C/3.52 14.8 5.9 8.9 19.0 95 16 39 18
2K7-1 2.0 C/3.52 18.2 7.0 10.5 23.5 95 20 48 19
4K1-1 3.0 D/4.18 22.0 9.0 13.5 34.5 95 25 70 20
Heatsinkless series
The Drives in the heatsinkless series are minimized
in volume in order to save space. They are built with
a base plate and need to be installed on an external
sink to dissipate the heat generated, please refer to the
power circuit losses table below.
These drives are typically used in machines, where
space is limited or increased flexibility in installations
is required.
8
Technical Data
3-phase Supply Voltage 200 - 240 V ± 10 %
1)
Heatsinkless versions also available, see page 7.
Order code type: ACS 141-xHx-1.
2)
Fuse type: UL class CC or T (symbol KTK-R, JJN or JJS). For non-UL installations IEC269 gG.
Use 140 °F (60 °C) rated power cable (164 °F (75 °C) if Tamb above 113 °F (45 °C)).
3)
The power ratings in HP apply to most 2- and 4-pole motors. The current ratings are the same
regardless of the supply voltages. The rated current of the Drive must be higher than or equal to
the rated motor current to achieve the rated motor power given in the table.
4)
Overload current allowed for one minute every 10 minutes.
Protection limits/Overvoltage
Trip limits
- Running V DC: 842 (corr. to 595 V input)
- Start inhibit V DC: 661 (corr. to 380 - 415 V input)
765 (corr. to 440 - 480 V input)
Protection limits/Undervoltage:
- Running V DC: 333 (corr. to 247 V input)
- Start inhibit V DC: 436 (corr. to 380 - 415 V input)
505 (corr. to 440 - 480 V input)
9
Technical Data
3-phase Supply Voltage 380 - 480 V ± 10 %
1)
Heatsinkless versions also available, see page 7.
Order code type: ACS 143-xHx-3.
2)
Fuse type: UL class CC or T (symbol KTK-R, JJN or JJS). For non-UL installations IEC269 gG.
Use 140 °F (60 °C) rated power cable (164 °F (75 °C) if Tamb above 113 °F (45 °C)).
3)
The power ratings in HP apply to most 2- and 4-pole IEC 34 motors. The current ratings are the
same regardless of the supply voltages. The rated current of the Drive must be higher than or
equal to the rated motor current to achieve the rated motor power given in the table.
4)
Overload current allowed for one minute every 10 minutes.
Protection limits/Overvoltage
Trip limits
- Running V DC: 842 (corr. to 595 V input)
- Start inhibit V DC: 661 (corr. to 380 - 415 V input)
765 (corr. to 440 - 480 V input)
Protection limits/Undervoltage:
- Running V DC: 333 (corr. to 247 V input)
- Start inhibit V DC: 436 (corr. to 380 - 415 V input)
505 (corr. to 440 - 480 V input)
10
Technical Data
Connection Diagrams ACS 100 & ACS 140
ACS 100 ACS 140
DI configuration DI configuration
ABB standard default (0)
DI configuration DI configuration
3-wire default (1)
The supply voltage may be switched on only after the cover has been refitted and snapped into place.
Please refer to the appropriate User’s Manual for detailed connection instructions.
11
Technical Data
Connection Diagrams ACS 400
ACS 400 ACS 400
DI configuration DI configuration
NPN connected (sink) PNP connected (source)
Signal termination is
selected by jumper J2
not terminated.
The supply voltage may be switched on only after the cover has been refitted and snapped into place.
Please refer to the ACS 400 User’s Manual for detailed connection instructions.
12
Options
Control Panels
control run
modes indicator
control modes
fault units shaft
indicator display direction
shaft
modes
display direction
up/down
modes menu
start/stop menu enter
green LED
red LED
direction start/stop
enter reset
13
Options
DriveWindow Light
Comp-AC set-up and control tool - Win95, Win98, WinNT compatible
Gasket
Cable Hole
14
Options
Fieldbus Control
Fieldbus Control Highlights
Greater Manufacturing Flexibility
Drive Control
The drive Control Word (16 bit) provides a wide vari-
ety of functions from Start, Stop and Reset to Ramp
Generator control. Typical setpoint values like Speed
and Torque can be transmitted to the drive with 15
bit accuracy.
Drive Monitoring
Frequency and current can be monitored and used to
provide control data for the manufacturing process.
Drive Diagnostics
Accurate and reliable diagnostic information can be
obtained via the drive Alarm and Fault Words, help-
ing to cut drive down-time and production losses.
ABB AC Drives can connect to all major automa- Drive Parameter Handling
tion systems. This is achieved with a dedicated gate- Total integration of the drives into the production
way concept between the fieldbus systems and ABB process is achieved by drive parameter reading and
Distributed Drive Communication System1) (DDCS). writing.
DDCS is a high speed optical link combining fast data
transfer and excellent noise immunity. Reduced Installation and Engineering Effort
3 (A)
RS485 bus 2 (C) RS232/RS485
termination 1 (B) mode select jumper
jumpers S2 S5
and S3
3 (A)
communication
2 (C)
speed setting
1 (B)
DIP-switch S1
RS232 terminal X4
15
Options
ACS 400 Gateways
1)
Software version 1.3 or later is compatible with ACS 400. N.A. = Not Applicable
2)
Fieldbus module version 1.2 or later is compatible with ACS 400.
Gateway Module Technical Data DDCS adapter for ACS 400 allows
Power supply connection of fieldbus modules.
Supply voltage: 24 VDC ±10 %
Current consumption: 60..160 mA
Connections
Bus-line: Screw terminals
Drive link: Fiber optics
Environmental limits
Ambient temperature: 0..50 °C DDCS
16
Options
EMC Filters
Series ACS 100/140-IFxx-x
ABB ACS 100, ACS 140 and ACS 400 drives meet the without intermediate transformers, to a low voltage
requirements of the Second Environment as standard. power supply network which supplies buildings used
An appropriate EMC filter is required only when oper- for domestic purposes. A Second Environment instal-
ating in the First Environment. lation includes all others than those connected directly
Product Standard EN6180003 defines the First Envi- to a low voltage power supply network which supports
ronment as an installation that includes domestic prem- buildings used for domestic purposes.
ises. It also includes establisments connected directly,
17
Options
EMC Filters
Series ACS 400-IFx1-3
Selection table and dimensions for IP 20 EMC filters
3-phase supply voltage 380 - 480 V, 3.0 - 37 kW
Always use RFI Ferrite ACS-CHK-A or ACS-CHK-C with series ACS400-IFx1-3 EMC fi lters. The
motor cable, including the shield, must be fed through the hole in the ferrite. Ferrites ACS-CHK-A
or ACS-CHK-C are supplied in the same package as the input filter.
18
Options
Dynamic Braking Units
Compact-sized
braking units with
braking chopper
and resistor.
Dimensions
Braking unit Width Height Depth H1 W1 Weight
order code in/mm in/mm in/mm in/mm in/mm lbs./kg
ACS-BRK-A 3.54/90 9.45/240 7.09/180 7.72/196 2.64/67 2.65/1.2
ACS-BRK-B 3.54/90 11.81/300 11.22/285 9.06/230 2.64/67 3.31/1.5
ACS-BRK-C 5.91/150 19.69/500 13.66/347 19.13/486 3.35/136 16.53/7.5
ACS-BRK-D 10.63/270 23.62/600 17.72/450 22.91/582 9.92/252 45.19/20.5
ACS-BRK-F 3.54/90 11.81/300 11.22/285 9.06/230 2.64/67 3.31/1.5
19
The ABB Product Family
Small AC Drives
The Comp-AC family includes the ACS 100, ACS 140, and ACS 400, covering sizes
from ¼ hp to 50 hp and voltages from 200 to 480 V.
Large AC Drives
The ACS 600 Single and Multi-Drive family includes drives from 3 hp to 4,000 hp and
voltages from 230 to 690 V.
Medium-Voltage Drives
ABB’s highly reliable ACS 1000 is available from 400 hp to 6,700 hp and voltages of
2.3, 3.3, and 4.16 kV.
Motors
Low-voltage AC motors from ABB range from ¼ hp to 800 hp and voltages from 208 to
480 V. Medium-voltage AC motors are also available.
ABB
ABB Automation Inc.
3AUA489002B4894 R0101 Rev B
USA
Telephone: (414) 785-3416
(800) 243-0696
Fax: (414) 785-0397
All specifications are subject to change without prior notice.