0% found this document useful (0 votes)
51 views6 pages

RCR Efficiency Calculation

The document contains temperature and efficiency data from heat exchanger tests. For a washing range test, the fresh water temperature increased from 24.8°C to 62.8°C, and the drain water increased from 31.1°C to 84.3°C, resulting in an efficiency of 63.9%. For an MCS-02 test, the fresh water increased from 24°C to 52°C and the drain water from 50°C to 75°C, with an efficiency of 54.9%. The data suggests the washing range heat exchanger performed better than the MCS-02 unit.

Uploaded by

Public Demand
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLSX, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
51 views6 pages

RCR Efficiency Calculation

The document contains temperature and efficiency data from heat exchanger tests. For a washing range test, the fresh water temperature increased from 24.8°C to 62.8°C, and the drain water increased from 31.1°C to 84.3°C, resulting in an efficiency of 63.9%. For an MCS-02 test, the fresh water increased from 24°C to 52°C and the drain water from 50°C to 75°C, with an efficiency of 54.9%. The data suggests the washing range heat exchanger performed better than the MCS-02 unit.

Uploaded by

Public Demand
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLSX, PDF, TXT or read online on Scribd
You are on page 1/ 6

84.3 62.

8
31.1 24.8

t1 24.8
t2 62.8
t3 84.3

t2-t1 38
t3-t1 59.5
64%

MCS -02

T1= Temperature in fresh makeup water before the heat exchanger 24


T2= Temperature in fresh makeup water after the heat exchanger 52
T3= Temperature in drain water temperature before the heat exchanger 75

T2-T1/T3-T1 28 51

effeciency 54.9

Washing Range

T1= Temperature in fresh makeup water before the heat exchanger 24.8
T2= Temperature in fresh makeup water after the heat exchanger 62.8
T3= Temperature in drain water temperature before the heat exchanger 84.3

T2-T1/T3-T1 38 59.5

effeciency 63.9
S# Set Point Wash Box Running Temperature Remarks
1 90 88.9
2 90 88.7
3 90 84.1
4 80 101
5 80 70 PT-100 out of order
6 80 85.6
7 80 84.3
8 70 98
9 70 86.5
10 60 59.7
11 60 72.3
12 60 72.5
13 60 65.5
14 60 65.8
15 25 45.1
16 25 25
Washing Range
E Actual Heat Transfer 0.63865546218
Max Possible heat Transfer

Value Unit
Qa m 15133 Kg/Hr
C 4.2 KJ/Kg.C
Fresh Water T2 62.8 C
T1 24.8 C
dT 38

Qa 2415226.8 KJ/Hr

Qd m 15133 Kg/Hr
C 4.2 KJ/Kg.C
Drain Water T2 84.3 C
T1 31.1 C
dT 53.2

Qd 3381317.52

dtmax 59.5

Qmax 3781736.7

Designed
Actual Qrec Max Qrec
Version Flow(m3 (KJ/h) (KJ/h)
/h)

RCR 30 18 2415227 3781737


174.0343

7.251429

7000

116.6667

10-Feb m3/day m3/hr kg/hr


WR 11.5hr 174.0343 15.13342 15133.42

Kj/hr
230685.9 2652888

2.514453

Current Designed
Decrese in
Effectivn Effectivn Effeciency
ess (%) ess (%)

63.9 70 6.1
MCS 02
E Actual Heat Transfer 0.5490196078
Max Possible heat Transfer

Value Unit
Qa m 8281 Kg/Hr
C 4.2 KJ/Kg.C
Fresh Water T2 52 C
T1 24 C
dT 28 C

Qa 973846 KJ/Hr

Qd m 8281 Kg/Hr
C 4.2 KJ/Kg.C
Drain Water T2 75 C
T1 50 C
dT 25

Qd 869505

dtmax 51 267807.54

Qmax 1773790 266068.53

4922268

Current
Version Designed Actual Qrec Max Qrec Effectivness
Flow(m3/h) (KJ/h) (KJ/h)
(%)

RCR 30 18 973846 1773790 54.9


174.0343

7.251429

7000

116.6667

10-Feb
WR 11.5hr
m3/day m3/hr
MCS2 18.5hr 153.2168 8.281989 8281.989

15.1

KJ/hr

4.66mmbtu
3662.76
1241653 MW/hr
Designed
Effectivness Decrese in
Effeciency
(%)
0.074
70 15.1
44.4