Mkvie Overview
Mkvie Overview
Presenter
    18 November 2003                                     Introducing Networked I/O
   2
              18 November 2003
              GE Proprietary Information – Privileged & Confidential
  Application Range
9H Combined Cycle
Proprietary Design
Industrial Steam
Governors
  3
           18 November 2003
           GE Proprietary Information – Privileged & Confidential
  Flexible Architecture
                Mark VI Enhanced
Processors                                           I/O Packs                 Redundancy
                                                                      1 Pack   • Dual (Process Runs if Controller Fails)
                       Switches &
                                                                               • Triple (Process Runs if Controller has
                        I/O Net
                                                                                 Partial or Complete Failure)
 Simplex                                              Simplex
                          Simplex
                                                                               Distributed / Remote I/O
                                                                               • Less Installation & Maintenance Cost
      Dual                   Dual                        Dual                  • More Flexible Application
                            Triple
                                                                               On-line Repair / I/O Packs
  Triple                                                Triple                 • Hot Swap in Redundant Systems
                                                                               • Improved MTTR / Availability
             Flexible Redundancy
  4
             18 November 2003
             GE Proprietary Information – Privileged & Confidential
1 Control vs. Integrated Controls
                                      Plant Data Highway
                                                           Ethernet                11Control
     Operator &                                                                       Controlwith
                                                                                              withDistributed
                                                                                                   DistributedI/O
                                                                                                                I/Ofor:
                                                                                                                    for:
    Maintenance                                                                    ••Turbine
                                                                                      Turbine&&Process
                                                                                                ProcessSensors
                                                                                                         Sensors
      Stations                                                                     ••10,
                                      Unit Data Highway                               10,20,
                                                                                          20,40ms
                                                                                              40msSystem
                                                                                                    SystemFrame
                                                                                                            FrameRates
                                                                                                                  Rates
                                                                                   ••Simplex,
                                                                                      Simplex,Dual,
                                                                                               Dual,Triple
                                                                                                     TripleRedundancy
                                                                                                            Redundancy
                                                           Ethernet
                                         Controller(s)
                                                                                                  Remaining Process
                                                                                                 • Power Island
                                                                                                 • Balance of Plant
5
         18 November 2003
         GE Proprietary Information – Privileged & Confidential
The Building Blocks
     The Controllers                                                        The I/O
The Software
The Networks
6
    18 November 2003
    GE Proprietary Information – Privileged & Confidential
Mark VIe Controller Rack
      Redundant Controllers
7
       18 November 2003
       GE Proprietary Information – Privileged & Confidential
 Mark VIe I/O Packs
                                            Features
                                          • Dual 100MB Ethernet Ports
                                          • Low I/O Density
                                          • On-line Repair per I/O Block
                                          • Operation -30C to 65C
                                          • Accuracy -30C to 65C
                                          • NFPA Class 1, Div 2 with Local Temp Sensor
                                          • Infrared Transceiver for Low Level Diagnostics
                                            - Monitor I/O Values, Set I/O Pack Host/
                                                     Function Names, Error Status
                                            - Requires Windows Based Diagnostic Tools
                                                     on Laptop or Handheld PC
                                            - Ethernet TSM Support
• I/O Packs Plug into Mk VI
 Termination Boards                             z     Processor         32 Bit RISC CPU 266MHz
• Barrier & Box Type TBs                        z     Cache             32k bytes
                                                z     Ram               32M bytes @133Mhz
                                                z     Flash             16M bytes
                                                z     Communication     Dual 10/100 Full Duplex Ethernet
                                                z     Power             28Vdc
                                                z     Ethernet Task Rate1.8ms
  8
         18 November 2003
         GE Proprietary Information – Privileged & Confidential
Terminal Boards
        Barrier Terminal Blocks                                                 Box Type Terminal Blocks
         & 1, 2, or 3 I/O Packs                                               1 I/O Pack, but Dual Networks
                                                        • Barrier Type
                                                          - Derived from Mark VI
                                                          - Full Set of Functionality
                                                          - Simplex, Dual, Triple Redundant
                                                        • Box Type
                                                          - Subset of Barrier Type Functionality
                                                          - Simplex or Dual Redundant
                                                        • New I/O Types vs. Mark VI (Ex: Solid-State Relays)
                                                          - New I/O Types Backwardly Compatible to Mark VI
9
    18 November 2003
    GE Proprietary Information – Privileged & Confidential
Centralized I/O
                                            Triple Redundant Cabinet – Nuclear BOP
IONet Switches
 10
        18 November 2003
        GE Proprietary Information – Privileged & Confidential
Remote I/O
      Thermocouple TB
                                              MS5001N at GEAE Plant in Lynn, Mass.
                                                                                      Signal Quality
                                                                                     • Processing at TB
                                                                                     • Processing in
                                                                                      Main Cabinet
11
      18 November 2003
      GE Proprietary Information – Privileged & Confidential
Remote I/O Panel with “S” Type Boards
Terminal Boards
12
     18 November 2003
     GE Proprietary Information – Privileged & Confidential
Environmental Validation
Stress              Upper                                   Highly Accelerated Life Test (HALT)
           Destruct Limit                                   Purpose: Increase Design Reliability
                                                          • Applied During Design Cycle to Identify Limiting
                    Upper                                   Design Factors
                                                                                              Thermal Imaging
           Operating Limit                                • Improve Design Margins
                                                          • Result: Increased Reliability      U1  Q1
                                                                                                           U2
                    Upper
             Specification                                  Increase Stress to:
                                                          • Discover Operating Limits         R1          R23
14
     18 November 2003
     GE Proprietary Information – Privileged & Confidential
Turbine I/O
                                                                           Unique Turbine Sensors
                                                                                Types
     Benefits
                                                                                • Servos
     • Fewer Single Point Failures                                              • LVDT
       - Big Deal in Redundant Systems
                                                                                • Vibration
     • Less Equipment to Maintain                                               • Flame
     • Better Diagnostics (Can Directly See the Sensor)                         • Shaft V/I
     • Fewer Spare Parts                                                        • Synch (Auto & Backup)
                                                                                • PLU / EVA
15
          18 November 2003
          GE Proprietary Information – Privileged & Confidential
General Purpose I/O
                                                                                              Redundancy
                                I/O Type - General Purpose                            Board   Packs/Board
      24 DI (125Vdc, group isolated) 1ms SOE                                       TBCIH1      1 or 2 or 3
      24 DI (24Vdc, group isolated) 1ms SOE                                        TBCIH2      1 or 2 or 3
      24 DI (48Vdc, group isolated) 1ms SOE                                        TBCIH3      1 or 2 or 3
      24 DI (115/230Vac, 125Vdc, point isolated) 1ms SOE on 125Vdc                 TICIH1      1 or 2 or 3
      24 DI (24Vdc, point isolated) 1ms SOE                                        TICIH2      1 or 2 or 3
      24 DI (24Vdc, group isolated) 1ms SOE                                        STCIH1           1
      12 "C" mech. relays w/6 solenoids, coil diagn. (115/230Vac, 24/125Vdc)       TRLYH1B       1 or 3
      12 "C" mech. relays w/6 solenoids, voltage diagn. (115/230Vac, 125Vdc)       TRLYH1C       1 or 3
      12 "C" mech. relays w/6 solenoids, voltage diagn. (24Vdc)                    TRLYH2C
       6 "A" mech. relays for solenoids, solenoid impedance diagn. (24/125Vdc)     TRLYH1D       1 or 3
      12 "A" solid-state relays/inputs (115/230Vac)                                TRLYH1E       1 or 3
      12 "A" solid-state relays/inputs (125Vdc)                                    TRLYH2E       1 or 3
      12 "A" solid-state relays/inputs (24Vdc)                                     TRLYH3E       1 or 3
      36 mech. relays, 12 voted form "A" outputs           Specifications          TRLYH1F         3
        12 fused branches                                     •
                                                             Operation: -30 to +65CWPDFH1A
      36 mech. relays, 12 voted form "B" outputs                                   TRLYH2F         3
        12 fused branches                                     •
                                                             Accuracy: -30 to +65C WPDFH3A
      10AI (V/I inputs) & 2AO (4-20/0-200ma outputs)          •
                                                             I/O Filtering in Firmware
                                                                                   TBAIH1C     1 or 2 or 3
      10AI (V/I inputs) & 2AO (4-20/0-200ma outputs)                               STAIH1A          1
                                                             (Not Application Software)
      16 AO (4-20ma outputs) 8 per I/O Pack                                        TBAOH1C       1 or 2
       8 AO (4-20ma outputs)                                                       STAOH1A          1
      12 Thermocouples                                                             TBTCH1B     1 or 2 or 3
      24 Thermocouples (12 per I/O Pack)                                           TBTCH1C       1 or 2
      12 Thermocouples                                                             STTCH1A          1
      16 RTDs 3 wires /RTD (8 per I/O Pack)                                        TRTDH1C       1 or 2
       8 RTDs 3 wires /RTD                                                         SRTDH1A          1
       6 Serial ports for I/O drivers RS232, RS422, RS485                          PSCAH1A          1
16
     18 November 2003
     GE Proprietary Information – Privileged & Confidential
      Dual Redundant Input Options                                         Dual Redundant Output Options
                                                IONet                                                                        TB
                      IONet                                                                 IONet                 IONet
   Sensor                           Switch                    Controller    Controller                 Switch
                                                   Exchange
                                                                                                                                  Process Output
                                                                                Data
                                    Switch                    Controller
                                                                            Controller                 Switch
                                                                                                                             TB
                      IONet                     IONet                                       IONet                 IONet
Sensor - A                          Switch                    Controller    Controller                 Switch
                                                                                Data
Sensor - B
                                    Switch                    Controller    Controller                 Switch
Two Sensors on Two TBs & Dual Controllers Dual Outputs to Three I/O Packs
                                                IONet
                      IONet
   Sensor                           Switch                    Controller
                                                   Exchange
Switch Controller
 17
             18 November 2003
             GE Proprietary Information – Privileged & Confidential
     Triple Redundant Input Options                                                 Triple Redundant Output Options
                         IONet                     IONet                                            IONet                IONet
Sensor - A                             Switch                          Controller   Controller                Switch
                                                                                                                                         Outputs Driven
                                                                                                                                         from Common TB
                                                      State Exchange
                                                                                    Controller                Switch
Sensor - B
                                       Switch                          Controller
                                                                                    Controller                Switch
Sensor - C
                                                                                                 Voting at Termination Board
                                       Switch                          Controller
                                                                                                    IONet                IONet
                                                                                                                                         1 of 3 Servo Coils
                          Fanned Inputs to Three Controllers                        Controller                Switch
                         IONet                     IONet
Sensor - A                             Switch                          Controller
                                                                                    Controller                Switch                     1 of 3 Servo Coils
                                                      State Exchange
Sensor - B
                                       Switch                          Controller
                                                                                    Controller                Switch
                                                                                                                                         1 of 3 Servo Coils
Switch Controller
18
             18 November 2003
             GE Proprietary Information – Privileged & Confidential
                                                              IONet
19
     18 November 2003
     GE Proprietary Information – Privileged & Confidential
IONet Switches
                                                                  Features
                                                                • Operating Temp: -40 to 85C
                                                                • Operating Humidity: 10 to 95% Non-Condensing
                                                                • Shock: 200g @ 10ms
                                                                • Vibration / Seismic: 50g, 5-200Hz, Tri-axial
                                                                • MTBF: > 2M hours
                                                                • Auto-sensing 10/100 Base TX, Duplex, and MDIX
                                                                • Up to 2.6Gb/s, High Speed Backplane
  Switch Types                                                  • Steel Enclosure, Prevents EFI and RFI
• N-TRON 500 Series                                             • DIN-Rail or Rack Mounted
• 508TX – 8 10/100 BaseTX RJ-45 Ports                           • Redundant Power Inputs 10-30Vdc,
• 516TX – 16 10/100 BaseTX RJ-45 Ports                            - 200ma (w/o fiber) 400ma (w fiber) at 24Vdc
• 509FX – 8 10/100 BaseTX RJ-45 Ports                           • Bi-color LED’s for Link, Speed, Activity, and Duplex Status
           1    100 BaseFX Fiber Port
• 517FX – 16 10/100 BaseTX RJ-45 Ports                            Emissions and Safety Approvals
           1    100 BaseFX Fiber Port                           • FCC Part 15 Class A
                                                                • UL Listed (US & Canada)
                                                                • Class 1, Div 2, Groups A, B, C, D, T4A
                                                                • CE: EN55011, EN61000-6-2 and –6-4
                                                                • EN61000-4-2,3,4,5,6,11, EN61010-1 Class III,
                                                                 Pollution Degree 2
20
       18 November 2003
       GE Proprietary Information – Privileged & Confidential
IONet Specifications
Controller                           Local I/O                       TB
                                                                    Pack                          Field
     U                              Switch                                                       Device
     C       IONet - Cat. 5                        IONet - Cat. 5              Field Wire
     C        100m / 328'                           100m / 328'               300m / 984'
     A
                                                                     100Base TX              100Base FX
                          IEEE Specification                         802.3u                  802.3u
                          Wire Speed                                 100Mbps                 100Mbps
                          Cable Type                                 UTP Cat. 5              Fiber (multi-mode)
                          Connector Type                             RJ-45                   SC
                          Max I/O Packs / Network                    199                     199
                          Topology                                   Star                    Star
21
         18 November 2003
         GE Proprietary Information – Privileged & Confidential
                                                   ToolboxSTTM
22
     18 November 2003
     GE Proprietary Information – Privileged & Confidential
I/O Configuration& Diagnostic Tools (ToolboxSTTM)
                                                               Toolbar
                                                               Select Category          z   View I/O Data
                                                                                        z   I/O Calibration
                                                                                        z   Diagnostic Messages
         Select
         Device
                                                                   Active Pictorial of Equipment
                                                                   z  Terminal Board
                                                                   z  I/O Packs w/Diagnostic LEDs
                                                                   z  I/O Network Status
                                                                                                  Overview of I/O Network
Hardware ID
23
      18 November 2003
      GE Proprietary Information – Privileged & Confidential
Field Programming Tools (ToolboxSTTM)
                                                                                              Features
                                                                                                Features
                                                                                              Field
                                                                                                FieldProgrammable
                                                                                      z
                                                                                          z            Programmable
                                                                                              Floating
                                                                                                FloatingPoint
                                                                                      z
                                                                                          z                Point
                                                                                              Dynamic
                                                                                                Dynamic DataDisplay
                                                                                      z                   Data
                                                                                          z                      Display
                                                                                      z       Drag    & Drop  Points
                                                                                          z     Drag & Drop Points
                                                                                              Math
                                                                                                MathBlocks
                                                                                      z
                                                                                          z            Blocks
                                                                                              Macros
                                                                                                Macros(User
                                                                                                          (UserBlocks)
                                                                                      z
                                                                                          z                      Blocks)
                                                                                              Function
                                                                                                Function & LadderBlocks
                                                                                      z                   & Ladder
                                                                                          z                           Blocks
                                                                                      z       Multiple   Block Libraries
                                                                                          z     Multiple Block Libraries
                                                                                              Editors
                                                                                                EditorsFor:
                                                                                      z
                                                                                          z              For:
                                                                                              - -Application
                                                                                                   ApplicationSoftware
                                                                                                               Software
                                                                                              - -I/O  Assignments
                                                                                                   I/O Assignments
                                                                                              - -Tuning
                                                                                                   TuningConstants
                                                                                                           Constants
                                                                                              Password
                                                                                                PasswordProtection
                                                                                      z
                                                                                          z                  Protection
                                                                                              Boolean
                                                                                                Boolean & AnalogForcing
                                                                                      z                  &  Analog
                                                                                          z                          Forcing
24
     18 November 2003
     GE Proprietary Information – Privileged & Confidential
Trending Tools (ToolboxSTTM)
                                                                      Features
                                                                        Features
                                                                      Automatic
                                                                        AutomaticUpload
                                                                                     UploadofofCapture
                                                                                                CaptureBlocks
                                                              z
                                                                  z                                      Blocks
                                                              z       Micro-second     Resolution
                                                                  z     Micro-second Resolution
                                                                      Drag
                                                                        Drag&&Drop
                                                                                 DropofofVariables
                                                                                          VariablestotoTrender
                                                              z
                                                                  z                                     Trender
                                                              z       Browser    for Variables  Selection
                                                                  z     Browser for Variables Selection
                                                                      100’s
                                                                        100’sofofSignals
                                                                                  Signalsper
                                                                                           perTrend
                                                              z
                                                                  z                             Trend
                                                                      - -Mask
                                                                          Mask & Unmask of SelectedVariables
                                                                               &  Unmask    of Selected   Variables
                                                              z       Video  Type    Forward-Reverse
                                                                  z     Video Type Forward-Reverse
                                                                      Left-Right
                                                                        Left-RightDrag
                                                                                    DragofofTime
                                                                                              TimeAxis
                                                              z
                                                                  z                                 Axis
                                                                      Dual
                                                                        Dual Cursor (Delta, Min, Max,Average)
                                                              z             Cursor    (Delta, Min,  Max,
                                                                  z                                       Average)
                                                              z       Stacked    Traces
                                                                  z     Stacked Traces
                                                                      Alarm
                                                                        AlarmMessages
                                                                               Messageson   onTrip
                                                                                                TripTrend
                                                              z
                                                                  z                                  Trend
                                                              z       Events   Log   Linked  to Trend
                                                                  z     Events Log Linked to Trend
                                                                      Export
                                                                        Exporttoto.CSV
                                                              z
                                                                  z                .CSV
25
     18 November 2003
     GE Proprietary Information – Privileged & Confidential
                                                              Power
26
     18 November 2003
     GE Proprietary Information – Privileged & Confidential
Power Sources, Converters, Supplies
                             Internal Power Converters
                             Create 28Vdc for:
                             • Compact PCI® Controller(s)
                             • IONet Switches
                             • I/O Packs                                    Power for Electronics
Field Power Sources                24Vdc                                        Controllers
• 1 Source                             125Vdc                                      Switches
• 2 Sources                                                     28Vdc
• 3 Sources                                 115/230Vac                               I/O Packs
27
      18 November 2003
      GE Proprietary Information – Privileged & Confidential
Power Sources and Supplies
          Incoming Power Sources                                                         Termination Boards
     z    24Vdc
                                                                                     z   Power requirements vary according
     z    125Vdc
                                                                                         to the application needs. Example:
     z    115/230Vac
                                                                                         125Vdc field solenoids
     z    Any Redundant Combination
                                                                                     z   Most power for transducers comes
       Controller Power Supplies                                                         “through” the I/O Packs, is current
                                                                        I/O
                                                                                         limited per point, and fed to the
     Controller                                                        Pack              transducers.
                        Second Power Supply
                                                                              I/O Packs
                        Power Supply 175W                                z    Single 16-32Vdc from Local Supply
                        Typically: 24Vdc or                              z    Exception: Servo I/O Pack is 26-32Vdc
                        115/230Vac                                       z    Local Supply(s): 24Vdc, 115/230Vac, 125Vdc
                                                                         z    Hot-swap with Solid-state Breaker & Soft-start
28
          18 November 2003
          GE Proprietary Information – Privileged & Confidential
                                          Mark VI vs. Mark VIe
29
     18 November 2003
     GE Proprietary Information – Privileged & Confidential
Mark VI VME Control Module
           Mark VI e
     I/O Processing Moved
     to Termination Boards                                     • Passive Termination Boards
                                                               • Latching “D” Type Connectors
                                                               • ID Chip on Each Board
30
      18 November 2003
      GE Proprietary Information – Privileged & Confidential
Mark VI vs. Mark VIe Architectures
                                              Plant Data Highway (PDH) - Ethernet
                                               Operator Stations
                                               Maintenance Stations
                                               Historian
                                                                                                  Peer-to-Peer Communications
                                              Unit Data Highway (UDH) - Ethernet                         with GE Controls
                                                Mark VI                                                       Mark VI e
                                             Control Module                                                 Control Module
                                   Main                                                              Main
                                 Processor                                                         Processor
Compact PCI
                                                                                                      Cat 5 / Fiber
                                                                                         Switch
                                                              37 Pin
                                                              Cable
                                              Termination                                                   Termination
              IONet - 10MB Ethernet             Board                                                         Board
                "Internal" IO Bus                                                  IONet - 100MB Ethernet
                                                                                      "Internal" IO Bus                I/O Pack
                                                                                                                      Processor &
                                                                                                                      Conditioning
                                                                                                  Local or
                                                                                                  Remote
                                                                                                  Mounting
31
     18 November 2003
     GE Proprietary Information – Privileged & Confidential
    Mark VI & Mark VIe Comparison
         Mark VI                                         Mark VI Enhanced                   Benefit
z        VME Architecture                          z     Compact PCI® Architecture      z   Change from Backplane to Network Based I/O
z        No Remote I/O                             z     Remote I/O                     z   Lower Installed Cost & Long Term Maintenance
z        Speed - Electronics                       z     Speed - Electronics            z   Speed - Electronics
         - 20MHz Backplane, Rated                        - 160MHz Backplane, Rated          - Improved Performance
         - 300MHz CPU, 16MB Flash                        - 650MHz CPU, 32MB Flash           - Improved Performance
         - 50Mhz I/O Card Processor                      - 266Mhz I/O Pack Processor        - Improved I/O Performance (10ms to 1.8ms)
         - 10MB Ethernet I/O                             - 100MB Ethernet I/O               - Improved I/O Performance
z        Speed – System                            z     Speed – System                 z   Speed – System
         10ms Simpl, 20ms some TMR                       10ms Any Configuration             - Improved Performance in Redundant Applica.
z        Simplex & TMR Redundancy                  z     Simplex, Dual, and TMR         z   Flexible Redundancy & Cost Competitiveness
z        Separate Main/Comm. Cards                 z     Common Main/Comm Card          z   Improved Control Performance & Reliability
z        On-line Repair per Card Rack              z     On-line Repair per I/O Pack    z   Better Maintainability, MTTR, Reliability
z        1 Link to Each I/O Card                   z     2 Links to Each I/O Pack       z   Improved Communications Reliability
z        12 bit Analog Outputs                     z     14 bit Analog Outputs          z   Improved Accuracy
z        No LEDs at TBs for DI & DO                z     LEDs on I/O Packs for DI&DO    z   Better Maintainability
z        No Temp Sensor at TBs                     z     Temp Sensor on I/O Packs       z   Better Maintainability
z        125Vdc Electronics Power                  z     28/24Vdc Electronics Power     z   Improved Conformance to Industry Standards
z        LAN Based Diagnostics                     z     LAN & Wireless Diagnostics     z   Remote Access for Ease of Maintainability
z        Limited Third Party Interfaces            z     Expanded Third Party Interf.   z   Better Systems Integration & More Versatile I/O
z        NTP Time Synch 1-10ms                     z     PTP Time Synch 1 micro-sec.    z   NTSB-Class Root Cause Analysis & Global SOE
                                                                                            Coordination
    32
               18 November 2003
               GE Proprietary Information – Privileged & Confidential
                                         Third Party Interfaces
                                            & Time Synch
33
     18 November 2003
     GE Proprietary Information – Privileged & Confidential
Third Party Interfaces
                Plant Data Highway                                HMI Interfaces
                                Ethernet TCP/IP               z   Modbus Serial/Ethernet Client/Server
               HMI                                            z   GSM Ethernet TCP-IP Server
                                                              z   OPC Ethernet Client / Server
                                                              z   DNP 3.0 Serial/Ethernet Server
                                                              z   PI Server Interface
Controller(s)
Dual Triple
34
     18 November 2003
     GE Proprietary Information – Privileged & Confidential
 Third Party Interfaces
 Feature                                            Modbus                 GSM           OPC            DNP 3.0
Physical Layer                                   Serial / Ethernet        Ethernet    Ethernet       Serial / Ethernet
Client / Server                                  Client / Server          Server     Client / Server     Server
Time Tags
Alarm Queue & Commands
Alarm / Event Excep. Reports
 35
        18 November 2003
        GE Proprietary Information – Privileged & Confidential
Time Synch Between Controllers
                   Wall Clock
                 Time Reference
                      Master
                      Clock
                                                                                   Plant Data Highway (PDH) - Ethernet
                 IRIG-B               HMI
                                     Server               +/-1ms Time Accuracy & Time
                                                          Coherence to Time Reference
                          Time
                          Card
                                                                                                                     Mark VI e
                                                                        "R"                   "S"                     "T"
                   Mark VI e             Mark VI e                    Controller            Controller              Controller
                                                                  U                     U                       U
                                                                  C                     C                       C
                       Controller Coordination                    C                     C                       C
                       - UDH Communicator                         A                     A                       A
                         - Generates Process Alarms
                       - Designated Controller                           IONet                IONet
                         - Supplies Initialization Data
                         - Keeps Master Clock
                         - Master for Control Data
36
     18 November 2003
     GE Proprietary Information – Privileged & Confidential
                                                              Backup
37
     18 November 2003
     GE Proprietary Information – Privileged & Confidential
Architecture
                 Plant Data Highway
                                   Ethernet TCP/IP
                 HMI
                                                                               I/O Pack         General Purpose I/O
                                                                                                Discrete I/O
                                       ToolboxSTTM                              I/O CPU         Analog I/O
                                                                               Supply           Thermocouples
                                                                                                RTDs
  Operator &                                                                   Processor        Communications
 Maint. Station                                                                2 Ethernet
                                                                                                Turbine-Specific I/O
                                                           100MB Ethernet
                                                                               Data             Speed & Overspeed
                 Unit Data Highway                                             Acquisition
                                                                                                Servo Control
                                                       GE Control Systems                       Vibration & Position
                                                                               Card             Synchronizing
          Controller            Controller            Controller                                Combustion Monitor
                                                                                                PLU and EVA
                       PS
     Processor
                       Opt.
                                                                              Term. Board
                                   Dual                Triple
                                  Option               Option
                       PS                                                                    Terminal
                                                                                              Block
38
                  18 November 2003
                  GE Proprietary Information – Privileged & Confidential
Mark VIe Product Introduction Plan
     SYSTEM
      SYSTEMAPPLIACTION
             APPLIACTION                 - -(First
                                             (FirstCustomer/Article)
                                                    Customer/Article)           ATQ
                                                                                 ATQ            Ready
                                                                                                 ReadytotoShip
                                                                                                           Ship           Std.
                                                                                                                           Std.Reqn.
                                                                                                                                Reqn.Cycle
                                                                                                                                      Cycletime
                                                                                                                                             time
                                                                                                    ____                __(define / code / test)
                                                                                                                         __(define / code / test)
     • Balance of Plant - TMR control, New or CM&U (Lungmen)                    Sept’03         Apr ‘04                      24 to 36 wks
       • Balance of Plant - TMR control, New or CM&U (Lungmen)                   Sept’03         Apr ‘04                      24 to 36 wks
             •40 msec TMR Cont. (Compact PCI Controller CPU)                               (Lungmen has extended test in Salem into 1H’04)
              •40 msec TMR Cont. (Compact PCI Controller CPU)                               (Lungmen has extended test in Salem into 1H’04)
             •CI, RO, AI, AO, RTD, TC I/O
              •CI, RO, AI, AO, RTD, TC I/O
             •QNX6 runtime & ToolboxST
              •QNX6 runtime & ToolboxST
     • Balance of Plant - Dual control, New or CM&U                             Dec ‘03         Apr ’04                       16 to 24 wks
       • Balance of Plant - Dual control, New or CM&U                            Dec ‘03         Apr ’04                       16 to 24 wks
     • Aero Derivative Turbine - Dual control (AEP LM6000PC)                  Dec ’03          Mar ‘04                        6 to 8 wks Kits only
       • Aero Derivative Turbine - Dual control (AEP LM6000PC)                 Dec ’03           Mar ‘04                       6 to 8 wks Kits only
             • 10 msec Dual Cont.                                                      (first engine test on Houston test line Jan ’04)
               • 10 msec Dual Cont.                                                      (first engine test on Houston test line Jan ’04)
             • DIN Rail Terminal Boards
               • DIN Rail Terminal Boards
             • Servos, PTUR; (w/o PVIB and PPRO)
               • Servos, PTUR; (w/o PVIB and PPRO)
             • QNX6 runtime & ToolboxST
               • QNX6 runtime & ToolboxST
             • with PVIB and PPRO                                             Jan ‘04          Jul ‘04
               • with PVIB and PPRO                                            Jan ‘04           Jul ‘04
             • (LM6000PD)                                                     Jan ‘04          Aug ‘04
               • (LM6000PD)                                                    Jan ‘04           Aug ‘04
             • (LMS100)                                                       Sep ‘04          Dec ‘04
               • (LMS100)                                                      Sep ‘04           Dec ‘04
     • Aero Derivative Turbine / Compressor - TMR control (O&G Darwin )       Nov’ 03          Mar ’04                        20 to 24 wks, skid
       • Aero Derivative Turbine / Compressor - TMR control (O&G Darwin )      Nov’ 03           Mar ’04                       20 to 24 wks, skid
             • 10 msec TMR Cont., LM2500+ DLE Compressor Drive, integrated control skid
               • 10 msec TMR Cont., LM2500+ DLE Compressor Drive, integrated control skid
             • Second CPU for auxiliaries
               • Second CPU for auxiliaries
             • w/o PVIB and PPRO
               • w/o PVIB and PPRO
             • QNX6 runtime & ToolboxST
               • QNX6 runtime & ToolboxST
             • with PVIB and PPRO                                             Jan ‘04          Jul ‘04
               • with PVIB and PPRO                                            Jan ‘04           Jul ‘04
     • HD Turbine - TMR control, CM&U GT / ST (Lynn GT)                         Dec ‘03         Jul ‘04                        14 to 20 wks
       • HD Turbine - TMR control, CM&U GT / ST (Lynn GT)                        Dec ‘03         Jul ‘04                        14 to 20 wks
             • 40 msec TMR Control                                                         (Lynn site test Feb ’04 w/ MK6 VVIB & VPRO)
               • 40 msec TMR Control                                                        (Lynn site test Feb ’04 w/ MK6 VVIB & VPRO)
             • Uses Mark VI controller for VPRO and VVIB interface
               • Uses Mark VI controller for VPRO and VVIB interface
             • QNX6 runtime & ToolboxST
               • QNX6 runtime & ToolboxST
             • with PVIB and PPRO
               • with PVIB and PPRO
     • HD Turbine - Dual control, CM&U GT / ST                                  Dec ‘03         Aug ‘04                       12 to 24 wks
       • HD Turbine - Dual control, CM&U GT / ST                                 Dec ‘03         Aug ‘04                       12 to 24 wks
             • with PVIB and PPRO
               • with PVIB and PPRO
     • Simplex Turbine control, CM&U GT / ST                                    Jun ’04         Dec ‘04                       12 to 24 wks
       • Simplex Turbine control, CM&U GT / ST                                   Jun ’04         Dec ‘04                       12 to 24 wks
             • with PVIB and PPRO
               • with PVIB and PPRO
     • HD Turbine - TMR control, New Unit GT / ST                               Jun ’04         Dec ‘04                       12 to 24 wks
       • HD Turbine - TMR control, New Unit GT / ST                              Jun ’04         Dec ‘04                       12 to 24 wks
             • 3 ph. PT/CT - PLU (PGEN)
               • 3 ph. PT/CT - PLU (PGEN)
             • with PVIB and PPRO
               • with PVIB and PPRO
             • w/o Advanced I/O PAMB (acoustic monitor / lean blowout)
               • w/o Advanced I/O PAMB (acoustic monitor / lean blowout)
             • with ToolboxST for EX2100 & LS2100
               • with ToolboxST for EX2100 & LS2100
             • with Advanced I/O PAMB (acoustic monitor / lean blowout)         TBD ~’05        TBD ~’05
               • with Advanced I/O PAMB (acoustic monitor / lean blowout)        TBD ~’05        TBD ~’05
     •Next Gen HMI                                                              Dec ’04         Dec ’04
      •Next Gen HMI                                                              Dec ’04         Dec ’04
39
      18 November 2003
      GE Proprietary Information – Privileged & Confidential