AS 3600:2018
(incorporating Amendment No. 1)
O% Austrotion
7) STANDARD
Concrete structures
STANDARI
Australia‘Accessed by SWINBURNE UNIVERSITY OF TECHNOLOGY on 27 Sep 2019 (Document currency not guaranized when printed)
‘This Australan Standarck® was prepared by Commitee 80-002, Concrate Structures. It was
{2pproved on behalf ofthe Council of Standards Australia on 22 June 2078.
This Standerd was published on 29 June 2018.
‘The folowing are represented on Committee 8-002
Australian Building Codes Board
Bureau of Stee! Manufacturers of Australia
‘Cement Concrete and Aggregates Australia —Cement
‘Cement Concrete and Aggregates Australa—Concrete
Concrete intitte of Austria
Consuit Australia
Engineers Ausiala
Ls Trobe University
Maser Builders Australia
‘National Precast Conerate Association Austraka
Stee! Reinforcement insitute of Austrata
University of Melbourne
University of Now South Wales
Universty of Sydney
‘This Standard was issued in craft form for comment as DR AS 9600:2018.
‘Standards Australa wishes to acknowledge the participation of the expert indwiduals that
Contributed to the development of this Standard through ther representation on the
CComsritee ang through the public comment period.
Keeping Standards up-to-date
‘Ausraian Standards® are fving docurnents thal rlloct progress in science, lechnology and
sysioms. To maintain theic currency, af Standards are periodical reviowed, ene tow eds
{are pubished. Between editions, amendments may be issued.
Standards may also be withdrawn. It's important that readers assure themselves they are
lusng a current Standard, which should include any amendments that may have been
published since the Standard was published.
stated information about Austraian Standards, crafts, amendments and new projects can
'be found by visting www standards org.au
‘Stendards Australia weicomes suggestions for improvernents, and encourages readers 10
‘not us mmediatety of any apparent inaccuracies or ambiguities, Contact us via era at
‘mail@standards.org.au, or wite to Standarcs Australia, GPO Box 476, Sydney, NSW 200.‘cessed by SWINBURNE UNIVERSITY OF TECHNOLOGY on 27 Sep 2019 (Document curency not guaranteed when printed)
AS 3600:2018
Australian Standard®
Concrete structures
Fits published in part as AS CA2—1094
AAS ADS fist published 1934
‘AS CA2redated 1937,
MP 13 fest publishes 1957
AS CA2—1937 and AS A26—1924 revised, amalgamated and redesignated AS CA2—1958,
“Third edvon 1963,
MP 13-1957 revised and redesignated AS CA35—1963,
‘Sevond eation 1075.
Fourth ection AS CA2—1973,
‘AS CA2—1973 revised and redesignated AS 1480—1974,
‘AS CAI5—1973 revised and redesignated AS 14811974,
‘Second ection AS 14811978,
Second edtion AS 14201962,
‘AS 1480—1962 and AS 1461-1978 revised, amalgamatod and redes.gnated AS 3600—1988,
Fourth esion 2008.
Fifth edtion 2018,
Re’ssued incorporating Amendment No.1 (November 2018)
COPYRIGHT
© Standards Ausialia Limited
All rights are reserved. No part ofthis work may be reproduced or copied in any form or by
‘any means, electronic or mechanical, including photocopying, without the. witlen
Dermission ofthe publisher, unless otherwise permitted under the Copyright Act 1968.
Published by SAI Global Limited under neence trom Standards Austealia Limited, GPO Box
476, Sydney, NSW 2001, Australia
ISBN 978 1 76072 146 6‘cessed by SWINBURNE UMVERSITY OF TECHNOLOGY on 27 Sep 2019 (Document cutrency not guaranteed when printed)
PREFACE
This Standard was prepared by Standards Australia Committee BD-002, Concrete
Structures, to supersede AS 3600—2009.
This Standard incorporates Amendment No. 1 (November 2018). The changes required by
the Amendment are indicated in the text by @ marginal bar and amendment number against
the clause, note, table. figure or part thereof affected.
The principal objective of this Standard is to provide users with nationally acceptable
unified rules for the design and detailing of concrete structures and members, with or
without steel reinforcement or prestressing tendons, based on the principles of structural
engineering mechanics. The secondary objective is to provide performance criteria against
which the finished structure can be assessed for conformance with the relevant design
requirements.
The following list indicates the major differences between this edition and the 2009 edition
of AS 3600:
(a) Addition of the following new sections:
(i) Section 14 Design for Earthquakes Actions (formerly Appendix C).
(ii) Section 15 Diaphragms
(iii) Section 16 Stee! Fibre Reinforced Conerete.
(iv) Section 18 Design for Fatigue.
() Appendix C Residual Tensile Strength Test for SERC.
(©) Revision of the following requirements:
(Phi factors,
(ii) Maximum steel strength.
(iii) Shear in deep slabs.
(iv) Fire design, including
(A) axis distances for fire design;
(B) continuous top reinforcement; and
(C)_ minimum slab thickness,
(v) Modification of models and calculations of.
(A) shrinkage;
(B) creep;
(C) deflections; and
(D) development lengths for higher strength steels.
(vi) Steel shrinkage in areas modelled by strut and tie.
(vii) Punching shear.
(viii) Ductility for pre-cast concrete connections.
(ix) Heating and re-bending bars.
(x) Crack control.‘Accesseo by SWINBURNE UNIVERSITY OF TECHNOLOGY on 27 Sep 2019 (Document currency not guaranteed when printed)
3 AS 3600:2018
Statements expressed in mandatory terms in notes to figures and tables are decmed to be
requirements of this Standard,
The terms ‘normative’ and ‘informative’ arc used in Standards to define the application of
the appendices to which they apply. A ‘normative’ appendix is an integral part of a
Standard, whereas an ‘informative’ appendix is only for information and guidance‘Accessed by SWINBURNE UNIVERSITY OF TECHNOLOGY on 27 Sep 2019 (Document currency nat guaranteed when printed)
AS 3600:2018 ‘
CONTENTS,
SECTION | SCOPE AND GENERAL
1.1 SCOPE AND APPLICATION.....
1.2 NORMATIVE REFERENCES .....,
1.3 EXISTING STRUCTURES.
14 DOCUMENTATION.
LS CONSTRUCTION,
1.6 DEFINITIONS.
1.7 NOTATION.
SECTION2 DESIGN PROCEDURES, ACTIONS AND LOADS
2.1 DESIGN PROCEDU
22 DESIGN FOR STRENGTH,
23 DESIGN FOR SERVICEAB
24 DESIGN FOR FATIGUE... .
2.8 ACTIONS AND COMBINATIONS OF ACTION
SECTION3 DESIGN PROPERTIES OF MATERIALS
3.1 PROPERTIES OF CONCRETE ....
3.2 PROPERTIES OF RFINFORCEMENT ...
3.3 PROPERTIES OF TENDONS.....
3.4 LOSS OF PRESTRESS IN TENDONS
3.5 MATERIAL PROPERTIES FOR NON-
SECTION 4 DESIGN FOR DURABILITY
4.1 GENERAL...
42 METHOD OF DESIGN FOR DURABILITY...
43° EXPOSURE CLASSIFICATION
44 REQUIREMENTS FOR CONCRETE FOR EXPOSURE CLASSIFICATIONS Al,
A2, BI, B2, Cl AND C2... 61
4.5 REQUIREMENTS FOR CONCRETE FOR EXPOSURE CLASSIFICATION U.... 62
4.6 ABRASION. scr
4.7. FREEZING AND THAWING
48 AGGRESSIVE SOILS. csscinn
4.9. RESTRICTIONS ON CHEMICAL CONTENT IN CONCRETE,
4.10 REQUIREMENTS FOR COVER TO REINFORCING STEEL A!
SECTION $_ DESIGN FOR FIRE RESISTANCE
5.1 SCOPE.....
$2. DEFINITIONS.
4.3. DESIGN PERFORMANCE CRI
5.4. FIRE RESISTANCE PERIODS (FRPs) FOR BEAMS
5.5 FIRE RESISTANCE PERIODS (FRPs) FOR SLABS...
$6 FIRE RESISTANCE PERIODS (FRPs) FOR COLUMNS.
5.7 FIRE RESISTANCE PERIODS (FRPs) FOR WALLS...
5.8 INCREASE OF FIRE RESISTANCE PERIODS (FRPs) BY USE
‘OF INSULATING MATERIALS ..‘Accessed by SWINBURNE UNIVERSITY OF TECHNOLOGY on 27 Sep 2019 (Document currency nol uaranieed when panied)
5 AS 3600:2018
SECTION 6 METHODS OF STRUCTURAL ANALYSIS
61
62
63
64
8S
66
67
68
69
6.10
GENERAL concn
LINFAR ELASTIC ANALYSIS
ELASTIC ANALYSIS OF FRAMES INCORPORATING SECONDARY
BENDING MOMENTS... i
LINEAR ELASTIC STRESS ANALYSIS...
NON-LINEAR FRAME ANALYSIS
NON-LINEAR STRESS ANALYSIS.
PLASTIC METHODS OF ANALYSIS...
ANALYSIS USING STRUT-AND-TIE MODELS .......
IDEALIZED FRAME METHOD OF ANALYSIS...
SIMPLIFIED METHODS OF FLEXURAL ANALYSIS ..
SECTION 7. STRUT-AND-TIE MODELLING.
1
22
73
74
1S
76
GENERAL...
CONCRETE STRUTS.
THES sig acon
NODES... 5s
ANALYSIS OF STRUT-AND-TIE MODELS .
DESIGN BASED ON STRUT-AND-TIE MODELLING.
SECTION $ DESIGN OF BEAMS FOR STRENGTH AND SERVICEARILITY,
8
a2
83
84
8S
86
a7
BR
89
ot
92
93
o4
95
9.6
97
98
STRENGTH OF BEAMS IN BENDING.
STRENGTH OF BEAMS IN SHEAR
GENERAL DETAILS FOR BEAMS.......
LONGITUDINAL SHEAR IN COMPOSITE AND MONOLITHIC BEAN
DEFLECTION OF BEAMS, oe
CRACK CONTROL OF BEAMS...
VIBRATION OF BEAMS.
T-BEAMS AND L-BEAMS
SLENDERNESS LIMITS FO)
‘STRENGTH OF SLABS IN BENDING.
STRUCTURAL INTEGRITY REINFORCEMENT |
‘STRENGTH OF SLABS IN SHEAR.....
DEFLECTION OF SLABS...
CRACK CONTROL OF SLABS.
VIBRATION OF SLABS
MOMENT RESISTING
CONCENTRATED LOADS.
LONGITUDINAL SHEAR IN COMPOSITE SLABS.
SECTION 10 DESIGN OF COLUMNS FOR STRENGTH AND SERVICEABILITY
1.1
102
103
104
los
10.6
10.7
los
109
GENERAL...
DESIGN PROCEDURES
DESIGN OF SHORT COLUMNS.
DESIGN OF SLENDER COLUMNS ...
SLENDERNESS..
STRENGTH OF COLUMNS IN COMBINED BENDING AND COMPRESSION 158
REINFORCEMENT REQUIREMENTS FOR COLUMNS. 161
TRANSMISSION OF AXIAL FORCE THROUGH FLOOR SYST
CRACK CONTROL. Cr ‘i
170‘Accessed by SWINBURNE UNIVERSITY OF TECHNOLOGY on 27 Sep 2019 (Document currency nat quarenteed when printed)
AS 3600-2018 ‘
SECTION IT DESIGN OF WALLS,
11.1 GENERAL..... 7
112 DESIGN PROCEDURES...
11.3 BRACED WALLS.
114 EFFECTIVE HEIGH’
11.5 SIMPLIFIED DESIGN METHOD FOR WALLS SUBJECT TO VERTICAL
COMPRESSION FORCES... =
11.6. DESIGN OF WALLS FOR IN-PLANE SHEAR FORCES -
11.2 REINFORCEMENT REQUIREMENTS FOR WALLS ..
SECTION 12 DESIGN OF NO:
SURFACES
12.1 GENERAL. ai
122. STRUT-AND-TIE MODELS FOR THE DESIGN OF NON-FLEXURAL
MEMBERS.
123 ADDITIONAL REQUIREMENTS FOR CONTINUOUS CONCRETE NIBS
AND CORBELS. sii a
124 ADDITIONAL REQUIREMENTS FOR STEPPED JOINTS IN BEAMS
AND SLABS
12.8 ANCHORAGE ZONES FOR PRESTRESSING ANCIORAGES
12.6 BEARING SURFACES,
12.7 CRACK CONTROL......
LEXURAL MEMBERS, END ZONES AND BEARING
TT
SECTION 13 STRESS DEVELOPMENT OF REINFORCEMENT AND TENDONS
13.1 STRESS DEVELOPMENT IN REINFORCEMENT.
13.2 SPLICING OF REINFORCEMENT.
13.3. STRESS DEVELOPMENT IN TEN!
13.4 COUPLING OF TENDON’
14
142. DEI
143. STRUCTURAL DUCTILITY FACTOR () AND STRUCTURAL
PERFORMANCE FACTOR (S))
144 GENERAL EARTHQUAKE DESIGN REQUIREMENTS
145, INTERMEDIATE MOMENT-RESISTING FRAMES (IMRFs)
146 LIMITED DUCTILE STRUCTURAL WALLS. .
147 MODERATELY DUCTILE STRUCTURAL WALLS.
SECTION 15 DIAPHRAGMS
15.1 GENERAL...
152. DESIGN ACTION!
153 CAST IN-PLACE TOPPINGS...
154 DIAPHRAGM REINFORCEMENT,
SECTION 16 STEEL FIBRE REINFORCED CONCRETE
16.1 GENERAL.
16.2 DEFINITIONS.
16.3, PROPERTIES OF SFRC cotton
164 DESIGN OF SERC MEMBERS CONTAINING REINFORCEMENT
OR TENDONS... sis
165 OURABILITY
16.6 FIRB ooo.‘Accessed by SWINBURNE UNIVERSITY OF TECHNOLOGY on 27 Sep 2019 (Document cutrency not guaranteed when printed)
? AS 3600:2018
Page
16.7. PRODUCTION OF SFRC.....
221
SECTION 17 MATERIAL AND CONSTRUCTION REQUIREMENTS:
17.1, MATERIAL AND CONSTRUCTION REQUIREMENTS FOR CONCRETE,
AND GROUT
172. MATERIAL AND CONSTRUCTION REQUIREMENTS
FOR REINFORCING STEEL 0...
173. MATERIAL AND CONSTRUCTION REQUIREMENTS
FOR PRESTRESSING DUCTS, ANCHORAGES AND TENDONS.
17.4 CONSTRUCTION REQUIREMENTS FOR JOINTS,
AND EMBEDDED ITEMS... iene 232
17.5. TOLERANCES FOR STRUCTURES AND MEMBERS...
17,6 FORMWORK visinssisninsinssniansitinn
177 PREFABRICATED CONCRETE STRUCTURES
iia RED
SECTION 18 DESIGN FOR FATIGUE
18,1 GENERAL. eae :
182 MAXIMUM STRESS I ETE.
18,3 PLAIN CONCRETE WITH COMPRESSION-TENSION STRESS.
18.4 PLAIN CONCRETE WITH PURE TENSION OR COMBINED TENSION-
COMPRESSION STRESS.......
13,8. SHEAR LIMITED BY WER COMPRES:
18.6 SHEAR IN SLABS.
18.7 ADJUSTMENT FACTOR FOR BOND BEHAVIOUR IN REINFORCING.
AND PRESTRESSIGN STEEL.
18.8 TENSILE STRESS RANGE IN 3
18.9 CALCULATION OF STRESSES IN REINFORCE!
OF FLEXURAL MEMBERS.....
INT AND TENI
SECTION 19 JOINTS, EMBEDDED ITEMS AND FIXINGS,
19.1 JOINTS.
192 EMBEDDED ITEMS.
19.3. FIXINGS
is Roe 247
SECTION 20 PLAIN CONCRETE
20,1 GENERAL...
20.2 DURABILITY
20,3. PEDESTALS
20.4 FOOTINGS.
ESTALS AND FOOTINGS
SECTION 21 SLAB-ON-GROUND FLOORS, PAVEMENTS AND FOOTINGS
21 GENERAL cose
21.2. DESIGN CONSIDERATIONS.
21,3, FOOTING:
APPENDICES
A REFERENCED DOCUMENTS.
B TESTING OF MEMBERS AND STRUCTURES
D RESIDUAL TENSILE STRENGTH TEST FOR
BIBLIOGRAPHY...‘Accessed by SWINBURNE UNIVERSITY OF TECHNOLOGY on 27 Sep 2019 (Document currency not quaranieed when printed)
AS 3600:2018 ®
STANDARDS AUSTRALIA
Australian Standard
Concrete structures
SECTION 1 SCOPE AND GENERAL
1.1 SCOPE AND APPLICATION
1.1.1 Scope
‘This Standard sets out minimum requirements for the design and construction of concrete
building structures and members that contain reinforcing steel or tendons, or both. It also
sets out minimum requirements for plain concrete pedestals and footings.
NOTES:
1 The general principles of conerete design and construction and the criteria embodied in this
Standard may be appropriate for concrete structures other than buildings, members not
specifically mentioned herein and to materials outside the limits given in Clause 1.1.2.
2. Is intended that the design of a structure or member to which this Standard applies be
carried out by, or under the supervision of, a suitably experienced and competent person,
For guidance on the design of maritime structures refer to AS 4997
4 If alternate materials and methods to those prescribed in this Standard are to be used, they
would need to be considered as part of the development of a Performance Solution to
demonstrate compliance with the relevant Performance Requirements of the National
Construction Code (NCC) and be accepted by the relevant building authority,
This Standard is not intended to apply to the design of mass conerete structures.
1.1.2 Application
This Standard applies to structures and members in which the materials conform to the
following:
(@) Concrete with
(i) characteristic compressive strength at 28 days (f’) in the range of 20 MPa to
120 MPa; and
(ii) with a saturated surface-dry density in the range 1800 kg/m? to 2800 kg/m’.
(b) Reinforcing steel of Ductility Class N or E in accordance with AS/NZS 4671
NOTE: These reinforcing materials may be used, without restriction, in all applications
referred to in this Standard. This Standard has been written using Ducility Class N
reinforeing steels which are readily available in Australia, Where Ductility Class Nis
referenced in this Standard, the Earthquake Ductility Class E steels may be substituted but the
availability of supply in Australia needs to be checked prior to specification on design
drawings.
(c) Reinforcing sicel of Ductility Class L in accordance with AS/NZS 4671 may be used
as main or secondary reinforcement in the form of welded wire mesh, or as wire, bar
and mesh in fitments, provided it is not used in any situation where the reinforcement
is required to undergo large plastic deformation under strength limit state conditions.
NOTE: The use of Ductility Class L reinforcement is further limited by other clauses within
the Standard,
© Standards Austialla, www standards org au‘Aecossed by SWINBURNE UNIVERSITY OF TECHNOLOGY on 27 Sep 2019 (Daciment currency not guaranieed when printed)
8 AS 3600:2018
(@) Higher reinforcing steel grades >500 MPa to 800 MPa mecting the requirements of
Table 3.2.1. For ultimate Himit states the strength of the reinforcement in design
models shall not be taken as greater than 600 MPa unless noted otherwise.
(©) Prestressing tendons conforming with AS/NZS 4672.1 and tested in accordance with
ASINZS 4672.2
(Steel fibres conforming to ISO 13270:2013 and mecting the requirements of
Clause 16.3.3.8.
3. Exclusions
The requirements of this Standard shall not take precedence over design requirements and
material specifications set out in other Australian Standards that deal with specific types of
structures,
1.2 NORMATIVE REFERENCES
Normative documents referred to in this Standard are listed in Appendix A.
NOTE: Informative documents referred to in this Standard are listed in the Bibliography at the
end of this document
1.3 EXISTING STRUCTURES.
The general principles of this Standard shall be applied when evaluating the strength or
serviceability of an existing structure.
No’ rials that do net conform with the material
specifications herein and may have been designed to different requirements, but the general
principles of this Standard would apply. (See also Appendix B.)
sting structures are Tikely to cantasn
1.4 DOCUMENTATION
The drawings and/or specification for conerete structures and members shall include, when
required, the following:
(a) Reference number and da
of issue of applicable design Standards
(b) Imposed actions (live loads) used in design,
(©) The earthquake design category determined from AS 1170.4.
(4) Any constraint on construction assumed in the design
(e) Exposure classification for durability
(Fire resistance level (FRL), if applicable.
(g) Class and grade designation of concrete
(h) Any required properties of the concrete.
(i) The curing procedure.
G)_ Grade, Ductility Class and type of reinforcement and grade and type of tendons,
(K) The size, quantity and location of all reinforcement, tendons and structural fixings
and the cover to each.
(1) The location and details of any splices, mechanical connections and welding of any
reinforcement or tendon.
(m) ‘The maximum jacking force to be applied in each tendon and the order in which
(endons are to be stressed
(n) The shape and size of each member.
worw standards org av © Standards Austealia‘Aecessed by SWINBURNE UNIVERSITY OF TECHNOLOGY on 27 Sep 2019 (Document currency not guaranteed when printed)
(0) The fi
(p) Class of formwork in accordance with AS 3610 and AS 3610.1 as applicable for the
surface finish specified.
and method of control for unformed surfaces.
(q) The minimum period of time after placing of concrete before stripping of forms and
removal of shores,
(8) The location and details of planned construction and movement joints, and the
method to be used for their protection.
1.5 CONSTRUCTION
Alll conerete structures, designed in accordance with this Standard, shall be constructed so
that all the requirements of the design, as contained in the drawings and specifications, are
achieved.
1.6 DEFINITIONS
1.6.1 General
For the purposes of this Standard, the definitions below apply.
1.6.2. Administrative definitions
1.6.
1 Building authority or other relevant regulatory authority.
The body having statutory powers to control the design and construction of the structure in
the area in which the structure is to be constructed.
1.6.2.2 Drawings
‘The diagrams forming part of the documents setting out the work to be executed.
1.6.2.3. Specification
The requirements forming part of the documents setting out the work to be executed.
1.6.5 Technical detinitions
1
1 Action
Set of concentrated or distributed forces acting on a structure (direct action), or deformation
imposed on a structure or constrained within it (indirect action).
NOTE: The term ‘load? is also often used to describe direet actions.
1.6.3.2 Action effects
Internal forces, bending moments and torsion due to actions (i
the stress resultants),
1.6.3.3 Anchorage zone
Region between the face of the member where the prestress is applied and the cross-section
at which a linear distribution of stress duc to prestress is achieved.
1.6.3.4 Average ambient temperature
Average value of the daily maximum and minimum ambient temperatures over the defined
period at a site.
1.6.3.5 Average axis distance
See Clause 5.2.1.
1.6.3.6 Axis distance
Distance from the centre-line axis of a longitudinal bar or tendon to the nearest surface
exposed to fire (see Figure 5.2.2)
© Standards Austrais www standards org au‘Accessed by SWINBURNE UNIVERSITY OF TECHNOLOGY on 27 Sep 2019 (Doctmentcutrency not guaranteed when printed)
u AS 3600:2018
3.7 B-region
Portion of a member in which the assumption that plane sections remain plane can be
applied.
iF
3.8 Basic creep coeffictent
Mean value of the ratio of final creep strain to clastic strain for a specimen loaded at
28 days under a constant stress of 0.4! (sce Clause 3.1.8.2).
Mw
9 Boutle-shaped compression field
Compression field that is wider at mid-tength than at its ends {see Figure 7.2.1(c)]
1.6.3.10 Braced column
Column in a structure for which the lateral actions, applied at the ends in the direction
under consideration, are resisted by components such as masonry infill panels, shear walls
or lateral bracing,
A Characteristic strength
Value of the material strength, as assessed by standard test, thal is exceeded by 95% of the
material (lower characteristic strength).
1.6.3.12 Closed fitment
A unit or multiple units of reinforcement used as an external or internal fitment that form a
continuous perimeter around a concrete element with the ends of the fitment anchored into
the conerete using a minimum of 135% hooks around a longitudinal bar.
16.313 Closed ue
A unit of reinforcement used as an external or internal fitment having a straight leg and
minimum of 135° hooks at each end fixed around a longitudinal bar.
1.63.14 Collector
An clement that takes the distributed lateral action from a diaphragm and delivers it to a
vertical clement. Also known as a drag bar, sirut or distributor. A distributer takes the
actions from a vertical clement and distributes it into the diaphragn
18 Column strip
See Clause 6.1.4.1
1
3.16 Composite concrete member
Member consisting of concrete members constructed separately but structurally connected
so the member responds as a unit to applied actions.
1.6.3.17 Concrete
Mixture of cement, aggregates and water, with or without the addition of chemical
admixtures,
18 Construction joint
Joint that is located in # structure or part of a structure for convenience of construction and
made so that the load-carrying capacity and serviceability of the structure, or part of the
structure, will be unimpaired by the inclusion of the joint.
16.319 Cover
Distance between the outside of the reinforcing steel or tendons and the nearest permanent
surface of the member, excluding any applied surface finish
‘www standards org 2u © Standards Australia‘Accessed by SWINBURNE UNIVERSITY OF TECHNOLOGY on 27 Sep 2019 (Docunent currency not guaranteed when printed)
AS 360022018 2
1.63.20 Creep coefficient
Mean value of the ratio of creep strain to clastic strain under conditions of constant stress.
1.63.21 Critical opening
Opening through the thickness of a slab where an edge, or part of the edge, of the opening
is located at a clear distance of less than 2.55, from the critical shear perimeter
[see Figure 9.3(A)(b)}.
1.6.3.2 Critical shear perimeter
Perimeter defined by a line geometrically similar to the boundary of the effective arca of a
Support or concentrated load and located at a distance of dom/2 therefrom
{see Figure 9.3(A)]
1.63.23 Cross tie
An internal fitment with a single reinforcement leg anchored at one end with a 135°
(minimum) hook and anchored at the other end with a 90° cog. Both the hook ond cog are
anchored around a longitudinal bar. See Figure 10.7.4.2,
1.6.3.24 D-region
Portion of a member within a distance equal to the member depth (D), from a discontinuity.
1.6.3.28 Design life
Period for which a structure or a structural member is to remain fit for use for its designed
purpose with maintenance.
1.6.3.26 Design strip
See Clause 6.1.4.2
1.6.3.27 Diaphragm
A horizontal or near horizontal concrete element such as a floor or roof used to transmit
horizontal actions into the vertical elements of the force resisting system.
1.63.28 Direct loading
Loading on a structure that includes the self-weight of its component members and
externally applied loads
1.6.3.29. Discontinuity
Abrupt change in geometry or loading, including prestress.
1.6.3.30, Duct
Conduit (plain or corrugated) to accommodate prestressing tendon(s) for post-tensioned
installation.
1.6.3.31 Ductility Class
Designation relating to the ductility of reinforcement ('L’ designates ‘low’, ‘N’ desi
normal’, “E’ designates ‘earthquake’).
NOTE: For further information refer to ASINZS 4671
1.6.3.32 Durability
Ability of a structure and its component members to perform the functions for which they
have been designed, over a specitied period of time, when exposed to their environment.
1.6.3.33 Effective area of a support or concentrated load for slabs in shear
‘Area totally enclosing the actual support or load and for which the perimeter is a minimum
[see Figure 9.3(A)].
© Standards Austaia wow standards.org au‘Accessed by SWINBURNE UNIVERSITY OF TECHNOLOGY on 27 Sep 2018 (Document currency not guaranteed when printed)
B AS 360022018
6.3.34 Effective depth
Distance from the extreme compressive fibre of the concrete to the resultant tensile force in
the reinforcing steel and tendons in that zone, which will be tensile at the ultimate strength
condition of pure bending,
1.6.3.35 Embedded items
Items, other than reinforcement and tendons, that are embedded in a concrete member or
structure.
NOLE: Embedded items include pipes and conduits with their associated fittings, sleeves,
permanent inserts for fixings and other purposes, prestressed anchorages, holding-down bolis and
other supports,
1.6.3.36 Exposure classification
Designation indicative of the most severe environment to wl
subjected during its design life (see Table 4.3)
a concrete member is to be
1.6.3.37 Fan shaped compression field
Compression field that has non-parallel straight sides [see Figure 7.2.1(b)}
1.6.3.38. Fire resistance
Ability of a structure or part of it to fulfil its required funetions (loadbearing and/or
separating function) for a specified fire exposure, for a specified time.
1,6.3.39. Fire resistance level (FRL)
Fire resistance periods for structural adequacy, integrity and insulation expressed in that
order.
NOTE: Fire resistance levels for structures, parts and elements of construction are specified by
the relevant authority e.g. in the Building Code of Australia (BCA)].
1.6.3.40. Fire resistance period (FRP)
Time, in minutes, for a member to reach the specified failure criteria (i.e. structural
adequacy, integrity and/or insulation) if tested for fire in accordance with the appropriate
Standard.
NOTE: For structures that need to conform with the BCA requirements, the appropriate Standard
is AS 15304)
4
41 Fire-separating function
Ability of a boundary element of a fire compartment (e.g. wall, floor or roof) to prevent fire
spread by passage of flames or hot gases (integrity) or ignition beyond the exposed surface
(thermal insulation) during a fire.
NOTE: When tested in accordance with AS 1530.4, prototypes of such members are exposed to
fire from only one direction at 9 time and are assumed to be similarly exposed for the purpose of
interpreting Section 5
1.6.3.42 Fitment
Unit of reinforcement commonly used to restrain from buckling the longitudinal reinforcing
ars in beams, columns and piles, Larry shear, (orsion and diagonal (cusivn, set ay ha
for longitudinal reinforcement; or provide confinement to the core concrete.
NOTE: Also referred to commonly as a stirrup,
ture or helical reinforcemen
1.63.43 Fixing or fastener or anchor or lifter
Material cast into or installed into concrete after it has cured for the purpose of maintaining
in position reinforcement, tendons, ducts, formwork, or inserts, used to lift concrete
members. or to transfer load from other elements into concrete lifting of members,
www standards org au © Standards Austratia‘Accessed by SWINBURNE UNIVERSITY OF TECHNOLOGY on 27 Sep 2019 (Document curency nat guaranteed when painted)
AS 3600-2018 “
1.63.44 Flat plate
Flat slab without drop panels.
1.6.3.45 Flat slab
Continuous two-way solid or ribbed slab, with or without drop-panels, having at least (wo
spans in each direction, supported internally by columns without beams and supported
externally by walls or columns with or without spandrel beams, or both.
46 Footing
Part of a structure in direct contact with and transmitting load (o the supporting foundation.
1.6.3.47 Foundation
Soil, subsoil or rock, whether built-up or natural, by which a structure is supported,
1.6.3.48 Grout
A mixture of cement and water, with or without the addition of sand, or chemical
admixtures, that is proportioned to produce a material that will subsequently harden to
achieve the specified compressive strength.
1.6.3.49 Headed reinforcement
Steel bar that achieves anchorage by means of a head or end plate.
1.6.3.80 Helical reinforcement
Unit of reinforcement that is wound in a helical fashion around the main longitudinal
reinforcing bars in a column or pile restraining them from buckling and to carry shear,
torsion and diagonal (ension or around tendons at an anchorage to resist bursting action
effects.
1.6.3.
Hollow-core slab or wall
Slab or wall having mainly a uniform thickness and containing essentially continuous voids.
1.6.3.52 Initial force
Force immediately after transfer, at a stated position in a tendon
1.6.3.3 Insulation (fire)
The ability of a fire-separating member, such as a wall or floor, to limit the surface
temperature on one side of the member when exposed to fire on the other side.
1.6.3.84 Integrity (fire)
Ability of a fire-separating member to resist the passage of flames or hot gases through the
member when exposed to fire on one side.
1.6.3.55 Jacking force
Force in a tendon measured at the jack.
1
56 Ligature (reinforcement)
ee “Fitment”
1.6.3.87 Lightweight concrete
Concrete having a saturated surface-dry density in the range of 1800 kg/m! to 2100 kgim’,
1.6.3.8 Limit state
Limiting condition at which the structure ceases to fulfil its designed function.
© Standards Austraia worn standards.org au‘Accessed by SWINBURNE UNIVERSITY OF TECHNOLOGY on 27 Sep 2019 (Document currency not guaranteed when panied)
Is AS 3600:2018
1
Ability of a structure or member to sustain sp
1
3.89 Loadbearing function
1d actions during the fire.
3.60 Loadbearing wall or column
Member designed to support or transmit vertical loads additional to its own weight where
the design axial force at mid-height of the member is greater than the lesser of 0.03 f 4, or
2d
1
3.61 Mean strength
Statistical average of a number of test results representative of the strength of a member,
prototype or material
1.6.3.62 Middle sirip
See Clause 6.1.4.3.
re
63 Movement joint
Joint that is made between paris of a structure for the specific purpose of permitting relative
movement between the parts of the structure on either side of the joint
1.6,3.64 Node
Point in a joint ina strut-and-tie model where the axes of the struts, ties and concentrated
forces acting on the joint intersect.
1.6.3.65 Nodal zone
Volume of conerete around a node, which is assumed to transfer strut-and-tie forces through
the node,
1.63.66 One-way slab
Slab characterized by flexural action mainly in one direction
1
67 Plain concrete member
Member either unreinforced, containing less than minimum reinforcement or reinforced but
assumed to be unreinforced for the purpose of design.
1.6.3.68 Post-tensioning
Tensioning of tendons after the concrete has hardened,
1.6.3.69 Prestressed concrete
Conerete into which internal stresses are induced deliberately by tendons
NOTE: It includes concrete commonly referred to as “partially prestressed”
Li
10 Prestressing steel
See ‘Tendon’,
ik
3.71. Pretensioning
Tensioning of tendons before the concrete is placed.
1.63.72 Prismatic compression field
Compression field that is parallel sided [see Figure 7.2.1(a)]
1.6.3.73 Reinforcement
Steel bar, wire or mesh but not tendons.
NOTE: Commonly referred to as reinforcing steel
wu standards org au © Standards Australia‘Aecessed by SWINBURNE UNIVERSITY OF TECHNOLOGY on 27 Sep 2019 (Docement currency not guaranteed when printed)
AS 360022018, 6
1.63.74 Ribbed slab
Slab incorporating parallel ribs in one or two directions,
1.63.75 Self-compacting concrete
Conerete that is able to flow and consolidate under its own weight, completely fill the
formwork or excavation even in the presence of dense reinforcement, whilst maintaining
homogeneity and without the need for additional compaction, and which conforms with
specified requirements for slump flow, viscosity and passing ability,
1.6.3.76 Shear wall
Wall that is designed to resist lateral forces acting in or parallel to the plane of the wall.
1.6.3.77 Short column
Column in which the additional bending moments due to slenderness can be taken as zero,
1.6.3.78 Slender column
Column that does not satisfy the requirements for a short column.
1.6.3.79 Span support
See Clause 6.1.4.4
1.6.3.80, Strength grade
Numerical value of the characteristic compressive strength of concrete at 28 days (/7), used
in design
16:
Structural adequacy (fire)
Ability of a member to maintain its structural function when exposed to fire.
1.63.82, Sirut-and-tie model
Truss model made up of struts and ties connected at nodes
1.63.83. Tendon
Wire, strand of bar (or any discrete group of such wires, strands or bars) that is designed to
be pretensioned or post-tensioned.
1.6.3.84 Tie
‘Tension member in a strut-and-tie model.
16:
85 Torsion strip
Strip of slab of width a, whose longitudinal axis is perpendicular to the direction of Mf!
[sce Figure 9.3(B)}
1.6.3.86 Transfer
Time of initial transfer of prestressing forces from the tendons to the conerete.
1.6.3.87 Transmission length
Length, at transfer, over which the stress in a pretensioned tendon builds up from zero at
one end to its full value
1.6.3.8 Transverse width
See Clause 6.1.4.5.
1.6.3.89 Two-way slab
Slab characterized by flexural action in twa directions
© Standards Austraia wow standards.org 2u‘Aecessed by SWINBURNE UNIVERSITY OF TECHNOLOGY on 27 Sep 2019 (Doctment currency nat guaranteed when printed)
0 AS 3600-2018
1.63.90 Uniform strain
Strai
in the reinforcement at maximum stress, corresponding (o the onset of necking.
1.63.91 Upper characteristic strength
Value of the material strength, as assessed by standard test, which is exceeded by 5% of the
material.
1.7 NOTATION
The symbols used in this Standard, including theie definitions, are listed below.
Unless a contrary intention appears, the following applies:
(a) The symbols used in this Standard shall have the meanings ascribed to them below,
with respect to the structure, or member, or condition to which a clause is applied,
(b) Where non-dimensional ratios are involved, both the numerator and denominator shall
be expressed in identical units.
(c) The dimensional units for length, force and stress, in all expressions or equations,
shall be taken as millimetres (mm), newtons (N) and megapascals (MPa) respectively,
unless noted otherwise,
(d) An asterisk (*) placed after a symbol as @ superscript (e.g. M) denotes a design
action effect due to the design load
Symbol Definition
As = cross-sectional area of a reinforcing bar
Assn cross-sectional area of the fitment
Ave the cross-sectional area of the bar (see Clause 13.1.4)
Ac smallest cross-sectional area of the concrete stru( at any point along its
Tength and measured normal to the line of action of the strut
(see Clauses 5.6.3 and 7.2.3); or
cross-sectional area bounded by the centre-line of the outermost fitments
(see Clause 10.7.3.3)
Acar = the effective area of concrete in tension surrounding the bars with depth
‘heat equal to the lesser of 2.5(D-d), (D-kel)/3 oF D/2 (see Clause 8.6.2.3)
Ap = total area enclosed by ouside perimeter of concrete section
(see Clause 8.2.1.2)
Aw = area of concrete within the tensile zone (mm’) at ultimate
(see Clause 16.4.2)
As = gross cross-sectional area of a member
Ave = the net bearing area of the head (see Clause 13.1.4)
An = an arca enclosed by the median lines of the walls of a single cell
(see Clause 8.3.3)
Aa = area enclosed by centre-line of exterior closed transverse torsion
reinforcement, including area of holes (if any) (see Clause 8.2.5.6)
Ay cross-sectional arca of prestressing steel
An cross-sectional area of the tendons in the zone that will be tensile under
ultumate load conditions
wow standards org.au © Standards Australia‘Accessed by SWINBURNE UNIVERSITY OF TECHNOLOGY on 27 Sep 2018 (Document currency not guaranteed when pated)
AS 3600-2018
Symbot
A
Ay
Aw
da
Ay
Avene
Aww
Aw
Au win
Ay
© Standards Austraia
Defi
cross-sectional area of reinforcement (see Clauses 3.4.3.2 and 13.2.2); or
cross-sectional area of a single anchored bar of diameter dy
(see Clause 13.1.2.3)
cross-sectional area of compressive reinforcement
area of fully anchored reinforcement crossing the interface
cross-sectional area of steel bar (tendon, wire) (see Clause 5.2.1)
area of reinforcement in the ith direction crossing a strut
(see Clause 7.2.4)
cross-sectional area of longitudinal tensile reinforcement; or
cross-sectional area of reinforcement in the zone that would be in tension
under the design loads if the effects of prestress and axial loads are
ignored
cross-sectional area of shear reinforcement
cross-sectional area of minimum shear reinforcement
cross-sectional area of the bar forming a closed fitment,
cross-sectional area of a transverse bar along a development or lap length
(see Clause 13.1.2.3)
cross-sectional area of the minimum transverse reinforeement along the
development length (see Clause 13.1.2.3)
a reference area taken as Ay ~ 15 600 mn (see Clause 16.4.2)
area enclosed by shear flow path, including any area of holes therein
(see Clause 8.2.1.2)
a bearing area (see Clause 12.6)
largest area of the supporting surface that is geometrically similar to and
concentric with A, (see Clause 12.6)
a distance; or
shear span, equal to the distance between the centroids of a
and a support reaction in a structure (see Clause 7.2.4); or
pplied toad
perpendicular distance from the nearer support to the section under
consideration (see Clause 9.6); of
dimension of the critical shear perimeter measured parallel to the
direction of M! [see Figure 9.3(B)]
axis distance of steel bar (tendon, wire) “i” from the nearest exposed
surface (see Clause 5.2.1)
average axis distance (see Clause 5.2.1)
axis distance (see Clause 5.2.2)
Jength of a support in the direction of the span (see Clause 6.1.4.4)
wow standards org.2u‘Accessed by SWINBURNE UNIVERSITY OF TECHNOLOGY on 27 Sep 2019 (Document currency not guaranteed when pred)
1” AS 3600:2018
Symbol Definition
6 ® width of a rectangular cross-section or member; or
= width of beam at the centroid of the bottom reinforcement
(see Clause 5.4.1); or
= width of ribs [see Table $.5.2(C) and Table 5.5.2(D)|; oF
wall thickness (see Table 5.7.2)
be = core dimension measured between the centre-lines of the outermost
fitments measured across the width of the section (see Clause 10.7.3.3)
ber = effective width of a compression face or flange of a member
be = width of the shear plane (see Clause 8.4.3)
b = size of rectangular, or equivalent rectangular column, capital, or bracket,
measured in the direction of the span for which moments are being
determined (sce Clause 14.5.3.2)
bs = dimension of an opening (see Clause 9.3.1.2 and 9.3.1.5)
b = size of rectangular, or equivalent rectangular column, capital, or bracket,
measured transverse to the direction of the span for which moments are
being determined (see Clause 14.5.3.2)
by effective width of a web for shear (see Clause 8.2.6)
be = awidth of the web; or
= minimum thickness of the wall of a hollow section (see Clause 8.3.3)
ety = cover (o reinforcing steel or tendons
ca ~ a dimension (in millimetres) corresponding to the smaller of the concrete
cover to a bar developing stress and half the clear distance to the next
parallel bar developing stress, as shown in Figure 13.1.2.2
D = overall depth of a cross-section in the plane of bending; or
depth or breadth of the symmetrical prism as appropriate
(see Clause 12.5.6)
Dy ~ fatigue damage factor
Dy = overall depth of a spandrel beam
De = smaller column cross-sectional dimension if rectangular, or the column
diameter if circular (see Table 5.6.3, Table 5.6.4 and Clause 10.7.4.3)
a overall depth of a slab or drop panel
= the member depth at the theoretical cut-off point or debonding point
(see Clause 8.1.1.1)
a = effective depth of a cross-section in the plane of bending
a = nominal diameter of a bar, wire or tendon
d. = depth of the idealized strut (see Clause 7.2.4); or
core dimension measured between the centre-lines of the outermost
filments measured through the depth of the section (see Clause 10.7.3.3)
ds ~ diameter of a prestressing duct (see Clause 8.2.6)
a = diameter of the bar forming the tie (see Paragraph C4.2.2, Appendix C)
www slandards org au © Standards Australia‘Accessed by SWINBURNE UNIVERSITY OF TECHNOLOGY on 27 Sep 2019 (Document currency not guaranteed when parted)
AS 3600:2018,
Symbol
te
4,
d
lor
,
a.
dhe
dy
fis
Kis
Sas
© Standards Australia.
Definiti
‘maximum nominal aggregate size (see Clause 8.2.4.2)
mandrel pin diameter for bending reinforcement
distance from the extreme compressive fibre of the conerete to the
centroid of the outermost layer of tensile reinforcement or tendons (not
less than 0.8D for prestressed concrete members)
mean value of dy, averaged around the critical shear perimeter
distance from the extreme compressive fibre of the concrete to the
centroid of the tendons in that zone, which will be tensile under ultimate
strength conditions
overall dimension measured between centre-lines of the outermost
fitments (see Clause 10.7.3.3)
distance from the extreme compressive fibre of the concrete to the
centroid of compressive reinforcement (see Clause 8.1.7)
the effective shear depth of the member calculated in accordance with
Clause 8.2.1.9
electrical conductivity (see Clause 4.8.2)
mean value of the modulus of elasticity of concrete at 28 days
mean value of the modulus of elasticity of concrete at the appropriate age,
determined in accordance with Clause 3.1.2
design action effect (see Clauses 2.2.2 to 2.2.6)
modulus of elasticity of tendons, determined in accordance with
Clause 3.3.2
modulus of elasticity of reinfarcement, determined in accordance with
Clause 3.2.2
eccentricity of prestressing force or load; or
the base of Napierian logarithms
an additional eccentricity (see Clause 11.5.1)
total vertical component of the external load carried through the shear
span (see Clause 12.2.1)
uniformly distributed design load, factored for strength or serviceability,
as appropriate
effective design service load per unit length or area, used in serviceability
design
oad recorded at CMOD, (see Figure 16.3.3.8)
characteristic residual tensile strength of concrete (at 28 days) at a Crack
Opening Displacement (COD) of 0.5 mm
characteristic residual tensile strength of a concrete (at 28 days) at a
Crack Opening Displacement (COD) of 1.5 mm
mean values of the tensile strength at Crack Opening Displacement
(COD) of 0.5 mm.
one standards.org 20‘Accessed by SWINBURNE UNIVERSITY OF TECHNOLOGY on 27 Sep 2019 (Document currency not guaranteed when pind)
Symbol
Sism
Seow
Son
Seni
Se
Sos
Sow
Sec
te
Soo
fo
i
Seow
te
fo
Sot
fin
Sram
Seam
farm
f
f
tee
Se
wow standards org.au
2 AS 3600:2018
Definition
mean values of the tensile strength at Crack Opening Displacement
(COD) of 1.5 mm
compressive strength for fatigue effects
mean value of cylinder strength (see Clause 3.1.1.2)
mean value of the in situ compressive strength of concrete at the relevant
age (see Clause 3.1.1.2 and Table 3.1.2)
uniaxial tensile strength of concrete (see Clause 3.1.1.3)
measured flexural tensile strength of concrete (sce Clause 3.1.1.3)
measured splitting tensile strength of concrete (see Clause 3.1.1.3)
concrete shear strength (see Clause 9.2.4)
characteristic minimum breaking strength (see Clause 3.3.1)
the stress in prestressing tendons when strain in the surrounding concrete
is zero (see Clause 8.2.4.2.1)
yield strength of tendons determined in accordance with Clause 3.3.1
average confining pressure on the core cross-section taken at the level of
the fitments (see Clause 10.7.3.3)
effective confining pressure applied to the core of a column
(see Clause 10.7.3.3)
stress in reinforcement in the ith direction crossing a strut
characteristic yield strength of reinforcement (referred to as Re in
ASINZS 4671), determined in accordance with Clause 3.2.1
characteristic yield strength of reinforcement used as fitments
mean flexural tensile strength corresponding to the limit of
proportionality. determined in accordance with Clause 16.3.3.8 with Fx
substituted by
mean residual flexural tensile strength corresponding to 2 CMOD of,
0.5 mm, determined in accordance with Clause 16.3.3.7
= mean residual flexural tensile strengths corresponding to a CMOD of
1.5 mm, determined in accordance with Clause 16.3.3.7
mean residual flexural tensile strength corresponding to a CMOD of
2.5 mm, determined in accordance with Clause 16.3.3.7
characteristic compressive (cylinder) strength of concrete at 28 days
characteristic compressive strength of the concrete in the column
(sce Clause 10.8)
effective compressive strength of the conerete in the joint
(see Clause 10.8)
is the characteristic strength of concrete at transfer (see Clause 8.1.6.2)
characteristic compressive strength of the conerete in the slab or beams
(see Clause 10.8)
characteristic uniaxial tensile strength of conercte (see Clause 3.1.1.3)
© Standards Australia[Accessed by SWINBURNE UNIVERSITY OF TECHNOLOGY on 27 Sep 2019 [Docunent currency not guaranteed when printed)
AS 3600:2018
Symbol
Sos
Ig
de
Tetons
h
J
© Standards Australia
Definition.
characteristic flexural tensile strength of concrele at 28 days
(sce Clause 3.1.1.3)
the characteristic residual tensile strength of SFRC corresponding COD w:
(see Clause 16.4.4.2.1)
permanent action (dead load)
dead load, per unit length ot area
permanent distributed load normal to the shear interface per unit length,
newtons per millimetre (N/mm) (see Clause 8.4.3)
floor-to-floor unsupported height of wall
effective height of a wall
overall depth of a joint (see Clause 10.8)
flange thickness of a ribbed slab
distance between tip of the notch and top of cross section in millimetres
(see Clause 16.3.7)
second moment of area of the uncracked concrete cross-section about the
centroidal axis,
second moment of area of @ column
second moment of area of a cracked section with the reinforcement
transformed to an equivalent area of concrete
an effective second moment of area (see Clause 8.5.3 and
Clause 16.4.7.3.2)
maximum effective second moment of area (see Clause 8.5.3)
second moment of area of a flexural member
a torsional modulus
time after prestressing, in days (see Clause 3.3.4.3)
a factor that accounts for the weighted average effectiveness of transverse
reinforcement in controlling potential splitting cracks along a
development or lap splice length (see Clause 13.1.2.3)
fibre orientation casting bias factor and is taken as 0.64
(see Clause 16.4.4.2.1)
a coeff
, ratio or factor used with and without numerical subscripts
coefficient that accounts for the bond properties of the bonded
reinforcement (sce Clause 8.6.2.3)
4 coefficient that accounts for the longitudinal strain distribution
(see Clause 8.6.2.3)
the three-dimensional orientation factor (see Clause C2)
three-dimensional orientation factor (see Clause 16.3.3.4)
cohesion coefficient (see Clause 8.4.3)
factor used in serviceability design to take account of the long-term
effects of creep and shrinkage
wow standards.org au‘Accessed by SWINBURNE UNIVERSITY OF TECHNOLOGY on 27 Sep 2019 (Document currency not guaranteed when printed)
‘Symbol
kd
ke
he
ky
hy
dis
Lo
www standards org au
2 AS 3600:2018
Definition
the depth of the neutral axis on the cracked section (see Clause 8.6.2.3)
a factor to reduce the allowable fatigue stress range in reinforcement at
the location of a bend radius d/2.ki = 0.35 +0.026 (dice) 40 M
consideration being given to the fact that this value has a range of £20%:
(b) determined by test in accordance with AS 1012.17; and
(©) for standard strength grades at 28 days determined from Table 3.1.2.
TABLE 3.1.2
CONCRETE PROPERTIES AT 28 DAYS
EG wo] sf 2 ] | so % | 100
fen (MP8) 25 3h 2 as | 59 | oo
fuses) | 2] | 3) | 53 | oe | 2)
F.«mPay | 24000 | 26700 | 30100 | 32400 | 34800 | 37400 | 39600 42200
3.1.3, Density
The density of concrete (p) shall be determined by test in accordance with cither
AS 1012.12.1 of AS 1012.12.2,
Nom
E: For normal-weight concrete the density may be taken as 2400 kg/m"
3.1.4 Stress-steain curves
The stress-strain curve for concrete shall be either—
(a) asstimed to be of curvilinear form defined by recognized simplified equations; or
(b) determined from test data
For design purposes, the shape of the in situ uniaxial compressive stress-strain curve shall
bbe modified so that the maximum stress is 0.9 f"
3
5. Poisson’s ratio
Poisson’s ratio for concrete (¥) shall be either —
(a) taken as equal to 0.2; oF
{b) determined by test in accordance with AS 1012.17.
3.1.6 Coefficient of thermal expansion
The coefficient of thermal expansion of concrete shall be either—
(2) taken as equal to 10 x 10°*/°C, consideration being given to the fact that this value
has a range of 420%; or
(b) determined from test data.
wine standards org au © Standards Australia‘Accessed by SWINBURNE UNIVERSITY OF TECHNOLOGY on 27 Sep 2019 (Doctment currency not guaranteed when printed)
AS 3600:2018 a
AL
at}
© Standards Australia
3.1.7 Shrinkage
3
‘The design shrinkage strain of concrete (4) shall be determined.
1 Calculation of design shrinkage strain
(a) from measurements on similar local concrete;
(b) by tests after eight weeks of drying modified for long-term value, in accordance with
AS 1012.13; or
(©) by calculation in accordance with Clause 3.1.7.2,
3.
7.2. Design shrinkage strain
When the design shrinkage strain of concrete (c,) is to be calculated, it shall be determined
as the sum of the chemical (autogenous) shrinkage strain (éqe) and the drying shrinkage
strain (4) —
ret Bont 3.17.20)
“The autogenous shrinkage strain shall be taken as
bow =the * (110%) 3.1.72)
where 1 is the time (in days) after setting and ¢,.. is the final autogenous shrinkage strain
given by—
50 MPa #%, =(0.07/; -0.5)x 50x10
3.1.7.2(3)
For; >SOMPa 42, =(0.08/’~1.0) x 50 «10%
‘AC any time £ (in days) alter the commencement of drying, the drying shrinkage strain shall
be taken as—
Ft A Keon 3.1.7.2(4)
and fy is obtained from Figure 3.1.7.2 and ky is equal to 0.7 for an arid environment, 0.65
for an interior envionment, 0.6 for a temperate inland environment and 0.5 for a tropical or
near-coastal or coastal environment.
The basic drying shrinkage strain (cea) is given by—
Beas =(0.9-0.005 2) 6.45 3..7.2(8)
where @2y5 =800%10" or determined by testing.
NOTE: Conerete exposed to early drying undergoes shrinkage due to capillary suction. This can
resull in cracking and poor service performance, particularly of exposed slabs. The amount of
shrinkage from suction depends on the ambient conditions and the concrete mix, and can exceed
the combined shrinkage from other causes, Therefore, it is important to prevent excessive drying
of concrete between the commencement of casting and the application of curing at the completion,
of finishing,
Consideration shall be given to the fact that c, has a range of +30%.
Typical final design shrinkage strains after 30 years are found in Table 3.1.7.2.