MFM 10-1
Mobile, battery operated sheath fault
location system up to ± 10 kV DC
                                                           	 Testing, prelocation and pinpointing
                                                              of sheath faults
                                                           	 Audio frequency option with 8.44 kHz
                                                           	 High current of up to 750 mA
                                                           	 Only one HV connection cable
                                                           	 Automatic measurement and protocolling
                                                           	 Safe operation via connection box
                                                           	 In line with DIN EN 50191, VDE 0104 and BGI 891
DESCRIPTION
The MFM 10-1’s intuitive menu-driven operation and         bi-polar function ensures that external thermoelectric
automatic measurement and evaluation system enables        and galvanic influences are eliminated. A multi-section
cable sheaths to be tested and sheath faults to be pre-    facility permits the entry of cable segments with different
located and pinpointed as simply as possible. Data is      parameters. Difficult cable faults can be “burned” thanks to
entered using the proven Megger rotary encoder principle   the available high current of up to 750 mA.
and is supported by a touch screen.
                                                           MFM 10-1 can also use its integrated protocolling feature
The very powerful 10 kV DC source with positive and        with the approved MeggerBook RE software to easily
negative polarity allows HV cables to be tested. The       generate test reports.
Connection plan
                                                                                                              MFM 10-1
                                                                                               Mobile, battery operated
                                                                           sheath fault location system up to ± 10 kV DC
ALL FEATURES AT A GLANCE                                                TECHNICAL DATA*
	 Solid IP53 PELI trolley case – easy handling                         Functions	                  Testing, prelocation and pinpointing,
                                                                        	                           burning, direct resistance measurement,
	 Wide range input for all supply voltages                             	                           voltage and current limiter,
	 Powerful rechargeable battery                                        	                           quick event/transient recognition
                                                                        Display	                    5.7’’ 320 x 240; LCD, LED backlight
	 Improved prelocation with voltage drop method                        User Interface	             Rotary encoder & touch screen
	 Highest accuracy by bi-polar measurement                             Output voltage	             0 … 10 kV DC, bipolar
                                                                        Output current	             750 mA @ 0,4 kV,
	 Independent from the resistance of supplementary wires and test      	                           200 mA @ 0,4 … 1,5 kV
   leads                                                                	                           60 mA @ 5 kV, 30 mA @ 10 kV
	 Very fast and fully automatic measurement                            Pinpointing	                0 … 10 kV DC pulsed
                                                                        Pulse rates	                0,5:1; 1:2; 1,5:0,5; 1,5:3,5
	 Detection, storage and indication of fast events                     	                           4.8 Hz for the use with A-Frame
	 Protocolling by MeggerBook RE Software                               Accuracy	                   ± 0,1% for the fault location
                                                                        	                           relative to the cable length
	 Burning                                                              Audio frequency (option)	   8,44 kHz, 15 W
	 Slim HV connector and just one HV cable                              Protocolling	               MeggerBook RE Software via USB stick
                                                                        Mains Supply	               88 ... 264 V, 50 … 60 Hz, 800 VA
	 Fault locating of high-resistive faults inside cables                Battery	                    NIMH, 340 Wh, for all operations
	 Integrated discharge up to 10 μF                                     DC supply	                  12 V … 24 V DC / charge only
                                                                        Max. discharge capacity	    10 µF
	 Graphical display of voltage and current                             Operation conditions	       - 25 °C … + 55 °C, 93 % rel. humidity
                                                                        Dimensions	                 500 x 457 x 305 mm
	 Very fast pulse rate of 0.5:1 in connection with the ESG NT
                                                                        Weight	                     25 kg including cable
                                                                        Protection class	           IP 53, with lid closed
                                                            
                                                            Emergency off (button)          
                                                                                            Rotary encoder
                   
                   Touchscreen
                                                                                                            
                                                                                                            Connector for ext.
                                                                                                                safety equipment
                                                                                                          
                                                                                                          Fused mains connector
                           MFM 10-1
                           Mobile, battery operated sheath fault                                             
                                                                                                             Ground connector
                           location system up to ± 10 kV DC
                                                                  
                                                                  Mains switch and                   
                                                                                                     HV-Cable connector
                                                                     HV control switches
           
           Charger plug
                                          
                                          USB connector
* We reserve the right to make technical changes.
                                                                                                                 MFM 10-1
                                                                                                  Mobile, battery operated
                                                                              sheath fault location system up to ± 10 kV DC
                                                 ORDERING INFORMATION
 Sets:                            Description                                                                                    Order No.
 MFM10-1 Standard set             consisting of: MFM10-1 sheath fault locator, USB stick with EasyProt software for                1012572
                                  data transfer and test report generation, KST10 Velcro bag, VL MFM10 cable set
                                  (mains lead EU/UK/US, HV test lead 4 m, ground lead 5 m, crocodile clamps green/
                                  yellow blue, measuring lead blue, automotive adapter)
 MFM10-1 audio frequency set      consisting of: MFM10-1 sheath fault locator with audio frequency generator                       1012573
                                  function, USB stick with EasyProt software for data transfer and test report
                                  generation, KST10 Velcro bag, VL MFM10 cable set (mains lead EU/UK/US, HV test
                                  lead 4 m, ground lead 5 m, crocodile clamps green/yellow blue, measuring lead
                                  blue, automotive adapter)
 Test leads (optional):
 HSK_36_5                         HV test lead 5 m                                                                          90035172-001
 HSK_36_10                        HV test lead 10 m                                                                        118307484-001
 HSK_36_15                        HV test lead 15 m                                                                             2003858-001
 HSK_36_20                        HV test lead 20 m                                                                             2003859-001
 Accessories (optional):
 External emergency switchbox                                                                                                      2010012
 Connection cable 5 m for                                                                                                        820003129
 external emergency switchbox
 HV connection set for large                                                                                                     118308004
 terminals
     19“ version for vehicle                                                    ESG NT earth fault probe for DC step voltage
     Test lead 5, 10, 15, 20 m                                                          HV connection set for large terminals
SALES OFFICE                                 MFM-10-1_DS_EN_V03b
Megger Germany GmbH                          www.megger.com
Dr.-Herbert-Iann-Str. 6                      ISO 9001
D-96148 Baunach
Germany                                      The word ‘Megger’ is a registered trademark.
T	 +49 9544 68-0
E	team.international@megger.com