Thermal Trend
Infrared Thermographic Inspection
Of
Selected Electro-Mechanical Equipment
Provided For
Acme Paper Mill
3/9/2003
Summary:
An Infrared Electrical / Mechanical inspection was preformed on 3/9/2003 for Acme Paper Mill
All of the items inspected are listed in the inventory section of this Thermal Trend report. Any anomalies that were
found at the time of the inspection (if any) are documented in the Problem Detail section of this report with there
appropriate associated data, i.e. Thermograms, Photos, comments, measurements, etc.. And are also listed in the
Prioritized list of problems section, in there order of priority based on the components temperature rise, as compared
to a similar reference component of equal type, loading, and environmental influences, at the time of the inspection.
The final decision as to the repair priority of any and all problems in this report rests on the owners, management,
facilities engineering team. The IR Thermographer assumes no liability directly or indirectly as a result of this
inspection or the decisions made as to establishing the priority and timeline of repair decisions made by the owners,
management, facilities engineering team.
Executive Overview:
# of locations in the database: 412
# of pieces of equipment in the database: 1545
# of problems (open and closed covering all inspections)
all acute and chronic: 604
all acute: 471
all chronic: 131
# of problems, acute and chronic
all closed (covering all inspections): 453
all open (tested or not tested in this inspection): 151
I herby certify that the above project was inspected by myself or under my direction and that the enclosed data is the
direct result of this inspection.
Professional
Thermographers © 2002 ABYSS Corp., All rights reserved. Thermal Trend name and mark
Association are registered trade marks of ABYSS Corp.
YOUR FOOTER HERE
Thermal Trend
Reconciliation Matrix
Site: Acme Paper Mill
Database: Acme Paper Mill.mdb
Insp#19 Insp#18 Insp#17 Insp#16 Insp#15
# of Locations that were tested 307 226 2 320 286
# of Locations that were not-tested 105 186 410 92 126
# of pieces of equipment that were tested 839 794 5 1028 892
# of pieces of equipment that were not-tested 706 751 1540 517 653
Total # of all open problems (tested or not) 155 117 73 97 137
acute & chronic
# of open acute & chronic problems 115 65 0 72 130
documented
# of open acute & chronic problems not 491 541 606 534 476
tested
# of problems closed 38 0 25 80 32
Professional
Thermographers © 2002 ABYSS Corp., All rights reserved. Thermal Trend name and mark
Association are registered trade marks of ABYSS Corp.
YOUR FOOTER HERE
Thermal Trend
Inventory Report
Site: Acme Paper Mill Inspection # 19
Database: Acme Paper Mill.mdb
Open
Problem Status Barcode Location \ Equipment
Text34:
No Tested CTRL SECTION (ABOVE STARTERS) ONLY
Text34:
Yes Tested 10266V HV5,#2 PM 4 REFINER (CTRL SECTION)
Text34:
No Tested 10266B COMPUTER XFER SWITCH FOR OFFICE
Text34:
No Tested 100JXW DAF POLYMER AF DRIVE CAB
Text34:
No Tested 100JXX DAF POLYMER PLC
Text34:
No Tested 102HWM GENIUS BLOCKS G5A-G6A
Text34:
No Tested 10266D ICP5F FED FROM 1-2 8L
Text34:
No Tested 10266G LAB FEED XFER
Text34:
No Tested 10266F MAIN OFFICE FEED XFER SWITCH
Text34:
No Tested 100LNR MCC B1
Text34:
No Tested 10266A B1-14, #2PM FALSE CEILING ROOF SWEEP
Text34:
No Tested 102HWK B1-9, #2 SF SURGE CHST AGIT
Text34:
No Tested 100LNP MCC F1
Text34:
No Tested 100LNQ MCC H1
Text34:
No Tested 102669 H1-14, CLEAR WW TO CLOUDY WW
Text34:
No Tested 102HWH H1-5R, NORTH STARCH COOKER
Text34:
Yes Not Tested 102HWJ H1-6, #2 PM LSFSC PUMP
Text34:
Yes Tested 103HM1 H1-8, STARCH SLURRY TANK AGIT
Text34:
Yes Tested 103HM0 H1-9L, LTG XFMR H1 FEED
Text34:
No Tested 100LNS MCC H-2
Text34:
No Tested 100JXU H2-1, EAST COUCH PIT AGIT #2 PM
Text34:
Yes Tested 102HWL H2-9, #2 S.F. SURGE CHEST TO 2 PM FILLER CHEST PMP
Text34:
No Tested 100LNN MCC H3
Text34:
Yes Tested 10266K H3-2R, # 2 PM PLC ALT PWR
Text34:
No Tested 100LNK MCC- I-1
Text34:
Yes Tested 10, #2 PM TOP LINER M.C. TO #3 & 4 REFINER
Text34:
Yes Tested 102HWP 13,COUCH PIT AGIT W.
Text34:
No Tested 101REA I.1-9 #2 TOP LINER SCREEN
Text34:
No Tested 102HWN I1-7, TOP LINER MACH CHEST
Text34:
No Tested 100LNL MCC- I-2
Text34:
Yes Tested 1038MN 11, #1 HD SURGE CHEST TO #2 PM TOP LINER MACH. CHEST
Text34:
No Tested 10266Q 12L, 2 PM # 3 SPROUT EXCITER
Text34:
No Tested INCOMING LINES
Text34:
No Tested 100LNM MCC Z2
Text34:
Yes Tested 103HLZ 16, SLICE WARMING PUMP
Text34:
No Tested 10266L 5, MAN COOLING NO.1 FAN NORTH
Text34:
No Tested 9, BOTTOM LINER CHEST
Text34:
No Not Tested 10266M MR 10 AC DISCONNECT (OUTSIDE OF RM)
Text34:
No Tested 100JXT NEW FORMANS OFFICE XFR SWITCH
Text34:
No Not Tested 10266W PNL 1CP4F (S'6' PWR FOR # 2 PM PLC)
Text34:
No Not Tested 100JXY PNL 1CP4F-A
Text34:
No Not Tested 100LNT PNL 1CP5F
Text34:
No Tested 10266E STRONG ACID F1-1R, B1-16B XFER
Professional
Thermographers © 2002 ABYSS Corp., All rights reserved. Thermal Trend name and mark 17
Association are registered trade marks of ABYSS Corp.
YOUR FOOTER HERE
Thermal Trend
Thermal Problem Details Report
Site: Acme Paper Mill
Database: Acme Paper Mill.mdb
Problem Status OPEN Severity Code:1
Location: PULP MILL \ DFS1 \ MCC DD-3 Inspection # 19 Problem # 62
Problem Date/Time:3/10/2003 2:18:17 PM
Equipment: DD3-4, CHIP SCREEN AREA MAIN DISC.
Indirect Temp. Measurement:
No
Voltage: 480 Barcode: 101RGM Component Temp:275 @ 72%
Rated Load: 90 Amps Asset ID: Reference Temp:100 @ 72%
GPS:
Temp Rise: 175 @ 72%
IR Image File: TH720062.SIT Photo File: 62.jpg
Component: C phase load side wire lug/fuse clip connection on fused disconnect switch.
Probable Cause:Loose or corroded connection
Recommendation:Clean inspected and retorque wire lug and retension fuse clip
Instances Subreport
300
Insp # Prob # Date Comp Ref. Temp Sev. Load %Load Wind Amb. 250
T e m p T e m p Rise Code Spd. Temp 200
19 62 3/10/2003 275 100 175 1 65 72% 74
150
18 48 10/7/2002 195 96 99 1 60 67% 74
100
16 25 8/30/2002 155 100 55 2 62 69% 74
50
15 10 8/30/2002 133 105 28 3 68 76% 74
0
14 34 8/30/2002 116 100 16 4 60 67% 74
CompTemp RefTemp
10 1 8/30/2002 116 98 18 4 45 50% 60
Problem Status: Not repaired Repair made, but needs IR recheck Closed
Repair assigned to: Repair target date:
Repair assigned by: Date:
Repaired by: Date:
Type of defect found:
Corrective action taken:
Professional
Thermographers © 2002 ABYSS Corp., All rights reserved. Thermal Trend name and mark 62
Association are registered trade marks of ABYSS Corp.
YOUR FOOTER HERE
Thermal Trend
Prioritized List by Temperature Rise
Site: Acme Paper Mill
Inspection #: 19
Database: Acme Paper Mill.mdb
Problem #: 75 Barcode: 100JZS Temp. Rise:300 % Load: N/A
Temp Phase Load
Location: AFL (FIBERLINE) \ MCC ROOM \ VFD QQQ4
Component: 440 LEFT
Equipment: QQQ4-8 THIRD CHIP PUMP Reference: 140 N/A
Component:Front left bolted connection on line reactor. Ambient: 76
Wind Speed:
Rat. Load:
Picture: 75.jpg
IR Filename: TH720075.SIT Severity Code:1
Problem #: 62 Barcode: 101RGM Temp. Rise:175 % Load: 72%
Temp Phase Load
Location: PULP MILL \ DFS1 \ MCC DD-3
Component: 275 C Phase 65
Equipment: DD3-4, CHIP SCREEN AREA MAIN DISC. Reference: 100 A Phase 65
Component:C phase line side wire lug/crimp connection on circuit breaker. Also check B Ambient: 74
phase. Wind Speed:
Rat. Load: 90
Picture: 62.jpg
IR Filename: TH720062.SIT Severity Code:1
Problem #: 104 Barcode: 102688 Temp. Rise:155 % Load: 50%
Temp Phase Load
Location: OFF SITE \ RIVER PUMPS \ SUB W CINDER BLOCK HOUSE \ SILO
PUMPS MCC W4 Component: 250 C Phase 200
Equipment: W4-7 NORTH BARGE PUMP SOFTSTART Reference: 95 A Phase 200
Component:C phase load side wire lug connection or internal problem in "MB MAG" Ambient: 68
(bottom) contactor. Wind Speed:
Rat. Load: 400
Picture: 104.JPG
IR Filename: TT720028.SIT Severity Code:
Problem #: 72 Barcode: Temp. Rise:151 % Load: N/A
Temp Phase Load
Location: COGENERATION \ HSRG
Component: 266 N/A
Equipment: NORTH SIDE OF HRSG Reference: 115 N/A
Component:HSRG HEATING ON WEST END BETWEEN 2ND & 3RD COLUMNS EAST Ambient: 58
FROM WEST. Wind Speed: 0
Rat. Load:
Picture: 72.JPG
IR Filename: Th720072.BMP Severity Code:
Professional
Thermographers © 2002 ABYSS Corp., All rights reserved. Thermal Trend name and mark 1
Association are registered trade marks of ABYSS Corp.
YOUR FOOTER HERE
Thermal Trend
Visual Problem Details Report
Site: Acme Paper Mill
Database: Acme Paper Mill.mdb
Problem Status OPEN Severity Code:3
Location: SECONDARY FIBER \ SF4 MCC RM
Inspection # 19 Problem # 3
Equipment: LTG CONTACTOR LP ZZ3-IR CIRC #36 Problem DateTime: 4/1/2003 10:19:39 AM
Barcode: 103HNL Asset ID: GPS:
Photo File: v2a.jpg
Component: Left phase line & load side crimp connections are burnt & discolored (#36), not running at time of inspection.
Probable Cause:Bad crimp connections
Recommendation:Replace crimp connections.
Instances Subreport
Inspection Problem Date Sev.
Number Code
19 3 4/1/2003 3
Problem Status: Not repaired Repair made, but needs IR recheck Closed
Repair assigned to: Repair target date:
Repair assigned by: Date:
Repaired by: Date:
Type of defect found:
Corrective action taken:
Professional
Thermographers © 2002 ABYSS Corp., All rights reserved. Thermal Trend name and mark 2
Association are registered trade marks of ABYSS Corp.
YOUR FOOTER HERE
Thermal Trend
Visual Problem List
Site: Acme Paper Mill
Inspection #: 19
Database: Acme Paper Mill.mdb
Problem #: 3 Barcode: 103HNL
Severity Code:3
Location:
Equipment: LTG CONTACTOR LP ZZ3-IR CIRC #36
Component:Left phase line & load side crimp connections are burnt & discolored (#36), not
running at time of inspection.
Picture: v2a.jpg
Problem #: 1 Barcode:
Severity Code:1
Location:
Equipment: 480V BREAKER SECTION
Component:Holes in top of cabinet for cables not properly attached @ strain relief (no strain
relief).
Picture: v1.jpg
Problem #: 5 Barcode: 1026CD
Severity Code:4
Location:
Equipment: TRUCK DUMP SUMP PUMP STARTER BOX
Component:Yellow jacket nest inside encloser.
Picture: v7.jpg
Problem #: 4 Barcode: 1026CE
Severity Code:2
Location:
Equipment: TRUCK DUMP LTG XFMR DISCONNECT
Component:Disconnect has come loose from mounting and is hanging by conduit.
Picture: v5.jpg
Professional
Thermographers © 2002 ABYSS Corp., All rights reserved. Thermal Trend name and mark 1
Association are registered trade marks of ABYSS Corp.
YOUR FOOTER HERE
Thermal Trend
Before Verses After Thermal Details Report
Site: Acme Paper Mill
Database: AcmePaperMill.mdb
Problem Status CLOSED Severity Code: 0
Location: 1st FLOOR \ MCC B, F, H, I RM Inspection # 19 Problem # 1
Problem Date/Time: 9/8/2003 7:18:01 AM
Equipment: DIST PNL MD-B1 Indirect Temp. Measurement: No
Voltage: 480 Barcode: 104LKA Component Temp: 78 @ 24%
Rated Load: 200 Amps Asset ID: Reference Temp: 78 @ 24%
GPS: Temp Rise: 0 @ 24%
Before: IR Image File: AAAA0001.sit Photo File: IMG_1456.JPG
After: IR Image File: AAAA0005.sit Photo File: IMG_1456.JPG
Component: A (top) phase load side wire lug connection on circuit breaker for PANEL PDP-1
Type of Defect:
Action Taken:
Instances Subreport
12 0
Insp # Prob # Date Comp Ref. Temp Sev. Load %Load Wind Amb. 10 0
Temp Temp Rise Code Spd. Temp 80
1 1 9/8/2003 98 78 20 4 47 23% 70
60
40
20
0
CompTemp RefTemp
Professional