Operation manual for Main A/C System:
This is the Main menu that appears when power
on.
When pressing main menu ,another POP up
screen will appear like this which contains
1. AHU and compressor control menu
2. Cooling Application menu
3. Heating application menu
4. Humidifier control
5. Alarm list
AHU & Compressor control menu :
1. In this menu we can control AHU fan .And
also we can moniter the status the fan .
2. Condenser start/stop and its status can
be done here
3. Compressor start/stop and status can be
done here.
aa
Cooling Application Menu:
The sensor reads the outdoor/return/supply sir
which can be seen here.
We can know whether the liquid line solenoid valve
is in operation or not by LSV ON/OFF
The cooling set point parameter is: 24deg c
The cooling deviation is: 1 deg c
Heating application Menu:
The sensor reads the outdoor/return/supply sir which
can be seen here.
We can see whether the heater is ON/OFF
condition.
Here it contains another Pop-up screen called
heating parameter setting. This can be set as
follows.
Heating parameter Menu:
It shows return air temperature reading:
The heating parameters can be set as follows:
1.1 First stage heating : 20 deg C
1.2 Second stage heating: 18 deg C
1.3 Third stage heating: 16 deg c
1.4 Heating deviation : 1 deg c
Humidifier control menu:
In this menu we can control humidifier operation
and its status.
Alarm List Menu:
The List of alarms that can be seen is:
1. Condensing fan motor overload
2. Compressor motor overload
3. High discharge pressure
4. AHU fan motor overload
5. Heater overheat