PVC Insulated, PVC Sheathed/Armoured Or Non-Armoured Cables
Application
PVC insulated/PVC sheathed armoured power cables for electricity supply are normally used in free ar, laid direct in
ground, drawn into cable ducts, outdoor and indoor, power stations, industry and distribution board and in subscriber
network where there is a risk of mechanical damage. The cables are suitable for continuous operation at maximum
conductor temperature of 70°C
Specification
PVC insulated, PVC sheathed armoured power cables meets the following cable specifications :
Ms69 Specification for conductors in insulated cables and cords
Ms 138 PVC insulation and sheath of electric cables
M274 PVC insulated cables for electricity supply
Construction
The conductor comprise of circular / sectoral stranded & compacted plain annealed copper wites according to MS 69.
The insulation material consists of a layer of extruded type TH pvc compound as per MS 138.
The core identification is by coloured insulation PVC compound throughout the core length.
For multicore cable, the cores shall be laid up with non-hygroscopic material as the filler and a layer of binder shall be
applied over the laid up cores.
The inner sheath shall consists ofa layer of extruded PVC compound applied over the binder around the laid up cores.
For single core cable, the armouring shall consists of single layer of non-magnetic material such as aluminium wire,
For multicore cable it shall consist of single layer of galvanized steel wite applied helically over the extruded inner sheathing.
‘The outer sheathing shall consist ofa layer of extruded type TMI pyc compound in accordance with MS 138. Special outer
sheathing material such as pve with termite or rodent protection and flame retardant are available upon request.Olympic Cabie
1 Core CU/PVC 450/750V
Nominal Approx. Approx. Test Max. Current Guent_ Volt drop
cross Overall Cable Voltage conductor | ratingbased | =rgbesedon for 3 phase
ee exlosedin
sectional | Diameter Weight
area resistance at
20°C
(mm?) (mm) (kg/km) | (kV/15min) (vk) (Amp) (Amp) (W/A/kmn)
15 3.0 21 25 124 19 16 25.15
36 33 25 7A 26 22 154
42 49 25 461 34 29 9.58
47 68 25 3.08 44 37 6.40
61 14 25 1.83 61 52 381
67 173 25 11s 81 70 239
84 an 25 0.727 92 152
95 351 25 0.524 113 110
Wd 475 25 0.387 138 0.82
128 669 25 0.268 176 057
149 926 25 0.193 213 0.42
16.4 1153 25 0.153 246 035
183 1424 25 0.124 270 0.29
20.4 1781 25 0.0991 305 0.25
23.2 2331 25 0.0754 356 0.21
25.9 2916 25 0.0601 406 0.19
29.1 3714 25 0.0470 481 0.17
324 4744, 25 0.0366 549 0.16
36.0 6069 25 0.0283 629 0.15
40.5 7741 25 0.0221 703 014
1 Core CU/PVC/PVC 300/500V
Nominal | Approx. Approx. Test Max. Current Curent Volt drop
cross- Overall Cable Voltage conductor | ratingbased ©"™ngbastlon for 3 phase
sectional Diameter Weight oc ondipped oor ona
area resistance at | direct at wall/in
20°C 25°C ‘tmunkingat25°C
(mma) (mm) (kg/km) | (kV/15min) | (O/km) (amp) (amp) (V/A/kmn)
15 46 36 20 124 16 4 25.15
25 52 50 20 7A 23 19 154
4 60 n 20 461 30 25 9.58
6 65 94 20 3.08 390 32 6.40
10 79 147 20 1.83 53 43 3.81
16 91 216 20 115 n 57 240
25 11.0 330 20 0.727 94 75 1.52
35 123 423 20 0.524 116 a 1.101 Core CU/PVC/PVC 600/1000V
Nominal Approx. Approx. Test Max. Curent Volt drop
cross- Overall Cable Voltage conductor ratingbased _ for 3 phase
sectional | Diameter Weight Dc onlaidin air
area resistance at intrefoil at
20°C arc
(mma) (mm) (kg/km) | (kV/Smin) —(Q/km) (Amp) (V/A/km)
50 13.6 553 35 0387 145 0.82
70 15.0 734 35 0.268 188 0.57
95 172 1030 35 0.193 230 0.42
120 18.6 1266 35 0.153 268 0.35
150 206 1558 35 0.124 310 0.29
185 22.7 1937 35 0.0991 356 0.25
240 255 2515 35 0.0754 422 0.21
300 28.1 3130 35 0.0601 488 0.19
400 318 3976 35 0.0470 571 0.17
500 35.0 5044 35 0.0366 652 0.16
630 383 6411 35 0.0283 744 O15
800 421 8096 35 0.0221 845 0.14
2 Core CU/PVC/PVC 600/1000V
Nominal Shaped Approx. — Approx. Test Max. Volt drop
cross- Overall Cable Voltage _ conductor forsingle
sectional Diameter | Weight i | phase ac
area
(mm2) (mm) (kg/km) {kV/Smin) | (Q/km) | (Amp) (V/Arkm)
15 Wa 184 35 124 19.5 29
25 122 225 35 741 27 18
4 141 308 35 461 36 u
6 15.2 380 35 3.08 46 73
10 WA 514 35 1.83 63 44
16 19.2 679 35 115 85 28
25 226 997 35 0.727 175
35, 208 969 3S 0.524 138 1.25
50 238 1269 35 0.387 168 0.94
70 26.2 1698 35 0.268 0.65
95 297 2285 35 0.193 0.50
32.2 2806 35 0.153 041
35.6 3420 3S 0.124 0.34
39.1 4233 35 0.0991 0.29
438 5480 35 0.0754 0.24
48.2 6784 35 0.0601 0.21
544 8584 35 0.0470 0.185
CC: COMPACTED CIRCULAR STRANDED
‘SC: SECTORAL STRANDED COMPACTED.3 Core CU/PVC/PVC 600/1000V
Shaped | Approx. Approx. Test ‘Max. Current Volt drop
Overall Cable Voltage conductor "tingbzsedon ratingbasedon| for 3 phase!
Diameter Weight pc | mead ae
resistance at wal/cciing/in| airat XC
20°C eunkinget30C
(mm) kg/km) (KW/Smin) (Qk) (Amp) (Amp) | (W/A/Km)
ng 233, 35 124 15 185 25
286 35 741 20 25 15
35 461 27 34 95
35 3.08 34 43 64
35 1.83 46 60 38
35 115 62 80 24
35 80 15
35 99 Mi
35
35
35
35
35
35
35
35
35
CC: COMPACTED CIRCULAR STRANDED
‘SC: SECTORAL STRANDED COMPACTED.4 Core CU/PVC/PVC 600/1000V
Nominal | Shaped Approx. Approx. Test Max, | Cunent | Gurent | Volt drop
cross- Overall Cable Voltage _ conductor |rating based "=t"ebelon| for 3 phase!
sectional Diameter Weight ondipped roe
area directat ratzoc
30°C
(mm) (mm) (kg/km) (Kv/Smin) (vk) | (Amp) (Amp) (W/A/Krn)
15 27 275 35 A 75 185 25
137 341 35 741 24 25 15
160 470 35 461 32 34 95
174 591 35 3.08 4 64
196 815 35 57 38
22.2 1136 35 76 24
263 1661 35 96 15
264 1728 35 1
306 2303 35
345 3184 35
393 4333 35
42.7 5347 35
475 6559 35
52.2 8175 35
588 10660 35
649 13270 35
16851 35
CC: COMPACTED CIRCULAR STRANDED
‘SC: SECTORAL STRANDED COMPACTED.Olympic Canie
1 Core CU/PVC/AWA/PVC 600/1000V
Nominal Approx. Approx. Test Max. Current Curent Volt drop
cross- Overall Cable Voltage | conductor | ratingbased ratingbased for 3 phase
sectional Diameter Weight bc ‘ondiipped onli inair
area resistanceat_—_directat trefoilat
20°C 30°C 4c
(mm) (mm) (kg/km) (KW/Smin) | (Q/km) (Amp) (Amp) (V/Alkm)
16 159 432 3S 115s 84 79 2.39
25 174 566 3S 0.727 7 107 1st
35 185 668 3S 0.524 145 134 1.09
50 20.2 836 3S 0.387 179 157 0.82
70 216 1057 3S 0.268 225 201 057
95 23.9 1385 35 0.193 269 244 0.42
120 253 1649, 35 0.153 309 282 0.35
150 271 1963 35 0.124 320 339 0.29
185 29.2 2374 35 0.0991 399 370 0.24
240 32.0 3003 3S 0.0754 465 436 0.21
300 353 3738 35 0.0601 515 493 0.18
400 39.4 4685 35 0.0470 575 572 0.16
500 426 5822 35 0.0366 622 636 0.15
630 47.0 7421 35 0.0283 0.14
2 Core CU/PVC/SWA/PVC 600/1000V
Nominal Shaped Approx. Approx. Test Max. Volt drop
cross- Overall Cable Voltage conductor for single
sectional Diameter Weight oc phase a.c
area resistance at
20°C freeairat 30°C
(mm?) (mm) (kg/km) (KV/Smin) (Q/km) (Amp) (Amp) (W/A/km)
15 155 423 35 121 2 22 29
25 163 483 35 741 28 31 18
4 189 707 35 461 38 4 u
6 20.0 818 35 3.08 49 33 73
10 219 998 35 183 67 72 44
16 247 1358 35 115 29 97 28
25 28.3 1800 35 0.727 18 128 175
35 263 1716 35 0.524 145 157 1.25
50 295 2125 35 0387 175 190 0.94
70 32.1 2664 35 0.268 222 241 0.65
95 36.4 3611 35 0.193 269 291 0.50
393 4288 35 0.153 310 336 0.41
427 5048 35 0.124 356 386 0.34
474 6446 35 0.0991 405 439 0.29
523 7983 35 0.0754 476 516 0.24
56.9 9543 35 0.0601 347 592 0.21
635 11736 35 0.0470 621 683 0.185
CC:COMPACTED CIRCULAR STRANDED SC: SECTORAL STRANDED COMPACTED3 Core CU/PVC/SWA/PVC 600/1000V
Nominal Shaped Approx. — Approx. Test Max. Current Curent Volt drop.
cross Overall Cable Voltage conductor | ratingbased ingbasedon for 3 phase
sectional Diameter | Weight ondipped |?"
area z directat —/reeairat
30°C 30°C
(mm) (mm) (kg/km) = (kV/Smin) | (O/km) (Amp) (Amp) (V/A/km)
15 160 a7 35 124 18 19 25
176 637 35 7A 25 26 15
196 800 35 461 33 35 95
20.9 35 3.08 a2 45 64
236 35 58 62 38
258 35 7 83 24
298 35
294 35
33.1 35
376 3S
4138 35
448 35
35
35
35
35
35
CC COMPACTED CIRCULAR STRANDED
‘SC : SECTORAL STRANDED COMPACTED.4 Core CU/PVC/SWA/PVC 600/1000V
Shaped Approx. Approx. Test Max. Curent Gurent | Volt drop
Overall Cable Voltage conductor rating based "t”9besedon) for 3 phase
Diameter Weight DC oncipped | *Proms
resistanceat| directat | / freairat
20°C 30°C 30
(mm) (kg/km) (KW/Smin) | (Q/krm) (Amp) (Amp)_|(V/A/km)
75 594 35 121 18 19 25
185 688 35 7A 25 26 15
208 35 461 33 35 95
22.2 35 3.08 a2 4s 64
25.1 35 1.83 58 62 38
27 35 115 7 83 24
32.2 35 110
323 3S
379 35
416 35
416 35
514 35
562 3S
613 35
3S
35
35
CC: COMPACTED CIRCULAR STRANDED
‘SC: SECTORAL STRANDED COMPACTED.Copper Low Voliage Capie
Plain Annealed Copper
Galvanized Stee!
Round Wire
Wrapping Tape ~~
Black PVC
600/1000V XLPE Insulated, PVC Sheathed/Armoured Or Non-Armoured Cables
Application
XLPE insulated, PVC sheathed/armoured power or non armoured cables for electricity supply are commonly installed in
free air, laid direct in ground, drawn in cable ducts, outdoor and indoors, power stations, industry and distribution boards
and in subscriber networks where there isa risk of mechanical damage. The cables are suitable for continuous operation at
‘amaximum conductor temperature of 90°C
Specification
XLPE insulated, PVC sheathed armoured power cables meets the following cable specifications:
1EC60228 Conductors of insulated cables
1EC.60502-1 Power cables with extruded insulation and their accessories for rated voltages from 1kV (Um = 1.2k¥) up
10 30kV (Um= 36KV) - Part 1: Cables for rated voltages of 1KV (Um =1.2kV) and 3kV (Um = 3.6kV)
8S 2627 Wrought aluminium for electrical purposes
Construction
The conductor comprise of sectoral/circular stranded & compacted plain annealed copper wire according to IEC 60228.
The insulation material consists of a layer of extruded xlpe compound as per IEC 60502-1
The core identification is by coloured insulation XLPE compound throughout the core length.
For multicore cable, the insulated cores shall be laid up with non-hygroscopic material as the filler and a layer of binder
shall be applied over the laid up cores.
The inner sheath shall consists of a layer of extruded PVC compound applied over the binder around the laid up cores.
For single core cable, the armouring shall consists of single ayer of non-magnetic material such as aluminium wire.
For multicore cable it shall consist of single layer of galvanized steel wire applied helically over the extruded inner sheathing,
‘The outer sheathing shall consist of a layer of extruded PVC type ST2 compound in accordance with IEC 60502-1. Special
‘outer sheathing material such as pyc with termite or rodent protection and flame retardant are available upon request.1 Core CU/XLPE/PVC 600/1000V
Nominal Approx. | Approx. Test Max. Current Curent.—_-Volt drop
cross- Overall Cable Voltage conductor ratingbased_ratingbased for 3 phase
sectional meter | Weight Dc ondipped onli inair
area resistanceat directa _trefoil at
20°C 30°C 40°C
(mm) (mm) (kg/km) (kV/Smin) (Qk) (amp) (Amp) (W/A/km)
15 58 a7 35 124 2B : 26.83
25 62 59 35 71 31 : 16.43
4 68 7 35 461 41 : 10.22
6 73 100 35 3.08 54 - 683
10 83 144 35 1.83 74 : 4.06
16 89 204 35 115 99 - 255
25 106 305 35 0.727 130 126 1.61
35 Wz 304 35 0.524 161 156 7
50 13.4 517 35 0.387 209 190 0.87
70 15.0 721 35 0.268 268 246 061
95 169 977 35 0.193, 326 300 0.45
120 186 1215 35 0.153, 379 350 0.37
150 20.7 1497 35 o.124 436 405 031
185 23.0 1867 35 0.0991 500 465 0.26
240 258 2424 35 0.0754 590 551 0.22
300 285 3016 35 0.0601 681 638 0.19
400 319 3831 35 0.0470 793 746 0.17
500 354 4880 35 0.0366 904 852 0.16
630 396 6261 35 0.0283 1033 973 015
800 443 7982 35 0.0221 1179 1105 0.145
1000 48.7 9980 35 0.0176 1323 1228, 0142 core CU/XLPE/PVC 600/1000V
Nominal Shaped Approx. Approx. Test Max, | Gnertiaing Cunentrating Volt drop
cross- ‘Overall Cable Voltage | conductor an) basedona for single
sectional Diameter | Weight _Dc al Peer ere)
area resistance at wal /edingin fecarenorc 3
20°C tunkingat 00
(mm) (mm) | (kg/km) | (KW/Smin) | (Qvkm) (Amp) (Amp) (V/A)
16 cc 180 611 35 15 a1 105 290
25 cc 24 908 35 0.727 19 136 1.90
35 sc 196 902 35 0.524 146 168 135
50 sc 22 1170 35 0.387 175 205 1.00
70 sc 25.0 1603, 35 0.268 21 263 0.69
95 sc 25 2125 35 0.193 265 320 052
120 sc 304 2645 35 0.153 305 373 0.42
150 sc 338 3229 35 0.124 334 430 035
185 sc 375 4026 35 0.0991 384 493 0.29
240 sc a6 5189 35 00754459 583 024
300 sc 45.6 6423 35 0.0601 532 674 0.21
400 sc 518 8160 35 0.0470 625, 787 019
CC :COMPACTED CIRCULAR STRANDED
‘SC: SECTORAL STRANDED COMPACTED3 Core CU/XLPE/PVC 600/1000V
Nominal | Shaped | Approx. | Approx. Test Max. Curent Currentrating Volt drop
cross- Overall | Cable Voltage conductor ratingbased basedona for 3 phase
sectional Diameter | Weight DC —_ondlipped | Perforated
area resistance at direct at
20°C 30°C
(mm?) (mm) (kg/km) (KV/Smin) — (Q/km) (Amp) (Amp) (V/A/km)
cabletray /
freeairat 40°C
19.0 826 35 11s 96 a1 255
228 1213 35 0.727 19 116 1.65
224 1275 35 0.524 147 144 115
254 1666 35 0.387 179 175 0.87
29.0 2320 35 0.268 229 224 0.60
324 3110 35 0.193 278 271 0.45
358 3878 35 0.153 322 315 0.37
398 4740 35 0.124 371 363 030
441 5914 35 0.0991 424. a5, 0.26
49.1 7641 35 0.0754 500 490 0.21
54.1 9499 35 0.0601 576 565 0.185
614 12075 35 0.0470 667 674 0.165
16
25
35
50
70
95
120
150
185
240
300
400
BAASAABBAABAR
4 Core CU/XLPE/PVC 600/1000V
Nominal Shaped | Approx. Approx. Test Max. | Curent Gumentrating Volt drop
cross- Overall Cable Voltage conductor ratingbased basedone for 3 phase
sectional Diameter Weight pc ‘onclipped Perforated
area resistance at directat
20°C 30°C
(me) (mm) (kg/km) (KW/Smin) | (Q/kmm) (Amp) (Amp) (V/A)
eabletay /
free airat arc
16 20.7 1023 35 1.15 96 91 255
25 249 1511 35 0.727 ug 16 165
35 25.0 1605 35 0.524 147 144 115
50 287 2128 35 0.387 179 175 0.87
70 328 2986 35 0.268 229 224 0.60
95 36.7 4036 35 0.193 278 a 0.45
120 407 5065 35 0.153 322 315 037
150 453 6200 35 0.124 371 363 030
185 50.3 7772 35 0.0991 424 as 0.26
240 56.1 10106 35 0.0754 500 490 0.21
300 618 12579 35 0.0601 576 565 0.185
400 70.3 16036 35 0.0470 667 674 0.165
(CC: COMPACTED CIRCULAR STRANDED
SC: SECTORAL STRANDED COMPACTED1 Core CU/XLPE/AWA/PVC 600/1000V
Test
Voltage
Nominal
cross-
sectional
area
Approx.
Cable
Weight
Approx.
Overall
Diameter
(mma) (mm) (kv/5min)
(kg/km)
conductor
resistance at
(O/krn)
Max. Current
rating based
onclipped
directat
30°C
(Amp)
Current
rating based
on id in air
trefoil at
40C
(Amp)
oc
20°C
Volt drop
for 3 phase
(W/Asken)
16
25
35
50
70
95
120
150
185
240
300
400
500
153
168
179
194
21.0
22.9
24.5
26.3
28.4
30.8
33.9
38.2
4
46.0
401
521
632
782
1009
1306
1572
1874
2279
2861
3560
4503
5606
7193
35
35
35
35
35
35
35
35
35
35
35
35
35
35
0.
2 Core CU/XLPE/SWA/PVC 600/1000V
Test
Voltage
Nominal
cross-
sectional
area
Shaped | Approx.
Overall
meter
Approx.
Cable
Weight
(mma) (mm) (ka/kmn)__ (kV/Smin)
0.727
0.524
0.387
0.268
0.193
0.153
0.124
0.0991
0.0754
0.0601
0.0366
0.0283
is 99
130
161
220
277
333
383
437
496
579
662
77
791
861
Ww
160
202
259
315
366
421
481
569
.0470
Max. Curent Cnet
conductor rating based "atnabasedon
DC | ondipped |_2 peforated
resistanceat | directat
20°C 30°C
(Afkmm) (Amp)
255
1.61
1.16
0.87
061
0.45
0.36
0.30
0.25
0.21
0.18
0.16
0.15
014
Volt drop
for single
phase
ac
(V/Asken)
16
25
35
50
70
95
120
150
185
240
300
400
235
26.9
25.1
277
307
334
377
a
446
503
543
609
1237
1660
1595
1961
2499
3127
4080
4788
5756
7879
9040
1167
35
35
35
35
35
35
35
35
3S
3S
35
35
CC: COMPACTED CIRCULAR STRANDED
‘SC: SECTORAL STRANDED COMPACTED.
115
0.727
0.524
0.387
0.268
0.193
0.153
0.124
0.0991
0.0754
0.0601
0.0470
110
146
180
219
279
338
392
451
515
607
698
787
2.90
1.90
135
1.00
0.69
0.52
0.42
0.35
0.29
0.24
0.21
0.193 Core CU/XLPE/SWA/PVC 600/1000V
Nominal Shaped Approx. Approx. Test Max. Current —Currentrating Volt drop
cross- Overall Cable Voltage conductor ratingbased basedona for 3 phase
sectional Diameter Weight Dc ondlipped a)
area resitanceat directa gaye seagic
20°C 30°C
(mm2) (mm) (kg/km) | (kV/Smin) — (Q/km) (Amp) (Amp) (V/A/km)
16 245 1465 3S 115 99 90 2.55
25 285 1988 35 0.727 124 19 1.61
35 279 2084 35 0524 154 147 1.16
50 313 2601 35 0.387 187 179 0.87
70 35.7 3601 35 0.268 238 228 0.61
95 395 35 0.193 289 277 04s
42.9 35 0.153 335 321 0.36
48.1 35 0.124 386 369 030
528 35 0.0991 4a 421 0.25
578 35 0.0754 497 0.21
63.2 35 0.0601 599 571 0.18
705 35 0.0470 662 0.16
4 Core CU/XLPE/SWA/PVC 600/1000V
Nominal Shaped Approx. Approx. Test Max. Curent —Currentrating | Volt drop
cross- Overall © Cable Voltage conductor ratingbased besedona | for 3 phase
sectional meter Weight DC _ ondlipped aoa
area resstanceat directat geo ar aeaore
20°C 30°C
(mma) (mm) (kg/km) (kV/Smin) (Q/km) (Amp) (Amp)_‘|_ (V/A/km)
16 26.2 1490 35 115 94 90 255
25 30.6 1951 35 0.727 124 19 161
35 30.7 2395 35 0.524 154 147 1.16
50 354 3252 35 0.387 187 179 0.87
70 399 4285 35 0.268 238 228 061
95 44.0 5467 35 0.193 289 277 0.45
120 492 7048 3S 0.153 335 321 0.36
150 54.0 3442 35 0.124 386 369 030
185 59.0 10136 3S 0.0991 441 421 0.25
240 65.2 12720 3S 0.0754 520 497 0.21
300 709 15405 35 0.0601 599 371 0.18
400 813 20193 35 0.0470 673 662 0.16
CC:COMPACTED CIRCULAR STRANDED
‘SC: SECTORAL STRANDED COMPACTEDSales & Marketing Offic
PJEXIM SDN BHD
Lot No. H-81-03, Diaman
Commercial Centre,
Jalan PIU 1A/41A, Ara Jaya
47301 Petaling Jaya,
Selangor Darul Ehsan, Malaysia
Tel :603-7804 7211, 78047611
Fax 603-7805 1811
Email: exim@olympic-cablecommy
Olympic Cable
Factory (Malaysia)
‘Qlymplc Cable Company (M) SDN BHD
Lot PT 2126-2131, Jalan PK
‘Taman Perindustrian Krubong,
75250 Melaka, Malaysia
PO. Box 326,
75760 Melaka, Malaysia
Tel :606-337 3088/90
Fax 1606-337 3099
Email: mareclympic-cablecommy
Factory (Vietnam):
OVICables (Vietnam) Co, LTD
t E-AAT-CN & Lot -481-CN,
‘My Phuoc 2 Industrial ark
Ben Cat District
Binh Duong Province
(84) (0650) 3553 683/84
(84) (0650) 3553 685,