Installation Instructions
Model HLIM
Loop Isolator Module
OPERATION              The SIEMENS Model HLIM Loop Isolator Module isolates short circuits on FireFinder-
                       XLS analog loops. By placing devices between HLIMs during installation, a short in
                       the wiring within that group is disconnected from the rest of the loop. The remainder
                       of the devices continue
                       to operate. The HLIM
                                                               FRONT                            BACK
                       operates in both Class A
                       and Class B circuits.
                       A yellow LED flashes                                                IN - LINE 1
                                                                                           IN - LINE 2
                       when a device detects a                    FAULT
                                                                                           OUT - LINE 1
                       short circuit. The HLIM                                             OUT - LINE 2
                       then isolates that part of
                       the loop. When the short
                       is removed, the HLIM
                       automatically restores        Figure 1
                       the loop to normal            The HLIM-1 Loop Isolator Module
                       operation. The HLIM
                       does not have a loop address and therefore does not require address programming
                       nor does it reduce the loop capacity below 252 devices.
                       Remove all system power before installation, first the battery and then the AC.
INSTALLATION           The HLIM is a polarity insensitive module. Refer to Figure 1 for the location of the
                       two input terminals and two output terminals. Line 1 and Line 2 can be either line of
                       the loop.
                       The HLIM may be used in two circuit configurations as follows:
Class B                (See Figure 2) In Class B wiring each HLIM isolates a branch on the circuit. Note that
                       a short on the main branch causes the entire loop to fail. To prevent this, mount the
                       HLIMs at the FireFinder-XLS enclosure and run each branch independently.
                                                                   Siemens Building Technologies
P/N 315-033170-2                                                                      Fire Safety
1. All wiring must comply with
   national and local codes.
2. In order to provide adequate                     LINE 1
   protection, it is recom-         ANALOG LOOP
   mended that you do not
                                                    LINE 2
   install more than 20 devices
   on a single HLIM.
3. Minimum wire gauge is
   18 AWG.
4. The total wire resistance
   (both wires) between HLIMs
   cannot exceed 20 ohms.
5. Do not install more than 15
   HLIMs per DLC loop.
6. All circuits are supervised.
7. Refer to DLC Installation                                 IN    IN      OUT OUT          IN    IN    OUT OUT        IN    IN   OUT OUT
   Instructions, P/N 315-033090
   for the list of compatible
   devices.
8. All terminals are power        Figure 2
   limited.                       HLIM Wiring Diagram - Class B Installation
Class A Single Loop               (See Figure 3) In Class A wiring the HLIMs are wired in series with the loop wiring.
                                  This results in a single continuous loop. If any group in the loop has a short, that
                                  group is lost and a Class A circuit failure results. The FireFinder-XLS displays commu-
                                  nication errors for the devices and a Class A failure for the loop itself.
1. All wiring must comply with
   national and local codes.               INSIDE ENCLOSURE
2. In order to provide adequate
   protection, it is recom-
                                                  OUT OUT IN      IN                 OUT OUT IN    IN             OUT OUT IN      IN
   mended that you do not
                                  TO ANALOG
   install more than 20 devices   LOOP RETURN
   on a single HLIM.                       LINE 2
3. Minimum wire gauge is                   LINE 1
   18 AWG.
4. The total wire resistance
   (both wires) between HLIMs                 LINE 1
   cannot exceed 20 ohms.                     LINE 2
5. Do not install more than 15
   HLIMs per DLC loop.            TO ANALOG
                                  LOOP FEED
6. All circuits are supervised.
                                                  IN   IN OUT OUT                    IN   IN OUT OUT              IN   IN OUT OUT
7. Refer to DLC Installation
   Instructions, P/N 315-033090
   for the list of compatible
   devices.
8. All terminals are power        Figure 3
   limited.                       HLIM Wiring Diagram - Class A Installation (Single Loop)
Siemens Building Technologies                                          2                                                    P/N 315-033170-2
Fire Safety
Mechanical Installation         (See Figure 4)
                                          Use a standard 3 1/2-inch deep, double gang electrical switchbox or a 4-inch
                                           square electrical box that is 2 1/8 inches deep.
                                          Connect the field wiring. Press the HLIM into the box and fasten the
                                           module plate to the box.
                                          Cover the module front plate with the plate supplied and fasten with screws
                                           supplied.
ELECTRICAL RATINGS              Input power:                24 VDC, 1mA max
                                                                                      DOUBLE GANG BOX
                                                                                      3 1/2-INCHES DEEP
                                        4-INCH SQUARE BOX
                                        2 1/8-INCHES DEEP
                                                                                                             SWITCHPLATE
                                                                                                          4-INCHES SQUARE
                                                                                                              (SUPPLIED)
                                                                       SWITCHPLATE
                                                                    4-INCHES SQUARE
                                                                        (SUPPLIED)
                                Figure 4