TRI-FUEL
PORTABLE
              OWNERS MANUAL                                   GENERATORS
               MODELS
               HPS6000HE
               HPS9000E
               HPS12000HE
                                                            HPS 6000HE
                                HPS 9000E
                                                           HPS12000HE
             INSTALLATION, OPERATION,
             and MAINTENANCE INSTRUCTIONS
Downloaded from www.Manualslib.com manuals search engine
        Read and understand all instructions in the manual before starting and
        operating the generator set.
        USING THIS MANUAL                                                     TABLE OF CONTENTS
          Congratulations on your choice of a WINCO HOME                      INTRODUCTION                               i
        POWER generator set. You have selected a high-                        GUIDE TO PRODUCT SAFETY                    1
        quality, precision-engineered generator set designed                  SPECIFICATIONS                             2
        and tested to give you years of satisfactory portable                 Intended Uses                              2
        service.                                                              Restricted Uses                            2
          To get the best performance from your new engine                    Unit Capabilities                          3
        generator set, it is important that you carefully read and            PREPARING THE UNIT                         3
        follow the operating instructions in this manual.                     Unpacking the unit                         3
          Should you experience a problem please follow the                   Unit Preparation                           4
        “Things To Check” section near the end of this manual.                Battery Installation                       4
        The warranty listed in this manual describes what you                 Battery Charging                           5
        can expect from WINCO, Inc should you need service                    Low Oil Level Shutdown System              5
        assistance in the future.                                             LP/NG INSTALLATION                         5
                                                                              Installing the Fuel Line                   6
        PROPER USE AND INSTALLATION                                           Fuel Pressure                              6
                                                                              Tank Sizing                                7
        You must be sure your new engine generator set is:                    Changing Fuel Types                        7
        * Properly serviced before starting                                   STARTING INSTRUCTIONS                      7
        * Operated in a well ventilated area                                  Initial Starting                           7
        * Operated so that exhaust gases are dispersed safely                 Starting                                   7
        * Wired by a qualified electrician                                    Starting Hints                             8
        * Operated only for its designed purposes                             Stopping And Storage                       8
        * Used only by operators who understand its operation                 Operating Speed                            8
        * Properly maintained                                                 Connecting The Loads                       9
                                                                              Wiring                                     9
        COPY YOUR MODEL AND SERIAL                                            OPERATOR CARE AND MAINTENANCE              10
        NUMBER HERE                                                           Engine Care                                10
                                                                              Generator Care                             10
        No other HOME POWER generator has the same serial
                                                                              Cleaning                                   11
        number as yours. It is important that you record the
                                                                              Troubleshooting - Things To Check BEFORE
        number and other vital information here. If you should
                                                                                  You Call For Service                   11
        ever need to contact us on this unit it will help us to
                                                                              WARRANTY                                   13
        respond to your needs faster.
        MODEL______________________________________
        SERIAL NUMBER _____________________________
        PURCHASE DATE_____________________________
        DEALER_____________________________________
                                                                     Page i
Downloaded from www.Manualslib.com manuals search engine
                                                                                  3. DEADLY EXHAUST GAS - Exhaust fumes from any
             GUIDE TO PRODUCT SAFETY                                              gasoline engine contain carbon monoxide, an invisible,
                                                                                  odorless and deadly gas that must be mixed with fresh air.
             This engine generator set has been designed and
             manufactured to allow safe, reliable performance. Poor                   a. Operate only in well ventilated areas.
             maintenance, improper or careless use can result in potential            b. Never operate indoors.
             deadly hazards; from electrical shock, exhaust gas                       c. Never operate the unit in such a way as to allow
             asphyxiation, or fire. Please read all safety instructions               exhaust gases to seep back into closed rooms (i.e.
             carefully before installation or use. Keep these instructions            through windows, walls or floors).
             handy for future reference. Take special note and follow all
             warnings on the unit labels and in the manuals.                      4. NOISE HAZARD - Excessive noise is not only tiring, but
                                                                                  continual exposure can lead to loss of hearing.
             ANSI SAFETY DEFINITIONS
             ______________________________________________________                   a. Use hearing protection equipment when working
             DANGER:                                                                  around this equipment for long periods of time.
                DANGER indicates an imminently hazardous situation                    b. Keep your neighbors in mind when permanently
             which, if not avoided, will result in death or serious injury.           installing this equipment.
             This signal word is to be limited to the most extreme
             situations.                                                          5. CLEANLINESS- Keep the generator and surrounding
             ______________________________________________________               area clean.
             ______________________________________________________
             WARNING:                                                                 a. Remove all grease, ice, snow or materials that
                WARNING indicates a potentially hazardous situation                   create slippery conditions around the unit.
             which, if not avoided, could result in death or serious injury.          b. Remove any rags or other material that could create
             ______________________________________________________                   potential fire hazards.
             ______________________________________________________                   c. Carefully wipe up any gas or oil spills before starting
             CAUTION:                                                                 the unit.
                CAUTION indicates a potentially hazardous situation                   d. Never allow leaves or other flammable material to
             which, if not avoided, may result in minor or moderate injury.           build up around the engine exhaust area.
             It may also be used to alert against unsafe practices.
             ______________________________________________________               6. SERVICING EQUIPMENT- All service, including the
             NOTE:                                                                installation or replacement of service parts, should be
                CAUTION is also used on the unit labels and in this manual        performed only by a qualified technician.
             to indicate a situation that could result in serious damage or
             destruction of the equipment and possible personal injury.               a. Use only factory approved repair parts.
             ______________________________________________________                   b. Do not work on this equipment when fatigued.
                                                                                      c. Never remove the protective guards, cover, or
             1. ELECTRIC SHOCK- The output voltage present in this                    receptacle panels while the engine is running.
             equipment can cause a fatal electric shock. This equipment               d. Use extreme caution when working on electrical
             must be operated by a responsible person.                                components. High output voltages from this
                                                                                      equipment can cause serious injury or death.
               a. Do not allow anyone to operate the generator without                e. Always avoid hot mufflers, exhaust manifolds, and
               proper instruction.                                                    engine parts. They all can cause severe burns
               b. Guard against electric shock.                                       instantly.
               c. Avoid contact with live terminals or receptacles.                   f. Installing a home-standby generator is not a “do-it-
               d. Use extreme care if operating this unit in rain or snow.            yourself” project. Consult a qualified, licensed
             . e. Be sure the unit is properly grounded to an external                electrician or contractor. The installation must comply
               ground rod driven into the earth.                                      with all national, state, and local codes.
             2. FIRE HAZARD- Gasoline and other fuels always present a
             hazard of possible explosion and/or fire.
                a. Do not refuel when the engine is running or hot. Allow
                the engine to cool at least two minutes before refueling.
                b. Keep fuel containers out of reach of children.
                c. Do not smoke or use open flame near the generator
                set or fuel tank.
                d. Keep a fire extinguisher nearby and know its proper
                use. Fire extinguishers rated ABC by NFPA are
                appropriate.
                e. Store fuel only in an approved container, and only in
                a well-ventilated area.
             60707-115                                                       Page 1                                                      6190-00
Downloaded from www.Manualslib.com manuals search engine
         SPECIFICATIONS                                              MODEL                            HPS12000HE
         MODEL                            CSAHPS6000HE               Generator
         Generator                                                   Surge Watts*                      12000
         Surge Watts*                      6000                      Continuous Watts*                 10800
         Continuous Watts*                 5500                      Volts 120/240
         Volts                            120/240                    AMPs @ 240 Volts                   45.0
         AMPs @ 240 Volts                   22.9                     AMPs @ 120 Volts                   90.0
         AMPs @ 120 Volts                   45.8                     * Derate 10% for LP and 20% for NG
         * Derate 10% for LP and 20% for NG                          Engine                             Honda
         Engine                               Honda                  Size                               20 HP
         Size                                 11 HP                  Model                          GX620K1VXE2
         Model                            GX340K1WE2                 Type -                   See Engine Shroud For Type
         Type -                     See Engine Shroud For Type       Fuel Capacity-                     15 gal
         Fuel Capacity-                       4.5 gal                Fuel Consumption
         Fuel Consumption                                                   Gasoline                   1.67 gal/hr
                Gasoline                     1.0 gal/hr                     LP                          2.2 gal/hr
                LP                           1.6 gal/hr                     NG                         200 cu ft/hr
                NG                          160 cu ft/hr             Starting System                   12V Electric
         Starting System                 Recoil/12V Electric         Stop System                           Key
         Stop System                             Key                 Complete Unit
         Complete Unit                                               Weight (dry)                       274 LBS
         Weight (dry)                         212 LBS                Dimensions LxWxH                 32 X 22 X 22
         Dimensions LxWxH                   30 X 22 X 22             Fuel                          Gasoline/LP/NG
         Owner Must Provide                                          Oil Type                       SG SF/CC CD
         Fuel                          Gasoline/LP/NG                Oil Weight (for general use)       10W -30
         Oil Type                       SG SF/CC CD                  See engine manual for additional information
         Oil Weight (for general use)       10W -30                  Oil Capacity                     1.3 Quarts
         See engine manual for additional information                Battery 12 Volt              Group U1/235CCA
         Oil Capacity                     1.2 Quarts
         Battery 12 Volt                 U1/235CCA                   INTENDED USES
                                                                     These engine generator sets have been designed primarily
         MODEL                             CSAHPS9000E
                                                                     for portable use. Both 120 and 240 Volt AC receptacles are
         Generator                                                   provided in the 'control panel' to plug in your loads (lights,
         Surge Watts*                      9000                      portable tools, and small appliances). These units are dual
         Continuous Watts*                 8000                      wound generators, therefore the 120 Volt loads must be
         Volts 120/240                                               equally split with 1/2 of the rated capacity available on each
         AMPs @ 240 Volts                   33.3                     of the two 120 Volt circuits. See unit capabilities for further
         AMPs @ 120 Volts                   66.7                     explanation.
         * Derate 10% for LP and 20% for NG
                                                                     These portable units require large quantities of fresh air for
         Engine                          Briggs & Stratton           cooling of both the engine and the generator. Fresh air is
         Size                                 16 HP                  drawn from both the engine end and the generator end and is
         Model                                303447                 exhausted at the center of the unit. For safety, long life and
         Type -                     See Engine Shroud For Type       adequate performance, these units should never be run in
         Fuel Capacity-                       4.5 gal                small compartments or enclosed areas without positive fresh
         Fuel Consumption                                            air flow.
                Gasoline                     1.3 gal/hr
                LP                           1.9 gal/hr              RESTRICTED USES
                NG                          180 cu ft/hr             DO NOT remove from the cradle assembly. Removal of the
         Starting System                 Recoil/12V Electric         generator from the cradle assembly may cause excessive
         Stop System                             Key                 vibration and damage to the engine generator set.
         Complete Unit                                               DO NOT install and operate these portable generators in a
         Weight (dry)                         274 LBS                small compartment., i.e. generator compartment of vehicles,
         Dimensions LxWxH                   32 X 22 X 22             motor homes or travel trailers. These compartments will not
         Fuel                             Gasoline/LP/NG             allow enough free flow fresh air to reach the engine
         Oil Type                            SE SG SF                generator set for cooling and will cause the unit to overheat,
         Oil Weight                      See Engine Manual           damaging both the engine and the generator. Small
                                         specific information        compartments will also develop hot spots where there is very
         Oil Capacity                       1.75 Quarts              little air flow and may cause a fire.
         Battery 12 Volt                    U1/235CCA                DO NOT attempt to operate at 50 cycles. These units are
                                                                     designed and governed to operate at 60 Cycles only.
        6190-00                                                  Page 2                                                  60707-115
Downloaded from www.Manualslib.com manuals search engine
             UNIT CAPABILITIES                                                    The figures given above are for an average load such as a
                                                                                  blower or fan. If the electric motor is connected to a hard
             Generator Connections - The diagram below represents a               starting load such as an air compressor, it will require more
             typical 5500 watt generator. Receptacles A and B are the             starting current. If it is connected to a light load, or no load
             two 120 Volt duplex receptacles. Up to 2750 watts at 120             such as a power saw, it will require less starting current.
             volts (22.9 Amps) can be taken from the generator at each            The exact requirement will also vary with the brand or
             of the receptacles. This generator produces 120 and 240              design of the motor.
             volt, 60 Hz (Hertz), AC (Alternating Current).
                                                                                  Self-excited generators respond to severe overloading
             CAUTION: EQUIPMENT DAMAGE                                            differently than the power line. When overloaded, the
                                                                                  engine is not able to supply enough power to bring the
                 CAUTION MUST BE EXERCISED TO PREVENT                             electric motor up to operating speed. The generator
                 OVERLOADING EITHER OF THE GENERATORS                             responds with high initial starting current, but the engine
                 120 VOLT OUTPUT CIRCUITS (A OR B).                               speed drops sharply. The overload may stall the engine. If
                                                                                  allowed to operate at very low speeds, the electric motor
                                                                                  starting winding will burn out in a short time. The generator
                                                                                  winding might also be damaged.
                                                                                  CAUTION: EQUIPMENT DAMAGE
                                                                                      RUNNING THE GENERATOR SET UNDER THESE
                                                                                      CONDITIONS MAY RESULT IN DAMAGING THE
                                                                                      GENERATOR STATOR AS WELL AS THE MOTOR
                                                                                      WINDING.
                                                                                  Because the heavy surge of current required for starting
                                                                                  motors is required for only an instant, the generator will not
                                                                                  be damaged if it can bring the motor up to speed in a few
                                                                                  seconds of time. If difficulty is experienced in starting
                                                                                  motors, turn all other electrical loads off and if possible
             Check the appliance or tool nameplates for the current and           reduce the load on the electric motor.
             voltage to insure compatibility. Remember that power taken           UNPACKING
             from receptacle C reduces the power available at both A
             and B. Any remaining 120 volt loads should be equally                CAUTION: EQUIPMENT DAMAGE
             divided between A and B. Failure to split the load will cause            THIS UNIT HAS BEEN SHIPPED WITHOUT OIL.
             permanent damage to the stator. Although circuit breakers                Failure to maintain the engine oil at the proper level will
             are provided, damage due to overloading constitutes abuse                result in serious engine damage.
             and will not be warranted. Refer to the generator nameplate
             for your unit's capabilities.                                        When you unpack your new ENGINE GENERATOR be sure
             Starting Electric Motors - Electric motors require much              to remove all the information sheets and manuals from the
             more current (amps) to start them than to run them. Some             carton.
             motors, particularly low cost split-phase motors, are very               1. This power plant was in good order when shipped.
             hard to start and require 5 to 7 times as much current to                   Inspect the power plant promptly after receiving it. If
             start them as to run them. Capacitor motors are easier to                   damage is noted, notify the transportation company
             start and usually require 2 to 4 times as much current to                   immediately; request proper procedures for filing a
             start them as to run them. Repulsion Induction motors are                   “concealed damage” claim. Title to the equipment
             the easiest to start and usually require 1 1/2 to 2 1/2 times               and responsibility for filing a claim rests with you
             as much to start them as to run them.                                       when a generator is sent F.O.B. shipping point. Only
             Most fractional horsepower motors take about the same                       you can legally file a claim.
             amount of current to run them whether they are of                        2. Before proceeding with the preparation of your new
             Repulsion-Induction (RI), Capacitor (Cap), or Split-Phase                   engine generator set for operation, take a couple of
             (SP) type. The chart below shows the approximate current                    minutes to insure that the unit you have received is
             required to start and run various types and sizes of 120 volt               the correct model and review the specification pages
             60 cycle electric motors under average load conditions.                     in this manual to insure that this unit fits your job
                          RUNNING            STARTING AMPS                               requirements.
                  HP       AMPS         SP        CAP      RI                         3. After removing the engine generator from the carton
                  1/6         3.2    16 TO 22  6 TO 13       5 TO 8                      locate and remove the shipping strap attached to the
                  1/4         4.5    22 TO 32  9 TO 18       7 TO 12                     generator shock mount. See attached tag for
                  1/3         5.2    26 TO 35 10 TO 21       8 TO 17                     removal instructions.
                  1/2         7.2    NOT MADE 14 TO 29      11 TO 18
                  1          13.0    NOT MADE 26 TO 52      20 TO 33
             60707-115                                                       Page 3                                                       6190-00
Downloaded from www.Manualslib.com manuals search engine
        UNIT PREPARATION                                                             Model         BCI Group            Capability (minimum)
        Before your engine generator was shipped from our factory
        it was fully checked for performance. The generator was                      HPS6000HE          U1              235 CCA
        load tested to its full capacity, and the voltage and                        HPS9000E           U1              235 CCA
        frequency were carefully checked and adjusted.                               HPS12000HE         U1              235 CCA
        OPERATING LOCATION                                                      CAUTION – PERSONAL DANGER
        DANGER: DEATH AND DISABILITY                                            NEVER dispose of a battery in a fire. The battery is capable
              DO NOT operate or install these units inside any                  of exploding.
            building or structure. These units produce carbon
            monoxide on all three of the operating fuels. Carbon                DO NOT open or mutilate the battery. Released electrolyte
            monoxide can kill or disable a person in a very short               is known to be harmful to the skin and eyes and to be very
            time. In addition, never operate these units in a                   toxic.
            location that will allow the carbon monoxide (exhaust)
            to seep into a building that is occupied.                           These engine generator sets are all NEGATIVE ground. Be
        The engine-generator models covered in this manual were                 very careful not to connect the battery in reverse polarity, as
        designed for portable use. The unit should be stored in a               this may short circuit the battery charging system on the
        dry location. During a power outage move the unit outdoors              engine.
        to a flat dry location such as a driveway, concrete pad or
        sidewalk for use. We recommend installing the optional                  CAUTION – A battery presents a risk of electrical shock and
        dolly kit or equivalent for ease of handling.                           high short circuit current. The following precautions must be
                                                                                observed when working with batteries.
        LUBRICATION
                                                                                1.     Remove watches, rings and other metal objects.
        Before starting the engine, fill the crankcase to the proper            2.     Use tools with insulated handles.
        level with a good quality oil. When filling the crankcase
                                                                                3.     Check both the battery cable ends and the battery
        with oil use the dipstick, there is some trapped oil in the
                                                                                       posts to be sure they are free of corrosion.
        engine. The recommended grade of oil and quantity of oil
                                                                                3.     Always connect the battery positive cable first and
        required is listed in the engine operator's manual. The
        necessity of using the correct oil, and keeping the crankcase                  then connect the battery negative cable. When
        full cannot be overemphasized. Engine failures resulting                       removing the battery cables from the battery reverse
        from inadequate or improper lubricant are considered abuse                     the procedure, disconnect the negative cable first and
        and are not covered by the generator or the engine                             then the positive cable.
        manufacturer's warranty.                                                4.     Be sure all connections are tight and coat the
                                                                                       terminals and cable end with dialectic grease.
        WARNING - Never overfill the crankcase with oil. If the
        crankcase is overfilled with oil the excess oil will be push out        WARNING – The electrolyte is a diluted sulfuric acid that is
        through the breather resulting in oil in the carburetor and air         harmful to the skin and eyes. It is electrically conductive
        filter.                                                                 and corrosive. The following precautions must always be
                                                                                taken.
        BATTERY INSTALLATION                                                           *     Always wear full eye protection and protective
        If you intend to use the power plant’s electric start system,                        clothing
        (required if you are intending to use either LP or NG Fuel)                    *     Where electrolyte contacts the skin, wash off
        you will need to purchase a battery to operate it. Units                             immediately with water.
        equipped with a recoil or rope start will operate satisfactorily               *     If electrolyte contacts the eyes, flush thoroughly
        without a battery on gasoline only.                                                  and immediately with water and seek immediate
                                                                                             medical attention.
        Installation and servicing of batteries must be performed or                   *     Spilled electrolyte is to be washed down with an
        supervised only by personnel knowledgeable of batteries and
                                                                                             acid neutralizing agent. A common practice is to
        the required precautions. Keep unauthorized personnel
                                                                                             use a solution of one pound of bicarbonate of soda
        away from batteries.
                                                                                             (baking soda) to one gallon of water. The
                                                                                             bicarbonate of soda solution is to be added until
        When installing or replacing batteries, use the proper group/                        the evidence of reaction, foaming, has ceased.
        size starting battery. The battery should be a Maintenance
                                                                                             The resulting liquid is to be flushed with water and
        Free lead acid design. Deep cycle batteries will not work for
                                                                                             the area dried.
        this application.
        6190-00                                                            Page 4                                                    60707-115
Downloaded from www.Manualslib.com manuals search engine
             DANGER – Explosive Fire Risk                                              oil level in the crankcase can fall below a safe limit, the Oil
                                                                                       Alert system will automatically shut down the engine (the
                   *   Never smoke when near batteries                                 engine switch will remain in the ON position).
                   *   Do not cause a flame or spark in the battery area
                   *   Always discharge static electricity from your body              GASOLINE FUEL
                       before touching batteries by first touching a                    When using gasoline always use a good grade of unleaded
                       grounded metal surface.                                         fuel. Leaded gasoline may be used if unleaded is not
                                                                                       available. Gasoline containing alcohol, such as gasohol is
             SERVICING BATTERIES                                                       not recommended. However, if gasoline with alcohol is
                                                                                       used, it must not contain more than 10 percent Ethanol and
             Batteries used on these units may over time lose water. This              must be removed from the engine during storage. DO NOT
             is especially true if you are using a trickle charger to maintain         use gasoline containing methanol. Always insure that the
             your battery. When refilling the battery with water use only              fuel is clean and free of all impurities. See your engine
             distilled water. Tap water will shorten the service life of the           manual for addition gasoline requirement and warnings.
             battery.                                                                  WARNING: FIRE DANGER
             Never fill the battery above the fill line. Over filling above the            Gasoline and its fumes are VERY explosive when
             upper level line may cause the electrolyte to overflow,                       proper precautions are not taken.
             resulting in corrosion to the engine or nearby parts.                     Never use gasoline that has been stored for an extended
             Immediately wash off any spilled electrolyte following the                period of time as the fuel will lose its volatile properties and
             procedure above.                                                          you will be left with only the varnish residue. This varnish-
                                                                                       like substance will clog the carburetor and will not burn
             BATTERY CHARGING                                                          properly. The use of a fuel additive, such as STA-BIL, or an
                                                                                       equivalent will minimize the formation of fuel gum deposits.
             Units equipped with electric start have a small flywheel                  If a unit has been out of operation for an extended period of
             charger built into the engine flywheel assembly for                       time it is best to drain old fuel from the engine and replace
             recharging the starting battery. This flywheel charger                    with fresh fuel before attempting to start.
             generates a small AC current that passes through a diode
             at the end of the charging lead to produce a DC charging                  NOTE: For areas of the country where seasonally blended
             current of about 1 AMP. This circuit is not designed to be                fuel is used do not keep and use winter blended fuel in the
             used as a battery charging circuit to recharge dead                       summer time. This may cause your unit to vapor lock during
             batteries.                                                                the hot summer use.
             LOW OIL LEVEL SHUTDOWN SYSTEM
                                                                                       LP/NG FUEL INSTALLATION
             Briggs & Stratton powered generators - Some engine
             generator sets come equipped standard with the Briggs &                   The information in this instruction is offered to assist you in
             Stratton OILGARD warning system.                                          providing the proper vapor fuel supply for your engine. This
             This low oil warning system will automatically stop the                   information is only provided to advise you of the engine’s
             engine before the oil level reaches an operational danger                 requirements and the decisions you must make. In no case
             point. This feature is designed to prevent costly repairs and             should this information be interpreted to conflict with any
             downtime.                                                                 local, state or national code. If in doubt, always follow local
                                                                                       codes.
             The OILGARD system uses a float in the engine crankcase
             to sense the oil level. If a low oil level condition should               DANGER: FIRE - PERSONAL INJURY -
             occur during operation, the float will ground out the                      All fuel lines must be installed by a qualified fuel
             magneto impulse, “killing” the engine. In addition, there is               supplier.
             an indicator light mounted on the engine shroud near the
             recoil starter. This light will blink on and off to indicate a low        The fuel source should be as close as possible to the
             oil level condition when you are attempting to start the unit.            outdoor operating location. This will reduce the installation
             To get the engine started, you must add the required                      cost of fuel runs. Connect the fuel supply line to the inlet of
             amount of oil to the engine crankcase.                                    the fuel demand regulator on the unit using a locally
             Use of the OILGARD system on applications that are                        approved flexible fuel line (see table for recommended line
             subject to shock, bumping or severe angles of operation (in               size). The pressure supplied to the demand regulator
             excess of 15 degrees) should be avoided. This is                          must be FOUR TO SIX OUNCES or 7 to 11 INCHES W.C.
             especially true if an unexpected shutdown would cause a                   (water column). The primary regulator at the fuel supply
             safety hazard or serious inconvenience for the operator.                  must be capable of delivering the proper volume of fuel at
                                                                                       this pressure.
             Honda powered generators - These engine generator
             sets come equipped standard with the Honda Oil Alert                      Have your local fuel supplier install a protected fuel
             System.                                                                   connection at the outside operating location. He should also
             The Oil Alert system is designed to prevent damage caused                 install a lockable fuel shut off valve at the connection point.
             by an insufficient amount of oil in the crankcase. Before the             Have your fuel supplier permanently install a flexible fuel line
                                                                                       to the demand regulator on the engine generator set.
             60707-115                                                            Page 5                                                       6190-00
Downloaded from www.Manualslib.com manuals search engine
                                                                               incorrect fuel pressure. Power and performance of the
         INSTALLING THE FUEL LINE                                              engine is in direct relation to the correctness of the fuel
         DANGER: PERSONAL INJURY                                               system. Shown below is a block diagram of a typical L.P.
          Units that are intended to be run unattended MUST                    or N.G. installation.
          have an electric fuel solenoid installed. This solenoid
          MUST be wired to AUTOMATICALLY turn off the fuel
          whenever the engine stops.
         Unit location will determine the size of fuel line that is
         required to supply the engine with a constant fuel pressure.
         Refer to the tables below for fuel line size, and recommended
         tank size. For distances of 100 feet and over, a two regulator
         fuel system is recommended. This system consisting of a
         primary 10-15# regulator at the tank and a 6 ounce
         secondary regulator installed about 10 feet from the
         generator. You need to run a 3/4 inch line or larger from the
         secondary regulator to the engine-generator set. When a two
         (2) regulator fuel system is used, a fuel line size of 3/8 inch is
         generally adequate for distances up to 300 feet. The line
         size from the table below applies to the distance from the
         second regulator to the demand regulator. A positive fuel
         shut-off device must be installed in the fuel line close to the
         engine generator set. This may be either a lockable manual
         shut-off valve available from your local fuel installer, or a 12
         volt DC fuel solenoid valve. This optional 12 volt DC valve is
         available through your local Winco dealer.
         The fuel line used to connect the supply line to the demand
         regulator must be a locally approved flexible fuel line.
         Products used will vary in different regions depending on
         availability and local codes. Consult with your local fuel
         supplier to insure complete compliance with ALL codes.
           1. Remove the pipe plug from the demand regulator.
                                                                                Reference numbers 1 through 3 in the block diagrams
           2. Connect the flex fuel line to the demand regulator to
                                                                               above are system parts supplied by customer.
              the optional fuel solenoid..
                                                                                   Reference number 4 is the engine generator set.
         DANGER: PERSONAL INJURY
          Do not use galvanized pipe in the fuel line runs. The                  Below is a table of the fuel pressure reading at each
          galvanized coating will become eroded and flake off,                 reference in the system.
          causing possible obstruction or damage to the
          regulator or fuel valve. The obstruction could cause an              Fuel Pressure Table
          inoperative engine or an explosive fuel leak.                        Single Regulator (L.P. Vapor only)
         Size of pipe required for generators operating on natural gas/                     1        3                 4
         LP gas.                                                               UNIT OFF  TANK PSI 7-11 in            7-11 in
                                                                                                  4-6 oz             4-6 oz
               Length of Fuel Line*              Fuel Line Size
                                                                               STARTING TANK PSI 7-11 in             7-11 in
                less than 25 feet             3/4 inch black pipe
                                                                                                  4-6 oz             4-6 oz
                25 to 100 feet                 1 inch black pipe
                                                                               NO LOAD   TANK PSI 7-11 in            7-11 in
                over 100 feet                 not recommended**
                                                                                                  4-6 oz             4-6 oz
         *allow an additional 3 feet for each standard elbow. Do not
                                                                               FULL LOAD TANK PSI 7-11 in            7-11 in
         use ‘street ells’ (restrictive)
                                                                                                  4-6 oz             4-6 oz
         ** Consult factory for fuel runs over 100 feet.
                                                                               Two (2) Regulator System (L.P. Vapor only)
         DANGER! - FIRE - PERSONAL INJURY -
          Be careful when sealing gas joints. Excessive sealing                                   1          2            3          4
          compound can be drawn into the solenoid, regulator or                UNIT OFF       TANK PSI 10-15 lbs     7-11 in     7-11 in
          carburetor causing an engine malfunction or dangerous                                                      4-6 oz      4-6 oz
          fuel leak.                                                           STARTING TANK PSI 10-15 lbs           7-11 in     7-11 in
                                                                                                                     4-6 oz      4-6 oz
         FUEL PRESSURE                                                         NO LOAD        TANK PSI 10-15 lbs     7-11 in     7-11 in
                                                                                                                     4-6 oz      4-6 oz
         Correct fuel pressure cannot be stressed enough. The most             FULL LOAD TANK PSI 10-15 lbs          7-11 in     7-11 in
         common cause for inoperative systems is an inadequate or                                                    4-6 oz      4-6 oz
        6190-00                                                           Page 6                                                60707-115
Downloaded from www.Manualslib.com manuals search engine
              Natural Gas                                                             FROM LP/NG TO GASOLINE
                            1                 3            4
                                                                                          1. With the engine running turn off the LP/NG fuel
              UNIT OFF      LINE PSI        7-11 in      7-11 in
                                                                                             supply.
                                            4-6 oz       4-6 oz
                                                                                          2. Run the engine until it runs out of fuel.
              STARTING LINE PSI             7-11 in      7-11 in
                                                                                          3. Remove the flexible fuel line from the demand
                                            4-6 oz       4-6 oz
                                                                                             regulator.
              NO LOAD       LINE PSI        7-11 in      7-11 in
                                                                                          4. Reinstall the plastic plug in the regulator.
                                            4-6 oz       4-6 oz
                                                                                          5. Check to be sure the gasoline fuel valve is off.
              FULL LOAD LINE PSI            7-11 in      7-11 in
                                                                                          6. Fill the gasoline fuel tank.
                                            4-6 oz       4-6 oz
                                                                                          7. Turn on the gasoline fuel valve.
                                                                                          8. Start the engine.
              Remember that whichever fuel delivery system or type of
              vapor fuel used, the fuel pressure at the demand regulator
              installed on the engine generator must be between 4 and 6
                                                                                      Optional Dolly Kit (HPS9000 & HPS6000)
              oz. (7-11 inches of water column). Any lower pressure and               An optional dolly kit is available for these engine generator
              the unit will starve for fuel under load. Any higher and the            sets. The dolly kit comes with instructions and parts list.
              unit will ‘flood’ when attempting to start.                             After installing the dolly kit, file the instructions and parts list
                                                                                      in the back of this manual for future reference. The
              LP TANK SIZING                                                          HPS12000HE is shipped standard with a dolly kit.
              Once above the minimum acceptable size, the size of L.P.                INITIAL START UP
              tank used will generally depend on how long you want the                Use the following checklist to verify the correct preparation
              unit to run without refilling. The tank sizes shown below are           of the engine generator before starting.
              the smallest recommended tank sizes based on the outside
              temperature. Keep in mind the colder it gets the slower L.P.            Before Starting always Check:
              will vaporize. This is the reason for the larger tanks at low              1. Engine oil, fill as required with correct grade and
              temperature. Minimum sizing is not based on running time.                     quantity. Use the dipstick.
                                                                                         2. Fuel level, fill as required with clean fresh fuel.
                Temp            60 deg f.    30 deg f.   0 deg f.   -20 deg f.           3. If you are using LP or NG besure the fuel is turned
              HPS6000HE         40 gal       50 gal      125 gal    350 gal                 on and all connection are tight.
              HPS9000E          70 gal       80 gal      200 gal    700 gal              3. Visually for loose parts.
              HPS12000HE        150 gal      250 gal     500 gal    1000 gal
                                                                                      STARTING
              CHANGING FUEL TYPES                                                     The throttle control on these generators is preset and locked
                                                                                      to operate at 3600 RPM (nominal) with no load speed set at
              These engine generator sets are designed to run on three                3750 RPM. Only a trained service technician should be
              different fuels; gasoline, natural gas or LP vapor. They may            allowed to adjust this speed setting. See “Operating Speed”
              be easily changed from one fuel to another.                             section for additional information.
                                                                                      NOTICE: ENGINE START LOCKOUT
              FROM GASOLINE TO LP/NG
                                                                                      This unit will not start if it is low on oil. The lubricating oil
                1. With the engine running turn off the gasoline                      level must be at the full mark before the engine will start.
                   fuel valve.                                                        MANUAL STARTING - Refer to the engine manual for
                2. Run the engine until it runs out of fuel.                          additional starting, operating, and stopping instructions.
                3. Remove the pipe plug from the demand
                   regulator.                                                         NOTICE: TRI-FUEL STARTING
                4. Install locally approved flexible fuel line.                        Tri-Fuel generators operating on vapor fuel, (either LP or
                5. Connect the LP/NG vapor fuel line.                                  NG) must be started using the electric start system
                6. Turn on the vapor fuel.                                             provided. You cannot hand crank the unit fast enough to
                7. Start the engine.                                                   develop the proper vacuum to make the vapor fuel system
                8. Apply the load to the generator.                                    work. In addition the demand regulator on the HP6000HE
                9. On the HPS6000 and the HPS9000 adjust the fuel                      has a primer button in the center, which must be
                   mixture valve to smooth the engine out. The                         depressed while engaging the starter. WHEN USING
                   HPS12000 has two different hose fittings. One is for                VAPOR FUEL NEVER USE THE CHOKE. Use of the
                   LP and one is for Natural Gas. Make sure the hose is                choke will prevent the air and fuel from properly mixing.
                   attached to the proper fitting.
              Note: Operating on LP/NG vapor fuel for an extended
              period of time without liquid fuel in the carburetor may
              damage the carburetor float, and the needle seat assembly.
              If you plan to convert back to gasoline, we recommend the
              float and needle seat assembly be removed from the
              carburetor. (Consult a local engine supplier for assistance.)
             60707-115                                                           Page 7                                                         6190-00
Downloaded from www.Manualslib.com manuals search engine
           1. Turn on the fuel supply.                                                     doesn’t deteriorate and clog the fuel system. Note:
           2. Move the choke to the full "on" position. A warm                             The use of a fuel additive, such as STA-BIL, or an
              engine will require less choking than a cold engine.                         equivalent, will minimize the formation of gum
           3. Grasp starter grip and pull slowly until starter engages,                    deposits during storage. Such an additive may be
              then pull cord rapidly to overcome compression,                              added to gasoline in the engine’s fuel tank or to
              prevent kickback and start the engine. Repeat if                             gasoline in a storage container.
              necessary.
           4. When the engine starts, open the choke gradually.                            a. Remove the remaining fuel from the fuel tank.
           5. The engine should promptly come up to operating                              b. Start the engine and allow it to run until all
              speed.                                                                          the fuel in the carburetor and the fuel lines has
         Electric Starting - If the engine is cold and stiff or if the                        been used up and the engine stops.
         battery is not fully charged, starting can be made easier by                      c. While the engine is warm, drain the oil and
         slowly hand cranking the engine through the compression                              refill with fresh oil.
         stroke before pushing the starter switch. This permits the                        d. Remove the spark plug, pour approximately
         starter to gain momentum before the heavy load of the                                1/2 ounce (15 cc) of engine oil into the cylinder
         compression stroke occurs. This minimizes the drain on the                           and crank slowly to distribute oil. Replace spark
         battery and improves the possibility of starting under such                          plug.
         adverse conditions. Always keep the battery charged, but                          e. Clean dirt and chaff from cylinder, cylinder
         especially during cold weather operation.                                            head fins, blower housing, rotating screen and
                                                                                              muffler areas.
            1. Turn on the fuel supply.                                                    f. Store in a clean and dry area.
            2. Move the choke to the full "on" position (for gasoline
               only). A warm engine will require less choking than a           OPERATING SPEED
               cold engine.
                                                                               The engine-generator must be run at the correct speed in
            3. Engage the engine start switch briefly to the START
                                                                               order to produce the proper electrical voltage and
               position. The starter life is improved by using shorter
                                                                               frequency.
               starting cycles with time to cool off between cranking
               cycles. Do not operate the starter more than 15                 CAUTION:                 EQUIPMENT DAMAGE
               seconds during each minute. Repeat if necessary.                      The output voltage should be checked to insure the
            4. When the engine starts, open the choke gradually.                     generator is working properly prior to connecting a load
            5. The engine should promptly come up to operating                       to the generator. Failure to do so could result in
               speed.                                                                damage to equipment plugged into the unit and
         CAUTION: EQUIPMENT DAMAGE                                                   possible injury to the individual.
            Never permit the choke to remain on after the engine has           All engines have a tendency to slow down when a load is
            run for a short time. It is not necessary to choke the             applied. When the electrical load is connected to the
            engine when it is warm. Avoid over-choking.                        generator, the engine is more heavily loaded, and as a
                                                                               result the speed drops slightly. This slight decrease in
         STARTING HINTS                                                        speed, together with the voltage drop within the generator
         NOTE: For areas of the country where seasonally blended               itself, results in a slightly lower voltage when the generator
         fuel is used do not keep and use winter blended fuel in the           is loaded to its full capacity than when running no load.
         summer time. This may cause your unit to vapor lock during            The slight variation in speed also affects the frequency of
         the hot summer use.                                                   the output current. This frequency variation has no
                                                                               appreciable effect in the operation of motors, lights and
            1. Cold weather                                                    most appliances. However, electronic equipment and
               a. Use the proper oil for the temperature expected.             clocks will be affected if correct RPM is not maintained.
               b. Use fresh winter grade fuel. Winter grade                    See Load vs. Output chart.
                  gasoline is blended to improve starting. Do not
                                                                               Although individual units and models may vary slightly, the
                  use summer gasoline.
                                                                               normal voltage and frequency of the engine-generators
               c. A slightly richer fuel mixture will usually improve
                                                                               described in this book are approximately as follows, under
                  cold starting.
                                                                               varying loads:
            2. Hot weather
               a. Use the proper oil for the temperature expected.                                          LOAD vs. OUTPUT
                                                                               __________________________________________________________________________________________________________________
               b. Use only summer blended gasoline. Using
                                                                                     Generator   Frequency                                                     Voltage
               gasoline left over from winter may cause the unit
                                                                                     Load           Speed                                                      120V
                  to vapor lock.
                                                                                     Applied* (RPM)       (Hz)                                                 Recpt.
               c. DO NOT over-choke the unit.                                  __________________________________________________________________________________________________________________
                                                                                     None                   3750                        62.5                   129V
         STOPPING AND STORAGE                                                        Half                   3600                        60.0                   120V
                                                                                     Full                   3540                        59.0                   115V
            1. Remove the load.                                                __________________________________________________________________________________________________________________
            2. Turn off key the on engine to ‘ground out’ the spark                  *Portion of plant’s rated output current.
               and shut the unit down.                                         The speed of the engine was carefully adjusted at the
            3. Before extended storage (over 30 days) certain                  factory so that the generator produces the proper voltage
               precautions must be taken to ensure the fuel                    and frequency. For normal usage, the speed setting
        6190-00                                                           Page 8                                                                                          60707-115
Downloaded from www.Manualslib.com manuals search engine
             should not be changed. If the generator is being run                   WIRING
             continuously on a very light load, it is often advisable to
             lower the operating speed slightly. Whenever making any                ‘Hard Wiring’ this unit directly into a temporary construction
             speed adjustments check the unit with a voltmeter or                   site electrical system or into a home as a back up is NOT A
             tachometer and be sure the speed is correct.                           SIMPLE DO-IT-YOURSELF JOB. For your safety all wiring
             Lower voltage may damage both the generator and any load               must be done by a qualified electrician and conform to the
             connected to it. Running the engine at excessively high                National Electric Code and comply with all state and local
             speeds results in high voltage, which may significantly                codes and regulations. Check with local authorities before
             shorten the life of appliances being used.                             proceeding.
             Output voltage should be checked periodically to ensure                These generators come equipped with a 4 wire 120/240 volt
             continued proper operation of the generating plant and
                                                                                    receptacle designed to power both 120 and 240 volt loads.
             appliances. If the generator is not equipped with a                    There are 2 hots, a neutral, and a ground wire connection in
             voltmeter, it can be checked with a portable meter.
                                                                                    the 4 wire 120/240 volt receptacle (L14-30R). This
             Frequency can be checked by using an electric clock with a
                                                                                    receptacle is protected by a double pole circuit breaker rated
             sweep second hand. Timed against a wrist watch or a stop               for generator output. Below is a table of the matching plugs
             watch the clock should be correct within +/- 2 seconds per
                                                                                    for each of the models, note the 12 kW has two 4-wire plugs.
             minute.
             CONNECTING THE LOADS
                                                                                        MODEL          NEMA SPEC        SIZE       WINCO
             Applying The Load                                                                         FOR PLUG                    PART #
                                                                                        HPS6000HE      L14-30P          30 AMP     64492-000
             Allow the engine to warm up for two or three minutes before                HPS9000E       L14-30P          30 AMP     64492-000
             applying any load. This will allow the engine to reach                     HPS12000HE     L14-30P          30 AMP     64492-000
             normal operating temperature and oil to circulate throughout                 AND          14-60P           60 AMP     300137
             the engine. A short warm-up time will permit the engine to
             work more efficiently when the load is applied and will                CAUTION: EQUIPMENT DAMAGE
             reduce the wear in the engine, extending its life.                           Caution must be used when loading the generator,
             Receptacles have been provided to allow loads to be                          overloading either of the 120 volt sides will cause the
             connected to the generator. The loads should be added one                    breaker to trip, disconnecting all the loads
             at a time. If a large motor is being started or multiple motors
             are being started, they should be started individually and the         TEMPORARY SITE'S ELECTRICAL SYSTEM
             largest should be started first.
                                                                                    To connect these units directly to an un-powered, isolated
             Plug your tools such as drills, saws, blowers, sump pump
                                                                                    construction site TemPower panel, have your electrician
             and other items to be powered directly into the generator
                                                                                    connect to the control panel using a 120/240 volt, four wire
             receptacles. Before plugging in all the tools and cord sets,
                                                                                    twist-lock plug (L14-30P). The use of locking receptacles
             recheck the rating of the generator set. Be sure it can
                                                                                    and locking plugs provides the convenience of quick
             handle the intended load and is compatible with the voltage,
                                                                                    disconnect, for moving, while allowing non electrical workers
             phase, and current ratings.
                                                                                    to safely reconnect the power. In addition they prevent the
                                                                                    plug from being accidentally removed by bumping or
             CAUTION: EQUIPMENT OVERLOAD
                                                                                    vibration.
                 Keep the generator load within the generator and
                 receptacle nameplate rating. Overloading may cause                 EXISTING ELECTRICAL SYSTEM (Home Standby)
                 damage to the generator and/or the loads .
                                                                                    WARNING: PERSONAL DANGER
             Most electric tools and appliances will have the voltage and             NATIONAL ELECTRIC CODE REQUIRES a fully isolated,
             amperage requirements on their individual nameplates.                  double pole double throw manual transfer switch be
             When in doubt consult the manufacturer or a local                      installed any time a generator is being connected to an
             electrician. The nameplate amperage rating for electric                existing distribution system.
             motors can be misleading. See “Starting Electric Motors” in              NEVER BACK FEED A DRYER OR RANGE 240 VOLT
             Unit Capabilities (page 3).                                            RECEPTACLE
             These engine generator sets are inherently self regulating             If the generator set is connected to existing (electrical)
             based on engine speed. The engine governor will                        wiring circuits it is permitted only through a fully isolated
             automatically adjust itself to the load. No harm to the                manual transfer switch. The transfer switch prevents
             generator will result if it is operated with no load connected.        damage to the generator and other circuit components if
             Proper utilization of the receptacles located on the control           main line power is restored while the generator is
             panel is necessary to prevent damage to either the                     connected. Installing a transfer switch also permits the use
             receptacles or the generator. The generator is a limited               of normal fusing.
             source of electrical power, therefore pay special attention to
             the receptacle and generator ratings.
             60707-115                                                         Page 9                                                     6190-00
Downloaded from www.Manualslib.com manuals search engine
        Many homes and construction sites are wired for at least 60          2. Checking the Oil Level: The oil level must always be
        to 100 Amp entrance service, much greater than the capacity             checked before the engine is started. Take care to
        of these portable generators. When installing the generator             remove any dirt or debris from around the oil fill plug
        at these sites, a secondary emergency distribution panel may            before removing. Be sure the oil level is maintained.
        have to be installed, such as the Emergency Transfer/Service            to the “FULL” mark on the dipstick, DO NOT OVER
        (ET/S) system available through your Winco dealer. The                  FILL
        emergency distribution panel must be installed by a licensed
                                                                             3. Cartridge Air Cleaner - Remove and clean cartridge
        electrician according to all applicable codes. The electrician
                                                                                yearly or after every 25 hours, whichever occurs first.
        will move the critical circuits to be powered during the outage
                                                                                Service more often if necessary. Clean by tapping
        to the emergency panel. Keep in mind only a limited amount
                                                                                gently on flat surface. If very dirty, replace the cartridge
        of amperage is available from the generator set. Some circuit
                                                                                using only original equipment parts available at any
        breakers may still have to be turned off to prevent an
                                                                                engine service center.
        overload on the generator during the initial start up. See the
        nameplate on your generator for the amperage capabilities of             Do not use petroleum solvents, such as kerosene, to
        your unit.                                                               attempt to clean the cartridge. They may cause
                                                                                 deterioration of the cartridge. DO NOT OIL
        CAUTION: EQUIPMENT DAMAGE                                                CARTRIDGE, DO NOT USE PRESSURIZED AIR TO
                                                                                 CLEAN OR DRY CARTRIDGE.
           Failure to properly limit and balance the load applied to
           the generator will cause the generator to produce low             4. Dual Element Air Cleaner - Clean and re-oil foam pre-
           voltage and may damage the engine generator set. It                  cleaner at three month intervals or every 25 hours,
           may also cause severe damage to the loads connected                  whichever occurs first. Service more often under dusty
           to the generator at that time. Improper loading of the               conditions.
           generator set constitutes abuse and will not be covered
                                                                                 a. Remove knob and cover.
           by warranty.
                                                                                 b. Remove foam pre-cleaner by sliding it off the
                                                                                    paper cartridge.
        Grounding
                                                                                 c. Wash foam pre-cleaner in kerosene or liquid
                                                                                    detergent and water
        NOTE - These generators sets are shipped with the ground
                                                                                 d. Wrap foam pre-cleaner in cloth and squeeze dry.
        bonded to neutral. For an isolated ground system remove the
                                                                                 e. Saturate foam pre-cleaner in engine oil.
        neutral to ground bond in the receptacle panel. Be sure to
                                                                                    Squeeze to remove excess oil.
        reinstall before using the generator as a stand alone unit.
                                                                                 f. Install foam pre-cleaner over paper cartridge.
                                                                                    Reassemble cover and screw down tight.
        All units must be grounded. Drive a 3/4 or 1" copper pipe or
        rod into the ground close to the engine-generator set. The               Replace the cartridge included with Dual Element Air
        pipe must penetrate moist earth. Connect an approved                     Cleaner yearly or every 100 hours. Service more often
        ground clamp to the pipe. Run a No. 10 Awg wire from clamp               if necessary.
        to the generator ground lug on the “end cover”. Do not               5. Spark Plug - Clean and reset gap to the proper gap
        connect to a water pipe or to a ground used by a radio                  every 100 hours of operation. Do not blast clean spark
        system.                                                                 plug. Clean by scraping or wire brushing and washing
        ENGINE CARE                                                             with a commercial solvent. Poor spark will occur if
                                                                                terminal does not fit firmly on spark plug. If this
        If major engine service or repair is required contact an                happensreform the terminal to fit firmly on spark plug
        authorized engine service center. The manufacturer of these             tip.
        engines has established an excellent world-wide engine
        service organization. Engine service is very likely available        GENERATOR CARE
        from a nearby authorized dealer or distributor. Check the
        yellow pages of your local telephone directory under                 Proper care and maintenance of the generator is necessary
        “Engines-Gasoline” for the closest engine repair center or ask       to insure a long trouble free life.
        the dealer from whom you purchased the power plant.
                                                                             1. Exercising The Generator - The generator should be
        1. Change the oil after the first five hours of operation               operated every three to four weeks. It should be
           and every 50 hours thereafter under normal                           operated for a period of time sufficient to warm the
           operating conditions. Change engine oil every 25                     unit up and to dry out any moisture that has
           hours of operation if the engine is operated under                   accumulated in the windings. If left, this moisture can
           heavy load, or in high ambient temperatures.                         cause corrosion in the winding. Frequent operation of
            a. Remove oil drain plug at base of the engine                      the engine generator set will also insure that the set is
               and drain the oil with the engine warm.                          operating properly should it be needed in an
            b. Replace oil drain plug.                                          emergency.
            c. Remove oil filler plug and refill with new oil.
               Refer to the table in the engine manual for the
               proper grade of oil based on your operating
               temperature.
            d. Replace filler plug.
        6190-00                                                        Page 10                                                  60707-115
Downloaded from www.Manualslib.com manuals search engine
             2. Generator Maintenance - Any major generator                      TROUBLESHOOTING HINTS
                service including the installation or replacement of
                parts should be performed only by a qualified                      PROBLEM (SYMPTOMS) POSSIBLE CAUSES
                electrical service technician. USE ONLY FACTORY                  ——————————————————————————
                APPROVED REPAIR PARTS.                                             Won’t Start        *Low Oil Level.
                 a. Bearing - The bearing used in these generators is                                 *Fouled spark plug.
                    a heavy duty double sealed ball bearing. They                                     *Out of fuel.
                    require no maintenance or lubrication.                                            *Stop switch in stop position.
                 b. Receptacles - Quality receptacles have been utilized.                             *Wrong fuel pressure.
                    If a receptacle should become cracked or otherwise                                *Fuel is shut off
                    damaged, replace it. Using damaged or cracked                ——————————————————————————
                    receptacles can be both dangerous to the operator              Runs rough         *Wrong fuel pressure.
                    and destructive to the equipment.                                                 *Not enough fuel volume.
                                                                                                      *Fuel mixture not properly
             CLEANING                                                                                  adjusted.
                                                                                                      *Gasoline carburetor gummed up.
             Remove dirt and debris with a cloth or brush. DO NOT use                                 *Fuel filter plugged.
             high pressure spray to clean either the engine or the               _______________________________________________
             generator. This high pressure spray could contaminate the
             fuel system and the generator components.                                Voltage too low*Engine speed is too low.
                                                                                                     *Generator overloaded.
             1. Keep the air inlet screen on both the engine and                                     *Defective diode.
                generator free of any dirt or debris to insure proper                                *Defective stator.
                cooling. At least yearly remove the blower housing on                                *Defective rotor (field).
                the engine and clean the chaff and dirt out of the engine                            *Defective capacitor
                cooling fins and flywheel. Clean more often if                   ——————————————————————————
                necessary. Failure to keep these areas clean may                   Circuit Breaker   *Over loaded.
                cause overheating and permanent damage to the unit.                Trips             *Defective receptacle.
                                                                                                     *Weak or defective circuit
             2. Periodically clean muffler area to remove all grass, dirt        breaker.
                and combustible debris to prevent a fire.                        ——————————————————————————
                                                                                   Voltage too high  *Engine speed is too high.
             3. On engine mufflers equipped with spark arresters, the            ——————————————————————————
                spark arrester must be removed every 50 hours for                  Generator         *Overloaded.
                cleaning and inspection. Replace if damaged.                       overheating       *Insufficient ventilation.
                                                                                 ——————————————————————————
                                                                                   No output voltage *Short in load (disconnect).
                                                                                                     *Broken or loose wire.
                                                                                                     *Defective receptacle.
                                                                                                     *No residual magnetism
                                                                                                               (in generator).
                                                                                                     *Defective stator.
                                                                                                     *Defective rotor (field).
                                                                                                     *Shorted capacitor.
                                                                                                     *Shorted Diodes
                                                                                                     *Circuit beaker is defective.
                                                                                 ——————————————————————————
             60707-115                                                      Page 11                                          6190-00
Downloaded from www.Manualslib.com manuals search engine
                    DATE                                   ITEM             WORK PERFORMED
        6190-00                                                   Page 12                    60707-115
Downloaded from www.Manualslib.com manuals search engine
                                                                24 MONTH
                                                             Limited Warranty
               WINCO warrants to the original purchaser that the alternator is free from defects in workmanship and material for a period of
               two years*, provided it is installed, operated and maintained in accordance with WINCO written instructions.
               *NOTE: Units used for rental, demonstrations, commercial or prime power applications such as construction or
               utility, are warranted for 90 days. Units that are resold are not covered under this warranty. Any further warranty,
               whether expressed or implied, rests solely with the reseller.
               WINCO’s sole liability, and Purchaser’s sole remedy for a failure under this warranty, shall be limited to the repair of the
               product. At WINCO’s option, material found to be defective in material or workmanship under normal use and service will be
               repaired or replaced. This warranty does not include circuit breakers, receptacles or ENGINES. Engines are covered
               exclusively by the warranties of their respective manufacturers.
               THERE IS NO OTHER EXPRESS WARRANTY.
               To the extent permitted by law, any and all warranties are limited to 24 months from date of purchase. The user shall
               determine the suitability of the product for its intended use prior to placing the unit in service. The user shall assume all risks
               and liability in connection with determining the suitability of the unit for its particular use. Neither the manufacturer nor the
               seller shall be liable for any injury, loss or damage arising out of improper use or operation of this unit. In no event is WINCO
               liable for incidental or consequential damages.
               Some states do not allow limitation on the duration of implied warranty and some states do not allow the exclusion or limitation
               of incidental or consequential damages, so the above limitations may not apply in every instance. This warranty gives you
               specific legal rights which may vary state to state.
               WINCO reserves the right to change or improve its products without incurring any obligations to make such changes or
               improvements on products previously purchased.
               WINCO does not warrant products which have been subjected to misuse, negligence, modified or altered in any way or have
               been involved in an accident.
               For warranty service, return the product, transportation charges prepaid, to your nearest WINCO Authorized Service Center or
               to WINCO at Le Center Minnesota. When requesting warranty service, evidence of original purchase date must be presented.
             60707-115                                                        Page 13                                                        6190-00
Downloaded from www.Manualslib.com manuals search engine
          Phone - (507) 357-6831                           225 S. Cordova Ave.
          FAX -     (507) 357-4857                         LeCenter, Mn 56057