Refrigeration Piping
Refrigeration Piping
32-3009-03                        3
                                              Application
                                              Guide
General Information                           B — Oil return must always be consid-        3 – There is no direct penalty for pres-
                                              ered since some oil is continually being     sure drop in a liquid line provided
The four prime considerations in design-      circulated with the refrigerant and must     that 100% liquid is being delivered
ing a refrigerant piping system are:          be returned to the compressor. If the        to the expansion device, and that
   A – System Reliability                     recommended suction line sizes are           the liquid pressure available to the
   B – Oil Return                             used, no oil return problems should be       expansion device is adequate to
                                              encountered with split systems and no        produce the required refrigerant
   C – Friction Losses (Pressure Drop)        traps are recommended.                       flow. Pressure drop or gain due to
   D – Cost                                                                                vertical lift must be added to the friction
                                              C — Pressure drop or friction losses are     loss in liquid lines to determine the total
A — The piping system can affect              important from a performance stand-          pressure drop. The acceptable pressure
system reliability in a number of ways:       point. The following general statements      drop in the liquid line for equipment
• Oversized liquid lines significantly        point out the effects of pressure drop in    through 10 tons is 35 PSI for R-22 sys-
   increase the amount of refrigerant         the various components of the refriger-      tems and 50 PSI for R-410A systems.
   in the system, and thus creating the       ant piping system.
   potential for slugging, oil dilution,                                                   D — Cost is an obvious consideration
   or other damage to the compressor.         1 – Pressure drop in the suction line        and dictates that the smallest tubing
                                              reduces system capacity significantly        possible be used that will result in a
•   Undersized liquid lines and the           and increases power consumption per          system with acceptable friction losses.
    associated “flashing” of refrigerant      ton. The most generally accepted value
    causes starving of the evaporator coil.   for pressure drop in a suction line is a     The following pages cover the selection
    The results can be significant loss in    pressure drop equivalent to 2°F (approx.     of liquid lines and suction lines for split
    capacity, frosted evaporator coil, high   3 PSI with R-22 in the air conditioning      heat pump and cooling systems.
    superheat etc.                            range of evaporating temperatures or
                                              approx. 5 PSI for R-410A). As tubing runs    It is recommended that the user read
•   Oversized suction lines will result       become longer, it is inevitable that the     all of Chapter I in order to better under-
    in refrigerant velocities too low to      ASHRAE recommendation will be                stand the Tables, Charts, etc.
    provide adequate oil return to the        exceeded, at times. This trade-off, of
    compressor.                               somewhat greater suction line losses,        See the Index for a complete listing,
                                              for adequate oil return is an absolute       including page number, for all tables,
•   Undersized suction lines reduce           must, in order to preserve system            charts, etc.
    capacity and efficiency and contribute    reliability.
    to high superheat.                                                                     All installations must conform to any
                                              2 – Pressure drop in hot gas lines re-       codes or regulations applying at the
•   Excessive refrigerant line length         duces system capacity to a somewhat          site. The Safety Code for Mechanical
    reduces system capacity and effi-         lesser degree and increases power            Refrigeration, ASA-B-9-1 and the Code
    ciency, as well as system reliability     consumption to a slightly lesser degree      for Refrigeration Piping, ASA-B31.5
    (excessive refrigerant charge).           than does pressure drop in suction lines.    should serve as your guide toward a
    Keep refrigerant lines as short as        Since the only hot gas lines we are con-     safe piping system.
    conditions permit!                        cerned with are in heat pump systems
                                              where they also serve as suction lines,
                                              we will treat them as suction lines. (See
                                              Chapter III in this manual for information
                                              on hot gas lines for hot gas bypass.)
                                                                  4                                                          32-3009-03
                                              Application
                                              Guide
CHAPTER I                                     must be avoided. However, it prevails         The saturation pressure for R-22 at 110°F
                                              only when outdoor temperatures are            is approx. 226 PSIG Substracting 226
Refrigerant Piping                            relatively cool and under conditions          PSIG from the 260 PSIG condensing
                                              when air conditioning for most residen-       pressure, gives us a difference of 34 PSI.
                                              tial applications is not required.            While this pressure difference is 1 PSI
Liquid Lines for
                                                                                            less than the 35 PSI obtained with the
Split Cooling and                             Any situation such as an unusually long       125°F example used in earlier versions
                                              liquid line or a large difference in eleva-
Heat Pump Systems                             tion between the indoor and outdoor
                                                                                            of this manual, we will continue to use
                                                                                            35 PSI as the maximum liquid line pres-
The purpose of the liquid line is to          sections may require consideration as         sure drop. (A drop in liquid line tempera-
convey liquid refrigerant from the con-       discussed further below.                      ture of 1/3°F by natural cooling, will
denser to the expansion device such as
                                                                                            provide the needed 1 PSI.)
the expansion valve or FCCV Accutron.TM       The flashing of refrigerant to gas will
The expansion device in turn throttles        occur if the refrigerant absorbs heat         Note that the above mentioned tempera-
the refrigerant from the high side pres-      in the liquid line so that it is no longer    tures of 120°F and 110°F represent pres-
sure as it exists at the entrance to the      subcooled or if its pressure is reduced       sures of 418 PSIG and 365 PSIG with
device to the relatively low evaporator       below the saturation pressure corre-          R-410A, a difference of 53 PSI. For the
pressure. The high side pressure varies       sponding to its temperature.                  present, we will limit R-410A liquid line
through a wide range with the cooling                                                       pressure drop to 50 PSI.
load and the outdoor temperature. The         Normally, the liquid line temperature is      The foregoing has shown how to
expansion device has to handle this           above that of the surrounding ambient         figure the liquid line pressure drop
situation and the fact that a particular      so there is no “flashing” as a result of      and indicated that the heat loss to the
pressure drop is required to produce          temperature rise and usually there is         surroundings help to maintain adequate
the flow through the liquid line is not       enough cooling of the refrigerant to          subcooling. The amount of refrigerant
especially critical providing two             compensate for the fact that the pressure     in the system governs the amount of
conditions exist.                             gradually drops to maintain flow. In spe-     subcooling of the liquid as it leaves
                                              cial cases where the liquid line is run       the condenser. The appropriate installa-
The first condition is that the liquid line   through hot attics or other heat sources      tion and charging instructions should
transports the refrigerant completely as      the liquid line should be insulated.          be followed.
liquid and not allow the refrigerant to
flash partly into gas. This requires that     Table “C,” page 10, lists the equivalent      With regard to whether adequate head
the liquid temperature be lower than the      length of fittings, which must be added       pressure is available at the expansion
temperature which causes refrigerant to       to the linear length of the tubing to         device to give the required flow, note
vaporize at the pressure prevailing lo-       obtain the equivalent length of the line.     that an unusually high pressure drop in
cally in the tube, that is, the refrigerant                                                 a liquid line due to long lengths or large
must be subcooled throughout the              The pressure loss due to vertical lift        differences in elevation, has the same
length of the liquid line.                    (evaporator above the condenser) de-          effect as a reduced head pressure due
                                              pends on the difference in level between      to cooler outdoor temperatures entering
The second condition is that the pres-        the metering device and condenser (or         the air cooled condenser. Typically each
sure and amount of subcooling at the          receiver) and on the density of the refrig-   additional 10 PSI drop in pressure in the
entrance to the expansion device must         erant. At normal liquid line temperatures     liquid line means that the minimum out-
be adequate for the device to pass the        with R-22 the static pressure drop will be    door temperature at which the system
required flow into the evaporator to          0.50 PSI per foot of lift (.43 PSI per foot   will perform satisfactorily is raised by
suit the cooling load condition. If not,      with R-410A).                                 3 degrees. Allowance for this is signifi-
the evaporator is starved for refrigerant.                                                  cant only for unusual applications
This may cause one part to freeze ice         As an example, consider an air-cooled         where cooling is required at low outdoor
and gradually choke off the indoor air-       R-22 system with 95°F air entering the        temperatures. Performance for such
flow even though other parts of the           condenser, the condensing temperature         conditions is published in the Product
evaporator are warm for lack of refriger-     is 120°F (approx. 260 PSI).                   Manual and is based on 25 feet of line as
ant. When the evaporator is starved, the      After being subcooled in the condenser,       used for Standard Ratings. For marginal
reduced cooling effect reduces the head       the liquid R-22 leaves the condenser at       applications where a Head Pressure
pressure in the condenser and through-        110°F. Assuming the pressure at the           Control accessory is under consider-
out the liquid line, which tends still fur-   condenser outlet is the same as the con-      ation, the effect of liquid line pressure
ther to reduce the refrigerant flow. This     densing pressure of approx. 260 PSIG,         drop should be considered.
inadequate head pressure situation            the liquid R-22 has been subcooled 10°F.
32-3009-03                                                         5
Application
Guide
Note that equivalent lengths are used         •   Suction Line Selection – pages 8, 9
when calculating pressure drops. Actual           and 10
(linear) lengths are used when calculat-      •   Refrigerant Piping Limits – page 11
ing pounds of R-22 in a line set. (An
elbow contains about the same amount          •   Piping Accessories for Scroll and
of R-22 as does the same length of                Reciprocating Compressors – page 12
straight tubing.)                             •   Tubing Hints – page 13
Table “C,” page 10, lists equivalent          •   Air Conditioning Formulas – page 14
lengths for elbows, etc. for pressure
drop calculations.                            •   R-410A Refrigerant – pages 15, 16
                                                  and 17
In addition to friction loss, any pres-       Note: A worksheet for Manual Calculations is provided
sure drop due to liquid lift must be          on page 31.
accounted for (.5 PSI per foot of lift
for R-22 systems, .43 PSI per foot
with R-410A).
                     6                                                                      32-3009-03
                                                                       Application
                                                                       Guide
                                                                                         Table “A”
                                                         Liquid Line Selection Table For R-22 Systems
         Maximum Allowable Liquid Line Pressure Drop ..................................................................................................             =          35 PSI
         Subtract .5 PSI for each foot of Liquid Lift (if any) ......................................................................................................
         Do Not Exceed this value when selecting Liquid Line. ...............................................................................................
                                                                                      Pressure Drop (PSI)
                                                                                                    Total Equivalent Length
     Tube           Rated
     O.D.           BTUH            20'           40'            60'           80'           100'          120'           140'          160'           180'             200'       220'   240'
                   15000            4.3           8.7          13.0           17.4          21.7           26.0          30.4           34.7            —                —          —      —
      1/4"         18000            6.0          12.0          18.1           24.1          30.1            —             —              —              —                —          —      —
                   24000           10.2          20.3          30.5            —             —              —             —              —              —                —          —      —
                   15000            1.1           2.3           3.4            4.6           5.7            6.8           8.0            9.1          10.3              11.4      12.5    13.7
                   18000            1.6           3.2           4.7            6.3           7.9            9.5          11.1           12.6          14.2              15.8      17.4    19.0
     5/16"         24000            2.7           5.3           8.0           10.6          13.3           16.0          18.6           21.3          23.9              26.6      29.3    31.9
                   30000            4.0           8.0          11.9           15.9          19.9           23.9          27.9           31.8           —                 —         —       —
                   36000            5.5          11.1          16.6           22.2          27.7           33.2           —              —             —                 —         —       —
                   42000            7.3          14.6          22.0           29.3           —              —             —              —             —                 —         —       —
                   18000             .6           1.1           1.7            2.2           2.8            3.4           3.9            4.5           5.0               5.6       6.2     6.7
                   24000             .9           1.9           2.8            3.8           4.7            5.6           6.6            7.5           8.5               9.4      10.3    11.3
                   30000            1.4           2.8           4.2            5.6           7.0            8.4           9.8           11.2          12.6              14.0      15.4    16.8
      3/8"         36000            1.9           3.9           5.8            7.8           9.7           11.6          13.6           15.5          17.5              19.4      21.3    23.3
                   42000            2.6           5.1           7.7           10.2          12.8           15.4          17.9           20.5          23.0              25.6      28.2    30.7
                   48000            3.3           6.5           9.8           13.0          16.3           19.6          22.8           26.1          29.3              32.6       —       —
                   60000            4.9           9.8          14.7           19.6          24.5           29.4          34.3            —             —                 —         —       —
                   72000            6.8          13.7          20.5           27.4          34.2            —             —              —             —                 —         —       —
                   36000             .4            .8           1.2            1.6           2.0            2.4           2.8            3.2           3.6               4.0       4.4     4.8
                   42000             .5           1.0           1.6            2.1           2.6            3.1           3.6            4.2           4.7               5.2       5.7     6.2
                   48000             .7           1.3           2.0            2.6           3.3            4.0           4.6            5.3           5.9               6.6       7.3     7.9
      1/2"         60000            1.0           2.0           3.0            4.0           5.0            6.0           7.0            8.0           9.0              10.0      11.0    12.0
                   72000            1.4           2.8           4.1            5.5           6.9            8.3           9.7           11.0          12.4              13.8      15.2    16.6
                   90000            2.1           4.2           6.2            8.3          10.4           12.5          14.6           16.6          18.7              20.8      22.9    25.0
                  120000            3.5           7.0          10.5           14.0          17.5           21.0          24.5           28.8          31.5              35.0       —       —
                   90000             .6           1.2            1.9           2.5            3.1           3.7            4.3           5.0            5.6              6.2       6.8     7.4
      5/8"
                  120000            1.1           2.1            3.2           4.2            5.3           6.4            7.4           8.5            9.5             10.6      11.7    12.7
Note 1: A blank space indicates a pressure drop of more than 35 PSI.
Note 2: Other existing sources of pressure drop such as solenoid valves, etc. must be accounted for.
Note 3: A vertical run with a heat pump system always results in a liquid lift (heating or cooling).
Note 4: The smallest liquid line diameter that results in a total liquid line pressure drop of 35 PSI or less results in the most reliable system (fewer pounds of R-22).
32-3009-03                                                                                          7
                                               Application
                                               Guide
Suction Lines for                              do not. These compressors are provided       improper mixing of hot gas and
                                               with special piping which allows oil lev-    desuperheating liquid may result
Split Cooling and                              els in the two compressors to equalize.)     in slugging of liquid refrigerant.
Heat Pump Systems
                                               Do not use evaporator pressure regulat-      Do not tape or otherwise fasten liquid
Suction lines must return refrigerant                                                       lines and suction lines together unless
                                               ing valves (EPR valves) or similar throt-
vapor and oil from the evaporator to                                                        there is insulation between them. The
                                               tling valves in the suction line. Hermetic
the compressor during operation of the                                                      resultant heat exchange would increase
                                               compressors depend on suction gases
system, but should not allow oil or liquid                                                  suction gas superheat and may cause
                                               for cooling and as the EPR valve throttles
refrigerant to be returned as slugs at any                                                  overheating of the hermetic compressor.
time, because of the danger of broken          down to maintain a constant evaporator
                                               pressure, the quantity of suction gas        (See Tubing Hints on page 13.)
compressor valves, oil dilution, etc.
                                               returning to the compressor is reduced
                                               and its superheat is increased. The only     Suction lines must be insulated to pre-
Never attempt to operate two hermetic                                                       vent condensation and vapor sealed
compressors with a common suction              type of capacity modulation recom-
                                               mended (other than multiple units) is a      on the outside to prevent a build-up
line. It is impossible to return oil to each                                                of moisture in the insulation.
compressor at precisely the same rate          hot gas by-pass system properly applied
as it is being pumped. As a result, one        so as to keep suction gas superheat          It is advisable to avoid running
compressor will eventually run low on          within normal limits, and provide proper     refrigerant lines underground
oil in its sump and proper lubrication         velocity through the evaporator and          whenever possible. If it is absolutely
is no longer possible. Each hermetic           suction lifts (if any) for adequate oil      necessary to run refrigerant lines under-
compressor must have its own separate          return.                                      ground, they must be run in 6" P.V.C.
refrigerant system.                                                                         conduit. (See Figure 1 below.)
                                               High superheat will result in improper
(Our two compressor systems may                cooling of the hermetic compressor,
appear to violate this rule, but they          while excessively low superheat or
                                                                                    Figure 1
                                                                             Underground Conduit
                                                                         (For Underground Refrigerant Lines)
45° Ells
                                                                                                               No Joints In Copper
                                                                         6" PVC Pipe Schedule 40               Within The Conduit
                                               Use 45° elbows to facilitate pulling the     conduit is critical. Some installers install
                                               tubing through the conduit. The purpose      a drain in the lower parts of the conduit.
                                               of the conduit is to keep water away         Bear in mind, that if the water table rises
                                               from the refrigerant lines. Careful seal-    above the drain, water may be forced
                                               ing, where the lines enter and leave the     into the conduit.
                                                                   8                                                           32-3009-03
                                             Application
                                             Guide
About Suction Lines                          3 – Increase the indoor airflow some-          the compressor is equipped with sump
                                             what, within the 350 to 450 CFM per ton        heat, in order to bring the system up to
and Pressure Drops                           limits. (Some latent capacity will be lost.)   current requirements.)
ASHRAE recommends that suction line          4 – Select a different equipment
pressure drop be limited to a pressure       combination that provides the                  The Dilemma:
corresponding to 2°F (approx. 3.0 PSI        needed capacity.                               Suppose that a service man is attempt-
with R-22). This is usually not a problem
                                                                                            ing to check the refrigerant charge in
with line sets of 100 eq. ft. or less.       The pressure drop values show in Table         the existing 2-1/2 ton system, with 5/16"
                                             “B” are not required in order to select a      – 5/8" O.D. refrigerant lines, mentioned
A quick look at the pressure drop per        suction line. They are provided for your
100 ft. listed in Table “B” reveals that                                                    above (F.C.C.V. flow control). He is using
                                             information only. One example of their         the superheat method and, based on the
using the largest allowable suction line     use might be to evaluate an existing
diameter for each tonnage results in a                                                      existing indoor and outdoor conditions,
                                             system. For instance, careful measure-         has determined that 10° superheat, at
pressure drop of less than 3 PSI per         ments of an existing 2-1/2 ton system,
100 eq. ft. in all cases, except the 1 ton                                                  the outdoor unit is required.
                                             installed with a 5/16" liquid line and
system (3.3 PSI).                            5/8" suction reveal the following: 110         His compound gauge indicates 63 PSIG
                                             linear ft., 8 short radius elbows. The         or 36° evaporating temperature. Adding
Obviously, if line sets exceed 100 eq. ft.   equivalent length, 110 + (8 x 5.7*)
significantly, there will be cases where                                                    10° to the 36° tells him that he should
                                             = 155.6 ft. (*from Table “C” page 10).         try for a 46° suction line temperature,
the suction line pressure drop exceeds       155.6 ft. x 12.7/100 = approx. 19.8 PSI
3.0 PSI. (This is a price we must pay for                                                   right? Wrong in this case!
                                             suction line pressure drop (more than six
long line sets.)                             times the ASHRAE recommendation).              His actual evaporating pressure is
In those cases, where long tubing                                                           63 PSIG plus 19.8 PSI pressure drop,
                                             The approx. 20% loss in capacity tells         or approx. 83 PSIG (49° plus.) The
runs result in higher suction line           us that our 2-1/2 ton system is delivering
pressure drops than desired, do not                                                         desired suction line temperature = 59°.
                                             2 tons. This 20% loss in capacity, to-         Attempting to charge to the 46° suction
use a suction line diameter larger than      gether with a 10% loss in efficiency,
those listed in Table “B,” page 10,                                                         line temperature would undoubtedly
                                             makes a very strong case for replacing         result in a severe overcharge. The
for the system tonnage. To do so             the line set with a properly sized line set.
would result in refrigerant velocities                                                      extreme pressure drop not only resulted
too low to ensure oil return.                                                               in very substantial losses in capacity and
                                             Assuming that the 5/8" O.D. suction            efficiency, but could easily be the cause
                                             line is to be replaced with a 7/8" O.D.        of a severe overcharge (and possibly a
The net capacities indicated in Table “B”    suction line, and the installer was able
for the various equivalent lengths show                                                     compressor failure).
                                             to reduce the number of elbows to six
that there is approx. 1% loss in capacity    (long radius) elbows: the equivalent
for each 1.0 PSI of pressure drop. (Effi-                                                   Always select one of the suction line
                                             length = 110 + (6 x 5.3) or 141.8 ft.,         sizes listed in Table “B” for the nominal
ciency losses are approx. .5% per PSI        2.0 PSI/100 ft. (from Table “B”) x
of pressure drop.)                                                                          tonnage of your system. Oil return will
                                             141.8/100 = approx. 2.8 PSI suction line       be assured with any of the listed sizes.
                                             pressure drop.                                 The lowest possible capacity losses
If the net capacity, indicated for the
calculated equivalent length, falls a                                                       consistent with adequate oil return are
                                             The 30000 BTUH system will now deliver         afforded by the largest tube size listed.
little short of your requirement (and        approx. 29500 BTUH (140 eq. ft. value).
you have selected the largest allowable                                                     Short tubing runs may provide accept-
                                             The loss in efficiency is now less than        able losses with a smaller tube size.
tube diameter) one of the following          1%, which will be reflected in the
hints may remedy the situation:                                                             Net capacities are listed for all approved
                                             owner’s electric bill (favorably).             sizes for equivalent lengths up to 240 ft.
1 – Move the outdoor unit closer,
if possible.                                 (The installer, when replacing the
2 – Use as few elbows as possible, and       undersized refrigerant lines, should
use long radius elbows to reduce the         convert the indoor unit to expansion
equivalent length.                           valve flow control and make sure that
32-3009-03                                                        9
                                                                    Application
                                                                    Guide
                                                                                         Table “B”
                                               Allowable Suction Line Diameters and Net Capacities
               Tube    Nominal       P.D.                                                    Net Capacity For Equivalent Length
 Nom.          Size    Capacity      Per
 Tons          (In.)    (25 Ft.)    100 Ft.         40          60            80           100            120       140     160        180      200      220       240
  1.0           1/2     14685        11.7          14425      14080         13735         13390           13045      —       —          —        —        —         —
                5/8     15000         3.3          14925      14825         14725         14625           14525    14425   14325      14225    14125    14025     13925
  1.5           5/8     18000          4.7         17875      17705         17535         17365           17195    17025   16855      16685    16515    16345     16175
                3/4     19305          1.8         19255      19185         19115         19045           18975    18905   18835      18765    18695    18625     18555
                5/8     23695          8.1         23405      23020         22635         22250           21865    21480   21095      20710      —        —         —
  2.0           3/4     24000          3.0         23890      23745         23600         23455           23310    23165   23020      22875    22730    22585     22440
                7/8     24100          1.3         24055      23990         23925         23860           23795    23730   23665      23600    23535    23470     23405
                5/8     29370        12.7          28810      28665         27320         26575           25830      —       —          —        —        —         —
  2.5           3/4     30000         4.6          29795      29520         29245         28970           28695    28420   28145      27870    27595    27320     27045
                7/8     30195         2.0          30105      29985         29865         29745           29625    29505   29385      29265    29145    29025     28905
  3.0           3/4     35670          6.5         35320      34855         34390         33925           33460    32995   32530      32065    31600    31135     30670
                7/8     36000          2.8         35850      35650         35456         35250           35050    34850   34650      34450    34250    34050     33850
                3/4     41475          8.8         40930      40200         39470         38740           38010    37280   36550      35820      —        —         —
  3.5           7/8     42000          3.8         41760      41440         41120         40800           40480    40160   39840      39520    39200    38880     38560
               1-1/8    42295          1.0         42230      42145         42060         41975           41890    41805   41720      41635    41550    41465     41380
  4.0           7/8     47570          4.9         47220      46755         46290         45825           45360    44895   44430      43965    43500    43035     42570
               1-1/8    48000          1.3         47905      47780         47655         47530           47405    47280   47155      47030    46905    46780     46655
                7/8     59175          7.5         58510      57620         56730         55840           54950    54060   53170      52280    51390      —         —
  5.0          1-1/8    60000          2.0         59820      59580         59340         59100           58860    58620   58380      58140    57900    57660     57420
               1-3/8    60195           .7         60130      60045         59960         59875           59790    59705   59620      59535    59450    59365     59280
  6.0          1-1/8    72000          2.8         71700      71295         70890         70485           70080    69675   69270      68865    68460    68055     67650
               1-3/8    72325          1.0         72215      72070         71925         71780           71635    71490   71345      71200    71055    70910     70765
               1-1/8    89390          4.2         88825      88075         87325         86575           85825    85075   84325      83575    82825    82075     81325
  7.5          1-3/8    90000          1.5         89795      89525         89255         88985           88715    88445   88175      87905    87635    87365     87095
               1-5/8    90205           .6         90125      90015         89905         89795           89685    89575   89465      89355    89245    89135     89025
               1-1/8   118560          7.4     117245        115490        113785         111980        110225    108470   106715     104960   103205   101450     —
  10.0         1-3/8   120000          2.6     119230        118905        118280         117655        117030    116405   115780     115135   114530   113905   113280
               1-5/8   120450          1.1     120250        119985        119720         119455        119190    118925   118660     118395   118130   117865   117600
Note 1: Shaded values = more than 10% capacity loss.
Note 2: Blank space = more than 15% capacity loss.
                                                                                                   10                                                            32-3009-03
                                                                  Application
                                                                  Guide
Piping Limits
1. Compressor Protection
     A. Suction line accumulators are no longer required (on 1 through 10 ton systems).
     B. Protect reciprocating compressors as follows:
        • Up to 80 linear feet of rated tube sizes: OK as shipped.
        • Over 80 linear feet , or oversized lines: Apply sump heat1 and TXV indoor metering device.13
     C. Protect Scroll compressors as follows:
        • Up to 12 lbs. R-22 system charge2: OK as shipped.
        • 10.5 lbs. for R-410A.
        • Over 12 lbs. R-22 system charge2: Apply sump heat and TXV indoor metering device.1
     D. Liquid line solenoid valves (straight cooling systems only):*
        Cycle solenoid valve with compressor (no pump down).
        • If compressor is above the indoor unit, locate the liquid line solenoid valve near the indoor unit.
        • If compressor is below the indoor unit, locate the liquid line solenoid valve within 25 ft. of compressor.
     Note: If pump down is desired, a discharge check valve must be installed in the discharge line. (Locate the liquid line solenoid valve near the indoor unit.)
     * Liquid line solenoid valves are not required with TXV systems.
5. R-410A Systems
     A. Maximum linear length = 200 ft.
     B. Maximum linear liquid lift = 60 ft.
     C. Maximum linear suction lift = 200 ft.
6. Traps
     A. Traps are not recommended.
Notes:
1 If not factory furnished.
2 System charge = nameplate charge, plus tubing allowance (See page 12 for Tubing Allowance).
3 If a non-bleed TXV is applied to a single phase Reciprocating compressor system, a hard start kit will be required (not required with Scroll compressor systems).
4 Pub. No. 32-3312-01 (Windows® based) computer software contains complete piping data, including high rise systems, R-410A, pressure drops, net capacity,
   system charge, tube sizes, etc.
32-3009-03                                                                                     11
                                                                        Application
                                                                        Guide
Application Requirements                                                Liquid lifts up to 60 linear ft.                     Suction line accumulator is not required
Systems within the limits indicated                                     Suction lifts up to 200 linear ft.                   on 1 through 10 tons.
above, or systems beyond those limits
                                                                        This includes R-410A systems (recom-                 Do not apply pump down cycle, unless
which are equipped with compressor
                                                                        mended line sizes only), but does not                discharge check valve has been applied.
sump heat and indoor TXV refrigerant
                                                                        include two compressor systems which                 (See page 11.)
control, are O.K. for:
                                                                        are limited to 80 linear ft. and to lifts
Linear Lengths up to 200 ft.
                                                                        (liquid or suction) of up to 25 linear ft.
                                                                                                       12                                                                    32-3009-03
                                                    Application
                                                    Guide
                   Figure 3                                                       Figure 2
         Thermal Bulb Location                      Typical Straight Cooling System
                                                    (Outdoor Unit Above Indoor Unit)
LIQUID LINE
                                                                                  Figure 4
                                                                                 Tubing Hints
                  SUCTION LINE
                LARGER THAN 7/8"
STRAP HANGER
                                                                                       SADDLE
                                                               SADDLE SUPPORT
32-3009-03                                                          13
                                                                                        Figure 5
                                                                                    NO V                                                                          No V
Infiltration or Ventilation                 CFMo            2. CFMo =                                                                        2. CFMo =
                                                                                  60 min./hr.                                                                   60 min./hr.
Total Heat (HT) Btuh 5. HT = CFMT x 4.5 x (h1 – h2) = Btuh 6. HT = CFMT x 4.5 x (h2 – h1) = Btuh
Sensible Heat (HS) Btuh 7. HS = CFMT x 1.08 x (T1 – T2) = Btuh 8. HS = CFMT x 1.08 x (T2 – T1) = Btuh
Latent Heat (HL) Btuh 9. HL = CFMT x .68 x (W1 – W2) = Btuh 10. HL = CFMT x .68 x (W2 – W1) = Btuh
                                                                                   CFMo                                                                          CFMo
Entering Air Temperature (T1)               °F. D.B.       11. T1 = t1 +                x (t2 – t1) = °F.D.B. 1                             12. T1 = t1 –             x (t1 – t2) = °F.D.B. 2
                                                                                   CFMT                                                                          CFMT
 (Mixed Air)
                                                                 1 If duct heat gain is a factor, add to T1:                                    2 If duct heat loss is a factor, subtract from T1:
                                                                         Duct Heat Gain (Btuh)                                                          Duct Heat Loss (Btuh)
                                                                            CFMT x 1.08                                                                    CFMT x 1.08
                                            Btu/lb.                                    HT                                                                            HT
Enthalpy – Leaving Air (h2)                                17. h2 = h1 –                                  = Btu/lb. dry air                 18. h2 = h1 +                          = Btu/lb. dry air
                                            dry air                                 CFMT x 4.5                                                                    CFMT x 4.5
                                                           19. Refer to Enthalpy Table and read W.B. temperature                            20. Refer to Enthalpy Table and read W.B. temperature
Leaving Air W.B. Temperature                °F.W.B.
                                                               corresponding to enthalpy of leaving air (h2) (see #17).                         corresponding to enthalpy of leaving air (h2) (see #18).
Heat Required to Evaporate
Water Vapor Added to                         Btuh          21. HL = CFMo x .68 (W3 – Wo) = Btuh                                             22. HL = CFMo x .68 (W3 – Wo) = Btuh
Ventilation Air
                                                                               Excess Latent Capacity
                                                                                                                                                                     HL loss Btuh (see #22)
Humidification Requirements
                                           Lbs.
                                          water/hr.
                                                           23.
                                                                 (   Moisture )
                                                                     Make up = of System x % Run Time
                                                                                      1060 Btu/lb.
                                                                                                                           = lbs./hr.
                                                                                                                                               (
                                                                                                                                            24. Make up =
                                                                                                                                                Moisture    )             1060 Btu/lb.
                                                                                                                                                                                                  = lbs./hr.
* See Enthalpy of air (Total Heat Content of Air) Table for exact values.
                                                                                                   14                                                                                                   32-3009-03
                                               Application
                                               Guide
32-3009-03                                                                15
                                                                     Application
                                                                     Guide
                                                                                              Example
Given:              Rated system capacity = 42000 BTUH, 68 linear ft., 4 long radius elbows (no solenoid valve or other source of
                    pressure drop): 20 ft. liquid lift.
Step #1             20 x .43 = 8.6 PSI pressure drop due to liquid lift. 50 minus 8.6 = 41.4 PSI available for friction loss.
Step #2             68 + (4 x 3.2) = 80.8 eq. ft. (See Table “C,” page 10, for equivalent lengths.)
Step #3             Referring to Table A-R, we find that 80 ft. of 5/16" liquid line, (42,000 BTUH) = 30.7 PSI pressure drop.
                    (Well within our 41.4 PSI limit.)
                                                                                                    16                                                                                   32-3009-03
                                                                    Application
                                                                    Guide
32-3009-03                                                                                         17
                                               Application
                                               Guide
CHAPTER II                                     umes of vapor, as well as substantially          heat exchange capacity to provide the
                                               reducing the capacity of the metering            required additional subcooling for
High Rise Heat Pump                            device because of the mixture of vapor           systems up through 10 tons (and is
Applications                                   and liquid it would be forced to handle.         rated for both R-22 or R-410A).
(R-22 and R-410A)                              It is not unusual for high rise systems          It should be noted that although the
The demand for greater vertical separa-        to operate with total liquid line pressure       heat exchanger used with the high rise
tion for the indoor and outdoor sections       drops in excess of 100 PSI (R-22) with no        system is designed as a suction to liquid
of heat pump systems, over the years,          “flashing” (even higher with R-410A.)            heat exchanger, it is not used in that
has lead to the development of the high                                                         manner. (Suction gas is not routed
rise system. Until this time, the maxi-        As mentioned earlier, the (windows)              through the heat exchanger.) Instead,
mum allowable liquid lift for R-22 sys-        computer piping program will call for            the normal liquid flow is through the
tems was approximately 60 ft. The 60 ft.       the subcooler when ever it is required,          suction side of the heat exchanger. A
lift resulted in a pressure drop (60 x .5)     size the capillary tube and call for any         small portion of the liquid is fed through
of 30 PSI, which left only 5 PSI of the        other required accessories. The rest of          the capillary tube to the other side of the
allowable 35 PSI for friction loss. Some-      this chapter is designed to help the sys-        heat exchanger where it is evaporated
what higher liquid lifts can be tolerated      tem designer who does not have access            to chill the liquid R-22 the required
with R-410A systems, because the               to the computer program to apply the             number of degrees. A 3/8" O.D. suction
allowable (total) liquid line pressure         high rise system.                                line (insulated) is run from the heat
drop for R-410A systems is 50 PSI, also                                                         exchanger (located at the bottom of
                                               The heat exchanger used with the high            the liquid lift) to the common suction
the loss for each foot of liquid lift is .43
                                               rise system (refrigeration research              line of the outdoor unit (between the
PSI versus .50 PSI for R-22.
                                               #H-100, or Heat-X 3/4 HP) has sufficient         switch-over valve and the compressor).
However, when liquid lifts become high
enough to produce a total liquid line
pressure drop (lift + friction) of over
35 PSI with R-22 systems or 50 PSI with                                              Table “D”
R-410A systems, the high rise system
with subcooler will be required.                                          Subcooling Heat Exchangers
The high rise system is to be applied to
heat pump systems only, and only on
systems where the outdoor unit is above        ➤
the indoor unit. The indoor unit must
utilize expansion valve flow control.
                                                                     18                                                           32-3009-03
                                              Application
                                              Guide
The 3/8" O.D. suction line is teed into the   Figure 7 (below) indicates the hook-up                              door units. Note that there are now three
top of a horizontal common suction line,      for the heat exchanger and capillary                                connecting lines between the indoor and
or into the side of a vertical common         tube. The heat exchanger is to be located                           outdoor units (liquid line, gas line and a
suction line, thus preventing the drain-      at the bottom of the liquid lift (near the                          3⁄8” insulated suction line) running from
age of oil down the 3/8" O.D. tube.           indoor unit).                                                       the heat exchanger to the common suc-
                                              Figure 8, page 20, shows the piping                                 tion line (between the switchover valve
The fact that a small portion of the liquid   hook-up between the indoor and out-                                 and the compressor).
R-22, being circulated, is diverted to the
heat exchanger, and boiled to a vapor,
has no effect on system capacity. While a
slightly reduced quantity of liquid R-22 is
delivered to the system evaporator, each                                                   Figure 7
pound contains less heat, because of the
additional subcooling and the net cool-                               Piping Detail – Heat Exchanger
ing effect is the same. So what have we
accomplished? We have delivered 100%
liquid to the system expansion valve, in
spite of liquid line pressure drops of 100
PSI or more.
The heat exchanger and capillary tube
are to be purchased at your local parts
wholesaler.
Table “D,” page 18, provides a picture        To liquid line
and dimensional information for the           connection at
heat exchanger.                               outdoor unit                                                                       Insulated 3/8" line.
                                                                                                                                 Tee into common suction
Note that the heat pump indoor unit                                                                                              line, between S.O.V. and
                                                                                Refrigeration Research H-100 or
                                         Large connection
                                         to minimize
                                         pressure drop
                                                                                                                                 Small connection
32-3009-03                                                       19
                      Application
                      Guide
                                           Figure 8
High Lift Heat Pump Piping Schematic (Outdoor Unit above Air Handler)
Sub-Cooler
       Sub-Cooler
       Capillary
                                                                                                              Air Handler with
                            TXV                                                                               Expansion Valve Coil
Air Handler
                                                                         20                                                                                32-3009-03
                                               Application
                                               Guide
32-3009-03                                                            21
                                            Application
                                            Guide
CHAPTER III                                 4 – Unusually high latent loads, which       The remainder of the chapter will cover
                                            require very low evaporator tempera-         the field application of hot gas bypass,
Hot Gas Bypass                              tures, must limit capacity at reduced        including, bypass valve selection (siz-
(Capacity Modulation)                       load or reduced outdoor temperatures.        ing), sizing of the hot gas line, and infor-
                                            (Evaporator coils may frost.)                mation on accessories, such as solenoid
                                                                                         valves, auxiliary side connectors, etc.
Introduction                                5 – Fluctuating loads which may lead to
                                            excessive short cycling of equipment.        Some of the concerns which will be
Why Capacity Modulation?                                                                 covered are:
The typical residential cooling system      How Can We Modulate
performs reasonably well, with a simple                                                  • Oil return
                                            System Capacity?
on/off control (system thermostat).                                                      Introducing the hot gas at the evaporator
                                            1 – The application of multiple systems,
                                                                                         inlet (side port distributor, or, auxiliary
While cooling loads vary considerably       whenever practical, results in capacity
                                                                                         side connector), ensures adequate refrig-
from design conditions, to mild weather     modulation, without sacrificing effi-
                                                                                         erant velocity for oil entrainment,
cooling, the changes are usually gradual.   ciency, and should be the first consider-
                                                                                         through the evaporator, and any
Solar and internal loads as well as the     ation. (Multiple systems also have the
                                                                                         suction lifts.
flywheel effect of the home and furnish-    inherent advantage of not “putting all
ings tend to keep short cycling of the      your eggs in one basket,” in the event of    • Proper superheat in suction gas
system, in mild weather, within accept-     a system failure.) If very precise control     to compressor
able limits. Humidity control suffers       of capacity modulation is required, hot
somewhat during mild weather, but           gas bypass can be applied to the first       The refrigerant metering device must
with a carefully sized system, it is        stage system. An example of this could       be a thermostatic expansion valve. The
usually tolerable.                          be two five ton systems matched with a       valve will automatically compensate for
                                            dual circuited 10 ton air handler. Apply-    the highly superheated hot gas, and pro-
Loads, which vary more dramatically,        ing hot gas bypass to the first stage sys-   vide normally superheated suction gas
and over shorter periods of time, how-      tem, only, provides modulation from          to the compressor (thus preventing
ever, will often require some means of      10 tons to near 5 tons when both stages      compressor overheating or slugging).
capacity modulation in order to:            are called for. When first stage, only, is
                                            called for, modulation is from 5 tons to     • Undersizing of bypass valve
• Provide better humidity control           near zero.
• Provide better temperature control                                                     Select a valve capable of bypassing the
• Reduce short cycling problems             2 – Cylinder unloading. This method          maximum required, at the existing con-
                                            of capacity modulation is very effective     ditions, at the time of the minimum load.
• Avoid frosting of evaporator coils        on larger systems (factory applied). The     (Design load minus minimum load =
                                            industry has found that cylinder unload-     required bypass.) If the system is signifi-
Some examples of loads requiring
                                            ing is not cost-effective on systems of      cantly oversized, system capacity minus
capacity modulation are:
                                            10 tons capacity or less.                    minimum load = required bypass.
1 – High percentages of outside air.
                                            3 – Hot gas bypass. Hot gas bypass,          Allow for pressure drops through the
The current emphasis on improving           properly applied, provides very precise      sideport distributor, or auxiliary side
indoor air quality often leads to high      capacity modulation with a moderate          connector, hot gas line, solenoid
outside air percentages. Code require-      loss in efficiency. (Some energy is ex-      valve, etc.
ments, or high exhaust requirements         pended in pumping the bypassed gas
are also contributors. It is generally      through the system, which provides no        (An oversized bypass valve presents
accepted, that outside air percentages      cooling effect.)                             no problem, since it is a modulating
greater than 25% require capacity                                                        type valve, and will open only as far
                                            For applications where cylinder unload-      as is required. To maintain the desired
modulation.
                                            ing is not available, hot gas bypass is      evaporator pressure.) If more bypass is
2 – On/off type loads such as lighting,     undoubtedly the method of choice, if the     required than is available from a single
industrial processes, etc. can result in    application of multiple systems is not       valve, two valves can be piped in paral-
wide variations in loads.                   practical. (Hot gas bypass can be com-       lel. (Adjust both valves to open at the
                                            bined with multiple systems to provide       same pressure.)
3 – Special applications requiring very     even more precise modulation.)
close control of humidity, temperature,
or both.
                                                               22                                                           32-3009-03
                                              Application
                                              Guide
Low head pressure problems are likely         Operation – Hot Gas                                         the valve to the limit of its stroke. The
to occur with hot gas bypass applica-         Bypass Valve                                                amount of pressure change required to
tions due to:                                                                                             move the valve from the closed position
                                              The hot gas bypass regulator or dis-
                                                                                                          to its rated open position varies with
1 – Operation at low outdoor ambients         charge bypass valve automatically re-
                                                                                                          the refrigerant used and the minimum
                                              sponds to changes in suction pressure.
                                                                                                          evaporator temperature desired. Most
2 – The bypassed gas bypasses the             When the refrigerant evaporating pres-
                                                                                                          manufacturers’ valve capacity ratings
condenser, further reducing head pres-        sure is above the bypass valve setting,
                                                                                                          are based on a 6°F change in suction
sure. (The published low ambient limit        the valve remains closed. When the
                                                                                                          temperature (approximately 9 PSI for
does not apply when hot gas bypass is         cooling load drops, the suction pressure
                                                                                                          R-22). In other words, a 6°F change in
utilized.) The application of a head pres-    drops below the bypass valve setting
                                                                                                          evaporator refrigerant temperature is
sure control is highly recommended.           and the valve begins to open, bypassing
                                                                                                          required to move the valve from the
                                              a portion of the hot gas directly into the
                                                                                                          fully closed position to the rated open
                                              low side, thereby, maintaining the com-
                                                                                                          position or from the rated open position
                                              pressor suction pressure at a relatively
Hot Gas Bypass                                high level. The amount of valve opening
                                                                                                          to the fully closed position. This same
                                                                                                          valve would be able to open further if
The purpose of a hot gas bypass system        is proportional to the change in the suc-
                                                                                                          an 8°F or a 10°F change in evaporator
is to artificially load the compressor        tion pressure, thereby, providing capac-
                                                                                                          refrigerant temperature, which results
upon a decrease in evaporator load for        ity modulation. Capacity reduction over
                                                                                                          in a lower leaving air temperature,
one or more of the following reasons:         a wide range is possible with proper
                                                                                                          could be tolerated.
                                              selection of the components. This is
•   Prevent operation of the compressor       shown in the sample problem. (See                           Note 1: The values given in manufactures’ catalogs are valve
                                                                                                          capacities – not system capacities.
    at excessively low suction pressures.     page 23)
                                                                                                          Note 2: Use of discharge bypass valves alone will not main-
    This could cause compressor short                                                                     tain adequate head pressure for proper operation under low
    cycling, resulting in temperature and     If the suction pressure continues to drop                   outdoors ambient operating conditions (below 50 – 55°F).*
    humidity control variation.               below the valve setting, the valve contin-                  It will be necessary to use an approved low ambient control-
                                                                                                          ling device to maintain adequate high side pressure under
                                              ues to open until the limit of its stroke is                low ambient operating conditions. If bypassing 50% or more,
•   Prevent a significant drop in evapora-    reached. Most applications cannot toler-                    head pressure control is a must.
    tor temperature where reasonably          ate sufficient pressure change to open
    constant conditions must be main-
    tained. This is often necessary for
    precise temperature control.
                                                                                                   Figure 9
•   Prevent frosting of the evaporator coil
    causing serious loss of capacity be-                      Recommended Piping Hook-Up for Hot Gas Bypass
    cause of restricted airflow, and
    potential damage to the compressor.
32-3009-03                                                                23
                                             Application
                                             Guide
The cutaway view (below) of a typical        Application                                     •   Locate the bypass valve close to the
sporlan hot gas bypass valve illustrates                                                         compressor to avoid the accumula-
its construction.                            Figure #9 indicates the only recom-                 tion of significant amounts of liquid
                                             mended piping hook up for hot gas by-               refrigerant in the hot gas line when
When evaporator pressure (sensed             pass applied to Trane U.P.G. products.              not bypassing.
through the external equalizer line) falls   Introducing the hot gas at the inlet to the
                                             evaporator provides proper refrigerant          •   Externally equalized bypass valves
below the setpoint of the valve, spring                                                          are a must.
pressure against the diaphragm over-         velocity for oil return through the evapo-
comes evaporator pressure and begins         rator and suction lifts, if present (regard-    •   Adjustable bypass valves are recom-
to move the piston off its seat. This al-    less of the amount being bypassed).                 mended.
lows the high pressure, hot gas to flow      Good mixing of the bypassed gas with            •   Do not apply evaporator pressure
through the valve to maintain low side       the evaporating refrigerant takes place             regulating valves to Trane D.P.G.
pressure. When evaporator pressure           and the system expansion valve com-                 products (Trane or American
has fallen approx. 9 PSI (R-22) below        pensates for the added superheat.                   Standard).
the setpoint, the valve will be open to
its rated position.                          This hook-up does require either a side-
                                             port distributor or an auxiliary side con-
When evaporator pressure rises above         nector. In some cases, depending on the         Heat Pump Systems
the setpoint, it forces the valve closed.    size of the original distributor and the        When applying hot gas bypass to a heat
                                             required amount of bypass, a larger             pump system:
                                             distributor could be required.
                                                                                             A — The hot gas bypass valve inlet must
                                             An externally equalized bypass valve is         be connected to the discharge line be-
                                             recommended for all applications.               tween the compressor and the
                                                                                             switchover valve.
                                             Bypass valves should be sized gener-
                                             ously, in order to accommodate pressure         B — A hot gas solenoid valve must be
                                             drops in the hot gas line, etc.                 installed upstream of the bypass valve,
             Figure 10                                                                       and wired so that it opens in the cooling
                                             A hand valve installed upstream of the          mode only.
                                             bypass valve facilitates pump down for
     Typical Sporlan Hot Gas                 service operations. The bypass valve            C — Low head pressure problems
          Bypass Valve                       must be installed close to the tee in the       during bypass may occur, requiring
                                             discharge line, to prevent the accumula-        some means of head pressure control.
                                             tion of liquid R-22 in the hot gas line
                                             when not bypassing. External equalizer          D — If a 24 volt solenoid valve is used,
                                             lines should be connected approxi-              be sure that adequate transformer
                                             mately 6" downstream of the TXV                 capacity is available.
                                             Thermal Bulb. (The hot gas bypass
                                             valve external equalizer can be con-            E — Apply multiple systems whenever
                                             nected to the suction line near the out-        possible, to achieve capacity modula-
                                             door unit if desired.)                          tion.
                                                                  24                                                          32-3009-03
                                                         Application
                                                         Guide
Selecting The Hot Gas                                    very often, require the application of                    tions. Table “E” is based on the amount
                                                         a head pressure control device.                           (tons) of bypass required.
Bypass Valve
                                                         Pressure drops in the hot gas line,                       Chart “X,” page 24, can be used to calcu-
The bypass valve must be capable of
                                                         solenoid valve (if used), side-port dis-                  late the pressure drop in the hot gas line,
bypassing the difference between the
                                                         tributor (or auxiliary side connector                     if desired.
design load and the anticipated mini-
mum load (at the conditions existing                     plus distributor), all tend to reduce the                 Table “F” below, lists information on
when the minimum load occurs).                           capacity of the hot gas bypass valve.                     Sporlan Bypass Valves. (The selections
                                                         (Size it generously.)                                     in Table “F,” assume a 26°F evaporating
Anticipated lower head pressures at                                                                                temperature, and 80°F condensing tem-
the minimum load conditions (further                     Table “E” provides a simple method, for                   perature, for the minimum load condi-
aggravated by the fact that the bypassed                 the selection of a hot gas bypass valve,                  tions.) The adjustment range of 0 to
gas is bypassing the condenser) will                     and the hot gas line, for average condi-                  80 PSIG is recommended for R-22.
                                                                        Table “E”
                                          Quick Selection Table For Hot Gas Bypass Valves
                                                                        R-22 Refrigerant
                                                                                    Amount of Bypass Required
                                                                                (Design Load Minus Minimum Load)
                                                0 – 2 Tons                     2.5 – 4 Tons           4.5 – 8 Tons                              8.5 – 10 Tons
                                                 Sporlan                         Sporlan                Sporlan                                    Sporlan
   Hot Gas Bypass Valve                          ADRSE-2                         ADRPE-3                ADRHE-6                                    DRHE-6
                                                (or Equiv.)                     (or Equiv.)            (or Equiv.)                               (or Equiv.)
      Recommended
     Hot Gas Line O.D.
      Up to 50 Eq. Ft.                           1/2" O.D.                       5/8" O.D.                         3/4" O.D.                         7/8" O.D.
      51 to 100 Eq. Ft.                          1/2" O.D.                       5/8" O.D.                         7/8" O.D.                         7/8" O.D.
                                                                        Table “F”
                                                  Discharge Bypass Valve Capacities – Tons
 Capacities based on 6°F evaporator temperature change from closed to rated opening, discharge temperature 30°F above isentropic compression, 25°F
 superheat at the compressor, 0° subcooling, and includes both the hot gas bypassed and liquid refrigerant for desuperheating, regardless of whether the
 liquid is fed through the system thermostatic expansion valve or an auxiliary desuperheating thermostatic expansion valve.
                                                Minimum Allowable Evaporator Temperature At The Reduced Load – °F
               ADRS–2          0/30       —        —      —      —      —      —      —      —        —     2.93   3.77   4.73   2.82   3.63   4.57    2.72   3.51   4.42
               ADRSE–2         0/80      2.65     3.40   4.26   2.69   3.45   4.34   2.71   3.48     4.37   2.88   3.70   4.66   —      —      —       —      —      —
   22          ADRP–3          0/30       —        —      —      —      —      —      —      —        —     5.56   7.16   9.00   5.61   7.23   9.10    5.47   7.06   8.90
               ADRPE–3         0/80      4.50     5.78   7.25   4.72   6.06   7.61   4.80   6.17     7.75   5.24   6.73   8.47   —      —      —       —      —      —
                               0/30       —        —      —      —      —      —      —      —        —     10.5   13.5   17.0   10.6   13.7   17.2    10.3   13.3   16.7
               ADRHE–6
                               0/80      6.89     8.84   11.1   7.46   9.58   12.0   7.68   9.87     12.4   8.12   11.4   14.4   —      —      —       —      —      —
                                                                 Adjustable “Remote Bulb” Models
    12                        25/35      5.51     7.11   8.96   4.86   6.26   7.89
                                                                                                   These models are recommended for air conditioning
    22         DRHE–6         55/70      14.3     19.0   24.0   12.7   16.4   20.6
                                                                                                   temperature ranges only.
   134a                       25/35      7.03     9.26   11.9   6.06   7.98   10.2
   502                        65/80      13.9     18.2   22.6   12.6   15.8   19.4
32-3009-03                                                                      25
                                                                                                                                          Chart “J”
                 Pressure Drop in R-22 Vapor Lines
                                                                                                                                                                                        5 Tons of Bypass with a 7/8" O.D. Hot
                                                                                                                                                                                        Gas Line = 5.4 PSI/100' Pressure Drop.
                                                                                                                                                                                                   PRESSURE DROP — PSI / 100 FT.
                                                                                                                                                              0.1               .2     .3     .4   .5 .6 .7 .8 .9 1.0                        2            3        4      5       6 7 8 9 10
80°
                                      L
                                                                                                                                                                                                                                                                              R
                                   PE
                                                                                                                                                                                                                                                                            PO
                                 TY
                                                                                                                                                                                                                                                                          VA
                               D
                                               D
                                                        D
                                                                  D
                                                                                                                                                                                                                                                                       °F
OD
                                                                                              OD
                                                                                                                                                         OD
                                                                                                                                                         OD
                                                                                                                                                                           OD
                                                                             OD
                                                                                                                             OD
                                                                                                                                          OD
                                                                                                           OD
                                                                                                                                                                                                                                                                     20
                             "O
                                             "O
                                                      "O
                                                                "O
                                                                                                                                                                                                                                                                   N
                                                                                                                                                                                                                                                                  R
/8"
/8"
                                                                                          /8"
                                                                                                                                                    /8"
                                                                                                                                                    /8"
                                                                                                                                                                       /8"
/8"
                                                                         /8"
                                                                                                                                                                                                                                                                 O
                                                                                                       /8"
                                                                                                                                                                                                                                                                P
                                                                                                                                                   1
                                                                                                                                                                      1
                          1/2
                                          5/8
                                                   3/4
                                                             7/8
                                                                                                                                                                                                                                                               ED
                                                                                                                                                  -
                                                                                                                                                                     -
4-1
                                                                                                                      2-1
                                                                                                                                                                                                                                                              VA
2-5
                                                                                       1-3
                                                                                                                                                 3
                                                                                                                                                 3-5
                                                                                                                                                                    5
                                                                      1-1
                                                                                                    1-5
                                                                                                                                                                                                                                                            BAS
                                                                                                                                                                                                                                                           ED
                                                                                                                                                                                                                                                          )
                                                                                                                                                                                                                                                         T
                                                                                                                                                                                                                                                                        Guide
                                                                                                                                                                                                                                                       (°F
                                                                                                                                                                                                                                                     RA
                                                                                                                                                                                                                                                    P.
                                                                                                                                                                                                                                                   TU
                                                                                                                                                                                                                                                  M
                                                                                                                                                                                                                                                 A
                                                                                                                                                                                                                                                TE
                                                                                                                                                                                                                                              )S
                                                                                                                                                                                                                                             D.
                                                                                                                                                                                                                                           (°F
                                                                                                                                                                                                                                           N
                                                                                                                                                                                                                                        O
                                                                                                                                                                                                                                        P.
26
                                                                                                                                                                                                                                      C
                                                                                                                                                                                                                                     EM
                                                                                                                                                                                                                                S
                                                                                                                                                                                                                                AP
                                                                                                                                                                                                                               E
                                                                                                                                                                                                                              V
                                                                                                                                                                                                                             N
                                                                                                                                                                                                                             E
                                                                                                                                                                                                                           LI
                                                                                                                                                                                                                         E
                                                                                                                                                                                                                        G
                                                                                                                                                                                                                                                                        Application
                                                                                                                                                                                                                       R
                                                                                                                                                                                                                      E
                                                                                                                                                                                                                     N
                                                                                                                                                                                                                    HA
                                                                                                                                                                                                                   LI
                                                                                                                                                                                                                 ISC
                                                                                                                                                                                                                N
                                                                                                                                                                                                               D
                                                                                                                                                                                                              IO
                                                                                                                                                                                                            CT
                                                                                                                                                                                                          SU
                                                                                                                                                                                                      0 10 20 30 40 50       0  0  0 0
                                                                                                                                                                                                                           –4 –3 –2 –1
                                                                                                                                                                                                                             0
                                                                                                                                                                                                                           –5
                                                                                                                                                                                                                             0
                                                                                                                                                                                                                           –6
             1        2           3       4   5             10        20          30           50               100               200          300   500   1000                 2000   3000        5000             10,000                20,000       30,000
                      FLOW RATE — LB / MIN
32-3009-03
                                              Application
                                              Guide
Figures 11 and 12 on this page and 13         a 26° evaporating temperature (9.46 x                         Figure 11
on page 26 provide information on             .95 = approx. 9.0 tons). The above values
accessories for hot gas bypass applica-       are based on a 10 PSI pressure drop               Auxiliary Side Connectors
tions, plus capacity multipliers for eva-     across the solenoid valve. If no more
porating temperature changes other            than a 5 PSI pressure drop across the                                 ASC
than the standard 6°. (See Figure 12.)        solenoid valve can be tolerated, its          Distributor     Connection Sizes (Inches)
                                              capacity is 6.77 x .95 or approx. 6.4 tons       Type     ASC Type   Inlet Outlet Auxiliary
Figure 11 lists compatible distributor/       of bypass. (Selecting a hot gas bypass         Number     Number     ODM      ODF       ODF
auxiliary side connector combinations,        valve with some excess capacity, would        1620, 1622    ASC-5-4     5/8       5/8          1/2
complete with fitting sizes. (O.D.M. =        allow us to use the 10 PSI valve.) The        1112, 1113    ASC-7-4     7/8       7/8          1/2
outside diameter, male and O.D.F. =           solenoid valve’s capacity would be            1115, 1116    ASC-9-5    1-1/8     1-1/8         5/8
outside diameter, female.)                    derated somewhat more, assuming a             1117, 1126 ASC-11-7      1-3/8     1-3/8         7/8
Figure 12 lists bypass valve capacity         condensing temperature of 80° on a            1125, 1127
                                                                                                       ASC-13-9      1-5/8     1-5/8         1-1/8
multipliers for evaporating temperature       mild day. (The Table in Figure 13 is based       1143
changes, other than 6°F. Note that the        on a 100° condensing temperature.)
capacity multiplier for a 2°F evaporating     Figure 14, page 27, lists capacities for
change is .70 (26° evaporating tempera-       liquid line solenoid valves. (Do not con-                    Figure 12
ture). A 26° refrigerant evaporating          fuse Figure 14 with Figure 13, which
temperature, with normal airflows’            covers hot gas solenoid valves.) Much
                                                                                                     Capacity Multipliers
will result in a coil surface temperature     larger port sizes are required to handle
above 32°F. (Frosting should not occur.)                                                    For Evaporator Temperature Changes
                                              R-22 vapor.                                   Other Than 6°F Nominal Change
Figure 13 lists capacities of hot gas sole-                                                 Evaporator          Evaporator Temperature °F
                                              The circled values in Figure 14 indicate
noid valves. Hot gas solenoid valves are      that the ME9S230 (or 240) liquid line           Temp.
not usually required on straight cooling                                                     Change Refrigerant 40     26     20 0 and
                                              solenoid valve has a capacity of 8 tons           °F                                Below
applications, since pump down is not          at a 3 PSI pressure drop across the valve
normally permitted. (The hot gas sole-                                                                   12 & 134a   0.65    0.65     0.65
                                              (R-22).                                          2°                                             0.65
noid valve is required on heat pump                                                                      22 & 502    0.72    0.70     0.70
applications, however, in order to dis-       Could we use this solenoid valve on a            4°
                                                                                                         12 & 134a   0.80    0.80     0.80
                                                                                                                                              0.74
able the hot gas bypass during the            10 ton system? The answer is yes, if the                   22 & 502    0.87    0.85     0.85
heating mode.)                                4.7 PSI pressure drop does not result                      12 & 134a   1.11    1.11     1.11
                                                                                               8°                                             1.09
                                              in a total liquid line pressure drop of                    22 & 502    1.17    1.15     1.11
Note that a ME19S250 (or 270) hot gas         over 35 PSI (3.0 PSIG x (10/8)2 = 4.7 PSI).                12 & 134A   1.22    1.20     1.19
solenoid valve (R-22) has a capacity of                                                        10°                                            1.11
                                                                                                         22 & 502    1.34    1.27     1.25
9.46 tons x a correction factor of .95 for
32-3009-03                                                        27
                                                    Application
                                                    Guide
                                                                  Figure 13
                                             Hot Gas Solenoid Valve Capacities – Tons
Capacities based on 100°F condensing temperature, isentropic compression plus 50°F, 40°F evaporator and 65°F suction gas.
For other evaporator conditions use the multipliers in the table below.
          Valve Type                                                                                     Refrigerants
                                                             12                             22                           134a                        502
                   “E” Series
  “A” & “B”        Extended         Connections                                         Pressure Drop Across Valve Port – PSI
    Series        Connections         Inches           5           10             5                 10              5           10             5             10
     A3F1                —            1/4 SAE
                                                      0.26         0.35          0.37            0.51             0.31          0.42          0.30          0.42
     A3S1                —         1/4 or 3/8 ODF
      —                E5S120         1/4 ODF
                                                      0.61         0.84          0.88            1.22             0.74          1.00          0.72          1.00
      —                E5S130         3/8 ODF
    MB6F1                —            3/8 SAE
    MB6S1          ME6S130            3/8 ODF         1.01         1.43          1.51            2.10             1.27          1.74          1.30          1.70
    MB6S1          ME6S140            1/2 ODF
    MB9F2                —            3/8 SAE
      —            ME9S230            3/8 ODF         1.50         0.21          2.17            3.04             1.80          2.50          1.80          2.50
    MB9S2          ME9S240            1/2 ODF
   MB10F2                —            1/2 SAE
      —            ME10S240           1/2 ODF         2.30         3.20          3.37            4.69             2.80          3.90          2.80          3.80
   MB10S2          ME10S250           5/8 ODF
   MB14S2          ME14S250           5/8 ODF         3.20         4.40          4.58            6.40             3.80          5.30          3.80          5.30
   MB19S2          ME19S250           5/8 ODF
                                                      4.70         6.50          6.77            9.46             5.70          7.90          5.70          8.00
   MB25S2          ME19S270           7/8 ODF
   MB25S2          ME25S270           7/8 ODF
                                                      7.50         10.5          10.8            15.1             9.10          12.7          8.90          12.5
   MB25S2          ME25S290          1-1/8 ODF
                                                                          Correction Factors
                                                                          For evaporator temperatures at the reduced load condition
                                                                            Evaporator
                                                                          Temperature °F     40°          26°    20°      0°    -20°   -40°
                                                                            Multiplier       1.00         .95    .93      .87    .81   .75
                                                                           28                                                                              32-3009-03
                                                      Application
                                                      Guide
                                                                  Figure 14
                                      Liquid Line Solenoid Valve Capacity Selection Table
          Type Number                                                                         Tons of Refrigeration
                     “E” Series
   “A” & “B”         Extended                                                                 Pressure Drop – PSI
     Series         Connections
                                                        Port
       With Manual Lift Stem          Connections       Size                 1                                2                            3
         Normally Closed                (Inches)      (Inches)   12    22        134a   502      12      22       134a   502   12    22        134a   502
  A3P1       —       —         —     3/8 NPT Female
  A3F1       —       —         —      1/4 SAE Flare
                                                       .101      0.7   0.9       0.8    0.6      1.0    1.3       1.2    0.8   1.2   1.6       1.5    1.0
 A3S1        —     E3S120      —     1/4 ODF Solder
 A3S1        —     E3S130      —     3/8 ODF Solder
   —         —     E5S120      —     1/4 ODF Solder
                                                       .150      1.2   1.6       1.5    1.1      1.8    2.3       2.1    1.5   2.2   2.8       2.6    1.9
   —         —     E5S130      —     3/8 ODF Solder
   —      MB6P1      —         —     3/8 NPT Female
   —      MB6F1      —         —      3/8 SAE Flare
                                                       3/16      2.2   2.9       2.7    1.9      3.1    4.0       3.8    2.6   3.8   4.9       4.6    3.2
   —      MB6S1      —      ME6S130 3/8 ODF Solder
   —      MB6S1      —      ME6S140 1/2 ODF Solder
   —      MB9P2      —         —     3/8 NPT Female
   —      MB9F2      —         —      3/8 SAE Flare
                                                       9/32      3.6   4.7       4.4    3.0      5.1    6.6       6.2    4.3   6.2   8.0       7.5    5.2
   —         —       —      ME9S230 3/8 ODF Solder
   —      MB9S2      —      ME9S240 1/2 ODF Solder
32-3009-03                                                             29
Application
Guide
                   30                                                        32-3009-03
                                                                                                                                                                                        Refrigerant Pipe Sizing
                                                                                                                                                                                                    Worksheet
                  Project                                                                           Application
                                                                         ________________________________________ Outdoor Model                                                  ____________________________________
                  Address                                                                           Guide
                                                                         ________________________________________ Indoor Model                                                   ____________________________________
                                                                         ________________________________________                                           A.R.I. Capacity ____________________________________
                                                                            ■ Cooling                                 ■ Heat Pump
                  Piping Runs
Liquid line fittings/accessories equivalent total = (b) ________ ft Gas line fittings/accessories equivalent total = (x) ________ ft
                                                                                                     100
                                                                                                                =   100
                                                                                                                           =
                          32-3009-03                                                                                                               31
                                                             Standard Piping Size                                                          Oversized Piping
      Nominal
      Tonnage     #/Min
                             ARI (1)
                            Capacity     Gas
                                             Pipe Size
                                                    Liquid
                                                                Application
                                                                  Pressure Drops(1)
                                                                  Gas         Liquid
                                                                                            Lbs. R-22 (100 ft.)
                                                                                             Gas        Liquid        Gas
                                                                                                                          Pipe Size
                                                                                                                                 Liquid
                                                                                                                                              Pressure Drops(1)
                                                                                                                                              Gas         Liquid
                                                                                                                                                                     Lbs. R-22 (100 ft.)
                                                                                                                                                                      Gas        Liquid
                                                                (100 ft.)    (100 ft.)                                                      (100 ft.)    (100 ft.)
                                                                                            32                                                                          32-3009-03
             Application
             Guide
Notes
32-3009-03           33
Application
Guide
Notes
        34    32-3009-03
             Application
             Guide
Notes
32-3009-03           35
Literature Order Number
File No.                                                                      Pub. No. 32-3009-03     7/00
Supersedes                                                                    Pub. No. 32-3009-02     1/00
Stocking Location                                                                                   P.I. (L)
Since The Trane Company has a policy of continuous product improvement, it reserves the right to change
design and specifications without notice.