Fire-fighting System

Hya-Duo D FL

Type Series Booklet


Legal information/Copyright
Type Series Booklet Hya-Duo D FL

All rights reserved. The contents provided herein must neither be distributed, copied, reproduced,
edited or processed for any other purpose, nor otherwise transmitted, published or made available to a
third party without the manufacturer's express written consent.
Subject to technical modification without prior notice.

© KSB SE & Co. KGaA, Frankenthal 12/10/2021


Contents

Contents
Building Services: Water Supply ......................................................................................................................  4
Fire-fighting Systems.................................................................................................................................................................. 4
Hya-Duo D FL........................................................................................................................................................................ 4
Main applications........................................................................................................................................................... 4
Fluids handled ................................................................................................................................................................ 4
Operating data............................................................................................................................................................... 4
Design details ................................................................................................................................................................. 4
Designation .................................................................................................................................................................... 5
Configuration and function .......................................................................................................................................... 5
Materials ......................................................................................................................................................................... 6
Product benefits ............................................................................................................................................................. 6
Product information ...................................................................................................................................................... 6
Selection information .................................................................................................................................................... 7
Technical data ................................................................................................................................................................ 8
Selection aid for control cabinets ................................................................................................................................. 9
Selection chart.............................................................................................................................................................. 11
Characteristic curves..................................................................................................................................................... 12
Dimensions ................................................................................................................................................................... 21
Scope of supply ............................................................................................................................................................ 25
Accessories .................................................................................................................................................................... 25

3
Building Services: Water Supply
Fire-fighting Systems

Building Services: Water Supply Installation


▪ Stationary dry installation
Fire-fighting Systems
Drive
▪ Three-phase asynchronous motor
Hya-Duo D FL ▪ 220 – 240 V / 380 – 420 V, 380 – 420 V / 660 – 720 V
▪ Enclosure IP55
▪ Efficiency class IE3 to IEC 60034-30
▪ DOL starting up to and including 4 kW
▪ Soft starter
▪ Pressure-controlled starting and flow-controlled stopping

Automation
▪ Electro-mechanical control system, IP54
▪ Timer
▪ Manual-automatic selector switch
▪ Phase monitoring relay
▪ In automatic mode, the motor protection circuit only
outputs an alert.
▪ Terminal strip/terminals with identification for all
connections
▪ Pressure switch or remote ON/OFF, monitored for broken
wires and short circuit
Main applications ▪ Circuit diagram to VDE and parts list for electric parts
▪ Fire-fighting systems to DIN 14462 Indication via indicator lamps:
▪ Colour LED indicating lack of water (red)

Fluids handled ▪ Colour LED indicating a fault (amber)

▪ Fire-fighting water ▪ Colour LED indicating readiness for operation (green)

▪ Liquids not containing aggressive, abrasive or solid ▪ Colour LED indicating operation started by pressure switch
substances or remote ON/OFF (white)
Indication via volt-free isolating terminals:
Operating data ▪ Lack of water

Table 1: Operating properties ▪ Overflow

Characteristic Value ▪ Position of manual-automatic selector switch


3 ▪ Pump control via pressure switch or remote ON/OFF
Flow rate Q [m /h] ≤ 110
Q [l/s] ≤ 30,5 ▪ General fault message
Head H [m] ≤ 160 ▪ Drinking water stop
Fluid temperature T [°C] ≥ 0
Monitoring for broken wires and monitoring for short circuit:
≤ +70
▪ > 10.3 kΩ: broken wire
Operating pressure pd [bar] ≤ 16
Inlet pressure pinl [bar] ≤ 6 ▪ 10 kΩ: good state
Permissible inlet pressure p [bar] +0,3/-0,2 ▪ 1 kΩ: pump start through actuation of limit switch
fluctuation
▪ < 300 Ω: short circuit
Power supply U [V] 3/PE, AC 400, 50 Hz

Design details
1968.5/09-EN

Design
▪ Fully automatic fire-fighting system
1)
▪ Baseplate-mounted
▪ Discharge-side, direct-flow membrane-type accumulator,
approved for drinking water
▪ Vibration damping

1 Version with Movitec 90B excluded

4 Hya-Duo D FL
Building Services: Water Supply
Fire-fighting Systems

Designation

Example: Hya-Duo D FL 2 / 1506 C


Table 2: Designation key

Code Description
Hya-Duo Type series
D FL Fire-fighting system with three-phase motor
2 Number of pump sets
15 Pump size
06 Number of stages
C Design status

Configuration and function

Fig. 1: Illustration of the fire-fighting system


1 High-pressure centrifugal 4 Control cabinet
pump
2 Temperature monitoring 5 Pressure switch
3 Valve 6 Solenoid valve

Design
Fully automatic fire-fighting system, comprising two high-
pressure centrifugal pumps (1), piping and control cabinet (4)
on a common baseplate. The fire-fighting system comprises
one duty system and one back-up system. Anti-vibration
mounts are fitted at the pump feet and baseplate.
Function
The pump sets are started and stopped as a function of
pressure via an electro-mechanical control system. If the
pressure drops below the set start-up pressure pE , the pump
sets are started via the pressure switch. When consumption
decreases again, the pump sets are stopped as a function of
pressure after the set after-run time (up to 10 minutes).
Independently of the pressure switch, the fire-fighting system
can also be controlled via remote ON/OFF (e.g. a switch in the
wall hydrant). The pressure switch and remote ON/OFF input
are monitored for broken wires and short circuit. If a broken
1968.5/09-EN

wire or short circuit are detected, the fire-fighting system is


started up automatically and a fault is indicated.
In the event of a fire, pumping the fluid handled is of top
priority. In automatic mode, the protection features (dry
running protection, motor protection) cannot be enabled. If
the motor protection switch trips, the motor will keep running
on the power supply network without further monitoring. A
fault message is output.

Hya-Duo D FL 5
Building Services: Water Supply
Fire-fighting Systems

Materials
Table 3: Overview of available materials
Part No. Description Material
Pump
101 Inlet casing Stainless steel
101 Discharge casing Stainless steel
655 Hydraulic system Stainless steel
411 Sealing element FPM 80
- Plain bearing Aluminium oxide
433 Mechanical seal To EN 12756
433.01 Primary ring Silicon carbide
433.02 Mating ring Hard carbon
- Elastomer EPDM
Hydraulic design
- Piping Chrome steel
79.01 Control unit Steel, painted
- Accumulator Connection made of stainless steel
- Membrane Approved for drinking water
- Valves Movitec 2B to 15C: copper-base alloy / brass
Movitec 25B to 90B: GG/EPDM

Product benefits
▪ Design to DIN 14462 ensures reliable operation in the
event of fire.
▪ High operational availability by regular functional check
run
▪ Reliable operation by automatic minimum flow system
▪ Reliable operation with pressure switch and remote ON/
OFF monitored for broken wires and short circuit
▪ Operating reliability by redundant system design
▪ Hygienically safe with integrated timer controlling the
flushing device in the inlet line
▪ Anti-vibration mounts prevent solid-borne sound
transmission.

Product information

Product information as per Regulation No.


1907/2006 (REACH)
For information as per chemicals Regulation (EC) No. 1907/2006
(REACH), see https://www.ksb.com/ksb-en/About-KSB/Corporate-
responsibility/reach/ .
1968.5/09-EN

6 Hya-Duo D FL
Building Services: Water Supply
Fire-fighting Systems

Selection information

Lightning protection
▪ Electrical installations must be protected against overvoltage (compulsory since 14 December 2018) (see DIN VDE 0100-443
(IEC60364-4-44:2007/A1:2015, modified) and DIN VDE 0100-534 (IEC 60364-5-53:2001/A2:2015, modified). Whenever
modifications are made to existing installations, retrofitting a surge protective device (SPD) in accordance with VDE is
mandatory.
▪ A maximum cable length of 10 metres should not be exceeded between the surge protective device (usually type 1, internal
lightning protection) installed at the service entrance and the equipment to be protected. For longer cables, additional surge
protective devices (type 2) must be provided in the sub-distribution board upstream of the equipment to be protected or
directly in the equipment itself.
▪ The associated lightning protection concept must be provided by the operator or by a suitable provider commissioned by the
operator. Surge protective devices can be offered for the control units on request.

Selecting the fire-fighting system


For selecting the fire-fighting system see KSB EasySelect and/or the Planning Information for Fire-fighting Water Systems
(reference number 2300.023).

Example 0 20 Q [US.gpm] 40 60

0 10 Q [IM.gpm] 20 30 40 50
Specify the operating points: 500

▪ Flow rate required: 10 m3/h 10/13 4,0kW


140

▪ Head: 50 m (start-up pressure pE: 5.0 bar)


Calculation: 120
10/11 4,0kW 400

1. Transfer the values to the selection chart to select the 10/10 4,0kW

corresponding pump size.


100 10/09 4,0kW

ð Movitec 10/06 300


10/08 3,0kW
H [m]
ð Hya-Duo D FL / 1006 80
10/08 3,0kW

10/06 2,2kW

60 200
10/05 2,2kW

50 m
10/05 1,5kW H [ft]

40
10/03 1,1kW
100

10/02 0,75kW
20

0 0
Q [m³/h]
0 2 4 6 8 10 m3/h 12 14

0 1 Q [l/s] 2 3 4

Characteristic curve for determining the pressure booster system


(example)
1968.5/09-EN

Hya-Duo D FL 7
Building Services: Water Supply
Fire-fighting Systems

Technical data

Hya-Duo D FL with Movitec V


Table 4: Technical data (50 Hz)
Hya-Duo D FL Connection Nominal Nominal Starting S3) Mat. No. [kg]
power current current (soft
with Movitec V
PN IN start)2)
3~400 V
[kW] [A] [A] [kVA]
2/0202 B R2 0,37 0,94 - 0,7 29132613 123
2/0203 B R2 0,37 0,94 - 0,7 29132614 124
2/0204 B R2 0,37 0,94 - 0,7 29132615 125
2/0205 B R2 0,37 0,94 - 0,7 29132616 126
2/0206 B R2 0,55 1,33 - 0,9 29132617 130
2/0207 B R2 0,55 1,33 - 0,9 29132618 131
2/0208 B R2 0,55 1,33 - 0,9 29132619 132
2/0209 B R2 0,75 1,68 - 1,2 29132620 136
2/0210 B R2 0,75 1,68 - 1,2 29132621 137
2/0211 B R2 1,10 2,40 - 1,7 29132622 143
2/0212 B R2 1,10 2,40 - 1,7 29132623 144
2/0214 B R2 1,10 2,40 - 1,7 29132624 145
2/0216 B R2 1,50 2,92 - 2,0 29132625 154
2/0218 B R2 1,50 2,92 - 2,0 29132626 156
2/0402 B R2 0,37 0,94 - 0,7 29132629 123
2/0403 B R2 0,55 1,33 - 0,9 29132630 128
2/0404 B R2 0,55 1,33 - 0,9 29132631 129
2/0405 B R2 0,75 1,68 - 1,2 29132632 133
2/0406 B R2 1,10 2,40 - 1,7 29132633 139
2/0407 B R2 1,10 2,40 - 1,7 29132634 140
2/0408 B R2 1,50 2,92 - 2,0 29132635 147
2/0409 B R2 1,50 2,92 - 2,0 29132636 149
2/0410 B R2 1,50 2,92 - 2,0 29132637 150
2/0411 B R2 2,20 4,15 - 2,9 29132638 156
2/0412 B R2 2,20 4,15 - 2,9 29132639 157
2/0414 B R2 2,20 4,15 - 2,9 29132640 159
2/0416 B R2 3,00 5,59 - 3,9 29132641 187
2/0602 B R2 0,37 0,94 - 0,7 29132643 125
2/0603 B R2 0,75 1,68 - 1,2 29132644 134
2/0604 B R2 1,10 2,40 - 1,7 29132645 139
2/0605 B R2 1,10 2,40 - 1,7 29132646 140
2/0606 B R2 1,50 2,92 - 2,0 29132647 149
2/0607 B R2 1,50 2,92 - 2,0 29132648 150
2/0608 B R2 2,20 4,15 - 2,9 29132649 157
2/0609 B R2 2,20 4,15 - 2,9 29132650 158
2/0610 B R2 2,20 4,15 - 2,9 29132651 159
2/0611 B R2 3,00 5,59 - 3,9 29132652 178
2/0612 B R2 3,00 5,59 - 3,9 29132653 179
2/0614 B R2 3,00 5,59 - 3,9 29132654 180
2/0616 B R2 4,00 7,45 - 5,2 29132655 201
2/1002 B R2 0,75 1,68 - 1,2 29133674 158
1968.5/09-EN

2/1003 B R2 1,10 2,40 - 1,7 29133675 164


2/1004 B R2 1,50 2,92 - 2,0 29133676 175
2/1005 B R2 2,20 4,15 - 2,9 29133677 182
2/1006 B R2 2,20 4,15 - 2,9 29133678 184
2/1007 B R2 3,00 5,59 - 3,9 29133679 202
2/1008 B R2 3,00 5,59 - 3,9 29133680 203

2 Recommended triggering characteristic of fuse elements: gG or C


3 S = total rated power

8 Hya-Duo D FL
Building Services: Water Supply
Fire-fighting Systems

Hya-Duo D FL Connection Nominal Nominal Starting S3) Mat. No. [kg]


power current current (soft
with Movitec V
PN IN start)2)
3~400 V
[kW] [A] [A] [kVA]
2/1009 B R2 4,00 7,45 - 5,2 29133681 216
2/1010 B R2 4,00 7,45 - 5,2 29133682 218
2/1011 B R2 4,00 7,45 - 5,2 29133683 220
2/1013 B R2 5,50 10,00 - 6,9 29133684 327
2/1502 C DN 80 2,20 4,15 68,9 2,9 29135167 204
2/1503 C DN 80 3,00 5,59 41,9 3,9 29135168 225
2/1504 C DN 80 4,00 7,45 36,7 5,2 29135169 235
2/1505 C DN 80 5,50 10,00 51,0 6,9 29135170 339
2/1506 C DN 80 7,50 13,40 68,1 9,3 29135171 341
2/1507 C DN 80 7,50 13,40 68,1 9,3 29135172 351
2/1508 C DN 80 11,00 19,30 89,6 13,4 29135173 412
2/2502 B DN 100 4,00 7,45 36,7 5,2 29134402 381
2/2503 B DN 100 5,50 10,00 51,0 6,9 29134403 464
2/2504 B DN 100 7,50 13,40 68,1 9,3 29134404 478
2/2505 B DN 100 11,00 19,30 89,6 13,4 29134405 657
2/2506 B DN 100 11,00 19,30 89,6 13,4 29134406 663
2/2507 B DN 100 15,00 26,20 121,6 18,2 29134407 692
2/4002-2 B DN 100 5,50 10,00 51,0 6,9 29134553 420
2/4002 B DN 100 7,50 13,40 68,1 9,3 29134554 428
2/4003-2 B DN 100 11,00 19,30 89,6 13,4 29134555 585
2/4003 B DN 100 11,00 19,30 89,6 13,4 29134556 586
2/4004-2 B DN 100 15,00 26,20 121,6 18,2 29134557 595
2/4004 B DN 100 15,00 26,20 121,6 18,2 29134558 623
2/4005-2 B DN 100 18,50 31,80 147,2 22,0 29134559 533
2/4005 B DN 100 18,50 31,80 147,2 22,0 29134560 563
2/4006-2 B DN 100 18,50 31,80 147,2 22,0 29134561 568
2/4006 B DN 100 22,00 37,60 185,3 26,1 29134562 640
2/6001 B DN 150 5,50 10,00 51,0 6,9 29134564 490
2/6002-2 B DN 150 7,50 13,40 68,1 9,3 29134565 505
2/6002 B DN 150 11,00 19,30 89,6 13,4 29134566 659
2/6003-2 B DN 150 15,00 26,20 121,6 18,2 29134567 699
2/6003 B DN 150 18,50 31,80 147,2 22,0 29134568 706
2/6004-2 B DN 150 18,50 31,80 147,2 22,0 29134569 647
2/6004 B DN 150 22,00 37,60 185,3 26,1 29134570 726
2/6005-2 B DN 150 22,00 37,60 185,3 26,1 29134571 733
2/9002-2 B DN 150 11,00 19,30 89,6 13,4 29132379 780
2/9002-1 B DN 150 15,00 26,20 121,6 18,2 29132380 797
2/9002 B DN 150 15,00 26,20 121,6 18,2 29132381 797
2/9003-2 B DN 150 18,50 31,80 147,2 22,0 29132382 756
2/9003-1 B DN 150 22,00 37,60 185,3 26,1 29132383 828
2/9003 B DN 150 22,00 37,60 185,3 26,1 29132384 828

Selection aid for control cabinets


Table 5: Overview of control cabinets
Motor rating per pump Maximum connection cross-section Control cabinet size
1968.5/09-EN

Stranded Solid H × W × D


[kW] [mm2] [mm2] [mm]
5,5 6 10 600 × 800 × 250
7,5 6 10 600 × 800 × 250
11 10 16 600 × 800 × 250
15 16 25 600 × 800 × 250
18,5 16 25 600 × 800 × 250
22 16 25 1000 × 600 × 250

Hya-Duo D FL 9
Building Services: Water Supply
Fire-fighting Systems

Motor rating per pump Maximum connection cross-section Control cabinet size
Stranded Solid H × W × D
[kW] [mm2] [mm2] [mm]
30 35 50 1000 × 600 × 250
37 50 50 1000 × 800 × 300
45 70 95 1000 × 800 × 300

1968.5/09-EN

10 Hya-Duo D FL
Building Services: Water Supply
Fire-fighting Systems

Selection chart

Hya-Duo D FL; n = 2900 rpm

2 3 4 5 US.gpm 10 20 30 40 50 100 200 300 400 500

2 3 4 5 IM.gpm 10 20 30 40 50 100 200 300 400


200

500

400

100
300

200

50
2B 4B 6B 10B 15C 25B 40B 60B 90B
40

30 100

ft
20

50

40

10
30
H
[m]

20

4
0.4 0.5 Q[m³/h] 1 2 3 4 5 10 20 30 40 50 100 120

0.2 0.3 0.4 0.5 l/s 1 2 3 4 5 10 20 30


1968.5/09-EN

Hya-Duo D FL 11
Building Services: Water Supply
Fire-fighting Systems

Characteristic curves

Hya-Duo D FL with Movitec 2B, n = 2900 rpm

0 5 Q [US.gpm] 10 15
0 2Q [IM.gpm]4 6 8 10 12

140 2/18 1,5kW

2/16 1,5kW 400


120

2/14 1,1kW
100
2/12 1,1kW 300
2/11 1,1kW
80
2/10 0,75kw
2/09 0,75kW

60 2/08 0,55kW 200


2/07 0,55kW
2/06 0,55kW H [ft]
40 2/05 0,37kW
H [m] 2/04 0,37kW 100
2/03 0,37kW
20
2/02 0,37kW

0 0
0.0 0.5Q [m³/h]1.0 1.5 2.0 2.5 3.0 3.5
Q [l/s]
80.0 0.2 0.4 0.6 0.8 1.0
20
NPSH [m] NPSH [ft]
R R
0 0
60
Eta [%]
0
0.08 0.1
P [kW]
0.05 P [hp]
0.04
0.02
0.0 0.5Q [m³/h]1.0 1.5 2.0 2.5 3.0 3.5
Hya50MT2B/0
1968.5/09-EN

St = 1 P per stage

12 Hya-Duo D FL
Building Services: Water Supply
Fire-fighting Systems

Hya-Duo D FL with Movitec 4B, n = 2900 rpm

0 10 Q [US.gpm] 20 30
0 5 Q [IM.gpm] 10 15 20 25
500

140 4/16 3,0 kW

4/14 2,2kW 400


120

4/12 2,2kW
100
4/11 2,2kW
300
4/10 1,1kW
80 4/09 1,1kW

4/08 1,1kW

60 4/07 1,1kW 200


4/06 1,1kW
H [ft]
4/05 0,75kW
40
4/04 0,55kW
H [m] 100
4/03 0,55kW
20
4/02 0,37kW

0 0
0 1 Q [m³/h] 2 3 4 5 6 7
Q [l/s]
60.0 0.5 1.0 1.5
NPSH [ft]
R
NPSH [m] 10
R
0 0
80
Eta [%]
0
0.14
P [kW]
0.1 St=1 0.15
P [hp]
0.05
0.02
0 1 Q [m³/h] 2 3 4 5 6 7
Hya50MT4B/0

St = 1 P per stage
1968.5/09-EN

Hya-Duo D FL 13
Building Services: Water Supply
Fire-fighting Systems

Hya-Duo D FL with Movitec 6B, n = 2900 rpm

0 10 Q [US.gpm] 20 30 40
0 10 Q [IM.gpm] 20 30
160
500
6/16 4,0kW

140
6/14 3,0kW

120 400
6/12 3,0kW

6/11 3,0kW
100
6/10 2,2kW
300
6/09 2,2kW
80
6/08 2,2kW
6/07 1,5kW
60 200
6/06 1,5kW
6/05 1,1kW H [ft]
40 6/04 1,1kW
H [m] 100
6/03 0,75kW
20 6/02 0,37kW

0 0
0 2 Q [m³/h] 4 6 8 10
Q [l/s]
40.0 0.5 1.0 1.5 2.0 2.5
10
NPSH [m] NPSH [ft]
R R
0 0
80
Eta [%]
0

0.2 0.3
St=1
P [kW] P [hp]

0.0 0.0
0 2 Q [m³/h] 4 6 8 10
D50MT6B/0

St = 1 P per stage
1968.5/09-EN

14 Hya-Duo D FL
Building Services: Water Supply
Fire-fighting Systems

Hya-Duo D FL with Movitec 10B, n = 2900 rpm

0 20 Q [US.gpm] 40 60
0 10 Q [IM.gpm] 20 30 40 50
500

140 10/13 4,0kW

120 10/11 4,0kW 400

10/10 4,0kW

100 10/09 4,0kW


300
10/08 3,0kW
80
10/08 3,0kW

10/06 2,2kW
60 200
10/05 2,2kW

10/05 1,5kW H [ft]


40
10/03 1,1kW
H [m] 100
10/02 0,75kW
20

0 0
0 2 Q [m³/h] 4 6 8 10 12 14
Q [l/s]
50 1 2 3 4
15
NPSH [m] NPSH [ft]
R R
1 5
80
Eta [%]
0
0.4
St=1 0.4
P [kW] P [hp]

0.0 0
0 2 Q [m³/h] 4 6 8 10 12 14
Hya50MT10B/0

St = 1 P per stage
1968.5/09-EN

Hya-Duo D FL 15
Building Services: Water Supply
Fire-fighting Systems

Hya-Duo D FL with Movitec 15C, n = 2900 rpm

0 20 Q [US.gpm] 40 60 80 100
0 20 Q [IM.gpm] 40 60 80
160
500

140 15/10 11,0 kW

15/9 11,0 kW
120 400

15/8 11,0 kW

100
15/7 7,5 kW
300

80 15/6 7,5 kW

15/5 5,5 kW
60 200
15/4 4,0 kW
H [ft]
40 15/3 3,0 kW
H [m] 100
15/2 2,2 kW
20

0 0
0 5 Q [m³/h] 10 15 20
Q [l/s]
30 2 4 6
NPSHR
[ft]
[m]
NPSHR 5
0 0
80
Eta [%]
0
1
1.0
P [kW] P [hp]
0.5
0.2
0 5 Q [m³/h] 10 15 20

St = 1 P per stage
1968.5/09-EN

16 Hya-Duo D FL
Building Services: Water Supply
Fire-fighting Systems

Hya-Duo D FL with Movitec 25B, n = 2900 rpm

0 50 Q [US.gpm] 100 150


0 50 Q [IM.gpm] 100

140 25/07 15,0kW

120 25/06 11,0kW 400

100 25/05 11,0kW

300

25/04 7,5kW
80
H [ft]

25/03 5,5kW 200


60

H [m]

40 25/02 4,0kW

100

20

0 5 Q [m³/h]10 15 20 25 30 35
Q [l/s]
60 2 4 6 8 10
NPSH [ft]
R
NPSH [m] 10
R
0 0
80
Eta [%]
0
1.8
P [kW] St=1 2
P [hp]
1
1
0.6
0 5 Q [m³/h]10 15 20 25 30 35
Hya50MT25B/0

St = 1 P per stage
1968.5/09-EN

Hya-Duo D FL 17
Building Services: Water Supply
Fire-fighting Systems

Hya-Duo D FL with Movitec 40B, n = 2900 rpm

0 50 Q [US.gpm]100 150 200 250


0 50 Q [IM.gpm] 100 150 200
500
40/6 22,0kW
140
40/6-2 18,5kW

40/5 18,5kW 400


120
40/5-2 18,5 kW

100 40/4 15,0kW


300
40/4-2 15,0kW
80
40/3 11,0kW H [ft]

40/3-2 11,0kW
60 200

H [m] 40/2 7,5kW

40 40/2-2 5,5kW

100

20

0 10 Q [m³/h] 20 30 40 50
Q [l/s]
80 5 10 15
20
NPSH [m] NPSH [ft]
R R
0 0
100
Eta [%]
0
3.5
P [kW] 4
2 -1 P [hp]

0.5 1
0 10 Q [m³/h] 20 30 40 50
Hya50MT40B/0

St = 1 P per stage St = -1 P per stage with a smaller impeller


1968.5/09-EN

18 Hya-Duo D FL
Building Services: Water Supply
Fire-fighting Systems

Hya-Duo D FL with Movitec 60B, n = 2900 rpm

0 100 Q [US.gpm] 200 300


0 100 Q [IM.gpm] 200 300

60/5-2 22,0kW
120 400

60/4 22,0kW

100
60/4-2 18,5kW
300
60/3 18,5kW
80
H [ft]
60/3-2 15,0kW

60 200
60/2 11,0kW
H [m]

40 60/2-2 7,5kW

60/1 5,5kW 100

20

0 10Q [m³/h]20 30 40 50 60 70 80
Q [l/s]
60 5 10 15 20
NPSH [ft]
R
NPSH [m] 10
R
0 0
100
Eta [%]
0
5
6
P [kW] -1 P [hp]
2
1
0 10Q [m³/h]20 30 40 50 60 70 80
Hya50MT60B/0

St = 1 P per stage St = -1 P per stage with a smaller impeller


1968.5/09-EN

Hya-Duo D FL 19
Building Services: Water Supply
Fire-fighting Systems

Hya-Duo D FL with Movitec 90B, n = 2900 rpm

0 100Q [US.gpm]200 300 400 500

90 0 100 Q [IM.gpm] 200 300 400

90/03 22kW
80
90/03-1 22kW
250
90/03-2 18,5kW
70

60 200

90/02 15kW

50 90/02-1 15kW

90/02-2 11kW 150

40
H [ft]
H [m]

30 100

20

50

0 20 Q [m³/h] 40 60 80 100 120


Q [l/s]
80 10 20 30
20
NPSHR [m] NPSHR [ft]
0 0
100
Eta [%]
0
8 10
P [kW] St= 1
5 P [hp]
St=-1
4
2
0 20 Q [m³/h] 40 60 80 100 120
Hya50MT90B/0

St = 1 P per stage St = -1 P per stage with a smaller impeller


1968.5/09-EN

20 Hya-Duo D FL
Building Services: Water Supply
Fire-fighting Systems

Dimensions

Hya-Duo D FL with Movitec 2B / 4B / 6B

300 800

1460
R2
115

C1
925
750 C2
670
500

600

4 x Ø17
925

Fig. 2: Dimensions of Hya-Duo D FL with Movitec 2B / 4B / 6B [mm]

External thread R to DIN EN 10226

Flanges drilled to EN 1092-1 PN 16

Table 6: Dimensions [mm]


Hya-Duo D FL C1 C2
[mm]
2/02... 742 923
2/04... 742 923
2/06... 800 981
1968.5/09-EN

Hya-Duo D FL 21
Building Services: Water Supply
Fire-fighting Systems

Hya-Duo D FL with Movitec 10B

300 800

1460
R2
145

893 ±15
1074 ±15
1085
985
900
500

600

4 x Ø17

Fig. 3: Dimensions of Hya-Duo D FL with Movitec 10B [mm]

External thread R to DIN EN 10226

Flanges drilled to EN 1092-1 PN 16

1968.5/09-EN

22 Hya-Duo D FL
Building Services: Water Supply
Fire-fighting Systems

Hya-Duo D FL with Movitec 15C

DN 80, PN 16

1460
145

861 ±15
1060 ±15
1080
980
900
500

600

79
4 x Ø17

Fig. 4: Dimensions of Hya-Duo D FL with Movitec 15C [mm]

External thread R to DIN EN 10226

Flanges drilled to EN 1092-1 PN 16


1968.5/09-EN

Hya-Duo D FL 23
Building Services: Water Supply
Fire-fighting Systems

Hya-Duo D FL with Movitec 25B, 40B, 60B, 90B

D1
DN
H1

A A

30
73

760 B2 ± 5 B3 ± 5
868 B1 ± 10
1180
832 B ± 10
700
568
168
132

800
132
A-A 4 x Ø12,5
168

Fig. 5: Dimensions of Hya-Duo D FL with Movitec 25B / 40B / 60B / 90B [mm]

External thread R to DIN EN 10226

Flanges drilled to EN 1092-1 PN 16

Table 7: Dimensions [mm]


Hya-Duo D FL Connection D1 H1 B B1 B2 B3
[mm]
2/25... DN 100 1728 302 1074 854 351 503
2/40... DN 100 1903 337 1139 919 374 546
2/60... DN 150 1903 337 1320 1035 431 604
2/90... DN 150 1903 337 1335 1050 439 611

1968.5/09-EN

24 Hya-Duo D FL
Building Services: Water Supply
Fire-fighting Systems

Scope of supply
Depending on the model, the following items are included in
the scope of supply:
▪ Fire-fighting system
– Two vertical Movitec high-pressure centrifugal pumps
– Discharge-side piping
– Check valve
– Shut-off valves
– Discharge-side, direct-flow membrane-type
accumulator
– Pressure switch on the discharge side
– Pressure gauge
– Base frame
– Temperature sensor
▪ Control unit
– Two power supply connections
– Two motor protection switches
– Two master switches
– Two relays for broken wire monitoring / short-circuit
monitoring
– Two manual-automatic selector switches
– Two timers
– Two phase monitoring relays
– Two soft starters
– Two control transformers
– Terminal strip with markings for all connections

Accessories
See the separate type series booklet Accessories for
Pressure Booster Systems 1954.5.
1968.5/09-EN

Hya-Duo D FL 25
Glossary

Glossary

Back-up system
The part of the fire-fighting system / break tank package
booster set for fire-fighting which ensures the supply of
fire-fighting water in the event of a fire if the duty
system fails (see also duty system).

Duty system
The active part of the fire-fighting system / break tank
package booster set for fire-fighting which ensures the
supply of fire-fighting water in the event of a fire (see
also back-up system).

IE3
Efficiency class to IEC 60034-30: 3 = Premium Efficiency
(IE = International Efficiency)

Mat. No.
This identification number is composed of an 8-digit
numerical code that uniquely identifies a product
entered in SAP.

1968.5/09-EN

26
12/10/2021
1968.5/09-EN

KSB SE & Co. KGaA


Johann-Klein-Straße 9 • 67227 Frankenthal (Germany)
Tel. +49 6233 86-0
www.ksb.com

You might also like