VITALink® MC

www.r-scc.com 2-Hour Fire Rated Power Cable

Conductor NFPA 70
Annealed Copper
UL 2196
Armor
600 Volt, 90°C
Insulation Inner Jacket
Continuously Welded and LSZH Ceramifiable Silicone Ceramifiable Silicon Rubber Bedding Layer
NEC Type MC
Corrugated Copper
UL Listed
Systems FHIT 120, 120A, and 60

Applications
Overview
• Lighting, ventilation, elevators, fire pumps VITALink MC is a 600V 2-hour fire
®

• NFPA 70/NEC – Articles 695, 700, 728, 760 rated cable listed to UL2196. When
• NFPA 72, 101 installed per systems FHIT 120, 120A,
and 60, plus the NEC, VITALink® MC
Features meets the code requirements for 2-hour
• Up to 2-hour fire resistance Fire Rated Circuits, Electrical Circuit
• Splice available Integrity Systems, Survivability, and
• Superior resistance to flame propagation Circuit Integrity. VITALink® MC Cables
offer lowered cost, reliability and ease
• Only conventional tools required to terminate of installation advantages over MI cable
• Commercially available brass/stainless steel connectors and other methods of providing fire rated
• Printed number coding allows for easy identification (ICEA Method 4) circuits.
• Labor savings on termination, installation, and handling
The equipment grounding copper
armor is terminated with commercially
• Made in USA
available brass MC connectors and the
• Superior impact & crush resistance
cable connections are made without
• Low smoke, low toxicity, halogen free design
the need for splicing or use of special
• Welded armor forms an impervious barrier
tools. Compared to Mineral Insulated
• Flexible
(MI) cable, VITALink® MC is not exposed
to costly field expenses in preparing
• Long continuous lengths available
cable ends, special panel penetrations,
• Multiple sizes and conductor counts available
additional flexible terminations and the
• VFD cable design available
splicing of shorter lengths in longer
• Copper sheath exceeds the NEC requirement for equipment grounding conductor runs. VITALink® MC is not susceptible
Table 250.122 to failures caused by moisture ingress
Performance Standards through leaky seals or faulty storage.
• UL 2196 – Listed as up to 2-hour fire rated Electrical Circuit Integrity
Systems FHIT 120, 120A, and 60 of the UL Fire Resistance Directory
• IEEE 1202/FT4 vertical flame test; ST1 limited smoke
• UL 1569 – Listed as Type MC per NFPA 70 Article 330
• Copper conductors to ASTM B8

RSCC Wire & Cable LLC © 2020 • 20 Bradley Park Road • East Granby, CT 06026 USA • 800-327-7625 Tel: 860-653-8300 • Fax: 860-653-8301 • www.r-scc.com

VC01/10.27.20
VITALink® MC 2-Hour Fire Rated Power Cable

VITALink® MC Single Conductor 2-Hour Fire Rated Power Cable


Nom. Core Nom. Armor Approximate
Size # of Diameter Diameter Net Weight Ampacity 75˚C Ampacity 90˚C
Product Code (AWG kcmil) Conductor (In) (In) (Lbs/1000 ft) Conductor1 Conductor1
VM011X0-100  1/0  1  0.66  1.00  815  206  235 
VM012X0-100  2/0  1  0.70  1.04  925  239  271 
VM013X0-100  3/0  1  0.75  1.08  1,055  276  315 
VM014X0-100  4/0  1  0.81  1.16  1,235  324  368 
VM01250-100  250  1  0.89  1.22  1,410  361  411 
VM01350-100  350  1  0.99  1.35  1,795  448  510 
VM01500-100  500  1  1.13  1.50  2,350  560  638 
VM01750-100  750  1  1.34  1.73  3,285  720  821 

1Ampacitiesbased on NEC (NFPA 70-2017) Article 330.80(B) and Table 310.15(B)(20) adjusted to 30˚C ambient.
Termination device temperature rating shall match conductor temperature rating for ampacity.

VITALink® MC Multi Conductor 2-Hour Fire Rated Power Cable


Nom. Core Nom. Armor Approximate
Size # of Diameter Diameter Net Weight Ampacity 75˚C Ampacity 90˚C
Product Code (AWG kcmil) Conductor (In) (In) (Lbs/1000 ft) Conductor2 Conductor2
VM02014-100  14  2  0.49  0.82  395  203  253 
VM02012-100  12  2  0.53  0.82  415  253  303 
VM02010-100  10  2  0.58  0.89  475  353  403 
VM03014-100  14  3  0.52  0.82  425  203  253 
VM03012-100  12  3  0.56  0.89  475  253  303 
VM03010-100  10  3  0.61  0.94  542  353  403 
VM03008-100  8  3  0.72  1.04  675  50  55 
VM03006-100  6  3  0.80  1.16  840  65  75 
VM03004-100  4  3  0.91  1.24  1,140  85  95 
VM03003-100  3  3  0.97  1.30  1,210  100  115 
VM03002-100  2  3  1.04  1.41  1,400  115  130 
VM03001-100  1  3  1.21  1.59  1,715  130  145 
VM031X0-100  1/0  3  1.29  1.67  1,990  150  170 
VM032X0-100  2/0  3  1.39  1.80  2,345  175  195 
VM033X0-100  3/0  3  1.49  1.92  2,755  200  225 
VM034X0-100  4/0  3  1.62  2.04  3,305  230  260 
VM03250-100  250  3  1.80  2.26  3,870  255  290 
VM03350-100  350  3  2.02  2.48  5,015  310  350 
VM03500-100  500  3  2.30  2.82  6,720  380  430 
VM04014-100  14  4  0.57  0.89  480  203  253 
VM04012-100  12  4  0.62  0.94  575  253  303 
VM04010-100  10  4  0.67  1.00  635  353  403 
VM04008-100  8  4  0.80  1.16  815  50  55 
VM04006-100  6  4  0.89  1.22  990  65  75 
VM04004-100  4  4  1.00  1.35  1,285  85  95 
VM04003-100  3  4  1.07  1.41  1,475  100  115 
VM04002-100  2  4  1.15  1.50  1,710  115  130 
VM04001-100  1  4  1.34  1.73  2,125  130  145 
VM041X0-100  1/0  4  1.43  1.82  2,485  150  170 
VM042X0-100  2/0  4  1.54  1.95  2,935  175  195 
VM043X0-100  3/0  4  1.68  2.12  3,530  200  225 
VM044X0-100  4/0  4  1.82  2.26  4,205  230  260 
VM04250-100  250  4  2.00  2.46  4,925  255  290 
VM04350-100  350  4  2.25  2.71  6,420  310  350 
VM04500-100  500  4  2.60  3.13  8,740  380  430 
VM05014-100  14  5  0.63  0.94  535  20  25 
VM05012-100  12  5  0.68  1.00  615  25  30 
VM05010-100  10  5  0.74  1.08  720  35  40 
VM05008-100  8  5  0.88  1.22  930  50  55 
VM05006-100  6  5  0.99  1.30  1,160  65  75 
VM05004-100  4  5  1.11  1.48  1,525  85  95 

2Ampacities based on NEC (NFPA 70-2017) Table 310.15(B)(16) for 3 current carrying conductors at 30˚C ambient temperature.
Termination device temperature rating shall match conductor temperature rating for ampacity.

3Small conductor limitations per NEC (NFPA 70-2017) Article 240.4(D): 14 AWG = 15 amps, 12 AWG = 20 amps, 10 AWG = 30 amps.