UL2200
APD-NG125
APD-ULV350 NG/LP
AKSA Power Generation has been producing industrial generator sets with an innovative compact design and
excellence in quality for over 30 years. AKSA has been providing reliable power through three main production plants
and over 15 branch offices worldwide.
General Characteristics
Model Name APD-NG125
Engine Make PSI
Engine Model 8.8LT-NG / 8.8LNA-LP
Alternator Make Stamford
Control Panel Make & Model DSE 7320
Frequency & Speed 60Hz, 1800rpm
Enclosure Make & Model AKSA AUL 51/52
Genset Rating
NG NG LP Gas LP Gas
Engine Alternator Voltage PF Standby Standby Standby Standby
Power Current Power Current
UCI274E (Wnd-311) 480/277V 0.8 125kW 188A 100kW 150A
UCI274E (Wnd-06) 240/120V,1ph 1 125kW 520A 100kW 416A
8.8LT-(NG)
8.8LNA-(LP)
UCI274E (Wnd-311) 208/120V 0.8 125kW 434A 100kW 347A
UCI274E (Wnd-17) 600/347V 0.8 125kW 150A 100kW 120A
*EPA – Certified for Emergency Stationary Applications
Stand-by Power (Maximum): Power available at variable load in the event of main power network failure. No over load is permitted.
Prime Power: Power available at variable load in lieu of a main power network. Overload of 10% is permitted for 1 hour in every 12 hours of operation.
The above ratings represent the engine performance capabilities to conditions specified in accordance with ISO 8528/5 & ISO3046.
Derating may be required for conditions outside of the test conditions.
Codes & Standards
The Generator set is designed and manufactured in a facility certified to ISO9001 standards.
The Generator set is designed and manufactured in a facility certified to ISO14001:2015 standards.
AKSA Power Generation provides single source responsibility for the generator set & accessories.
The generator set, with its components, are prototype tested and production tested according to the UL test program.
The generator set meets NFPA70, 99, 110, 37 Level 1 when equipped with the necessary accessories and installed per
NFPA standards.
*Manufacturer reserves the right to make changes in model, technical specifications, color, equipment and accessories without prior notice.
www.aksausa.com www.aksausa.com
www.aksalatam.com
UL2200
APD-NG125 NG/LP
Engine Data Electric System
Manufacturer PSI System Voltage (dc) 12V
Model 8.8LT / 8.8LNA Battery Qty, Rating 1 x 80Ah,
Displacement & Cylinders 8.8 L / 8 Cylinders
Cooling System
Engine Type V-type, 4 Cycle
Radiator Cooling System Type Closed Circuit
Engine Speed 1800rpm
Coolant Capacity, engine only 14.5 quart
Engine Standby Power NG 147.2kW (8.8LT)
Cranking Temperature 160˚F
Engine Standby Power LP 138.25kW (8.8LNA)
Full Open Temperature 185 ˚F
Aspiration Forced Induction
Compression Ratio 10.1 : 1
Exhaust System
Type Air cooled manifold
Bore / Stroke 110.5 mm / 114.3 mm
Max. allowable back pressure 10.2 kPa
Governor type Electronic
Cont. rating catalyst
Dual Substrate
configuration
Fuel System
Exhaust Gas Flow at Rated 1017.9 cfm (8.8LT)
Fuel Type NG, LP Gas/Dual Fuel Power @ 1350 ˚F 803.9 cfm (8.8LNA)
Min NG Supply pipe size 1-1/4” NPTF
Air Intake System
Min LPG Supply pipe size ¾”
Combustion Air Required 315.2 cfm
Maximum EPR Rated Pressure 6.9 kPa / 1.0 psi
Max Intake Air Restriction
1.49 kPa
Max Pressure to EPR 2.7 kPA / 11.0 inH2O (Clean Element)
Min Pressure to EPR 1.7 kPA / 7.0 inH2O Air Filter Type Dry Paper Element
Fuel Consumption Lubrication System
Natural Gas LP Gas SAE 5W-30 API
(8.8LT) (8.8LNA) Oil Specifications
Rating SM or Newer
1965 cfh 576 cfh
Standby Power (100%)
55.7 m3/hr 16.3 m3/hr Oil Pan Capacity 8.0 qts
1529 cfh 442 cfh
Standby Power (75%)
43.3 m3/hr 12.5 m3/hr Oil filter; qt, type 1, Cartridge
1102 cfh 322 cfh
Standby Power (50%)
31.2 m3/hr 9.1 m3/hr
Max allowable oil temp 250˚F
688 cfh 205 cfh
Standby Power (25%)
19.5 m3/hr 5.8 m3/hr
*Manufacturer reserves the right to make changes in model, technical specifications, color, equipment and accessories without prior notice.
www.aksausa.com
UL2200
APD-NG125 NG/LP
Alternator Data Controller Data
Manufacturer Stamford Manufacturer DSE
Standards BS EN 60034 Model 7320 MK II
Control System PMG
Controller Features & Benefits
A.V.R. MX341
Microprocessor controlled, UL & NFPA110 Compatible
Voltage Regulation ±1% License free PC Software (Non-proprietary Software)
IP65 rating offers increased resistance to water ingress
Insulation System Class H
Modules can be integrated to building management systems
Protection IP23
Real time clock provides accurate event log
Rated Power Factor 0.8 Four line back-lit LCD text display
Five key menu navigation, two wire start/stop at Auto mode
Stator Winding Double Layer Concentric
Front panel editing with PIN protection
Winding Pitch Two Thirds
Support up to three remote display modules
Winding Leads 12 Configurable timers and alarms
Telephone Interference THF < 2 % Multiple date and timer scheduler
Integral PLC editor
Waveform Distortion No Load < 1.5 %
‘Protections disabled’ feature
Maximum Over speed 2250 rev/min
Load switching (load shedding and dummy load outputs)
Fully configurable via DSE Configuration Suite PC Software
Battery Charger & Electrical System Data
SCADA monitoring via DSE Configuration Suite PC Software
Manufacturer ComAp
Protection Instruments
Model InteliCharger
Gen. Voltage – under / over Gen. Voltage (L-L/L-N)
Input Voltage 85V ~ 264V AC Gen. Freq. – under / over Gen. Frequency
Engine Speed – under / over Engine speed
Output Voltage / Current 13.8V Float / 4A pk
Engine Oil Pressure – low Oil Pressure
Jacket Water Heater Data Engine Temp – low / high Water Temperature
Battery Voltage – low / high Battery Voltage
Manufacturer Hotstart
Weak Battery Run Time
Model TPS151GT10-000 Fail to Start / Stop Phase Sequence
Power monitoring
Charge Alternator Fail
Input Voltage 120V (kWh/kVAh/kVArh)
Over Current & Load Power
(kW/kVAr) (kWh/kVAh/kVArh)
Power 1500W
Unbalanced Load Power Factor
Independent Earth Fault Generator Current
Reverse Power Generator Load (%)
Loss of Speed Signal Earth Current
*Manufacturer reserves the right to make changes in model, technical specifications, color, equipment and accessories without prior notice.
www.aksausa.com
UL2200
APD-NG125 NG/LP
Enclosure Features Enclosure Features
Heavy Duty Steel / Aluminum Structure Internally Mounted Exhaust System with Rain Cap
E-Stop on Enclosure Coolant Fill Cap
Control Panel Eliminated from Engine Vibrations Removable Base Frame Lifting Hooks
Standard Sound Attenuation Foam Oil & Coolant Drain Ports
Plastic Covered Corrosion Resistant Locks & Hinges Easy Access for Maintenance
Open Skid Gen-Set Dimensions
Length 116 in
Width w/o lift hooks 43.3 in
Height 54 in
Dry Weight 3000 lb
Enclosed Gen-Set Dimensions – Level 1
Length 145.7 in
Width w/o lift hooks 43.3 in
Height 66.4 in
Dry Weight 4500 lb
Sound Pressure @ 7 meters 76 dBA
Enclosed Gen-Set Dimensions – Level 2
Length 145.7 in
Width w/o lift hooks 43.3 in
Height 82 in
Dry Weight 4875 lb
Sound Pressure @ 7 meters 72 dBA
*Manufacturer reserves the right to make changes in model, technical specifications, color, equipment and accessories without prior notice.
www.aksausa.com www.aksausa.com
UL2200
APD-NG125 NG/LP
Standard Features & Accessories Optional Accessories
UL2200 Certification Main Line CB (3 / 4 Poles – 80% / 100% rated)
Heavy Duty Steel Base Frame Upsize Alternator
PMG Anti-condensation Heater
Engine Jacket Water Heater Voltage Regulation ±0.5% w/MX321 AVR
Battery and Battery Rack Gas Regulator
Battery Charger
NG / LP Auto Changeover Control System
Anti Vibration Pads between Engine/Alternator & Base Frame
Low Gas Pressure Alarm
Critical Grade Silencer Inside Enclosure
Low Coolant Level Alarm
Residential Grade Silencer Set for Open Skid Sets
Oil Pan Heater
Exhaust outlet rain cap and radiator fill cap
Oil Temperature Display on Controller
Sound Absorb Foam Material for Enclosure
Manual Speed Adjust Rheostat
Emergency Stop Button
Manual Voltage Adjust Rheostat
Oil Drain Valve
Remote Annunciator Panel
Coolant Drain Valve
Remote Control & Monitoring Panel
Jacket Water Heater Isolation Valves
Advanced SMS Messaging
Flex Fuel Lines
Control Panel Heater
Secondary Lock-off Valve on Baseframe
Battery Disconnect Switch
Engine Manifold Cover
Battery Heater
Turbocharger Cover
Battery Charger 10/20 Amp
Protection Covers for Rotating Parts
Exhaust Insulation Cover Shunt Trip / Aux Contacts
Enclosure DC Light Spring Anti-vibration Isolators
Operations Manual Automatic Transfer Panel (ATS)
24 Months / 2000 hours Limited Standby Warranty 5 Years / 2000 hours Limited Comprehensive Warranty
AKSA POWER GENERATION USA LLC DISTRIBUTED BY:
371 Exchange Street, West Monroe,
Louisiana, 71292
Tel: 318.855.8377 Fax: 318.855.8381
E-mail: sales@aksausa.com
AKSA Power Generation USA is a member of
**Manufacturer
Manufacturer reserves
reserves the
the right
right to
to make
make changes
changes in
in model,
model, technical
technicalspecifications,
specifications, color,
color, equipment
equipment and
andaccessories
accessories without
withoutprior
prior notice.
notice.