Data Book for HVAC Load Calculation
Augmintech
In/out
R-VALUE (F° · SQ.FT. ·
MATERIAL THICKNESS HR/BTU)
Air Films
Exterior 0.17
Interior Wall 0.68
Interior Ceiling 0.61
Air Space
Minimum 1/2" up to 4" 1.00
Building Board
Gypsum Wall Board 1/2" 0.45
Gypsum Wall Board 5/8" 0.5625
Plywood 1/2" 0.62
Plywood 1" 1.25
Fiber board sheathing 1/2" 1.32
Medium Density Particle Board 1/2" 0.53
Insulating Materials
R-11 Mineral Fiber with 2x4 metal 5.50
studs @ 16" OC
R-11 Mineral Fiber with 2x4 wood 12.44
studs @ 16" OC
R-VALUE (F° · SQ.FT. ·
MATERIAL THICKNESS HR/BTU)
R-11 Mineral Fiber with 2x4 metal 6.60
studs @ 24" OC
R-19 Mineral Fiber with 2x6 metal 7.10
studs @ 16" OC
R-19 Mineral Fiber with 2x6 metal 8.55
studs @ 24" OC
R-19 Mineral Fiber with 2x6 wood 19.11
studs @ 24" OC
Expanded Polystyrene (Extruded) 1" 5.00
Polyurethane Foam (Foamed on site) 1" 6.25
Polyisocyanurate (Foil Faced) 1" 7.20
Masonry and Concrete
Common Brick 4" 0.80
Face Brick 4" 0.44
Concrete Masonry Unit (CMU) 4" 0.80
Concrete Masonry Unit (CMU) 8" 1.11
Concrete Masonry Unit (CMU) 12" 1.28
Concrete 60 pounds per cubic foot 1" 0.52
Concrete 70 pounds per cubic foot 1" 0.42
Concrete 80 pounds per cubic foot 1" 0.33
Concrete 90 pounds per cubic foot 1" 0.26
Concrete 100 pounds per cubic foot 1" 0.21
R-VALUE (F° · SQ.FT. ·
MATERIAL THICKNESS HR/BTU)
Concrete 120 pounds per cubic foot 1" 0.13
Concrete 150 pounds per cubic foot 1" 0.07
Granite 1" 0.05
Sandstone / Limestone 1" 0.08
Siding
Aluminum / Vinyl (not insulated) 0.61
Aluminum / Vinyl (1/2" insulation) 1.80
Flooring
Hardwood 3/4" 0.68
Tile 0.05
Carpet with fiber pad 2.08
Carpet with rubber pad 1.23
Roofing
Asphalt Shingles 0.44
Wood Shingles 0.97
Glazing
Single Pane 1/4" 0.91
R-VALUE (F° · SQ.FT. ·
MATERIAL THICKNESS HR/BTU)
Double Pane with 1/4" air space 1.69
Double Pane with 1/2" air space 2.04
Double Pane with 3/4" air space 2.38
Triple Pane with 1/4" air spaces 2.56
Triple Pane with 1/2" air spaces 3.23
Doors
Wood, solid core 1 3/4" 2.17
Solid insulated metal door, 1.5" - 2" 6.00 - 7.00
polystyrene insulation
ASTM C518 Calculated
Solid insulated metal door, 1.5" - 2" 2.20 - 2.80
polystyrene insulation
ASTM C1363 Operable
Solid insulated metal door, 1.5" - 2" 10.00 - 11.00
polyurethane insulation
ASTM C518 Calculated
Solid insulated metal door, 1.5" - 2" 2.50 - 3.50
polyurethane insulation
ASTM C1363 Operable
CLTD
CLTD for roof
CLTD For roof
CLTD For roof
CLTD For wall
Outdoor design conditions
Conduction through glass (transmission)
CLTD for glass
Solar load through glass
Q=SGHF*A*SC*CLF
SGHF
SC
CLF
Overall Factor (SHGC)
Internal load
Occupants (2017 ASHRAE, C18/T1:474)
Internal cooling load
Number of people
People (heat rate per people)
Light
Equipment and appliance
Infiltration
Apparatus Dew Point