SIVACON S4

IEC 61439 design verification

Frei verwendbar © Siemens AG 2015. Alle Rechte vorbehalten. siemens.com/lowvoltage


IEC 61439 History
Milestones of Switchboard Standards

1896 First publication of standards, rules and guidelines of the VDE with first security rules for switching and distribution boards.

1941 VDE 0100 "Regulations on the installation of power circuits with nominal voltages below 1000V"

1958 VDE 0100 §29 N Requirements for insulation, short-circuit strength and protection against contact with live parts

1967 VDE 0660 Teil 5 factory assembled switchgear assemblies


(1973) (EN (IEC) 60439)

VDE 0100 §30 b: Construction requirements for not factory


1973 assembled switching and distribution boards

1984 VDE 0660 Teil 500 (TTA) type-tested switchgear and VDE 0660 Teil 500: (PTTA) Partially type-tested switchgear and
controlgear assemblies controlgear assemblies
(1985)
(EN (IEC) 60439-1) (EN (IEC) 60439-1)
joint construction requirements

IEC 61439-1/2 New standard for power switchgear and controlgear assemblies
2009 VDE 0660-600-1/2

Frei verwendbar © Siemens AG 2015. Alle Rechte vorbehalten.


IEC 61439 Responsibility of manufacturer

IEC 60439 IEC 61439 valid as of Nov. 2014

LV switchgear and controlgear ASSEMBLY LV switchgear and controlgear ASSEMBLY

Original manufacturer
Type tests to verify the conformity Design Verification from original manufacturer

TSK type-tested Type-tested Not type-tested


SK device device
Test Derivation Assessment

System manufacture
System manufacture

PTTA
Partially type- new ASSEMBLY (original system)
tested switchgear

Manufacturer of assembly can:

Assembly manufacturer
Assembly manufacturer

• perform the installation according to the rules


of the original manufacturer
• In case of modification, the manufacturer of
the assembly will become original
manufacturer for the customized system
Routine verification

Routine verification

Ready-to-use ASSEMBLY
Ready-to-use ASSEMBLY

Frei verwendbar © Siemens AG 2015. Alle Rechte vorbehalten.