Stone Cladding Specs for Transbay Tower
Stone Cladding Specs for Transbay Tower
Section 04 42 00
Page 1
PART 1 GENERAL
1.1 RELATED DOCUMENTS
A. Drawings and general provisions of the Contract, including General Conditions and Division 1 Specification
Sections, apply to this Section.
1.2 SUMMARY
A. This Section includes:
1. Dimension stone panels set with individual anchors.
2. Dimension stone trim units, including bands, copings, sills and jambs.
B. Related Requirements:
1. Division 1 Section ‘Sustainable Design Requirements”.
2. Division 3 Section "Cast-in-Place Concrete" for installing inserts and weld plates in concrete for anchoring
dimension stone cladding.
3. Division 4 Section "Unit Masonry" for installing inserts in unit masonry for anchoring dimension stone
cladding and for stone trim in unit masonry walls.
1.3 DEFINITIONS
A. Definitions contained in ASTM C119 apply to this Section.
B. Dimension Stone Cladding Assembly: An exterior wall covering system consisting of dimension stone panels and
trim together with anchors, backup structure, secondary weather barrier (sheathing), mortar, adhesives,
fasteners, and sealants used to secure the stone to the building structure and to produce a weather-resistant
covering.
1. Backup structure includes structurally reinforced concrete masonry unit wall.
B. Manufacturer shall specialize in manufacturing the type of exterior stone cladding specified in this section, with
a minimum of 5 years of documented successful experience, and have the facilities capable of meeting all
requirements of Contract Documents as a single-source responsibility and warranty.
C. Fabricator Qualifications: Shop that employs skilled workers who custom fabricate dimension stone cladding
assemblies similar to that required for this Project and whose products have a record of successful in-
service performance.
D. Installer Qualifications: An experienced installer who has completed a minimum of three (3) projects utilizing
dimension stone cladding systems similar in material, design, and extent to those indicated for this Project
and whose work has resulted in construction with a record of successful in-service performance of not less
than 10 year.
1. Installer's responsibilities include engineering, fabricating, and installing dimension stone cladding system.
a. Information on drawings and in Specifications establishes requirements for both aesthetic effects
and performance of the dimension stone cladding system.
1) Aesthetic effects relative to formal characteristics are indicated by dimensions, arrangement,
alignment, and profiles of components and assemblies as they relate to sight lines and
relationships to one another and to adjoining construction.
2) Performance is indicated by criteria subject to verification either by preconstruction or field test,
if applicable, or by in-service experience.
b. Do not modify intended aesthetic effects, as judged solely by Architect, except with Architect's
approval and only to the extent exclusively needed to comply with performance requirements.
1) Where modifications are proposed, submit comprehensive explanatory data to Architect for review.
TRANSBAY
TOWER SAN FRANCISCO,
ISSUED FOR CALIFORNIA
Project 08044 EXTERIOR STONE CLADDING
Section 04 42 00
Page 2
E. Professional Structural Engineer Qualifications: A professional structural engineer who is legally qualified to
practice in jurisdiction where Project is located and who is experienced in providing dimension stone
cladding engineering services of the kind indicated.
1. Engineering services are defined as those performed for installations of dimension stone cladding
systems that are similar to those indicated for this Project in material, design, and extent.
F. Testing Agency Qualifications: Qualified according to ASTM E329 for testing indicated.
G. Welding Qualifications: Qualify procedures and personnel according to AWS D1.1/D1.1M, "Structural
Welding Code – Steel, AWS D1.2/D1.2M, "Structural Welding Code – Aluminum and AWS D1.3, "Structural
Welding Code
- Sheet Steel".
H. Mockups: Build mockups to verify selections made under Sample submittals and to demonstrate aesthetic
effects and set quality standards for materials and execution.
1. Build mockups of typical exterior wall area not less than 72 inches (1800 mm) long.
a. Include typical components, attachments to building structure, and methods of installation.
b. Include sealant-filled joint complying with requirements in Section 07 92 00 "Joint Sealants."
c. Locate mockup on site.
2. Approval of mockups does not constitute approval of deviations from the Contract Documents contained
in mockups unless Architect specifically approves such deviations in writing.
3. Subject to compliance with requirements, approved mockups may become part of the completed Work if
undisturbed at time of Substantial Completion.
I. Manufacturer’s identification tags or marks are not acceptable on surfaces which will remain exposed to view after
installation.
1. Evidence of “patching” after removal of tags or marks is not acceptable.
B. General: Design stone anchors and anchoring systems according to ASTM C1242.
1. Stone anchors shall withstand not less than two times the weight of the stone cladding in both
compression and tension.
2. Fabricate and install dimension stone cladding to withstand loads from wind, gravity, movement of building
structure, and thermally induced movement as well as to resist deterioration under conditions of normal
use including exposure to weather, without failure.
3. Except where specifically shown otherwise on drawings, provide all support steel and connection
elements and assemblies for support of dimension stone cladding.
4. Support member shapes shown on the drawings are not necessarily the exact shapes required or best
suited for the particular condition.
a. The Contractor is responsible for the design of the stone work, its anchorage to the structure
(including seismic restraint) and its water and airtight integrity.
b. Method of installing and anchoring of stone work shown on drawings is diagrammatic only and shall
be used for purposes of bidding.
c. Alternative methods of detailing proposed by Contractor and meeting specified criteria will be considered.
d. Design installation to meet performance requirements specified and allow for expansion, contraction
and differential deflection of supporting floors.
5. All points of support for the stonework shall be properly braced in the three orthogonal directions
(vertical, transverse, and longitudinal) to resist all loads from any direction including both wind pressure
and suction.
6. Anchorage and supports shall be designed to accommodate variation (up/down, in/out) from theoretical
location of supporting structure and adjacent construction.
7. Provide dead load support anchors for each individual stone panel.
a. Do not stack panels.
8. Capacity of stone anchors shall not be based on the use of epoxy or grout.
a. Dead load support of panels shall not depend on pull-out.
TRANSBAY
TOWER SAN FRANCISCO,
ISSUED FOR CALIFORNIA
Project 08044 EXTERIOR STONE CLADDING
Section 04 42 00
Page 3
C. Structural Performance: Dimension stone cladding assembly shall withstand the effects of gravity loads and
the following loads and stresses within limits and under conditions indicated:
1. Wind Loads: As indicated.
a. As obtained from the wind tunnel test.
a. In accordance with the local building code.
2. Equipment Loads: Allow for loads due to window cleaning and maintenance equipment.
D. Seismic Performance: Dimension stone cladding assembly shall withstand the effects of earthquake
motions determined according to ASCE/SEI 7 and as indicated on Structural Drawings.
E. Thermal Movements: Allow for thermal movements from ambient and surface temperature changes.
1. Temperature Change: 120 deg F (67 deg C), ambient; 180 deg F (100 deg C), material surfaces.
G. Safety Factors for Stone: Design dimension stone cladding assembly to withstand loads indicated without
exceeding stone's allowable working stress determined by dividing stone's average ultimate strength, as
established by testing, by the following safety factors:
1. Safety Factor for Granite: 3.
2. Safety Factor for Concentrated Stresses: 4 for granite and 10 for stone varieties other than granite.
I. Design stone anchors and backup structure to withstand loads indicated without exceeding allowable working
stresses established by the following:
1. For Cold-Formed Stainless Steel: ASCE 8, "Specification for the Design of Cold-Formed Stainless
Steel Structural Members."
2. For Cast-in-Place and Postinstalled Fasteners in Concrete: One-fourth of tested capacity when installed
in concrete with compressive strength indicated.
3. For Postinstalled Fasteners in Masonry: One-sixth of tested capacity when installed in masonry units
indicated.
J. Limit deflection in each prefabricated assembly caused by indicated loads and thermal movements, acting
singly or in combination with one another, to not more than 1/720 of assembly's clear span or the following,
whichever is smaller:
1. 1/16 inch (1.5 mm), measured in plane of wall.
2. 1/4 inch (6 mm), measured perpendicular to wall.
K. Provisions for Fabrication and Erection Tolerances: Allow for fabrication and erection tolerances of
building's structural system. Concrete fabrication and erection tolerances are specified in Section 03 30 00
"Cast-in-Place Concrete".
L. Leakage Resistance, Water and Air: Provide dimension stone cladding system that complies with the following:
1. Water Penetration: No uncontrolled water penetration beyond plane of back of dimension stone
cladding system that is not contained or drained back to exterior, as measured by testing mockup per
ASTM E331 at a differential pressure of 20 percent of positive design wind load, but not less than 10
lbf/sq. ft. (479 Pa).
M. Corrosion and Staining Control: Prevent galvanic and other forms of corrosion as well as staining by
isolating metals and other materials from direct contact with incompatible materials. Materials shall not stain
exposed surfaces of stone and joint materials.
1.6 SUBMITTALS
A. Submit the following according to Conditions of the Construction Contract and Division 1 Specification Sections.
TRANSBAY
TOWER SAN FRANCISCO,
ISSUED FOR CALIFORNIA
Project 08044 EXTERIOR STONE CLADDING
Section 04 42 00
Page 4
C. Preliminary Design Proposal: Submit a “preliminary design proposal” with Bid, including drawings as
necessary for the basic concept of the dimension stone cladding system installation.
D. Product Data: For each variety of stone, stone accessory, and manufactured product.
E. LEED Submittals:
1. Product Certificates for Credit MR 5: For products and materials required to comply with requirements
for regional materials, certificates indicating location of material manufacturer and point of extraction, harvest,
or recovery for each raw material. Include statement indicating distance to Project, cost for each
regional material, and fraction by weight that is considered regional.
F. Shop Drawings: Show fabrication and installation details for dimension stone cladding assembly, including
dimensions and profiles of stone units.
1. Show locations and details of joints both within dimension stone cladding assembly and between
dimension stone cladding assembly and other construction.
2. Include details of mortar joints, sealant joints, and mortar joints pointed with sealant.
3. Show locations and details of anchors and backup structure.
4. Show direction of veining, grain, or other directional pattern.
5. Include large-scale shaded elevations and details of decorative surfaces and inscriptions.
G. Engineering Data for Dimension Stone Cladding Systems: Submit the following items that have been signed
and sealed by a qualified professional engineer registered in the state in which this Project is located who is
responsible for their preparation and who certifies that they comply with requirements and recognized engineering
principles and practice.
1. Drawings indicating engineering and details of system; relationships to other wall components and
systems adjacent to, or penetrating, dimension stone cladding system; and method of joinery to latter
components and systems that achieve compliance with indicated performance requirements.
a. Where method for evacuating water that penetrates dimension stone cladding is through controlled
gutters, indicate path of moisture travel.
2. Testing program for demonstrating compliance of system with performance requirements.
3. Evaluation of test reports for compliance with performance requirements.
4. Engineering analysis of system evidencing its compliance with performance requirements.
H. Samples for Initial Selection: For joint materials involving color selection.
I. Stone Samples for Verification: Sets for each variety, color, and finish of stone required; not less than 12
inches (300 mm) square.
J. Samples:
1. Stone: Prior to the Architect’s visit to the fabricator’s plant for formal stone review, submit three samples
of each stone type, 30” square, showing full range of color, grain and finish of stone, including typical
inclusions in finished work from the proposed material source.
a. Architect’s review and acceptance of samples is for color, texture and grain only of the material
source proposed.
b. Formal review and acceptance of the material for actual use on the Project shall occur at the fabricator’s
plant.
c. Compliance with other requirements is Contractor’s responsibility.
d. Sample review and acceptance shall precede mock-up installation.
2. In addition to above, provide adjacent 12” x 12” sample panels showing sealant and grout materials for
Architect’s review.
3. Anchorage Devices: 3” long.
K. Colored Pointing Mortar Samples for Verification: For each color required. Make Samples using same sand
and mortar ingredients to be used on Project.
L. Sealant Samples for Verification: For each type and color of joint sealant required.
TRANSBAY
TOWER SAN FRANCISCO,
ISSUED FOR CALIFORNIA
Project 08044 EXTERIOR STONE CLADDING
Section 04 42 00
Page 5
N. Maintenance Data: Shall clearly indicate manufacturer's printed instructions for maintenance of installed
work, including methods and frequency recommended for maintaining optimum condition under anticipated
use conditions and precautions against materials and methods which may be detrimental to finishes and
performances.
1. Submit National Building Granite Quarries Association, Inc. recommended cleaning and maintenance
instructions for stone materials being used.
O. Hazardous Materials Notification: In the event no product or material is available that does not contain
asbestos, PCB or other hazardous materials as determined by the Owner, a "Material Safety Data Sheet"
(MSDS) equivalent to OSHA Form 20 shall be submitted for that proposed product or material prior to
installation.
P. Asbestos and PCB Certification: After completion of installation, but prior to Substantial Completion,
Contractor shall certify in writing that products and materials installed, and processes used, do not contain
asbestos or polychlorinated biphenyls (PCB), using format in Article 3 of General Conditions.
B. Welding certificates.
F. Cold-Weather Procedures: Detailed description of methods, materials, and equipment to be used to comply
with cold-weather requirements.
B. Store and handle stone and related materials to prevent deterioration or damage due to moisture,
temperature changes, contaminants, corrosion, breaking, chipping, and other causes.
1. Lift stone with wide-belt slings; do not use wire rope or ropes that might cause staining. Move stone, if
required, using dollies with cushioned wood supports.
2. Store stone on wood skids or pallets with nonstaining, waterproof covers. Arrange to distribute weight evenly
and to prevent damage to stone. Ventilate under covers to prevent condensation.
C. Mark stone units, on surface that will be concealed after installation, with designations used on Shop Drawings
to identify individual stone units. Orient markings on vertical panels so that they are right side up when units
are installed.
D. Deliver sealants to Project site in original unopened containers labeled with manufacturer's name, product
name and designation, color, expiration period, pot life, curing time, and mixing instructions for
multicomponent materials.
TRANSBAY
TOWER SAN FRANCISCO,
ISSUED FOR CALIFORNIA
Project 08044 EXTERIOR STONE CLADDING
Section 04 42 00
Page 6
E. Store cementitious materials on elevated platforms, under cover, and in a dry location. Do not use
cementitious materials that have become damp.
F. Store aggregates in locations where grading and other required characteristics can be maintained and
where contamination can be avoided.
G. Do not exceed building design loads during delivery and storage of stone and setting materials.
1. No portions of the building or Project site are designated as storage locations for the stone.
B. Cold-Weather Requirements: Do not use frozen materials or materials mixed or coated with ice or frost.
Remove and replace dimension stone cladding damaged by frost or freezing conditions. Comply with cold-
weather construction and protection requirements for masonry contained in ACI 530.1/ASCE 6/TMS 602.
C. Hot-Weather Requirements: Comply with hot-weather construction and protection requirements for masonry
contained in ACI 530.1/ASCE 6/TMS 602.
D. Environmental Limitations for Sealants: Do not install sealants when ambient and substrate temperatures
are outside limits permitted by sealant manufacturer or below 40 deg F (5 deg C) or when joint substrates are
wet.
1.11 COORDINATION
A. Coordinate installation of inserts that are to be embedded in concrete or masonry, flashing reglets, and
similar items to be used by dimension stone cladding Installer for anchoring, supporting, and flashing of
dimension stone cladding assembly. Furnish setting drawings, templates, and directions for installing such
items and deliver to Project site in time for installation.
B. Time delivery and installation of dimension stone cladding to avoid extended on-site storage and to coordinate
with work adjacent to dimension stone cladding.
1.12 WARRANTY
A. Comply with General Conditions and Division 1 Section “Product Requirements”.
TRANSBAY
TOWER SAN FRANCISCO,
ISSUED FOR CALIFORNIA
Project 08044 EXTERIOR STONE CLADDING
Section 04 42 00
Page 7
6. Cladding System Mockup Tests: For performance of dimension stone cladding system, evaluated for
compliance with requirements by mockup testing per ASTM E72, with a maximum test load equal to 4
times the design load.
a. Remove test mockups from laboratory when testing program is completed and dispose of legally; do not
use materials from mockups on Project.
B. Water Porosity Testing shall be performed on each type and finish of stone proposed.
1. A minimum of three specimens each is required, of correct outdoor/indoor finishes.
a. Minimum size is 12” by 12”, of thickness as proposed for project.
2. With the stone supported in a horizontal position, install a cylindrical sleeve (at least 2” in diameter), and
sealed to the exterior face of the stone specimen.
3. Fill sleeve with cold water to a depth of 10” and maintain depth for 10 days.
4. Record: When dampness is first visible on the interior surface, when water droplets are first visible on
the interior surface, and when water begins to drip from the interior surface.
a. If dripping occurs, collect and record (within any 1 hour period) the quantity of water volume collected.
b. Formation of water droplets (with or without dripping) constitutes failure.
c. All specimens must pass.
C. Preconstruction Sealant Compatibility Staining and Adhesion Testing: Submit to joint-sealant manufacturers,
for compatibility and adhesion testing according to sealant manufacturer's standard testing methods and
Section 07 92 00 "Joint Sealants" Samples of materials that will contact or affect joint sealants.
1. Submit not fewer than 9 pieces of each variety and finish of stone, setting buttons, and joint-sealant backings.
2. Schedule sufficient time for testing and analyzing results to prevent delaying the Work.
3. For materials failing tests, obtain joint sealant manufacturer's written instructions for corrective measures,
including use of specially formulated primers.
4. Sealant manufacturer's representative shall pick up samples at Project site after being notified by Contractor.
5. Lab testing shall be performed by sealant manufacturer at no cost to Architect, Contractor or Owner.
D. Preconstruction Field Testing of Sealants: Before installing joint sealants, field test their adhesion to joint
substrates according to Section 07 92 00 "Joint Sealants."
PART 2 PRODUCTS
2.1 UNAUTHORIZED MATERIALS
A. Materials and products required for work of this section shall not contain asbestos, polychlorinated biphenyls
(PCB) or other hazardous materials identified by the Owner.
B. Source Limitations for Stone: Obtain each variety of stone, regardless of finish, from single quarry, whether
specified in this Section or in another Section of the Specifications, with resources to provide materials of
consistent quality in appearance and physical properties.
1. For stone types that include same list of varieties and sources, provide same variety from same source
for each.
2. Make quarried blocks available for examination by Architect and the Owner.
3. The acceptable color range and grain variation for each stone type and finish will be developed through
a series of visits to each of the stone fabricators’ plants.
a. Set up a number of large uncut finished slabs (minimum of 11) of each type sufficient to demonstrate
the extreme range, veining, inclusions, knots, swirls, etc., that can be expected for the production
run material in a vertical position in the fabricator’s yard for viewing by the Architect and Owner.
b. The Architect will select the stones which are acceptable and conform to the requirements of the
specifications, rejecting any other stones falling outside the requirements.
c. Each approved stone panel will be cut in half, with one half being shipped to the Project site with
the initial shipment of stone and the other half remaining at the fabricator’s plant for quality control
purposes.
4. Establish procedures for blending the range of color and grain of stone panels.
a. Control variation from piece to piece to eliminate patchwork or “checkerboard” appearance.
b. Provide for evenly blended appearance of finish work.
TRANSBAY
TOWER SAN FRANCISCO,
ISSUED FOR CALIFORNIA
Project 08044 EXTERIOR STONE CLADDING
Section 04 42 00
Page 8
C. Source Limitations for Mortar Materials: Obtain mortar ingredients of uniform quality for each cementitious
component from single manufacturer and each aggregate from single source or producer.
D. Source Limitations for Other Materials: Obtain each type of stone accessory, sealant, and other material
from single manufacturer for each product.
E. Substitutions: Comply with Division 1 Section “Product Requirements” using form in Division 1 Section
“Substitution Request Form”.
2.3 GRANITE
A. Material Standard: Comply with ASTM C615.
B. Regional Content: For material that is extracted, harvested or recovered as well as manufactured within 500
miles of the project site – 101 First Street, San Francisco, CA, contractor shall document the cost and
percentage (by weight) of each material that is regional.
C. Varieties and Sources: Subject to compliance with requirements, provide the following:
1. Refer to Stone Schedule in this section.
D. Cut: Vein.
1. Orientation of Veining: Vertical.
F. Match Architect's samples for color, finish, and other stone characteristics relating to aesthetic effects.
G. Thickness: Not less than 1-1/4 inches (32 mm) unless otherwise indicated.
1. Minimum Thickness: Provide stone units of not less than thickness indicated, and not less than the
thickness required to meet the design criteria.
B. Cast-in-Place Concrete Inserts: Either threaded or wedge type unless otherwise indicated; galvanized
ferrous castings, either ASTM A47/A 47M malleable iron or ASTM A27/A 27M cast steel, with capability to
sustain, without failure, a load equal to 4 times the loads imposed as determined by testing per ASTM E488,
conducted by a qualified independent testing agency. Provide bolts, washers, and shims as needed, all hot-
dip galvanized per ASTM F2329.
C. Postinstalled Anchor Bolts for Concrete and Masonry: Chemical anchors, torque-controlled expansion anchors or
undercut anchors made from stainless-steel components complying with ASTM F593 and ASTM F594, Alloy
Group 1 or 2 (ASTM F738M and ASTM F836M, Alloy Group A1 or A4) for bolts and nuts; ASTM A240/A
240M, ASTM A276, or ASTM A666, Type 304 or 316, for anchors, with capability to sustain, without failure, a
load equal to 4 times the loads imposed, for concrete, or 6 times the load imposed, for masonry, as determined
by testing per ASTM E488, conducted by a qualified independent testing agency.
D. Threaded Fasteners: Heavy hexagon structural bolts, heavy hexagon nuts, and hardened washers.
1. For stainless steel, use annealed stainless-steel bolts, nuts, and washers; for bolts, ASTM F593 (ASTM
F738M); and for nuts, ASTM F594 (ASTM F836M), Alloy Group 2 (A4).
E. Weld Plates for Installation in Concrete: Comply with Section 05 50 00 "Metal Fabrications."
TRANSBAY
TOWER SAN FRANCISCO,
ISSUED FOR CALIFORNIA
Project 08044 EXTERIOR STONE CLADDING
Section 04 42 00
Page 9
C. Portland Cement-Lime Mix: Packaged blend of portland cement and hydrated lime.
D. Colored Portland Cement-Lime Mix: Packaged blend of portland cement, hydrated lime, and mortar
pigments. Mix shall produce color indicated or, if not indicated, as selected from manufacturer's standard
colors. Pigments shall not exceed 10 percent of portland cement by weight.
1. Products: Subject to compliance with requirements, provide one of the following:
a. Holcim (US) Inc.; Rainbow Mortamix Custom Color Cement/Lime.
b. Lafarge North America Inc.; Eaglebond.
c. Lehigh Cement Company; Lehigh Custom Color Portland/Lime Cement.
E. Aggregate: ASTM C144; except for joints narrower than 1/4 inch (6 mm) and pointing mortar, 100 percent
shall pass No. 16 (1.18-mm) sieve.
1. White Aggregates: Natural white sand or ground white stone.
2. Colored Aggregates: Natural-colored sand or ground marble, granite, or other durable stone; of color
necessary to produce required mortar color.
F. Water: Potable.
B. Setting Buttons: Resilient plastic buttons, nonstaining to stone, sized to suit joint thicknesses and bed depths
of stone units without intruding into required depths of pointing materials.
C. Concealed Sheet Metal Flashing: Fabricated from zinc-tin, alloy-coated stainless steel in thicknesses
indicated, but not less than 0.0156 inch (0.4 mm) thick, and complying with Section 07 62 00 "Sheet Metal
Flashing and Trim."
C. Flexible Flashing: For installation under copings, stones, at shelf angles and footings.
D. Cementitious Dampproofing for Limestone: Cementitious formulation recommended by ILI and nonstaining to
stone; compatible with joint sealants and noncorrosive to anchors and attachments.
E. Weep and Vent Tubes: Medium-density polyethylene tubing, 1/4-inch (6-mm) OD, Rectangular, cellular,
polypropylene or clear butyrate extrusion, 3/8 by 1-1/2 inches (9 by 38 mm), of length required to extend
from exterior face of stone to cavity behind.
F. Cellular Plastic Weep Hole/Vents: One-piece, flexible extrusion made from UV-resistant polypropylene
copolymer, of length required to extend from exterior face of stone to cavity behind, in color selected from
manufacturer's standard.
G. Mesh Weep/Vent: Free-draining mesh; made from polyethylene strands, of length required to extend from
exterior face of stone to cavity behind, in color selected from manufacturer's standard.
H. Wicking Material: Absorbent rope, made from cotton or UV-resistant synthetic fiber, 1/4 to 3/8 inch (6 to 10 mm)
in diameter, of length required to produce 2-inch (50-mm) exposure on exterior and 18 inches (450 mm) in
cavity between wythes.
I. Sealants for Joints in Dimension Stone Cladding: Manufacturer's standard chemically curing, elastomeric
sealants of base polymer and characteristics indicated below that comply with applicable requirements in Section
07 92 00 "Joint Sealants" and do not stain stone:
1. Silicone Joint Sealant: Single component, nonsag, neutral curing, Class 50.
2. Joint-Sealant Colors: As selected by Architect from manufacturer's full range of colors.
J. Sealant for Filling Kerfs: Same sealant used for joints in dimension stone.
TRANSBAY
TOWER SAN FRANCISCO,
ISSUED FOR CALIFORNIA
Project 08044 EXTERIOR STONE CLADDING
Section 04 42 00
Page 10
B. Control depth of stone and back check to maintain minimum clearance of 1-1/2 inches (38 mm) between backs of
stone units and surfaces or projections of structural members, fireproofing (if any), backup walls, and other
work behind stone.
C. Dress joints (bed and vertical) straight and at right angle to face unless otherwise indicated. Shape beds to
fit supports.
D. Cut and drill sinkages and holes in stone for anchors, fasteners, supports, and lifting devices as indicated or
needed to set stone securely in place.
E. Liners: Provide greater stone thickness where extent of cutouts indicated decreases effective strength of
remaining material, or for proper and sufficient anchorage suitable and adequate bearing areas or surfaces.
1. Use of liners properly sized by manufacturer and secured to stone facing permitted only where indicated.
F. Finish exposed faces and edges of stone to comply with requirements indicated for finish and to match
approved samples and mockups.
1. Exposed edges of dimension stone cladding shall have a uniform thickness.
G. Cut stone to produce uniform joints 3/8 inch (10 mm) wide and in locations indicated.
H. Contiguous Work: Provide chases, reveals, reglets, openings, and similar features as required to
accommodate contiguous work.
I. Fabricate molded work, including washes and drips, to produce stone shapes with a uniform profile
throughout entire unit length, with precisely formed arris slightly eased to prevent snipping, and with matching
profile at joints between units.
1. Produce moldings and molded edges with machines that use abrasive shaping wheels made to reverse
contour of molding shape.
J. Clean backs of stone to remove rust stains, iron particles, and stone dust.
K. Inspect finished stone units at fabrication plant for compliance with requirements for appearance, material,
and fabrication. Replace defective units.
1. Grade and mark stone for overall uniform appearance when assembled in place. Natural variations in
appearance are acceptable if installed stone units match range of colors and other appearance
characteristics represented in approved samples and mockups.
B. Portland Cement-Lime Setting Mortar: Comply with ASTM C270, Proportion Specification, for types of mortar
indicated below:
1. Set granite with Type S mortar.
2. Set limestone with Type N mortar.
C. Pointing Mortar: Comply with ASTM C270, Proportion Specification, for types of mortar indicated. Provide
pointing mortar mixed to match Architect's sample and complying with the following:
1. Packaged Portland Cement-Lime Mix Mortar: Use portland cement-lime mix of selected color.
2. Point granite with Type S mortar.
3. Point limestone with Type N mortar.
TRANSBAY
TOWER SAN FRANCISCO,
ISSUED FOR CALIFORNIA
Project 08044 EXTERIOR STONE CLADDING
Section 04 42 00
Page 11
PART 3 EXECUTION
3.1 EXAMINATION
A. Examine surfaces to receive dimension stone cladding and conditions under which dimension stone cladding
will be installed, with Installer present, for compliance with requirements for installation tolerances and other
conditions affecting performance of dimension stone cladding.
B. Prepare written report, endorsed by Installer, listing conditions detrimental to performance of dimension
stone cladding.
C. Proceed with installation only after unsatisfactory conditions have been corrected.
B. Execute dimension stone cladding installation by skilled mechanics and employ skilled stone fitters at Project
site to do necessary field cutting as stone is set.
1. Use power saws with diamond blades to cut stone. Produce lines cut straight and true, with edges
eased slightly to prevent snipping.
2. Field cutting not permitted without Architect’s approval for each instance.
C. Contiguous Work: Provide reveals, reglets, and openings as required to accommodate contiguous work.
E. Provide expansion, control, and pressure-relieving joints of widths and at locations indicated.
1. Sealing expansion and other joints is specified in Section 07 92 00 "Joint Sealants."
2. Keep expansion joints free of mortar and other rigid materials.
F. Install concealed flashing at continuous shelf angles, lintels, ledges, and similar obstructions to downward flow
of water, to divert water to building exterior. Extend flashing 6 inches (150 mm) at ends and turn up not less
than 2 inches (50 mm) to form end dams.
1. Install end dams to control the flow of water to the building exterior.
TRANSBAY
TOWER SAN FRANCISCO,
ISSUED FOR CALIFORNIA
Project 08044 EXTERIOR STONE CLADDING
Section 04 42 00
Page 12
G. Keep cavities open where unfilled space is indicated between back of stone units and backup wall; do not fill
cavities with mortar or grout.
1. Place weep holes in joints where moisture may accumulate, including at base of cavity walls and above shelf
angles and flashing. Locate weep holes at intervals not exceeding 24 inches (600 mm). Use weep and
vent tubes, plastic weep hole/vents or wicking material.
2. Place vents in cavity walls at tops of cavities, below shelf angles and flashing, and at intervals not
exceeding 20 feet (6 m) vertically. Locate vents in joints at intervals not exceeding 60 inches (1500 mm)
horizontally. Use weep and vent tubes or plastic weep hole/vents.
3. Fill space between back of stone units and back-up wall solidly with grout up to 12” above finish grade.
B. Attach anchors securely to stone and to backup surfaces. Comply with recommendations in ASTM C1242.
C. Provide compressible filler in ends of dowel holes and bottoms of kerfs to prevent end bearing of dowels and
anchor tabs on stone. Fill remainder of anchor holes and kerfs with sealant indicated for filling kerfs.
D. Set stone supported on clips or continuous angles on resilient setting shims. Use material of thickness required
to maintain uniform joint widths and to prevent point loading of stone on anchors. Hold shims back from face
of stone a distance at least equal to width of joint.
B. Set stone in full bed of mortar with head joints filled unless otherwise indicated.
1. Use setting buttons of adequate size, in sufficient quantity, and of thickness required to maintain uniform joint
width and to prevent mortar from extruding. Hold buttons back from face of stone a distance at least equal
to width of joint, but not less than depth of pointing materials.
2. Do not set heavy units or projecting courses until mortar in courses below has hardened enough to
resist being squeezed out of joint.
3. Support and brace projecting stones until wall above is in place and mortar has set.
4. Provide compressible filler in ends of dowel holes and bottoms of kerfs to prevent end bearing of dowels
and anchor tabs on stone. Fill remainder of anchor holes and kerfs with mortar.
C. Embed ends of sills in mortar; leave remainder of joint open until final pointing.
D. Rake out joints for pointing with mortar to depths of not less than 1/2 inch (12 mm). Rake joints to uniform
depths with square bottoms and clean sides.
E. Prepare stone-joint surfaces for pointing with mortar by removing dust and mortar particles. Where setting
mortar was removed to depths greater than surrounding areas, apply first layer of pointing mortar in layers not
more than 3/8 inch (10 mm) until a uniform depth is formed.
F. Point stone joints by placing pointing mortar in layers not more than 3/8 inch (10 mm). Compact each layer
thoroughly and allow to become thumbprint hard before applying next layer.
G. Tool joints with a round jointer having a diameter 1/8 inch (3 mm) larger than width of joint, when pointing mortar
is thumbprint hard.
H. Rake out mortar from sealant-pointed joints to depths required for sealant and sealant backing but not less
than 1/2 inch (12 mm). Rake joints to uniform depths with square bottoms and clean sides.
I. Set the following dimension stone cladding with unfilled head joints for installing joint sealants:
1. Cornices.
2. Copings.
3. Sills.
4. Belt and other projecting courses.
TRANSBAY
TOWER SAN FRANCISCO,
ISSUED FOR CALIFORNIA
Project 08044 EXTERIOR STONE CLADDING
Section 04 42 00
Page 13
B. Variation from Level: For lintels, sills, water tables, parapets, horizontal bands, horizontal grooves, and
other conspicuous lines, do not exceed 1/8 inch in 10 feet (3 mm in 3 m), 1/4 inch in 20 feet (6 mm in 6 m),
or 3/8 inch (10 mm) maximum.
C. Variation of Linear Building Line: For positions shown in plan and related portions of walls and partitions, do
not exceed 1/4 inch in 20 feet (6 mm in 6 m) or 1/2 inch in 40 feet (12 mm in 12 m) or more.
D. Variation in Cross-Sectional Dimensions: For thickness of walls from dimensions indicated, do not exceed plus or
minus 1/4 inch (6 mm).
E. Variation in Joint Width: Do not vary from average joint width more than plus or minus 1/8 inch (3 mm) or a
quarter of nominal joint width, whichever is less. For joints within 60 inches (1500 mm) of each other, do not
vary more than 1/8 inch (3 mm) or a quarter of nominal joint width, whichever is less from one to the other.
F. Variation in Plane between Adjacent Stone Units (Lipping): Do not exceed 1/16-inch (1.5-mm) difference
between planes of adjacent units.
B. Replace damaged or defective work in a manner that results in dimension stone cladding's matching
approved samples and mockups, complying with other requirements, and showing no evidence of
replacement.
C. In-Progress Cleaning: Clean dimension stone cladding as work progresses. Remove mortar fins and
smears before tooling joints. Remove excess sealant and smears as sealant is installed.
D. Final Cleaning: Clean dimension stone cladding no fewer than six days after completion of pointing and
sealing, using clean water and stiff-bristle fiber brushes. Do not use wire brushes, acid-type cleaning agents,
cleaning agents containing caustic compounds or abrasives, or other materials or methods that could damage
stone.
TRANSBAY
TOWER SAN FRANCISCO,
ISSUED FOR CALIFORNIA
Project 08044 EXTERIOR STONE CLADDING
Section 04 42 00
Page 14
END OF SECTION
TRANSBAY
TOWER SAN FRANCISCO,
ISSUED FOR CALIFORNIA