IEEE Standard Requirements For Secondary Network Protectors
IEEE Standard Requirements For Secondary Network Protectors
44-2000
                                                                                                                                                        (Revision of
                                                                                                                                           IEEE Std C57.12.44-1994)
                                         Sponsor
                                         Transformers Committee
                                         of the
                                         IEEE Power Engineering Society
                                         Abstract: The performance, electrical and mechanical interchangeability, and the safety of the
                                         equipment are covered. The proper selection of such equipment is established as a basis for use
                                         in this standard. Certain electrical, dimensional, and mechanical characteristics are described; and
                                         certain safety features of three-phase, 60 Hz, low-voltage (600 V and below) network protectors are
                                         taken into consideration. This equipment is used for automatically connecting and disconnecting a
                                         network transformer from a secondary spot or grid network.
                                         Keywords: grid network, network, protector, spot network
                                         No part of this publication may be reproduced in any form, in an electronic retrieval system or otherwise, without the prior
                                         written permission of the publisher.
--``,-`-`,,`,,`,`,,`---
                                    Use of an IEEE Standard is wholly voluntary. The existence of an IEEE Standard does not imply that there
                                    are no other ways to produce, test, measure, purchase, market, or provide other goods and services related to
                                    the scope of the IEEE Standard. Furthermore, the viewpoint expressed at the time a standard is approved and
                                    issued is subject to change brought about through developments in the state of the art and comments
                                    received from users of the standard. Every IEEE Standard is subjected to review at least every five years for
                                    revision or reaffirmation. When a document is more than five years old and has not been reaffirmed, it is rea-
                                    sonable to conclude that its contents, although still of some value, do not wholly reflect the present state of
                                    the art. Users are cautioned to check to determine that they have the latest edition of any IEEE Standard.
                                                                                                                                                        --``,-`-`,,`,,`,`,,`---
                                    Comments for revision of IEEE Standards are welcome from any interested party, regardless of membership
                                    affiliation with IEEE. Suggestions for changes in documents should be in the form of a proposed change of
                                    text, together with appropriate supporting comments.
                                    Interpretations: Occasionally questions may arise regarding the meaning of portions of standards as they
                                    relate to specific applications. When the need for interpretations is brought to the attention of IEEE, the
                                    Institute will initiate action to prepare appropriate responses. Since IEEE Standards represent a consensus of
                                    all concerned interests, it is important to ensure that any interpretation has also received the concurrence of a
                                    balance of interests. For this reason, IEEE and the members of its societies and Standards Coordinating
                                    Committees are not able to provide an instant response to interpretation requests except in those cases where
                                    the matter has previously received formal consideration.
                                                         Note: Attention is called to the possibility that implementation of this standard may
                                                         require use of subject matter covered by patent rights. By publication of this standard,
                                                         no position is taken with respect to the existence or validity of any patent rights in
                                                         connection therewith. The IEEE shall not be responsible for identifying patents for
                                                         which a license may be required by an IEEE standard or for conducting inquiries into
                                                         the legal validity or scope of those patents that are brought to its attention.
                                    IEEE is the sole entity that may authorize the use of certification marks, trademarks, or other designations to
                                    indicate compliance with the materials set forth herein.
                                    Authorization to photocopy portions of any individual standard for internal or personal use is granted by the
                                    Institute of Electrical and Electronics Engineers, Inc., provided that the appropriate fee is paid to Copyright
                                    Clearance Center. To arrange for payment of licensing fee, please contact Copyright Clearance Center, Cus-
                                    tomer Service, 222 Rosewood Drive, Danvers, MA 01923 USA; (978) 750-8400. Permission to photocopy
                                    portions of any individual standard for educational classroom use can also be obtained through the Copy-
                                    right Clearance Center.
                                             This is the first revision of IEEE Std C57.12.44, which was originally published in 1994. The main purpose
                                             of this revision is to incorporate the many improvement ideas received during the balloting for the original
                                             standard and to expand fuse information. The revision officially started with an IEEE Project Authorization
                                             Request approval on 29 September 1995. The revision was accomplished by the Working Group on
                                             Requirements for Secondary Network Protectors under the Underground Transformers and Network
                   --``,-`-`,,`,,`,`,,`---
                                             Protectors Subcommittee of the IEEE PES Transformers Committee. The major changes are the addition of
                                             figures depicting the terminals in Clause 11, the addition of fuse pictures and fuse curves in Annex B, and
                                             the conversion to metric as the primary dimensional system in accordance with IEEE policy. Clauses 4, 5, 6,
                                             8, 10, and 11 of the standard were significantly revised, as were Annexes B and C.
                                             A task force working group consisting of EEI, NEMA, and IEEE PES delegates developed the original doc-
                                             ument. The first working group meeting was held 24 February 1988, in Washington, D.C. The document was
                                             completed in late 1994 by the Working Group on Requirements for Secondary Network Protectors under the
                                             Underground Transformers and Network Protectors Subcommittee of the of the IEEE PES Transformers
                                             Committee. Mr. R. B. Robertson chaired the working group during the preparation and balloting of the orig-
                                             inal standard.
                                             This IEEE standard is a voluntary consensus standard. Its use becomes mandatory only when required by a
                                             duly constituted legal authority or when specified in a contractual relationship. To meet specialized needs
                                             and to allow innovation, specific changes are permissible when mutually determined by the user and the pro-
                                             ducer, provided such changes do not violate existing laws and are considered technically adequate for the
                                             function intended.
                                             The Working Group on Requirements for Secondary Network Protectors had the following membership dur-
                                             ing the revision process:
                                                                                    D. H. Mulkey, Chair
                                                     A. J. Alcantara, Jr.                  G. Miller                            E. Owen
                                                     E. A. Bertolini                       M. C. Mingoia                        B. Nutt
                                                     R. R. Butani                          J. R. Moffat                         P. G. Risse
                                                     R. W. Fisher                          C. G. Niemann                        A. L. Robinson, Jr.
                                                     R. D. Graham                          P. E. Orehek                         K. Romano
                                                     J. L. Harper                                                               W. G. Wimmer
                                    The final conditions for approval of this standard were met on 10 August 2000. This standard was condition-
                                    ally approved by the IEEE-SA Standards Board on 21 June 2000, with the following membership:
*Member Emeritus
                                                                               Noelle D. Humenick
                                                                           IEEE Standards Project Editor
--``,-`-`,,`,,`,`,,`---
                                                  1.1 Scope............................................................................................................................................ 1
                                                  1.2 Purpose......................................................................................................................................... 1
                                                  1.3 Word usage .................................................................................................................................. 1
2. References............................................................................................................................................ 1
3. Definitions............................................................................................................................................ 2
4. Service conditions................................................................................................................................ 4
6. Production tests.................................................................................................................................. 11
                                                  7.1      General....................................................................................................................................... 15
                                                  7.2      Closing characteristics ............................................................................................................... 15
                                                  7.3      Tripping characteristics.............................................................................................................. 15
                                                  7.4      Closing adjustment..................................................................................................................... 16
                                                  7.5      Tripping adjustment ................................................................................................................... 16
                                                  9.1      Nameplates................................................................................................................................. 20
                                                  9.2      Interrupting rating ...................................................................................................................... 20
                                                  9.3      AC voltage ratings ..................................................................................................................... 20
                                                  9.4      Dielectric test voltage ................................................................................................................ 20
1. Overview
1.1 Scope
                                    This standard describes certain electrical, dimensional, and mechanical characteristics and takes into consid-
                                    eration certain safety features of three-phase, 60 Hz, low-voltage (600 V and below) network protectors.
                                    They are used for automatically connecting and disconnecting a network transformer from a secondary spot
                                    or grid network.
1.2 Purpose
                                    This standard is intended for use as a basis for establishing the performance, electrical and mechanical inter-
                                    changeability, and safety of the equipment covered and to assist in the proper selection of such equipment.
                                    As used in this standard, the word “shall” indicates mandatory requirements. The words “should” and “may”
                                    refer to matters that are recommended and permissive, respectively, but not mandatory.
                                    NOTE—The introduction of this standard describes the circumstances under which the document may be used on a
                                    mandatory basis.
2. References
                                    All characteristics, definitions, tests, and voltage designations, except as specifically covered in this stan-
                                    dard, shall be in accordance with the standards listed below.
                                    When a standard referred to in this document is superseded by a revision, the revision shall not apply. The
                                    referenced standard and the specific referenced edition shall be the applicable referenced standard until the
                                    new version of the referenced document is incorporated by formal action or appropriate revision of the citing
                                    standard.
                                                    ANSI B1.1-1989, American National Standard for Unified Inch Screw Threads (UN and UNR Thread
                                                    Forms).1
ANSI B1.20.1-1983, American National Standard for Pipe Threads, General Purpose (Inch).
                                                    ANSI C57.12.40-1994, American National Standard for Secondary Network Transformers—Subway and
                                                    Vault Types (Liquid Immersed)—Requirements.
                                                    ANSI C57.12.70-1978 (Reaff 1992), American National Standard Terminal Markings and Connections for
                                                    Distribution and Power Transformers.
                                                    ANSI C84.1-1995, American National Standard Voltage Ratings (60 Hz) for Electric Power Systems and
                                                    Equipment.
                                                    IEEE Std 1-1986 (Reaff 1992), IEEE Standard General Principles for Temperature Limits in the Rating of
                                                    Electric Equipment and for the Evaluation of Electrical Insulation.2
                                                    IEEE Std 100, IEEE Standard Dictionary of Electrical and Electronics Terms, Sixth Edition.
                          --``,-`-`,,`,,`,`,,`---
                                                    ANSI C37.09-1979 (Reaff 1988), IEEE Standard Test Procedure for AC High-Voltage Circuit Breakers
                                                    Rated on a Symmetrical Current Basis.
IEEE Std C37.108-1989 (Reaff 1994), IEEE Guide for the Protection of Network Transformers.
                                                    IEEE Std C57.12.00-1993, IEEE Standard General Requirements for Liquid-Immersed Distribution, Power,
                                                    and Regulating Transformers.
                                                    IEEE Std C57.12.80-1978 (Reaff 1992), IEEE Standard Terminology for Power and Distribution
                                                    Transformers.
                                                    IEEE Std C57.91-1995, IEEE Guide for Loading Mineral-Oil-Immersed Overhead and Pad-Mounted Distri-
                                                    bution Transformers Rated 500 kVA and Less with 65 °C or 55 °C Average Winding Rise.
3. Definitions
                                                    An asterisk (*) following a definition indicates that the definition is identical to that which appears in IEEE
                                                    Std 100, IEEE Standard Dictionary of Electrical and Electronics Terms.
                                                    1ANSI publications are available from the Sales Department, American National Standards Institute, 11 West 42nd Street, 13th Floor,
                                                    New York, NY 10036, USA (http://www.ansi.org/).
                                                    2IEEE publications are available from the Institute of Electrical and Electronics Engineers, 445 Hoes Lane, P.O. Box 1331, Piscataway,
                                                    NJ 08855-1331, USA (http://standards.ieee.org/).
                                    3.1 arcing contacts: The contacts of a switching device on which the arc is drawn after the main (and inter-
                                    mediate, where used) contacts have parted.*
                                    3.2 desensitizing relay: A relay that prevents tripping of a network protector on transient power reversals,
                                    which neither exceed a predetermined value nor persist for a predetermined time.
                                    3.3 intermediate contacts: Contacts in the main circuit that part after the main contacts and before the arcing
                                    contacts have parted.*
3.4 main contacts: Contacts that carry all or most of the main current.*
                                    3.5 network limiter: An enclosed fuse for disconnecting a faulted cable from a low-voltage network distri-
                                    bution system and for protecting the unfaulted portions of that cable against serious thermal damage.*
                                                                                                                                                           --``,-`-`,,`,,`,`,,`---
                                    3.6 network master relay: A relay that functions as a protective relay by opening a network protector when
                                    power is back-fed into the supply system and as a programming relay by closing the protector in conjunction
                                    with the network phasing relay when polyphase voltage phasors are within prescribed limits.*
                                    3.7 network phasing relay: A monitoring relay that has as its function to limit the operation of a network
                                    master relay so that the network protector may close only when the voltages on the two sides of the protector
                                    are in a predetermined phasor relationship.*
                                    3.8 network protector: An assembly comprising a circuit breaker and its complete control equipment for
                                    automatically disconnecting a transformer from a secondary network in response to predetermined electrical
                                    conditions on the primary feeder or transformer, and for connecting a transformer to a secondary network
                                    either through manual control or automatic control responsive to predetermined electrical conditions on the
                                    feeder and the secondary network.
                                    NOTE—The network protector is usually arranged to connect automatically its associated transformer to the network
                                    when conditions are such that the transformer, when connected, will supply power to the network and to automatically
                                    disconnect the transformer from the network when power flows from the network to the transformer.*
3.9 network protector fuse: A back-up device for the network protector.
                                    3.10 network secondary distribution system: A system of alternating-current distribution in which the sec-
                                    ondaries of the distribution transformers are connected to a common network for supplying light and power
                                    directly to consumers’ services.
                                    3.11 phasing voltage: The voltage across the open contacts of a selected phase.
                                    NOTE—This voltage is equal to the phasor difference between the transformer voltage and the corresponding network
                                    voltage.*
3.12 pumping: The unintentional cyclical tripping and closing of a network protector.
                                    3.13 removable breaker: The removable breaker consists of the circuit breaker, disconnecting provisions,
                                    network relays, auxiliary panels, current transformers, control devices, other attachments, and all intercon-
                                    necting wiring, which can be rolled out of the network protector enclosure on rails for maintenance or
                                    removal.
                                    3.14 short-time current: The current carried by a device, an assembly, or a bus for a specified short time
                                    interval.*
                                                  3.16 solid-state or microprocessor network relay: A relay with no mechanical parts, using solid-state com-
                                                  ponents, that performs the combined functions of the master and phasing relays, and that may include a time
                                                  delay function.
                                                  3.17 spot network: A small network, usually at one location, consisting of two or more primary feeders,
                                                  with network units and one or more load service connections.
                                                  3.18 trip-free: The capability of a switching device to have the moving contacts return to and remain in the
                                                  opening position when the opening operation is initiated after the initiation of the closing operation, even if
                                                  the closing force and command are maintained.*
4. Service conditions
4.1.1 General
                                                  Network protectors conforming to this standard shall be suitable for operation at rated current under the fol-
                                                  lowing conditions.
4.1.2 Temperature
4.1.3 Altitude
4.1.4 Generation
                                                  The network protector is designed to be applied to a system with power generation only on the high voltage
                                                  side of the transformer that supplies networked secondary without any secondary power generation.
                        --``,-`-`,,`,,`,`,,`---
4.2.1 General
                                                  Conditions other than those described in 4.1.1 are considered unusual service, and when prevalent, shall be
                                                  brought to the attention of those responsible for the design and application of the apparatus. Examples of
                                                  some of these conditions are listed in 4.2.2 and 4.2.3.
                                                  Network protectors may be used at higher or lower ambient temperatures or at higher altitudes than those
                                                  specified in 4.1, but special consideration must be given to these applications. IEEE Std C57.91-1995 pro-
                                                  vides information on recommended practices for the accompanying transformer.
                                    The dielectric strength of network protectors, which depend primarily on air for insulation, decreases as the
                                    altitude increases due to the effect of decreased air density. Network protectors design voltage shall be de-
                                    rated using the correction factors of Table 1 in IEEE Std C57.12.00-1993.
                                    The insulation level at 1000 m multiplied by the correction factor must not be less than the required insula-
                                    tion level at the required altitude.
5. Design tests
                                    The design tests shall be divided into three separate categories designated as continuous current thermal,
                                    electrical, and mechanical endurance.
                                    The continuous current test shall be performed to demonstrate that the network protector can carry its rated
                                    continuous current at its rated frequency in an ambient temperature range between 10 °C and 40 °C without
                                    attaining a temperature rise in excess of those listed in Table 1 (see Annex A for more information.) The net-
                                    work protector shall be tested with the highest loss fuse that would normally be applied with that network
                                    protector rating.
90 50
105 65
130 90
155 115
180 140
200 160
220 180
                                    The network protector in its enclosure, with fuses, shall be connected to a balanced three-phase current source
                                    at the transformer side of the network protector with copper bus bar whose ampacity is rated to carry the full
                                    rated current. This bus bar shall extend a minimum of 1.2 m from the network protector. This bus bar shall have
                                    a current density range of 120 A/cm2 to 230 A/cm2.3 The transformer throat openings shall be suitably
                                    enclosed with an insulating panel permitting the transformer extension bus to exit, but to seal all openings at
                                    the throat area. The network side terminals shall be short circuited with the same size bus bar as used on the
                                    transformer side connection and shall extend a minimum of 1.2 m from the network side terminals.
                                    Thermocouples shall be used to measure the temperature. Thermocouples used for measuring the tempera-
                                    tures of insulation shall be located on the current carrying member or other metal part at a point as close as
                                    practical to the accessible junction of the insulation and the current carrying member or other metal part.
                                    Thermocouples used for measuring the temperature of the transformer or network side terminal connections
                                    and other conducting joints shall be located approximately 13 mm from the terminal or other conducting
                                    joints on the current carrying member. Thermocouples shall be held in intimate contact with the conductor
                                    surface by such methods as welding, drilling and peening, or cementing. Thermocouples may be used to
                                    determine the internal air temperature within the network protector enclosure by suspending the unmounted
                                    thermocouple bulbs in air.
                                    The bus entering or leaving the network protector shall not be used to add or remove heat during the contin-
                                    uous current thermal test. To determine this, three thermocouples shall be placed 30 cm apart along the bus
                                    attached to the network protector. The bus is then shielded from air convection flow such that the three ther-
                                    mocouples along the bus bar are within 5 °C of the adjacent thermocouple on the bus bar. These readings are
                                    only applicable to the final three readings taken at 30 min intervals and are not subject to the temperature
                                    variation criteria of the internal parts of the network protector. Refer to Figure 1 for the minimum number of
                                    thermocouples required.
                                                                                                                                                                     --``,-`-`,,`,,`,`,,`---
                                                                        NOTE—Thermocouples 1–16 shall be duplicated on all three phases.
                                    The rated continuous current of the network protector at rated frequency shall be applied continuously until
                                    the temperature rise stabilizes. The temperature rise shall be considered stable when three successive
                                    readings taken at 30 min intervals vary no more than ±1.0 °C. If the temperature rise at the end of the third
                                    interval is equal to the established limit (see Table 1) and if the temperature rise has increased since the
                                    previous reading, the test shall be continued one more interval.
                                    The network protector shall be tested at an ambient temperature between 10 °C and 40 °C. No correction
                                    factors need be applied. The temperature rise shall, in no case, exceed that specified in Table 1. The ambient
                                    temperature shall be determined by taking the average of the readings of the three thermocouples placed
                                    horizontally 30 cm from the projected periphery of the network protector enclosure and approximately on a
                                    vertical line as follows:
                                    All reasonable precautions shall be taken to reduce errors caused by the time lag between the temperature
                                    rise of large apparatus and variations in the ambient temperature. Therefore, the ambient sensing thermocou-
                                    ples shall be immersed in a suitable liquid, such as oil, in a suitable metal cup. The size of the metal cup
                                    should be determined by the size of the apparatus being tested, but in no case shall the cup be any smaller
                                    than 25 mm in diameter and 51 mm high.
5.1.4 Performance
                                    Network protectors shall be considered to have passed this test if the limits of observable temperature rise as
                                    listed in Table 1, for every point measured per Figure 1, are not exceeded. The resistance of the conductors
                                    shall be measured on the network protector and its enclosure, either as one unit or separately. The resistance
                                    values recorded should be representative of the values recorded after the continuous current thermal test and
                                    serve as a basis for quality control monitoring of production of the individual designs and establishing the
                                    maximum acceptable limits of the individual designs and configurations.
                                    The test circuit conditions shall be verified by measuring the current in the test circuit by short circuiting the
                                    supply side of the test circuit at the network protector. For the purpose of determining the X/R ratio, the ac
                                    current shall be measured in the first half cycle after the short circuit is initiated, this current being calculated
                                    in accordance with IEEE Std C37.09-1979. The test circuit shall have an X/R ratio between 6.6 and 8 with X
                                    and R in series. Any reactor used in the test circuit shall be an air-cored reactor. The test circuit impedances
                                    shall be such that the three-phase symmetrical currents are essentially equal. The time at which the magni-
                                    tude of the symmetrical current is required to meet a rating level of the network protector is specified for
                                    each test separately.
                                    In all cases the network protector enclosure shall be insulated from ground and shall be connected to ground
                                    through a 30 A current limiting fuse, having an interrupting rating capacity not less than the interrupting rat-
                                    ing of the network protector.
                                    The interrupting rating of the network protector, without fuses, shall be expressed in rms symmetrical amperes
                                    at the maximum design voltage of the network protector.
                                    All interrupting testing must be three phase with the removable breaker installed in its enclosure. The test
                                    circuit impedance being such that the average symmetrical phase current at the end of 1 s is not less than the
                                    interrupting rating of the network protector.
                                    Two separate tests shall be performed. One test shall energize from the transformer side with the network
                                    side shorted; the other test shall energize from the network side with the transformer side shorted.
                                             The operating duty of the network protector shall consist of an opening operation, followed by a 2 min inter-
                                             val, and another opening operation (O-2 min-O). For each opening operation, the network protector shall
                   --``,-`-`,,`,,`,`,,`---
5.2.1.3 Performance
                                             At the end of the test the network protector shall be in substantially the same mechanical condition as before
                                             the test. It shall be capable of withstanding rated voltage in the OPEN position, and it shall be capable of car-
                                             rying rated current without exceeding the temperature rise limit
                                             After the test, the network protector must be inspected, and may be maintained. The ground fuse must be
                                             verified to be intact.
                                             A network protector without fuses shall be given a short-time current rating, expressed in rms symmetrical
                                             amperes at the maximum design voltage of the network protector.
                                             All short-time current testing must be three phase, with the test circuit impedance being such that the aver-
                                             age symmetrical phase current at the end of 1 s is not less than the short-time rating of the network protector.
                                             The maximum peak current at the initiation of current shall not be less than 2.3 times the short-time symmet-
                                             rical current rating.
                                             The rated short-time current shall be maintained for a period of 1 s without the network protector breaker’s
                                             contacts parting. The test circuit is to be energized and de-energized only by the action of the test station
                                             breakers.
5.2.2.3 Performance
                                             At the end of the test, the network protector shall be capable of meeting its interrupting rating and capable of
                                             carrying rated continuous current without exceeding the temperature rise limit.
                                             After the test, the network protector must be inspected to verify that the main contacts are free of excessive
                                             burning or pitting. The ground fuse must be verified to be intact.
                                             For network protectors having either spring close mechanisms or stored-energy mechanisms, fault close lev-
                                             els shall be tested to verify the network protector’s ability, less the fuses, to close and latch its contacts.
                                             All fault close current testing must be three phase, with the test circuit impedance such that the rms total cur-
                                             rent of the maximum phase during the first half cycle is not less than 1.35 times the fault close and latch
                                             symmetrical current rating of the network protector. The maximum peak current at the initiation of current
                                             shall not be less than 2.3 times the fault close and latch symmetrical current rating.
                                    The fault closing shall consist of electrically closing the network protector breaker into the test circuit. The
                                    test circuit is then de-energized by the action of the test station breaker after 10 cycles.
5.2.3.3 Performance
Directly after this test is completed, the network protector breaker shall be checked to ensure the following:
                                         a)          The spring closing mechanism has completed its closing cycle successfully.
                                         b)          The main contacts are free from excessive burning or pitting.
                                         c)          The network protector breaker can be tripped manually.
                                    At the end of this test, the network protector shall be capable of carrying rated continuous current without
                                    exceeding its rated temperature rise and shall be capable of meeting its interrupting rating. The ground fuse
                                    must be verified to be intact.
                                    The network protector in its enclosure with fuses shall be subjected to fault currents that are a minimum of
                                    the interrupting rating to a maximum of 110% of the interrupting rating of the network protector. The trip
                                    circuit of the network protector shall be made inoperable for this test. This test is intended to show that the
                                    fuses are capable of clearing a phase to phase fault without arcing to ground.
                                    All fuse interrupting testing must be three phase with the removable breaker installed in its enclosure. The
                                    test circuit impedance shall be such that the average symmetrical phase current at the end of 1 s is not less
                                    that the interrupting rating of the network protector.
                                    Two separate tests shall be performed. One test shall energize from the transformer side with the network
                                    side shorted. The other test shall energize from the network side with the transformer side shorted.
                                    The operating duty cycle of the network protector fuse test shall consist of three separate three-phase fuse
                                    interruptions at the maximum interrupting rating and maximum design voltage of the network protector.
                                    Each test shall be conducted with new fuses. The network protector shall be inspected and may be main-
                                    tained as required. The test circuit shall remain energized for 1 s after interruption.
5.2.4.3 Performance
                                    Directly after each three-phase fuse interruption, the network protector shall be checked to ensure the
                                    following:
                                     --``,-`-`,,`,,`,`,,`---
                                   Copyright © 2000 IEEE. All rights reserved.                                                                    9
Copyright The Institute of Electrical and Electronics Engineers, Inc.
Provided by IHS under license with IEEE
No reproduction or networking permitted without license from IHS                                  Not for Resale
                                   IEEE
                                   Std C57.12.44-2000                                                              IEEE STANDARD REQUIREMENTS
                                    The removable breaker is to be mounted in its enclosure with the enclosure door in the closed position.
                                    Rated voltage of the network protector shall be supplied directly into the control circuitry in such a manner
                                    as to utilize as many control components as possible, such as auxiliary switch contacts, latch check contacts,
                                    auxiliary relays, closing motor, tripping device, motor seal-in contacts, resistors, rectifiers, and control
                                    transformers.
                                    Electrical heaters shall be strategically placed throughout the network protector enclosure. The heaters shall
                                    increase the internal enclosure air temperature to 95 °C ± 5 °C. On ventilated or open types of enclosures the
                                                                                                                                                           --``,-`-`,,`,,`,`,,`---
                                    entire network protector shall be placed into an environment whose ambient temperature is 95 °C ± 5 °C.
                                    Three thermocouples shall be mounted at convenient locations within the network protector enclosure. One
                                    thermocouple shall be located within 150 mm from the bottom of the enclosure. The second thermocouple
                                    shall be located at half the total height of the enclosure, while the third thermocouple shall be located within
                                    150 mm from the top of the enclosure. The average of the three temperature readings shall be used as the ele-
                                    vated temperature reading. Temperature stability must be maintained for 1.5 hours prior to proceeding with
                                    the mechanical test.
                                    The mechanism shall be operated 10 000 consecutive times without malfunction or interim adjustment. One
                                    operation is defined as a CLOSING and OPENING of the breaker under no electrical load.
                                    The rate of operation shall be at least one operation every 2 min. During each operation, the network protec-
                                    tor circuit breaker shall remain closed for no less than 1 s. The device used to control the input voltage shall
                                    have a system that controls the opening and the closing of the network protector circuit breaker and stops the
                                    test if the circuit breaker fails to OPEN or CLOSE. The control device should indicate the mode of failure.
5.3.4 Performance
                                    At the end of this test, the network protector breaker shall be thoroughly inspected to verify and record that
                                    the critical adjustments are in tolerance. Any change or modification must be reviewed as to its impact on its
                                    thermal and/or electrical test, if previously conducted.
                                    Any failure of the external control circuitry does not require the test counter to be reset to zero. The external
                                    control device can be replaced or repaired and the mechanical test may recommence.
                                    Any component that has been scorched, discolored, or burned by the internal heaters shall not be considered
                                    a failure.
                                    Any and all changes and/or modifications must be fully documented during this phase of the testing along
                                    with the starting/stopping counter readings.
6. Production tests
                                    The production tests shall be performed on every network protector. They are divided into the following
                                    categories:
                                         a)        Operational
                                         b)        Dielectric
                                         c)        Insulation resistance
                                         d)        Current path resistance
                                         e)        Mechanical
                                    The purpose of the operational test is to prove the ability of the network protector to function both in closing
                                    and opening the network protector breaker with and without relays under both nominal rated voltage and
                                    minimum voltage conditions.
                                                                                                                                                                    --``,-`-`,,`,,`,`,,`---
                                    With the relays removed, the test control leads should be connected to that portion of the control circuitry
                                    that will permit a remote CLOSE and OPEN operation of the removable breaker. The test source should be
                                    connected to the rated voltage of the network protector and the removable breaker should be tested 50 oper-
                                    ations per Table 2. The removable breaker contacts shall remain closed for a minimum of 1 s before the
                                    opening sequence is initiated.
                                    The voltage level should be reduced to 73% of rated voltage and initiate a CLOSE sequence. At this voltage
                                    level, the removable breaker must not close. Without changing the voltage level, the auxiliary motor relay
                                    contact should be mechanically closed. The motor must have sufficient torque at this voltage level to com-
                                    pletely CLOSE the removable breaker. The removable breaker should be manually tripped and the input
                                    voltage increased from 73–80% of rated voltage. Initiate a close sequence. The removable breaker shall
                                    operate through its auxiliary motor relay supplying power to the motor. The voltage should be reduced to
                                    7.5% of rated voltage. At this reduced level, an opening sequence should be initiated. The removable breaker
                                    must completely OPEN. Perform this sequence five times per Table 2.
                                                Three-phase test leads should be connected to the transformer side bus and the network side bus connec-
                                                tions. The ground lead should be connected to the removable breaker. The calibrated network relay(s) should
                                                be installed, and the input voltage adjusted to the rated voltage. Electrically close the removable breaker by
                                                raising the phasing voltage on the test circuit. The removable breaker shall CLOSE its contacts at a predeter-
                                                mined value. The removable breaker should be electrically tripped by applying reverse current on the test
                                                circuit. The removable breaker shall OPEN its contacts completely at a predetermined trip level. Perform
                                                this sequence 25 times per Table 2.
                                                The trip free operation of the mechanism shall be checked by attempting to electrically CLOSE the remov-
                                                able breaker contacts while mechanically holding the tripping component of the removable breaker in the
                                                trip position. The removable breaker contacts shall not CLOSE under these conditions. Perform this
                                                sequence five times per Table 2.
                                                On removable breakers without a stored-energy or spring close mechanism, with the removable breaker
                                                mounted in its enclosure, manually CLOSE the network protector by the use of the outside operating handle.
                                                Then, OPEN the network protector by use of the outside operating handle. The network protector shall
                      --``,-`-`,,`,,`,`,,`---
                                                CLOSE and OPEN its contacts through the outside operating handle. Perform this sequence five times per
                                                Table 2.
                                                On removable breakers having either stored-energy or spring closed mechanisms, the outside operating han-
                                                dle shall electrically complete the motor close circuit when the handle is placed in the CLOSE position. This
                                                test is performed with the removable breaker mounted in its enclosure and three-phase test leads connected
                                                to the transformer side of the network protector. Moving the outside operating handle to the CLOSE position
                                                shall complete the electrical circuit of the closing motor and the network protector shall close. Then, OPEN
                                                the network protector contacts by use of the outside operating handle. Perform this sequence five times per
                                                Table 2.
6.1.2 Performance
                                                The operational test as defined in Table 2 shall be performed without any malfunction of the network
                                                protector.
                                                Dielectric withstand tests shall be conducted on removable breakers and enclosures, either as one unit or
                                                separately. All barriers and insulation shall be in place. These tests prove the condition of all control wiring
                                                and bus insulation both phase-to-phase and phase-to-ground.
                                                The network relays are removed. The leads to the motor shall be disconnected from the circuit. Additional
                                                line to ground circuits shall be disconnected from ground. All open points on the harness, such as sockets,
                                                plugs, terminal boards, and relay connectors shall be electrically connected together and isolated from
                                                ground. Solid-state devices, such as diodes and rectifiers, shall be shorted or removed from the circuit.
                                    The dielectric test shall be conducted at 2200 V at 60 Hz for 1 min for each of the following points of appli-
                                    cation discussed in 6.2.1.1 through 6.2.1.3.
                                         a)        Between top phases and bottom phases, with the top phases grounded and the circuit breaker OPEN
                                         b)        Between all phases and ground with the circuit breaker closed
                                         c)        Between the outside phases and ground with the center phase grounded and the circuit breaker
                                                   OPEN
6.2.1.2 Enclosure
                                         a)        Between all phases on the network side (including secondary disconnects) and ground
                                         b)        Between the outside phases on the network side and ground, with the center phase grounded
                                         c)        Between all phases on the transformer side and ground
                                         d)        Between the outside phases on the transformer side and ground, with the center phase grounded
6.2.2 Performance
                                    Insulation resistance tests shall be conducted on the removable breaker and its enclosure, with all barriers
                                    and insulation in place, either as one unit, or separately.
                                    The network relays shall be removed. The leads to the motor shall be disconnected from the circuit. Addi-
                                    tional line-to-ground circuits shall be disconnected from ground. All open points on the harness, such as
                                    sockets, plugs, terminal boards, and relay connectors shall be electrically connected together and isolated
                                    from ground. Solid-state devices, such as diodes and rectifiers, shall be shorted or removed from the circuit.
                                    With the removable breaker CLOSED, the resistance should be measured at the following locations using
                                    direct current from an instrument set at 2500 V:
                                         a)        Between the main bus bars; left to center, center to right, and left to right
                                         b)        Between the main bus bars and ground; left, center, and right
6.3.2 Performance
The direct current resistance values shall be equal to or greater than 25 MΩ measured at 2500 V.
                                    The current path shall encompass all main current carrying conductors of both the enclosure and the
                                    removable breaker. The acceptable limits shall be established by each manufacturer for each amperage class
                                    of network protector and removable breaker, with and without fuses. These values shall be established from
                                    the continuous current thermal test (see 5.1.4). The limits shall be tabulated and subdivided into specific
                                    sections of the enclosure and the removable breaker.
                                    With the removable breaker placed in its enclosure and all fuses and disconnect links mounted, measure the
                                    resistance on each phase of the network protector using a 100 A minimum current test set.
6.4.2 Performance
                                    Mechanical tests shall be performed on network protectors to prove the mechanical fit between the remov-
                                    able breaker and its associated enclosure. It shall also prove the mechanical seals required on submersible
                                    types of enclosures.
                                                                                                                                                               --``,-`-`,,`,,`,`,,`---
                                    With the removable breaker out on its enclosure extension rails, roll the breaker into the enclosure. It shall
                                         a)        Roll smoothly and with no tendency for the breaker rollers to ride off the extension rails.
                                         b)        Align properly on the rails or racking device.
                                         c)        Ensure that the securing hardware aligns properly and is complete.
                                         d)        Ensure that the fuses fit properly in their designated location, and the alignment of the mating
                                                   surfaces provide solid contact with the fuse to insure proper current and heat transfer to the main
                                                   conductor.
                                    On submersible enclosures, the transformer throat area shall be temporarily sealed. The leak test shall be
                                    performed by pressurizing the completed network protector to a gauge pressure of 50 kPa4 and submerging
                                    it in a tank of water. Any sign of escaping air in the form of bubbles constitutes a failure. Minor leaks from
                                    the removable throat plate bolts, which do not interfere with detection of other leaks, shall be disregarded.
47.0 1bf/in2
7. Relay characteristics
7.1 General
                                    The relay characteristics shall be composed of the combination of the closing and tripping curves as well as
                                    the adjustment of the relay.
                                    Network protectors shall utilize 216 Y/125 V relays regardless of the three-phase, four-wire system voltage
                                    for which they are to be applied.
                                    The network protector shall close automatically if the net three-phase watt flow is into the network from the
                                    transformer and remains as a net three-phase watt flow into the network following the closure of the network
                                    protector.
                                    To ensure that both the watt and var flow in the network protector are into the network from the transformer,
                                    following closure of the network protector, the phasing voltage phasor shall lie between 85° and –15° from
                                                                                                                                                       --``,-`-`,,`,,`,`,,`---
                                    the in-phase or 0° line.
                                    The network protector shall trip automatically if the net three-phase power flow is into the transformer from
                                    the network.
                                    The network protector shall trip automatically for faults on the primary or for faults in the network trans-
                                    former. It shall also trip automatically upon the reverse magnetizing current of its associated transformer in
                                    the absence of a fault. This type of relay is described as having a watt characteristic, with a maximum
                                    response angle of 180°. The network relay trip characteristic can be plotted as a function of current magni-
                                    tude and the angle between the phase-to-ground voltage and phase current.
                                    As an option, the network protector shall trip automatically for faults on the primary feeder where the pri-
                                    mary feeder utilizes single-phase protective devices. It may also be applied where single phase to ground
                                    primary fault on ∆-Y transformers may exist and the station breaker relaying may be unable to detect this
                                    level of ground current. This type of single phase-to-ground fault relay is described as having a watt-var
                                    characteristic, with a maximum response angle of 120°.
                                    An additional option is the time delay relay or time delay function in which the normal tripping signal is
                                    delayed for an adjustable period of time. As backup protection during the time delay period, instantaneous
                                    overcurrent elements are engaged for primary feeder faults. The instantaneous overcurrent elements are
                                    adjustable from 50–200% of the network protector current transformer rating.
                                    The magnitude of the phasing voltage phasor shall be greater than a predetermined minimum threshold level
                                    from the network voltage, which shall serve as the reference phasor determining the network relay charac-
                                    teristic. This predetermined minimum level is chosen to assure that the network protector will not close when
                                    the magnitude of the phasing voltage is approaching zero. The closing adjustment threshold value shall be
                                    between 0.6 V and 2.0 V on a 216 V system. Refer to 9.6 for the closing voltage settings. The angle of the phas-
                                    ing voltage phasor in relation to the network voltage reference phasor shall be between 90° and –25° from the
                                    in-phase or 0-degree line. Any combination whereby the phasing voltage phasor exceeds the predetermined
                                    minimum value above the reference network phasor and falls within the predetermined allowable angular dif-
                                    ference between the two phasors shall call for the relay(s) contact(s) to close (see Figure 2).
                                    The network relay shall make its trip contact whenever the balanced net three-phase power (watt) flow is in
                                    the reverse direction (180° from a constant network side voltage) and exceeds a predetermined threshold
                                    value. The trip adjustment threshold value shall be 0.05–5% of the network protector current transformer
                                    rating. Refer to 9.7 for trip current settings. For watt characteristic relays, the trip setting is the current in
                                    amperes at 180° with respect to the phase-to-ground voltage to make the relay trip contact (see Figure 3).
--``,-`-`,,`,,`,`,,`---
                                    The network protector shall be equipped with provisions for installing three fuses mounted either internally
                                    or externally. Internal fuse mounting provisions are shown in Figure 4 and Figure 5, and are determined by
                                    the fuse selected. External fuse mountings may be in housings suitable for submersible operations, which
                                    shall be capable of being pressure tested along with the network protector enclosure per 6.5.2
                                                                                (a)                                                           (b)
                                               NOTE—Stud diameter is 1/2-13 UNC. Stud length provided shall be of sufficient length to permit removal of
                                               fuse mounting assembly with a standard depth insulated socket. This length is determined by the fuse
                                               selected.
                                                                        Figure 4—One and two hole internal fuse mounting patterns:
                                                                                    (a) 800–3500 A; (b) 2250–3500 A
                                                                          (a)                                                   (b)
                                           NOTE—Stud diameter is 1/2-13 UNC. Stud length provided shall be of sufficient length to permit removal of
                                           fuse mounting assembly with a standard depth insulated socket. This length is determined by the fuse selected.
                                                                        Figure 5—Four hole internal fuse mounting patterns:
                                                                                 (a) 2500–3500 A; (b) 4500–5000 A
                                    Fuses shall be selected with time-current characteristics (corrected to fuse’s operating ambient temperature)
                                    to provide maximum protection when compared to the thermal damage curve of its associated transformer.
                                    The minimum acceptable crossover point between the two curves should be no less than three times rated
                                    current. The maximum acceptable crossover point between the two curves should be no greater than seven
                                    times rated current. Under no circumstances are fuses to be applied whose average melting curve is faster
                                    than the network protector relay tripping response.
                                    Fuses for network protectors are not normal fuses and are specially designed for use in network protectors.
                                    They fall into the following four general categories:
                                         a)        Copper
                                         b)        Low loss
                                         c)        Alloy
                                         d)        Silver-sand current limiting
9. Rating requirements
9.1 Nameplates
Nameplates shall contain the following minimum information for the removable breaker and the enclosure:
                                                 a)   Manufacturer
                                                 b)   Place of manufacture
                                                 c)   Name of device (automatic network protector)
                                                 d)   Model of device (example: MG-8; CM-22)
                                                 e)   Identification serial number
                                                 f)   Rated system voltage
                                                 g)   Rated continuous current
                                                 h)   Rated symmetrical interrupting current
                                                 i)   Frequency
                                                 j)   Current transformer ratio
                                                 k)   Wiring diagram
                                                 l)   Weight (total and removable breaker)
                                                 m)   Submersible or nonsubmersible
                                                 n)   Installation and operating instructions reference
                                                 o)   Month and year of manufacture (uncoded)
                                            Network protectors shall have continuous current, interrupting, and close and latch ratings as indicated in
                                            Table 3. As an aid in selection, the table shows recommended transformer sizes as well as the protector con-
                                            tinuous current rating expressed as a percentage of the transformer nameplate current.
                                            The 60 Hz dielectric test voltage shall be 2200 V except for the motor, relays, and solid-state devices. The
                                            motor and solid-state devices shall be tested at 900 V. The network relays shall be tested at 1500 V. For
                                            equipment that has been in service, test voltages shall be not greater than 75% of the foregoing values.
                                            When measured line-to-line (L-L) or line-to-ground (L-G), at the protector terminals, the range of voltage
                                            for operation of the control mechanisms shall be as indicated in Table 5.
                                   aThe interrupting rating shall exceed the through fault rating of its associated transformer.
                                   bShort-time rating of network protectors without fuses shall be equal to the interrupting rating.
                                   cApplies only to network protectors having spring close or stored energy mechanisms.
                                                                                  Rated voltage
                                                                                                               Maximum design voltage (V)
                                                                                      (V)
                                                   Network protectors shall have provisions for adjusting the closing voltage as indicated in Table 6. The clos-
                                                   ing voltage shall be the median value.
                                                   Network protectors shall have provisions for adjusting the tripping current as indicated in Table 7. The trip-
                                                   ping current shall be the nominal value.
                                                                                                                                                               --``,-`-`,,`,,`,`,,`---
                                               3500                        3000            1.5                              6.0              150
                                    A network protector removable breaker shall be mounted in an enclosure to prevent contact with internal live
                                    parts.
                                    Submersible and nonsubmersible network protectors may be either separately mounted or transformer
                                    mounted. Open frame network protectors are mounted separately from transformers.
                                    The following shall apply to the removable breaker, submersible, and nonsubmersible network protector
                                    enclosures unless noted.
                                    The network protector shall include barriers, of insulating material, between phases and between phases and
                                    ground. After the removable breaker has been rolled out of its enclosure, its interphase barriers shall be
                                    readily removable.
                                    All studs, bolts, and screws shall be secured to prevent loosening under normal service conditions and
                                    transportation.
                                    Inspection windows shall be provided in the door of the enclosure so that the operation counter and position
                                    indicator can be seen without opening the door.
                                    An external operating handle shall be provided. Provisions shall be made with a latch to prevent accidental
                                    movement and means to padlock the handle with an 11 mm shackle padlock in each position: OPEN, AUTO,
                                    and CLOSE for manually operated protector; OPEN and AUTO for electrically operated protector. An elec-
                                    trically operated protector may have a NULL position for padlocking. This is the spring return position from
                                    the CLOSE position of the switch. The position of the operating handle shall be clearly indicated by name-
                                    plates visible from the front of the enclosure. An interlock shall be provided so that the removable breaker
                                    cannot be rolled into or out of the enclosure unless the removable breaker is open.
Placing the handle in the OPEN position shall cause the network protector to open and remain open.
Placing the handle in the AUTO position shall cause the network protector to be controlled by the relay(s).
                                    Moving the handle to the CLOSE position shall close the protector and shall permit the relay(s) to open the
                                    network protector.
This is the spring return from the CLOSE position; all contacts are open.
--``,-`-`,,`,,`,`,,`---
                                             If the external handle is mounted on the side, mountings shall be provided on both the right-hand and left-
                                             hand sides of the network protector enclosure so that the handle can be transferred from one side of the
                                             enclosure to the opposite side whenever the need arises. The handle shall be connected to the network pro-
                                             tector through the submersible enclosure by means of a watertight assembly. The seals used in this assembly
                                             shall be replaceable from outside the enclosure.
                                             The enclosure door shall be provided with hinges on the left-hand side that can be easily changed for hinging
                                             on the right-hand side without modification to the enclosure.
                                             Air test provisions shall be provided. This consists of a 1/2 inch NPT female fitting on the enclosure with a
                                             sampling device, made of corrosion resistant material, installed into the fitting using a suitable thread sealer.
                                             If the external handle is mounted on the side, it shall be provided on the left-hand side of the network protec-
                                             tor enclosure.
The enclosure door shall be provided with hinges on the right-hand side.
                                             The network protector enclosure and the removable breaker shall each include two lifting eyes with a
                                             minimum inside diameter of 25 mm and shall be located on opposite sides of the unit, in a vertical plane
                                             approximately through the center of gravity.
                   --``,-`-`,,`,,`,`,,`---
                                             Means shall be provided for rolling the removable breaker from its enclosure after it has been disconnected.
                                             This shall be accomplished by means of self contained, or detachable rails, or the equivalent, provided in the
                                             enclosure.
                                             Stops shall be provided to prevent the removable breaker from rolling off the rails. When extended, the rails
                                             shall not extend beyond the open enclosure door.
Provision shall be made for safely storing the rollout rails within the enclosure.
                                             If the removable breaker requires the removal and replacement of hardware, for its removal from the enclo-
                                             sure, the hardware shall be a 1/2 inch and/or 3/4 inch hexagon head. An insulated straight “T” socket wrench
                                             for the appropriate 1/2 inch and/or 3/4 inch hexagon hardware shall be available.
                                    Enclosure-grounding provisions shall consist of a copper-faced-steel or stainless-steel pad with two holes
                                    horizontally spaced on 44.5 mm centers and drilled and tapped for 1/2-13 UNC thread (refer to ANSI B1.1-
                                    1989). The ground pad shall be welded to the enclosure. The minimum thickness of the copper facing shall
                                    be 0.4 mm. The minimum threaded depth of holes shall be 13 mm. Thread protection for the ground pad
                                    shall be provided.
10.5.9 Materials
10.5.10 Nameplates
                                    A metal corrosion-resistant nameplate shall be affixed by corrosion resistant screws to the network protector
                                    enclosure and the removable breaker. It shall bear the rating and other essential operating data as specified in
                                    9.1.
                                    Submersible network protectors shall be provided with a gasketed cover plate to seal off and protect the net-
                                    work protector throat area, suitable for outdoor storage.
                                    The network protector main bus structure shall consist of a copper bus bar of adequate size to provide the
                                    specified ampere rating.
                                                                                                                                                              --``,-`-`,,`,,`,`,,`---
                                    A secondary disconnect with a minimum of four points shall be provided to connect and disconnect the aux-
                                    iliary and control circuits between the removable breaker and its enclosure
Spare contacts rated at 20 A and 600 V and mechanically driven shall be provided as follows:
                                         a)        One contact to be closed when the network protector is closed. Commonly known as an “a” contact.
                                         b)        One contact to be closed when the network protector is open. Commonly known as a “b” contact.
A nonresettable operation counter shall be provided that shall be easily read through the inspection window.
                                    A mechanical indicator shall be provided, which will indicate the OPEN and CLOSE positions of the
                                    network protector. The mechanical indicator shall be easily read through the inspection window. When the
                                    network protector is fully open, only the word OPEN shall be visible. When the network protector is fully
                                    closed, only the word CLOSE shall be visible.
NOTE—An intermediate breaker position shall be indicated by partial visibility of the word OPEN or CLOSE.
                                    All insulating materials in the network protector shall be track resistant per ASTM 495, ASTM D2303, and
                                    UL746A; flame resistant per ASTM D229 and UL94; and shall be asbestos-free.
10.5.18 Grounding
The operating mechanism and relay cases shall be grounded to the enclosure through the removable breaker.
10.6 Finish
                                                                                                                                                       --``,-`-`,,`,,`,`,,`---
                                    11. Other requirements
                                    This is an enclosure that is designed for outdoor or vault application subject to submersion or high humidity.
                                    It shall provide a degree of protection from unintentional contact with energized internal components when
                                    the door is closed. The enclosure shall have sealed interfaces at every entrance or exit point as well as the
                                    door having a gasketed surface. It shall be capable of withstanding an internal or external static gauge pres-
                                    sure of 105 kPa6 without rupture and shall remain watertight.
                                    This is an enclosure that provides a degree of protection from unintentional contact with energized internal
                                    components when the door is closed.
                                    This is an enclosure that provides a degree of protection against limited amounts of falling dirt, but is not
                                    required to prevent the entry of dust or liquids.
                                    This is an enclosure that provides a degree of protection against falling dirt or airborn dust, but is not
                                    required to prevent the entry of liquids. This enclosure shall have no intentional openings in its design and
                                    shall have a gasketed interface between the enclosure and the door.
615 1bf/in2
--``,-`-`,,`,,`,`,,`---
                                                   This is an enclosure that provides a degree of protection against falling dirt and water, but is not required to
                                                   prevent the entry of dust. It shall have provisions for drainage.
                                                   This is an enclosure that provides a degree of protection against falling dirt or water, and airborne dust. It
                                                   shall have no intentional openings in its design and shall provide a gasketed interface between the enclosure
                                                   and the door.
                                                   This is an open frame in which the removable breaker is clearly visible and offers no protection from unin-
                                                   tentional contact with energized components. It offers minimal protection from falling debris, dirt, dust, or
                                                   liquids.
Network protector enclosure mounting configurations are divided into the following two main categories:
                                                        a)   Transformer mounted
                                                        b)   Separately mounted
                                                   This is an enclosure that can be close coupled to its associated transformer through throat mounting
                                                   provisions. The throat opening, bolting pattern, and lower housing support shall be standardized as to the
                                                   following amperage of the network protector:
This is an enclosure having the provisions of being supported without the aid of its associated transformer.
Separately mounted enclosures shall be divided into two categories: wall mounted or free standing.
This is an enclosure that is designed to be self supported with provisions for attachment to the floor.
                                                   Network protector enclosures shall be supplied with terminations for connection to a secondary spot or grid
                                                   network. These terminations shall be of either the stud or spade type.
                                                   Stud-type terminals shall be threaded. Stud diameters and threading shall be as follows (see Figure 6):
                                                      —    1 1/2 inch diameter 12 threads/inch for network protectors in the 800–1875 A range
                                                      —    3 inch diameter 12 threads/inch for network protectors in the 2000–4500 A range
(a) (b)
                                                   Spade-type terminals shall have 9/16 inch diameter holes as follows (see Figure 7):
                                                      —    Network protectors in the 800–1875 A range shall have spades with 13 mm thick material with two
                                                           sets of two holes 44.5 mm apart and each set separated by 44.5 mm minimum.
                         --``,-`-`,,`,,`,`,,`---
                                                      —    Network protectors in the 2000–3000 A range shall have spades with 19 mm thick material with four
                                                           sets of two holes 44.5 mm apart and each set separated by 44.5 mm minimum.
                                                      —    Network protectors in the 3500–4500 A range shall have spades with 25 mm thick material with four
                                                           sets of two holes 44.5 mm apart and each set separated by 44.5 mm minimum.
(a) (b)
                                    Annex A
                                    (normative)
A.1 General
                                    The temperature limits and ratings of electrical equipment are influenced significantly by the characteristics
                                    of the insulation systems used. It is important to recognize the distinction between insulating materials and
                                    insulation systems.
                                    Insulating materials include processed compositions of nonconductive materials and combinations thereof,
                                    before they are fabricated into shapes and structures for use in specific electrical equipment. Electric conduc-
                                    tivity is very small, approaching zero, and electric isolation is provided.
                                    Insulation systems include fabricated and processed combinations of insulating materials specifically
                                    designed to perform the insulation functions needed in the associated electrical equipment. Such equipment
                                    may contain more than one insulation system.
                                    There are many different kinds of materials used for insulation purposes. Rapid advances in polymer chem-
                                    istry have produced insulating materials, which are so numerous and complex that simple chemical descrip-
                                    tion has become virtually impossible. Consequently, the traditional procedure of dividing insulating
                                    materials into several thermal classes, based upon broad descriptive statements of chemical composition, is
                                    no longer meaningful, adequate, or appropriate.
                                    By means of thermal aging tests and evaluation of service experience, an insulating material may be
                                    assigned a temperature index (TI). The TI provides a technical basis for comparing the thermal capability of
                                    insulating materials, but should not be related directly to the appropriate operating or service temperature for
                                    the equipment in which they are used. The latter depends on many factors including environment, service
                                    severity, mechanical stresses, geometry of materials (e.g., thickness), and the design of the insulation system
                                    in which the material is used.
                                    To promote standardization and to provide continuity with past procedures, it is desirable that the TI for
                                    insulating materials be grouped in material temperature classes as given in Table A.1.
                                    As an example, if a particular material is given a TI of 140 °C by thermal aging test or service experience, it
                                    is in the TI range of 130–154 and, therefore, is a Class 130 material.
                                    The TI of an insulating material is a value obtained by test or from service experience, and may be used as a
                                    guide, but does not imply an equipment thermal classification or a limitation on use in equipment. Tempera-
                                    ture classification for the purpose of rating electrical equipment should be defined in terms of the thermal
                                    endurance of the total insulation system.
--``,-`-`,,`,,`,`,,`---
                                                                                                         Range of the
                                                              Material             Former class                                                   Temperature rise
                                                                                                      temperature index
                                                          temperature class         designation                                                         °C
                                                                                                             °C
90 O 90–104 50
105 A 105–129 65
130 B 130–154 90
                                    An insulating material may be assigned more than one TI based upon different properties, environmental
                                    conditions, or material geometry. For example, a material can be assigned a TI based upon retention of
                                    mechanical properties and a different TI for retention of electrical properties. Thus, the TI describes perfor-
                                    mance characteristics that provide the designer with information for the selection of materials based upon
                                    engineering data rather than arbitrary classification.
                                    The temperature limits for electric equipment should be selected so that the equipment will provide a satis-
                                    factory service life under normal operating conditions. The temperature limit for an insulation system may
                                    not be directly related to the TI of the individual material included in it. In an insulation system, the thermal
                                    performance of insulating materials may be improved by the protective character of other materials used
                                    with them. A specific material as part of a system may be satisfactory for use at different limiting tempera-
                                    tures depending upon the type and design of equipment in which it is used and the kind of service to which
                                    the equipment is subjected.
                                    The ability of an insulation system to perform its function is also affected by the presence of other factors in
                                    addition to thermal stresses. These include electrical stresses, mechanical stresses, and environmental
                                    stresses, e.g., moisture, dirt, chemicals, or other contaminants.
                                    The limiting insulation temperature consists of the sum of limiting ambient temperature plus the limiting
                                    temperature rise. For most purposes, the temperature of the outdoor air is taken as the ambient, and 40 °C is
                                    normally chosen as the limiting ambient temperature. Other values for ambient temperature may be chosen
                                    in special circumstances.
                                    The temperature rise values generally used for electrical equipment are the results of long experience and
                                    have been proven reasonably satisfactory. This suggests that any changes in existing standards should be
                                    made only if they are clearly indicated in light of new test data, new or improved materials, additional
                                    operating experience, new measurement techniques, or changes in service requirements. Only carefully
                                    evaluated service experience and/or adequately accepted tests provide the basis for rational thermal
                                    classification of electrical equipment and the temperature limit of insulation systems.
                                    Based upon such an evaluation of the insulation system in a particular type of electrical equipment, the
                                    temperature rise value may be selected from Table A.1. These suggested temperature rise values have a
                                    numerical relationship to the material temperature classes but are not necessarily directly related to the TI of
                                    the materials used.
                                    As indicated previously, a material with a given TI may be acceptable for a different limiting temperature,
                                    either higher or lower, based on acceptable tests and/or service experience on the equipment in which it is
                                    used.
                                    For the expected service life of the equipment, the electrical and mechanical properties of the insulation
                                    system must not be impaired by the application of the limiting insulation temperature permitted by the
                                    particular limiting temperature rise specified. The word “impaired” implies any change that would disqualify
                                    the insulating material from performing its intended function whether creepage spacing, mechanical support,
                                    or dielectric barrier action.
                                    During the service life of the equipment, the insulation system may be exposed to stress factors that can ulti-
                                    mately impair its ability to perform its intended function. Usually service stresses that degrade the insulation
                                    result in a gradual deterioration over time. The following subclauses A.4.1–A.4.4 are brief comments on the
                                    major service stresses.
                                                                                                                                                              --``,-`-`,,`,,`,`,,`---
                                    Thermal aging of insulating materials is the progressive deterioration in electrical and mechanical properties
                                    as a result of prolonged exposure to high temperatures. The process of thermal aging is complex, and the
                                    mechanisms vary with different materials and under different service conditions.
                                    Different insulating materials react in different ways to the various aging processes, and it is essentially
                                    impossible to predict thermal performance from chemical composition.
                                    The normal electrical stress results from exposure to high voltages. Insulation deterioration can result in
                                    flashovers. Arcing fault currents can cause immediate damage or destruction of the insulation system,
                                    whether or not deterioration has occurred.
                                    Typical mechanical stresses result from supporting other components of the equipment, vibration from any
                                    cause, and differential thermal expansion. Insulation deterioration can cause mechanical failure leading to an
                                    electrical fault.
                                    Environmental stresses result from exposure to oxygen, moisture, dust, dirt, and chemicals. Some insulating
                                    materials will be more vulnerable to such exposure than others. The life of the equipment will be longer if
                                    the insulation system is suitably protected than if it were freely exposed to industrial atmospheres or the
                                    weather. The design and utilization of equipment should take appropriate account of the characteristics and
                                    capabilities of the insulating materials used.
                                                 Annex B
                                                 (informative)
B.1 General
                                                 The purpose of this tutorial is to furnish the application engineer with some guidance for the selection of net-
                                                 work protector fuses.
                                                 The selection of a protector fuse is still an art. There are trade-offs in selecting a fuse which may make one
                                                 fuse better than another depending on how the application engineer views the trade-offs available. The expe-
                                                 rience each engineer has had may differ and may suggest different practices than those outlined here.
Reference should be made to IEEE Std C37.108-1989 for an overall system view of protection.
                                                 The protector fuse is selected to allow for normal load current to flow and to provide backup for the protector
                                                 in the case where the protector fails to open on reverse current. The fuse clearing time should be long enough
                                                 to allow for
The minimum melt curve of the protector fuse should fall to the right of
                                                 The fuse clearing time should also be short enough to protect its associated transformer. The total clear curve
                                                 of the fuse should coordinate with the thermal damage curve of the transformer. The interrupting capability
                       --``,-`-`,,`,,`,`,,`---
                                                 of the fuses should be higher than the expected available fault. Some utilities use the maximum through cur-
                                                 rent as the maximum fault current that the fuse will have to interrupt. Some utilities, because of the remote
                                                 chance that the protector can fail internally, use the maximum fault current of the network as the interrupting
                                                 current that the fuse will have to interrupt.
                                           Copper link fuses with or without covers: (See Table B.1.) Fuses of this type have a relatively steep time-
                                           current characteristic, which makes this type of fuse hard to coordinate with cable limiters. These fuses are
                                           normally used on 216 Y/125 V networks with covers, and on the 480 Y/277 V networks without covers (see
                                           Figure B.1 for typical characteristic curves).
                                               CAUTIONS:
                                               1—Fuse characteristic curves vary with whether they are enclosed or external.
                                               2—Fuse characteristic curves will vary with the manufacturer and the curves in this document are representative
                                               only and should not be used for coordination.
                                                           Protector rating
                                              Fuse                                Cutler-            Richards            General
                                                              (open or                                                                        Typical fuse style
                                              curve                              Hammerb              Mfg.b              Electricb
                                                            submersible)a
                                           aRatings are those of the manufacturer. IEEE does not represent or warrant the accuracy     of these ratings.
                                           bFuse and manufacturer designations are illustrative only of this type of fuse and do not   constitute an endorsement by
                                            the IEEE of these products.
                 --``,-`-`,,`,,`,`,,`---
NOTE—These are typical characteristic curves and should not be used for coordination.
                                                   Low loss fuses: (See Table B.2.) Fuses of this type have time-current characteristics similar to the copper
                                                   link fuses, except that the heat loss is approximately half of the losses in ordinary copper fuses. This allows
                                                   increased loading of the network protector under contingency conditions. They are for 216 Y/125 V network
                                                   applications only (see Figure B.2 for typical characteristic curves).
                                                                  Protector rating
                                                      Fuse                                  Chase         Richards
                                                                     (open or                                                           Typical fuse style
                                                      curve                               Shawmutb         Mfg.b
                                                                   submersible)a
#1 1875 A S 2F LLLF2SKA
#2 2000 A S2 LLF2KA
#4 4000 A S4 LLF4KA
                                                       #5               5000 A                   S5       LLF5KA
                         --``,-`-`,,`,,`,`,,`---
                                                   aRatings are those of the manufacturer. IEEE does not represent or warrant the accuracy     of these ratings.
                                                   bFuse and manufacturer designations are illustrative only of this type of fuse and do not   constitute an endorsement by
                                                    the IEEE of these products.
NOTE—These are typical characteristic curves and should not be used for coordination.
                                    Alloy fuses: (See Table B.3.) Fuses of this type have a much longer time delay at higher currents and allow
                                    more time to burn secondary faults clear. They have a low melting temperature, making them more sensitive
                                    to unwanted fuse blowing where high ambient temperatures occur. Because of their longer time delay on
                                    higher currents, they will coordinate well with cable limiters and protectors (see Figure B.3 for typical char-
                                    acteristic curves).
Open Submersible
                                                                                                                1875 A            1173011
                                                          #4         1875 A          1173009         #4
2500 A NF7
3000 A NF10
                                                     aRatings are those of the manufacturer. IEEE does not represent or warrant the accuracy of these ratings.
                                                     bFuse and manufacturer designations are illustrative only of this type of fuse and do not constitute an endorsement   by
                                                       the IEEE of these products.
--``,-`-`,,`,,`,`,,`---
NOTE—These are typical characteristic curves and should not be used for coordination.
                                      Silver sand current-limiting fuses: (See Table B.4.) Fuses of this type are used primarily for 480Y/277 V
                                      applications. They have steep time-current characteristic and are sensitive to changes in ambient
                                      temperatures. They should be located where the vault ambient temperature does not exceed 32 °C and the
                                      ambient inside the fuse enclosure does not exceed 15 °C rise over the vault ambient. Silver sand fuses are not
                                      physically interchangeable with other types of fuses and must therefore, be located external to the network
                                      protector. Silver sand fuses are not waterproof in themselves; therefore, a separate waterproof enclosure
                                      must be supplied if the fuses are subjected to water. At low levels of overcurrent, these fuses may become
                                      damaged without complete melting. Subsequent transformer loading can then cause them to overheat, open,
                                      or catch fire (see Figure B.4 for typical characteristic curves).
#1 800 A NPL-800
#2 200 A NPL-1200
#3 1875 A NPL-1875
#4 2825 A NPL-2825
#5 3000 A NPL-3000
                                           aRatings are those of the manufacturer. IEEE does not represent or warrant the accuracy of these ratings.
                                           bFuse and manufacturer designations are illustrative only of this type of fuse and do not constitute an endorsement by
                                            the IEEE of these products.
--``,-`-`,,`,,`,`,,`---
NOTE—These are typical characteristic curves and should not be used for coordination.
--``,-`-`,,`,,`,`,,`---
B.4 History
                                                     Secondary networks first came into existence as fused secondaries of distribution transformers. Networks
                                                     later became more sophisticated when special relayed circuit breakers replaced the fuse. Evidently, early
                                                     relays and circuit breakers did not have the desired degree of reliability. Therefore, fuses were used in series
                                                     with circuit breakers for secondary network service. The sole purpose of the fuse was to act as backup pro-
                                                     tection should the network relay or circuit breaker fail to operate. Even though present network equipment
                                                     has a high degree of reliability, users have been reluctant to eliminate fuses.
                                                     Before the 1940s, most network protectors were rated 216 Y/125 V. Since then, the growth of 480 Y/277 V
                                                     spot networks has been steadily increasing. At present, a large percentage of protectors sold are of the 480 Y/
                                                     277 V class. Fusing practice was generally perfected and coordinated for the 216 Y/125 V systems, so with
                                                     the introduction of higher rated networks, the same philosophy of fusing for 216 Y/125 V systems was trans-
                                                     ferred to the 480 Y/277 V systems.
                                                     The most common types of network fuses (alloy and copper) were tested up to 600 V. The 216 Y/125 V alloy
                                                     fuse had to have arc horns and flash barriers added before it would successfully clear at 600 V. Before the
                                                     copper fuse would clear, the customary enclosure cover had to be removed. Another characteristic that
                                                     required investigation before applying network fuses to 480 V systems was the condensing of metal vapors
                                                     when a fuse clears. When either an alloy or copper fuse interrupts, a portion of the metal is vaporized and
                                                     condenses throughout the enclosed circuit breaker. The greater the current, the more vapor. From a
                                                     theoretical standpoint, it would not be good practice to disperse metal vapor over insulated parts and expect
                                                     those insulated parts to provide adequate insulation. In a 216Y/125 V system where electric arcs are self-
                                                     extinguishing, one would give little thought to metal vapors. However, 480Y/277 V arcs are typically self-
                                                     sustaining, so one should consider the possibility of metal vapors causing general arcing throughout an
                                                     enclosed protector.
                                                     In reality, every time a circuit breaker interrupts, a small amount of vapor is liberated. A good portion of it is
                                                     confined in the arc chute, but over a period of time, insulated parts become contaminated. Fuses liberate a
                                                     great deal more metal vapor than breakers during interruption; thus, after each fuse operation, all insulated
                                                     parts should be cleaned before the protector is placed back into service.
                           --``,-`-`,,`,,`,`,,`---
                                                     Metal vapor from tin alloy fuses is essentially nonconductive. Insulation resistance of a protector before and
                                                     after fuse operation does not significantly change. Conversely, copper vapor is conducting and will lower the
                                                     insulation resistance.
                                                     Silver sand current limiting fuses are heat generators and therefore, can only be used for applications where
                                                     they are external to the protector steel enclosure. Some types of silver sand fuses are difficult to coordinate
                                                     with the transformer and network relay. Silver sand fuses are not of waterproof construction.
Alloy fuses are used for internal applications. They are the easiest to coordinate with the transformer.
                                    Annex C
                                    (informative)
Pumping
C.1 General
                                    Pumping is defined as the unintentional cyclical tripping and closing of a network protector. Pumping usu-
                                    ally occurs because the network protector is improperly allowed to close when system conditions will cause
                                    reverse current to flow after closure. The reverse current immediately trips the protector, and the cycle is
                                    repeated. Pumping may also occur because the network protector properly attempts to close, and a mechani-
                                    cal defect causes immediate trip. Some of the typical causes of pumping are described below.
C.2 Causes
                                    The most common case occurs when an electromechanical phasing relay setting allows closure with a lag-
                                    ging phasing voltage. The ensuing power flow is in the reverse direction and pumping is established. With
                                    electromechanical relays, the phasing relay is in a separate package from the network master relay. With
                                    solid-state relays, the phasing relay function is normally included as part of a single network relay package.
                                    Thus, the solid-state phasing relay is less vulnerable to an incorrect setting.
                                    One typical case occurs when nondedicated feeders from different substations supply a spot network. This
                                    situation can result in the primary voltages being slightly different in both level and phase angle. With light
                                    network load and cyclical nonnetwork load (e.g., frequent motor starting), the network protector can trip and
                                    reclose many times over a short period. This condition results in excessive frequency of operation and in
                                    extreme cases, can develop into pumping. A solution to this problem is to apply time delays and/or increase
                                    the reverse current trip level.
                                    The most common condition occurs when the breaker mechanism has some defect that prevents successful
                                    closure. This is breaker trip-free operation, where attempts to close result in immediate trip. In this case, sys-
                                    tem voltage conditions may be correct for proper closing, but the breaker mechanism prevents successful
                                    closure. Hence, pumping is established.
                                    The net effect of pumping is to raise the temperature of the closing motor. Excessive pumping can raise the
                                    temperature to the point where the insulation fails and a short circuit develops in the motor winding.
--``,-`-`,,`,,`,`,,`---
                                    Annex D
                                    (informative)
                                    This path is considered unprotected because the substation relays, both phase overcurrent and ground, are
                                    typically set in such a fashion that they do not respond to faults that are initiated on the low voltage side of
                                    the transformer. Faults that originate in the unprotected zone, in theory, would produce reverse currents suf-
                                    ficient to operate the master relay. However, because such faults are very likely to be high resistance arcing
                                    faults, it may become a race as to whether the network protector will trip before the control wiring is
                                    destroyed. Even if the network protector successfully opens its circuit, the fault is still supplied from the
                                    transformer, and it will continue to supply fault current until the station breaker is operated remotely, or until
                                    the fault has migrated far enough into the low-voltage windings to permit the ground or phase overcurrent
                                    relays to operate.
--``,-`-`,,`,,`,`,,`---
                                    Annex E
                                    (informative)
--``,-`-`,,`,,`,`,,`---
                                    Annex F
                                    (informative)
F.1 General
                                    For faults on a network primary feeder, with one exception, the power flow, in terms of current, in the asso-
                                    ciated network protectors will be relatively high and always in the reverse direction, after the primary feeder
                                    breaker opens. Under these fault conditions, the reverse current trip setting of the network master relay is not
                                    an issue, as the reverse power flows are much higher than the available settings. This includes the case of a
                                    single line to ground fault, with network transformers connected grounded wye-grounded wye.
                                    The one exception to the above is a single line to ground fault on a network primary feeder, with network
                                    transformers connected ∆-grounded Y. For this case, the reverse power flow is of relatively low magnitude,
                                    after the primary feeder breaker has opened. To assure that a protector will open for this single line to ground
                                    fault, the reverse power flow after feeder breaker opening must be greater than the reverse current trip set-
                                                                                                                                                       --``,-`-`,,`,,`,`,,`---
                                    ting.
                                    Similarly, when the primary feeder breaker is opened in the absence of a fault, the power flows in the net-
                                    work protectors will be relatively low. To assure that all network protectors on that feeder will open, the
                                    reverse power flow in at least one network protector must exceed its trip setting. The remaining protectors on
                                    the feeder will then cascade open to clear the feeder.
                                    Cascading occurs when a primary feeder is opened, because the network transformer units associated with
                                    the protectors already tripped continue to be energized by the network units not yet tripped, via the primary
                                    interconnections. Hence, the exciting current of the transformers with open protectors is added to the reverse
                                    exciting current supplied by the closed protectors. The last protector to trip on any one feeder sees the sum
                                    total of no-load losses on all transformers connected to that feeder.
                                    When a primary feeder breaker is opened in the absence of a fault, there will be some variation in the voltage
                                    at each network protector, in both magnitude and phase angle. This results from small differences in cable
                                    impedances and transformer turns ratios. Hence, there will be a circulating current in the primary cable inter-
                                    connections. Just after the primary feeder breaker opens, there will be “circulating” reverse power flows in
                                    some protectors and forward power flows in others. A phase angle difference of 0.5 electrical degrees on half
                                    of the transformers can produce a power flow in each protector as high as 7% of the protector rating. A volt-
                                    age difference of ±0.5% of nominal on all transformers can produce a power flow in each protector as high
                                    as 1% of the protector rating.
                                    There are also I2R losses in the network transformer due to the circulating current and I2R losses in the
                                    transformer due to the flow of primary cable charging current. In most cases, these losses are small in com-
                                    parison to transformer no-load losses and the circulating power.
                                        In summary, the reverse power through at least some of the network protectors on an open primary feeder
                                        consists of the following:
                                        Another factor that will result in higher reverse watt flow in the network protector when the primary feeder
                                        breaker is open is the effect of voltage rise on the no-load transformer loss. Under many backfeed condi-
                                        tions, there will be voltage rises due to primary cable capacitance. With a 10% voltage rise, no-load loss in
                                        the back feeding network transformer will increase 15–30%.
                                        Reverse power flows with open primary breaker, single line to ground fault, and ∆-Y network transformers
                                        will be relatively low. If the primary feeder cables are very short, the power flows in each network protector
                                        at the instant of breaker opening will be almost the same as if the fault were not present.
                                        The network master relay is calibrated at rated three-phase voltage in terms of balanced three phase current,
                                        leading network line to ground voltage by 180°. The relay responds to the direction and magnitude of net
                                        (equivalent) three-phase power flow.
                                        References to protector current rating herein should be considered as referring to protector current trans-
                                        former rating. On some protectors, the current transformer (CT) primary rating is lower than the protector
                                        current rating. For example, the 1875 A protector uses 1600-5 A CTs.
                                        As seen from previous paragraphs, network protectors can trip on reverse current even though their relay set-
                                        ting is above no-load transformer losses. This applies whether the reverse current setting is at a minimum
                                        value of 0.05–0.1%, or the more commonly used values of 0.15–0.2%, of the protector rating. However, if
                                        the reverse current settings are too high, i.e., above 2–3% of the protector rating, the network protectors may
                                        not cascade open, when the primary feeder breaker is opened in the absence of a fault.
                                        For many years, transformer no-load losses were at levels high enough such that network relay sensitivity
                                        was not a major concern. For example, a typical 500 kVA 216 V transformer would have no-load losses in
                                        the range of 1200–1500 W. For the normal 1600 A or 1875 A protector used with the 500 kVA transformer,
                                        these no-load loss levels are 0.2–0.25% of the protector rating. Hence, a normal relay setting of 0.2% would
                                        be acceptable.
                                        Transformer losses have declined in recent years so that no-load losses in the 500 kVA transformers can now
                                        be as low as 500–600 W. These loss levels are 0.08–0.1% of the protector rating (1600 A–216 V). When such
                                        low loss transformers are added to existing grid networks, there is no need to revise previously established
                                        acceptable network relay setting levels for these new units. Even though the relay setting may be above the
                                        no-load losses for these units, they will still trip out because of the additional reverse power contributions
                                        and the cascading effect previously described. The example described above is generally representative of
                                        the higher network unit ratings as well.
                                        The only cases where a network protector would be required to trip only on the no-load losses of its associ-
                                        ated transformer are where a primary feeder supplies only one transformer or where the transformer has a
                                        primary breaker or load break switch, which isolates the transformer from the rest of the primary circuit.
                                        Under these conditions, the protector will trip when the primary breaker is opened only if the transformer
                                        no-load losses are greater than the network relay setting. These conditions should rarely occur.
--``,-`-`,,`,,`,`,,`---
                                    These rare cases may require a relay setting down near minimum levels of 0.05% or 0.1%, depending on
                                    transformer losses. The electromechanical network relay is normally provided with a minimum setting value
                                    of 0.1% of the protector rating. The newer solid state or microprocessor network relays are normally pro-
                                    vided with a minimum setting value of 0.05% of the protector rating.
                                    Network protector reverse current trip settings should be only as low as required to assure automatic opening
                                    when the primary feeder breaker is opened. Settings of 0.15% of protector current transformer rating will
                                    usually yield satisfactory performance, even with low loss network transformers. Extremely sensitive reverse
                                    current trip settings can cause unnecessary protector operations due to transient reverse power flows.
                                    Occasionally, system conditions may occur where sensitive reverse current tripping must be time delayed.
                                    Typically, this occurs on new construction sites, where the network load is light and elevators being lowered
                                    act as generators to create a temporary reverse current. To prevent excessive and/or undesirable trip opera-
                                    tions, a time delay is required for sensitive tripping, in the order of 1–5 min. When this time delay is intro-
                                    duced, a three-phase instantaneous overcurrent element must also be provided to trip for reverse fault
                                    currents. This element is typically set in the range of 50–250% of the protector current rating. For electrome-
                                    chanical relays, the time delay and instantaneous overcurrent functions are normally combined in one pack-
                                    age separate from the other network relaying functions. For solid state or microprocessor relays, all network
                                    relaying functions, including the above, are normally combined in one package.
--``,-`-`,,`,,`,`,,`---
                                                     Annex G
                                                     (informative)