INDEX
TLK 94                                             1
                                                                                   1.1
                                                                                   1.2
                                                                                    2
                                                                                   2.1
                                                                                          INSTRUMENT DESCRIPTION
                                                                                          GENERAL DESCRIPTION
                                                                                          FRONT PANEL DESCRIPTION
                                                                                          PROGRAMMING
                                                                                          FAST PROGRAMMING OF THE SET POINT
                                                                                   2.2    SELECTION OF CONTROL STATE AND PARAMETERS
              MICROPROCESSOR-BASED                                                        PROGRAMMING
                                                                                   2.3    PARAMETER PROGRAMMING LEVELS
                     DIGITAL                                                       2.4    CONTROL STATES
                                                                                   2.5    ACTIVE SET POINT SELECTION
              ELECTRONIC CONTROLLER                                                 3     INFORMATION ON INSTALLATION AND USE
                                                                                   3.1    PERMITTED USE
                                                                                   3.2    MECHANICAL MOUNTING
                                                                                   3.3    ELECTRICAL CONNECTIONS
                                                                                   3.4    ELECTRICAL WIRING DIAGRAM
                                                                                    4     FUNCTIONS
                                                                                   4.1    MEASURING AND VISUALIZATION
                                                                                   4.2    OUTPUT CONFIGURATION
                                                                                   4.3    ON/OFF CONTROL
                                                                                   4.4    NEUTRAL ZONE ON/OFF CONTROL
                                                                                   4.5    SINGLE ACTION PID CONTROL
                                                                                   4.6    DOUBLE ACTION PID CONTROL
                                                                                   4.7    PID CONTROL FOR MOTORIZED ACTUATORS WITH
                                                                                          TIME POSITIONING
                                                                                    4.8   AUTO-TUNING AND SELF-TUNING FUNCTIONS
                                                                                    4.9   CONTROL POWER LIMITATION
                                                                                   4.10   LIMITATION OF THE CONTROL POWER VARIATION
                                                                                          SPEED (MAXIMUM RATE OF RISE)
                                                                                   4.11   SPLIT RANGE FUNCTION
                                                                                   4.12   REACHING OF SET POINT AT CONTROLLED SPEED
                                                                                          AND AUTOMATIC COMMUTATION BETWEEN TWO
                                                                                          SET POINTS
                                                                                   4.13   SOFT-START FUNCTION
                                                                                   4.14   ALARMS OUTPUTS FUNCTIONS
                     OPERATING INSTRUCTIONS                                        4.15   HEATER BREAK ALARM FUNCTION
                              Vr. 01 (ENG) - 01/10                                 4.16   LOOP BREAK ALARM FUNCTION
                            cod.: ISTR-MTLK94ENG1                                  4.17   FUNCTION OF KEY “U”
                                                                                   4.18   DIGITAL INPUTS
                                                                                   4.19   RS 485 SERIAL INTERFACE
                            TECNOLOGIC S.p.A.                                      4.20   PARAMETERS CONFIGURATION BY A01
                                                                                     5    PROGRAMMABLE PARAMETERS TABLE
                                                                                     6    PROBLEMS , MAINTENANCE AND GUARANTEE
                            VIA INDIPENDENZA 56                                     6.1   ERROR WARNINGS
                         27029 VIGEVANO (PV) ITALY                                  6.2   CLEANING
                            TEL.: +39 0381 69871                                    6.3   GUARANTEE AND REPAIRS
                                                                                     7    TECHNICAL DATA
                            FAX: +39 0381 698730                                    7.1   ELECTRICAL DATA
                      internet : http:\\www.tecnologic.it                           7.2   MECHANICAL DATA
                          e-mail: info@tecnologic.it                                7.3   MECHANICAL DIMENSIONS, PANEL CUT-OUT AND
                                                                                          MOUNTING
                                                                                   7.4    FUNCTIONAL DATA
             FOREWORD                                                              7.5    MEASURING RANGE TABLE
                            This    manual     contains    the    information      7.6    INSTRUMENT ORDERING CODES
                            necessary for the product to be installed
                            correctly and also instructions for its               1 - INSTRUMENT DESCRIPTION
                            maintenance and use; we therefore recommend
                            that the utmost attention is paid to the following   1.1 - GENERAL DESCRIPTION
                            instructions and to save it.                         TLK 94 is a “single loop” digital microprocessor-based controller,
           This document is the exclusive property of TECNOLOGIC                 with ON/OFF, Neutral Zone ON/OFF, PID single action, PID dual
           S.p.A. which forbids any reproduction and divulgation , even          action (direct and reverse) control, PID for motorized actuators with
           in part, of the document, unless expressly authorized.                time positioning control. The instrument is equipped with
           TECNOLOGIC S.p.A. reserves the right to make any formal or            AUTO-TUNING function (FAST or OSCILLATING type),
           functional changes at any moment and without any notice.              SELF-TUNING function and automatic calculation of the FUZZY
           Whenever a failure or a malfunction of the device may cause           OVERSHOOT CONTROL parameter for PID control. The PID
           dangerous situations for persons, thing or animals, please            control has a particular algorithm with TWO DEGREES OF
           remember that the plant has to be equipped with additional            FREEDOM that optimises the instrument’s features independently
           devices which will guarantee safety.                                  of the event of process disturbances and Set Point variations.
                                                                                 Furthermore, the instrument allows for RS485 serial
           Tecnologic S.p.A. and its legal representatives do not assume
                                                                                 communication using MODBUS-RTU communication protocol and
           any responsibility for any damage to people, things or animals
                                                                                 a transmission speed up to 38.400 baud. The process value is
           deriving from violation, wrong or improper use or in any case         visualized on 4 red displays, the Set value is visualized on 4 green
           not in compliance with the instrument’s features .                    displays while the outputs status is indicated by 6 leds. The
                           TECNOLOGIC spa - TLK 94 -OPERATING INSTRUCTIONS - Vr.01 - 01/10 - ISTR-MTLK94ENG1 - PAG. 1
Downloaded from www.Manualslib.com manuals search engine
           instrument provides for the storage of 4 Set Points and can have          2 - PROGRAMMING
           up to 6 outputs : relay type or can drive solid state relays type
           (SSR), or it is also possible to have up to 2 analogue outputs.          2.1 - FAST PROGRAMMING OF THE SET POINT
           The input is programmable and accepts temperature probes                 This procedure permits rapid programming of the active Set Point
           (Thermocouples J,K,S,B,C,E,L,N,R,T; Thermo-resistances PT100,            and possibly the alarm thresholds (see par 2.3)
           Thermistors PTC and NTC; Infrared sensors mod. TECNOLOGIC                Push key “P”, then release it and the display will visualise “SP n”
           IRS) and normalized analogue signals (0/4..20 mA, 0/1..5 V,              (where n is the number of the Set Point active at that moment) and
           0/2..10 V, 0..50/60 mV, 12..60 mV). The instrument have 2                the programmed value.
           programmable digital inputs for free voltage contacts and can be         To modify the value, press “UP” key to increase it or the “DOWN”
           equipped with an input for the current transformer, working as a         key to decrease it.
           Heater Break Alarm function. Other important available functions         These keys change the value one digit at a time but if they are
           are: Loop-Break Alarm function, control power limitation, limitation     pressed for more than one second, the value increases or
           of the variation speed of the control power, split-range, reaching of    decreases rapidly and, after two seconds in the same condition,
           the Set Point at controlled speed, ramp and dwell function,              the changing speed increases in order to allow the desired value to
           Soft-Start function, parameters protection on different levels.          be reached rapidly.
                                                                                    Once the desired value has been reached, by pushing key P it is
           1.2 - FRONT PANEL DESCRIPTION                                            possible to exit by the fast programming mode or it is possible to
                                                                                    visualise the alarm thresholds AL1, AL2, AL3, AL4 (see par. 2.3).
                         6                                                7         To exit the fast Set programming it is necessary to push key P,
                                       Out1 Out2 Out3   Out4 Out5                   after the visualisation of the last Set Point, or alternatively, if no key
                         5                                                9         is pressed for approx. 15 seconds, the display will return to normal
                                                                                    functioning automatically.
                        13        PV                                      8         2.2 - SELECTION OF THE CONTROL STATE AND
                                                                    TUN
                                                                                    PARAMETERS PROGRAMMING
                        14                                                12        By pushing key "P" and holding it down for approx. 2 sec. it is
                                  SV                                                possible to enter into the main selection menu.
                                                                    SET   11
                        10
                                                                                                                                "rE G "
                                       Out6
                          4                                               3          H old fo r
                                                                                      2 s ec .
                          1                                               2
                                                        TLK 94
           1 - Key P : This is used to access the programming parameters
           and to confirm selection.                                                                                            "O F F "
           2 - Key DOWN : This is used to decrease the values to be set and
           to select the parameters. If the key is held down, the user returns to
           the previous programming level until he exits the programming
           mode. Outside the programming mode it permits visualisation of                                                    A U T O T U N IN G
           the current measured by the TAHB input, on the SV display.                                                        S E L F T U N IN G
           3 - Key UP : This is used to increase the values to be set and to
           select the parameters. If the key is held down, the user returns to
           the previous programming level until he exits the programming
           mode. Outside the programming mode it permits visualisation of                                                      "O P L O "
           the output control power, on the SV display.
           4 - Key U : This is a key with a function programmable by par.
           “USrb”. It can be set to : Activate Auto-tuning and Self-tuning
           functions, swap the instrument to manual control, silence the
           alarm, change the active Set Point, deactivate control (see par.
                                                                                    Using the "UP" or DOWN” keys, it is then possible to roll over the
           4.17) and modify the visibility of the parameters in “ConF” menu
                                                                                    selections:
           (see par. 2.3).
           5 - Led OUT1 : indicates the state of output OUT1                          "OPEr" to enter into the operating parameters menu
           6 - Led OUT2 : indicates the state of output OUT2                          "ConF" to enter into the configuration parameters menu
           7 - Led OUT3 : indicates the state of output OUT3                           "OFF"     to swap the regulator into the OFF state
           8 - Led OUT4 : indicates the state of output OUT4                           "rEG"     to swap the regulator into the automatic control state
           9 - Led OUT5 : indicates the state of output OUT5                           "tunE" to activate the Auto-tuning or Self-tuning function
           10 - Led OUT6 : indicates the state of output OUT6                         "OPLO" to swap the regulator to the manual control state and
           11 - Led SET : it indicates access to the programming mode and                       therefore to program the % control value using the
           the parameters level (see par. 2.3).                                                 “UP” and “DOWN” keys
           12 - Led TUN : indicates that the Self-tuning function is activated      Once the desired item has been selected, push key “P” to confirm.
           (light on) or that Auto-tuning (flashing ) is in progress.               Selecting "OPEr" and "ConF" gives the possibility of accessing
           13 - Display PV: normally indicates the process value                    other menus containing additional parameters and more precisely :
           14 - Display SV: normally indicates the active Set value, however it     "OPEr" – Operating parameters Menu: this normally contains the
           can be programmed, using par. “diSP”, to visualize other values.         Set Point parameters but it can contain all the desired parameters
                                                                                    (see par. 2.3).
                           TECNOLOGIC spa - TLK 94 -OPERATING INSTRUCTIONS - Vr.01 - 01/10 - ISTR-MTLK94ENG1 - PAG. 2
Downloaded from www.Manualslib.com manuals search engine
           "ConF" – Configuration parameters Menu: this contains all the            =SE : The active Set Point can be modified while the alarm
           operating parameters and the functioning configuration parameters        thresholds cannot be modified.
           (alarm configuration, control, input, etc.)                              =AE : The active Set Point cannot be modified while the alarm
           To enter the menu “ConF” select the option “ConF”, press the key         thresholds can be modified
           “P” and the display will show “0”.                                       =SAE : Both the active Set Point and the alarm thresholds can be
           At this request, enter, using keys “UP” and “DOWN”, the number           modified
           reported on the last page of this manual and push key “P”.               =SAnE : Both the active Set Point and the alarm thresholds cannot
           If an incorrect password is entered, the instrument exit from            be modified
           programming mode.
           If the password is correct, the display will visualise the code          2.4 - CONTROL STATE
           identifying the first group of parameters (“ ]SP “) and with keys “UP”   The controller can act in 3 different ways : automatic control (rEG),
           and “DOWN” it will be possible to select the desired group of            control off (OFF) and manual control (OPLO).
           parameters.                                                              The instrument is able to pass from one state to the other :
           Once the desired group of parameters has been selected, the code         - by selecting the desired state from the main selection menu suing
           identifying the first parameter of the selected group will be            the keyboard.
           visualised by pushing the “P” key.                                       - By using the key “U” on the keyboard; suitably programming par.
           Again using the “UP” and “DOWN” keys, it is possible to select the       “USrb” (“USrb” = tunE; “USrb” = OPLO; “USrb” = OFF) it is possible
           desired parameter and, if the key “P” is pressed, the display will       to pass from “rEG” state to the state programmed on the parameter
           show the parameter’s code and its programming value, which can           and vice versa.
           be modified by using the “UP” or “DOWN” keys.                            - Automatically (the instrument swaps into "rEG" state at the and of
           Once the desired value has been programmed, push key “P” once            the auto-tuning execution)
           more: the new value will be memorised and the display will show          When switched on, the instrument automatically reassumes the
           only the code of the selected parameter.                                 state it was in when it was last switched off.
           By using the “UP” or “DOWN” keys, it is then possible to select a        AUTOMATIC CONTROL (rEG) – Automatic control is the normal
           new parameter (if present) and modify it as described above.             functioning state of the controller.
           To select another group of parameters, keep the “UP” or “DOWN”           During automatic control, on the SV display, it is possible to
           key pressed for approx. 2 sec., afterwards the display will return to    visualize the control power on the display by pushing key “UP”.
           visualise the code of the group of parameters.                           The range of the power values goes from H100 (100% of the
           Release the key and by using the “UP” and “DOWN” keys, it will be        output power with reverse action) to C100 (100% of the output
           possible to select a new group.                                          power with direct action).
           To exit the programming mode, no key should be pressed for               CONTROL OFF (OFF) – The instrument can be swapped into the
           approx. 20 seconds, or keep the “UP” or “DOWN” pressed until exit        “OFF” state, i.e. the control and the relative outputs are
           from the programming mode is obtained.                                   deactivated.
           The programming and exit modes for the “OPEr” menu are the               The alarm outputs are instead working normally.
           same as those described for menu “ConF” with the difference that         BUMPLESS MANUAL CONTROL (OPLO) – By means of this
           to access the menù "OPEr" the Password is not required.                  option it is possible to manually program the power percentage
                                                                                    given as output by the controller by deactivating automatic control.
                                                                                    When the instrument is swapped to manual control, the power
                                                                                    percentage, visualised on the SV display, is the same as the last
                                                                                    one supplied and can be modified using the “UP” and “DOWN”
                                                                                    keys.
                                         Hold for                                   In case of ON/OFF control, 0% corresponds to the deactivated
                                          2 sec.
                                                                                    output while any value different from 0 corresponds to the activated
                   Hold for
                    2 sec.
                                          Hold
                                          Longer                                    output.
                                                                                    As in the case of visualization, the programmable values range
                                                                                    from H100 (100% output power with reverse action) to C100 (100%
                                                                                    output power with direct action).
           ATTENTION: The instrument is programmed in factory with all the          In case of motorized actuators with time positioning, the manual
           parameters, to exception of the Set Point "SP1" (and 2,3,4),             control of the output is obtainable in the following way :
           programmable in the menù "ConF" to the purpose to prevent wrong          - By pushing the UP key, the opening of the actuator is driven
           accidental programming from non experienced consumers.                   - By pushing DOWN key, the closing of the actuator is driven
                                                                                    For all time during which the manual control is active, “3 Pt” or
           2.3 - PARAMETERS PROGRAMMING LEVELS                                      “OPEn” is visible on the lower display if the UP key is pressed or
           The menu “OPEr” normally contains the parameters used to                 “CLOS” if the DOWN key is pressed.
           program the Set Point; however it is possible to make all desired        To return to automatic control, select "rEG" in the selection menu.
           parameters appear or disappear on this level, by following this
           procedure:                                                               2.5 - ACTIVE SET POINT SELECTION
           Enter the menu “ConF” and select the parameter to be made                This instrument permits pre-programming of up to 4 different Set
           programmable or not programmable in the menu “OPEr”.                     points (“SP1”, “SP2”, “SP3”, “SP4”) and then selection of which
           Once the parameter has been selected, if the LED SET is switched         one must be active. The maximum number of Set points is
           off, this means that the parameter is programmable only in the           determined by the par. "nSP" located in the group of parameters “
                                                                                    ]
           menu “ConF”, if instead the LED is on, this means that the                SP “.
           parameter is also programmable in the menu “OPEr”.                       The active Set point can be selected :
           To modify the visibility of the parameter, push key “U” : the LED        - by parameter "SPAt" in the group of parameters “ ]SP “.
           SET will change its state indicating the parameter accessibility level   - by key “U” if par. "USrb" = CHSP
           (on = menu ”OPEr” and “ConF”; off = menu “ConF” only).                   - by digital input if par. “diF” = CHSP or = SP1.2 or =HECo)
           The active Set Point and the alarm thresholds will only be visible on    - Automatically between SP1 and SP2 if a time “dur.t” (see par.
           the Set Point fast programming level (described in par. 2.1) if the      4.12) has been programmed.
           relative parameters are programmed to be visible (i.e. if they are       Set Points “SP1”, “SP2”, “SP3”, “SP4” will be visible depending on
           present in the menu “OPEr”).                                             the maximum number of Set Points selected on par. “nSP” and
           The possible modification of these Sets, with the procedure              they can be programmed with a value that is between the value
           described in par. 2.1, is instead subordinate to what is programmed      programmed on par. “SPLL” and the one programmed on par.
           in par. “Edit” (contained in the group “ ]PAn “).                        “SPHL”.
           This parameter can be programmed as :
                              TECNOLOGIC spa - TLK 94 -OPERATING INSTRUCTIONS - Vr.01 - 01/10 - ISTR-MTLK94ENG1 - PAG. 3
Downloaded from www.Manualslib.com manuals search engine
           Note : in all the following examples the Set point is indicated as 3.4 - ELECTRICAL WIRING DIAGRAM
           "SP", however the instrument will act according to the Set point
           selected as active.
                                                                                                                                     TLK 94
                                                                                                           DIG. IN 1       6a               +             12a
                                                                                                                                        +
             3 - INFORMATION ON INSTALLATION AND USE                                                       DIG. IN 2       5a                             11a        Out5
                                                                                                                           4a                             10a        Out4
                            3.1 - PERMITTED USE                                                                       A    3a                +       NO
                                                                                                                                                           9a
                            The instrument has been projected and                                                                                      C             Out3
                                                                                                             RS485 B       2a                              8a
                            manufactured as a measuring and control device
                                                                                                                                          + +        NO
                            to be used according to EN61010-1 for the                                                GND   1a                              7a
                            altitudes operation until 2000 ms .
                                                                                                                                          G
                                                                                                                                                       C             Out2
                                                                                                                           6b                             12b
                            The use of the instrument for applications not                                   TA HB
                                                                                                                                         + +         NC
           expressly permitted by the above mentioned rule must adopt all the                                              5b                             11b
                                                                                             +12 VDC                  Out6               G
                                                                                                                                                     NO
           necessary protective measures.                                                                                  4b                             10b        Out1
                                                                                               +
           The instrument CANNOT be used in dangerous environments                                                         3b                              9b
                                                                                                      +
           (flammable or explosive) without adequate protection.
           The installer must ensure that EMC rules are respected, also after                                              2b                              8b
                                                                                                                                                                     SUPPLY
           the instrument installation, if necessary using proper filters .                                                1b                              7b
                                                                                                                             +
                                                                                4..20 0/4..20 0/1..5 V PTC NTC Pt100 TC
           Whenever a failure or a malfunction of the device may cause           mA       mA
                                                                              (passive) (active) 0/2..10 V
           dangerous situations for persons, thing or animals, please                                                                    OUTPUTS
                                                                                                                                           RELAYS:
           remember that the plant has to be equipped with additional devices                              INPUT              Out1: 6A-AC1(3A-AC3)/ 250 VAC
           which will guarantee safety.                                                                                     Out2,3,4,5: 4A-AC1(2A-AC3)/ 250 VAC
                                                                                                                                     SSR: 12 VDC/20 mA
                                                                                                                                     ANALOG.: 0/4..20mA - 0/2..10V
           3.2 - MECHANICAL MOUNTING
           The instrument, in DIN case 48 x 96 mm, is designed for flush-in                 4 - FUNCTIONS
           panel mounting.
           Make a hole 45 x 92 mm and insert the instrument, fixing it with the            4.1 - MEASURING AND VISUALIZATION
           provided special brackets.                                                      All the parameters referring measurements are contained in the
           We recommend that the gasket is mounted in order to obtain the                  group “]InP”.
           front protection degree as declared. Avoid placing the instrument in            By using par. “HCFG”, it is possible to select the input signal type
           environments with very high humidity levels or dirt that may create
                                                                                           which may come: from a thermocouple (tc), a thermo-resistance or
           condensation or introduction of conductive substances into the
                                                                                           a thermistor (rtd), from a transducer with normalised analogue
           instrument.
                                                                                           signal in current (I) or tension (UoLt) or also from a signal coming
           Ensure adequate ventilation to the instrument and avoid installation
                                                                                           from the communication serial line of the instrument (SEr).
           in containers that house devices which may overheat or which may
                                                                                           Once the signal type has been selected, it is necessary to set the
           cause the instrument to function at a higher temperature than the
                                                                                           type of input probe on par. “SEnS”, which can be :
           one permitted and declared.
                                                                                           - for thermocouples J (J), K (CrAL), S (S), B (b), C (C), E (E), L (L),
           Connect the instrument as far away as possible from sources of
                                                                                           N (n), R (r), T (t) or for infrared sensors serie TECNOLOGIC IRS –
           electromagnetic disturbances such as motors, power relays, relays,
                                                                                           A range - with linearization J (Ir.J) or K (Ir.CA)
           solenoid valves, etc.
                                                                                           - for thermoresistances Pt100 IEC (Pt1) or thermistors PTC
           The instrument can be removed from its housing from the front side
                                                                                           KTY81-121 (Ptc) or NTC 103AT-2 (ntc)
           : it is recommended that the instrument be disconnected from the
                                                                                           - for normalised signals in current 0..20 mA (0.20) or 4..20 mA
           power supply when it is necessary to carry out this operation.
                                                                                           (4.20)
                                                                                           - for normalised signals in tension 0..50 mV (0.50), 0..60 mV (0.60),
           3.3 - ELECTRICAL CONNECTION                                                     12..60 mV (12.60), 0..5 V (0.5), 1..5 V (1.5), 0..10 V (0.10) or 2..10
           Carry out the electrical wiring by connecting only one wire to each             V (2.10).
           terminal, according to the following diagram, checking that the                 We recommend that the instrument be switched on and off
           power supply is the same as that indicated on the instrument and                whenever these parameters are modified, in order to obtain a
           that the load current absorption is no higher than the maximum                  correct measurement.
           electricity current permitted.                                                  For the instruments with input for temperature probes (tc, rtd) it is
           As the instrument is built-in equipment with permanent connection               possible to select the unit of measurement (°C, °F) through par.
           inside housing, it is not equipped with either switches or internal             “Unit”, and the desired resolution (0=1°; 1=0,1°) through par.
           devices to protect against overload of current: the installation will
                                                                                           “dP”.
           include an overload protection and a two-phase circuit-breaker,
                                                                                           Instead, with regards to the instruments with normalised analogue
           placed as near as possible to the instrument, and located in a
                                                                                           input signals, it is first necessary to program the desired resolution
           position that can easily be reached by the user and marked as
           instrument disconnecting device which interrupts the power supply               on par. “dP” (0=1; 1=0,1; 2=0,01; 3=0,001) and then, on par.
           to the equipment.                                                               "SSC", the value that the instrument must visualise at the
           It is also recommended that the supply of all the electrical circuits           beginning of the scale (0/4 mA, 0/12 mV, 0/1 V o 0/2 V) and, on
           connected to the instrument must be protect properly, using                     par. "FSC", the value that the instrument must visualise at the end
           devices (ex. fuses) proportionate to the circulating currents.                  of the scale (20 mA, 50 mV, 60 mV, 5 V or 10 V).
           It is strongly recommended that cables with proper insulation,                  In the case of infrared sensors (TECNOLOGIC IRS-"A" range), by
           according to the working voltages and temperatures, be used.                    programming the sensor as "Ir.J" or "Ir.CA", the par. "rEFL" is also
           Furthermore, the input cable of the probe has to be kept separate               present and it allows the correction of possible measuring errors
           from line voltage wiring. If the input cable of the probe is screened,          caused by the environment lighting and by the reflectivity of the
           it has to be connected to the ground with only one side.                        material. This parameter should be programmed with a high value
           We recommend that a check should be made that the parameters                    if the material to be measured is particularly bright / reflective and
           are those desired and that the application functions correctly before           must be reduced if the surface is particularly dark / not reflective,
           connecting the outputs to the actuators so as to avoid                          keeping in mind however that for most materials, the recommended
           malfunctioning that may cause irregularities in the plant that could            value is within 1.00 and 0.80.
           cause damage to people, things or animals.                                      The instrument allows for measuring calibration, which may be
                                                                                           used to recalibrate the instrument according to application needs,
                                                                                           by using par. “OFSt” and “rot”.
                            TECNOLOGIC spa - TLK 94 -OPERATING INSTRUCTIONS - Vr.01 - 01/10 - ISTR-MTLK94ENG1 - PAG. 4
Downloaded from www.Manualslib.com manuals search engine
           Programming par. “rot”=1,000, in par. “OFSt” it is possible to set a       4”). The option "On" it results usable for the output OUT6 (standard
           positive or negative offset that is simply added to the value read by      on all the models) to have an auxiliary supply output for input
           the probe before visualisation, which remains constant for all the         sensors
           measurements.                                                              - ANALOGICAL OUTPUTS 0/4..20 mA or 0/2..10 V (only
           If instead, it is desired that the offset set should not be constant for   OUT1,2):
           all the measurements, it is possible to operate the calibration on         With the parameter “Aorn” it is possible to set the beginning of the
           any two points.                                                            scale used for the output.
           In this case, in order to decide which values to program on par.           This parameter will therefore be set at:
           “OFSt” and “rot”, the following formulae must be applied :                 = 0 : if one intends to use the beginning of the scale as equal to 0
                   “rot” = (D2-D1) / (M2-M1) “OFSt” = D2 - (“rot” x M2)               (0 mA if the output is 0/4...20 mA, or 0 V if the output is 0/2...10 V)
           where:                                                                     = no_0 : if one intends to use the beginning of the scale other than
           M1 =measured value 1                                                       0 (4 mA if the output is 0/4...20 mA, or 2 V if the output is 0/2...10
           D1 = visualisation value when the instrument measures M1                   V)
           M2 =measured value 2                                                       The parameter “AonF” will be present by which it is possible to
           D2 = visualisation value when the instrument measures M2                   configure the function of the analogical output as:
           It then follows that the instrument will visualise :                       = 1.rEG : Primary control output
                                  DV = MV x “rot” + “OFSt”                            = 2.rEG : Secondary control output
           where: DV = visualised value           MV= measured value                  = r.inP : measurement retransmission output
           Example 1: It is desired that the instrument visualises the value          = r.Err : error retransmission output [SP-PV]
           effectively measured at 20° but that, at 200°, it visualises a value       = r.SP : Active Set Point retransmission output
           lower than 10° (190°).                                                     = r.SEr : output led by serial communication line of the instrument
           Therefore : M1=20 ; D1=20 ; M2=200 ; D2=190                                = OFF : deactivated output
           “rot” = (190 - 20) / (200 - 20) = 0,944                                    In the case that analogical output is configured as 1.rEG or 2.rEG
           “OFSt” = 190 - (0,944 x 200) = 1,2                                         the output signal will be proportional to the control power
           Example 2: It is desired that the instrument visualises 10° whilst the     calculated by the instrument starting from 0% (output signal
           value actually measured is 0°, but, at 500° it visualises a 50° higher     corresponding to the set beginning of the scale) up to 100% (output
           value (550°).                                                              signal corresponds to the maximum that can be supplied by the
           Therefore : M1=0 ; D1=10 ; M2=500 ; D2=550                                 type of output available).
           “rot” = (550 - 10) / (500 - 0) = 1,08                                      The analogical control outputs can only be used for PID single
           “OFSt” = 550 - (1,08 x 500) = 10                                           action or dual action controls.
           By using par. “FiL” it is possible to program time constant of the         If the set control mode was the ON/OFF type, the analogical output
           software filter for the input value measured, in order to reduce           could only take on the control states 0 % or 100 %.
           noise sensitivity (increasing the time of reading).                        In the case that the analogical output function should be configured
           In case of measurement error, the instrument supplies the power            for the retransmission of the signal, it is therefore necessary to
           as programmed on par. “OPE”.                                               programme another two parameters which set the minimum and
           This power will be calculated according to cycle time programmed           maximum reference values.
           for the PID controller, while for the ON/OFF controllers the cycle         Therefore, in these cases, set the parameter "AonL" with the value
           time is automatically considered to be equal to 20 sec. (e.g. In the       that the instrument must provide the minimum value (0/4 mA or 0/2
           event of probe error with ON/OFF control and “OPE”=50, the                 V) in output and the value to which the instrument must provide the
           control output will be activated for 10 sec., then it will be              maximum value (20 mA o 10 V) to the parameter "AonH" in output.
           deactivated for 10 sec. and so on until the measurement error
           remains.).                                                                 4.3 - ON/OFF CONTROL (1.rEG)
           By using par. “InE” it is also possible to decide the conditions of        All the parameters referring to the ON/OFF control are contained in
           the input error, allowing the instrument to give the power                 the group “]rEG”.
           programmed on par. “OPE” as output.                                        This type of control can be obtained by programming par."Cont" =
           The possibilities of par. “InE” are :                                      On.FS or = On.FA and works on the output programmed as 1.rEG,
           = Or : the condition occurs in case of over-range or probe breakage        depending on the measure, on the active Set Point “SP”, on the
           = Ur : the condition occurs in case of under-range or probe                functioning mode "Func” and on the hysteresis "HSEt".
           breakage                                                                   The instrument carries out an ON/OFF control with symmetric
           = OUr : the condition occurs in case of over-range or under-range          hysteresis if “Cont" = On.FS or with asymmetrical hysteresis if
           or probe breakage                                                          “Cont” = On.FA.
           Using par. “diSP”, located in the group “]PAn”, it is possible to set          PV                                             PV
           normal visualization of the SV display which can be the active Set           SP
           Point (SP.F), the control power (Pou), the Set Point operating when                                            H S Et
                                                                                                                                                                          H SE t
           there are active ramps (SP.o) or alarm threshold AL1, 2, 3, 4 .                                                              SP
                                                                                                                               tim e                                          tim e
                                                                                                ON             ON         ON                   ON             ON           ON
           4.2 - OUTPUT CONFIGURATION                                                  O UT                                             OUT
           The instrument’s outputs can be programmed by entering the                 1 .rE G           o ff        off                1.rEG            off        o ff
           group of parameters “]Out” where different parameters (depending                          H EAt - O n.F A                                C oo L - O n .F A
           on the type of outputs - digital or analogue - available on the                PV
                                                                                                                                         PV
                                                                                                                          H S Et
           instrument) are located.                                                     SP                                                                                H SE t
                                                                                                                          H S Et        SP
           Note: In the following examples, the number of outputs is                                                                                                      H SE t
           generically indicated with n                                                                                        tim e                                          tim e
           - DIGITAL OUTPUTS relay or SSR type :                                                ON             ON         ON                   ON             ON           ON
                                                                                       O UT                                             OUT
           The par. “OnF” can be set for the following functions :                    1 .rE G           o ff        off                1.rEG            off        o ff
           = 1.rEG : Main control output
                                                                                                     H EAt - O n.F S                                C oo L - O n .FS
           = 2.rEG : Secondary control output
           = ALno : Alarm output normally open                                        The control works in the following way : in the case of reverse
           = ALnc : Alarm output normally closed                                      action, or heating (“FunC”=HEAt), it deactivates the output, when
           = On : Output always activated                                             the process value reaches [SP + HSEt] in case of symmetrical
           = OFF : Output deactivated                                                 hysteresis, or [SP] in case of asymmetrical hysteresis and is then
           The coupling outputs number outputs – number alarms can be                 activated again when the process value goes below value [SP -
           made in the group referring to the alarm to the alarm (“]AL1, 2, 3,        HSEt]. Vice versa, in case of direct action or cooling
                                                                                      ("Func”=CooL), it deactivates the output, when the process value
                           TECNOLOGIC spa - TLK 94 -OPERATING INSTRUCTIONS - Vr.01 - 01/10 - ISTR-MTLK94ENG1 - PAG. 5
Downloaded from www.Manualslib.com manuals search engine
           reaches [SP - HSEt] in case of symmetrical hysteresis, or [SP] in "tcr1" - Cycle time of the output 1rEG (digital output only)
           case of asymmetrical hysteresis and is activated again when the "Int" - Integral Time
           process value goes above value [SP + HSEt].                                             "rS" - Manual Reset (if “Int =0 only)
                                                                                                   "dEr" - Derivative Time
           4.4 - NEUTRAL ZONE ON/OFF CONTROL (1.rEG - 2.rEG)                                       “FuOC” - Fuzzy Overshoot Control
           All the parameters referring to Neutral Zone ON/OFF control are This last parameter allows the variable overshoots at the start up of
           contained in the group “]rEG”.                                                          the process or at the changing of the Set Point to be avoided.
           This type of control can be obtained when 2 outputs are Please remember that a low value on this parameter reduces the
           programmed respectively as 1.rEG and 2.rEG and the par. “Cont” overshoot while a high value increase it.
           = nr .
           The Neutral Zone control is used to control plants in which there is P V
           an element which causes a positive increase (ex. Heater, S P                                                       2
           humidifier, etc.) and an element which causes a negative increase                                                  1
           (ex. Cooler, de-humidifier, etc).
           The control functions works on the programmed outputs depending                                                    3
           on the measurement, on the active Set Point “SP” and on the
           hysteresis "HSEt".
           The control works in the following way : it deactivates the outputs
           when the process value reaches the Set Point and it activates the
           output 1rEG when the process value goes below value [SP - HSEt],                                                                                       t im e
           or it activates the output 2.rEG when the process value goes above 1: “FuOC” OK
           [SP + HSEt].                                                                            2: “FuOC” too high
           Consequently, the element causing a positive increase has to be 3: “FuOC” too low
           connected to the output programmed as 1.rEG while the element
           causing a negative increase has to be connected to the output 4.6 - DOUBLE ACTION PID CONTROLLER (1.rEG - 2.rEG)
           programmed as 2.rEG.                                                                    All the parameters referred to PID control are contained into the
                     PV                                                                            group “]rEG”.
                                                                                                   The Double Action PID control is used to control plants where there
                                                                                           HSEt    is an element which causes a positive increment (ex. Heating) and
                   SP
                                                                                           HSEt    an element which causes a negative increment (ex. Cooling).
                                                                                                   This type of control is obtainable when 2 outputs are programmed
                                                                                                   respectively as 1.rEG and 2.rEG and the par. “Cont” = Pid.
                                                                                                   The element causing a positive increase has to be connected to
                                                                                         time
                           0N                                                   0N                 the output programmed as 1.rEG while the element causing a
            OUT 1.rEG
             (heating)                 off                          off                            negative increase has to be connected to the output programmed
                                                      0N                                           as 2.rEG.
            OUT 2.rEG                                                                              The Double Action PID control works on the outputs 1.rEG and
             (cooling)           off                                    off
                                                                                                   2.rEG depending on the active Set Point “SP” and on the
                                                                                                   instrument’s PID algorithm with two degree of freedom.
           4.5 -SINGLE ACTION PID CONTROL (1.rEG)                                                  In order to obtain a good stability of the process variable, in case of
           All the parameters referring to PID control are contained in the fast processes and with control by digital outputs, the cycle times
           group “]rEG”.                                                                           “tcr1” and “tcr2” have to have a low value with a very frequent
           The Single Action PID control can be obtained by programming intervention of the control outputs.
           par."Cont" = Pid and works on the output 1.rEG depending on the In this case it’s recommended to use solid state relays (SSR) to
           active Set Point “SP”, on the functioning mode "Func” and on the drive the actuators.
           instrument’s PID algorithm with two degree of freedom.                                  The Double Action PID control algorithm needs the programming of
                                                                                                   the following parameters :
                      PV
                                                                                                   "Pb" - Proportional Band
                       SP                                                                          "tcr1" - Cycle time of the output 1rEG
                                                                                                   “tcr 2” - Cycle time of the output 2rEG
                                                                                                   "Int" - Integral Time
                                                                                                   "rS" - Manual Reset (if “Int =0 only)
                                                                                                   "dEr" - Derivative Time
                                                                                             tim e “FuOC” - Fuzzy Overshoot Control
                 1 .rE G      0N           0N      0N       0N      0N       0N       0N           "Prat" - Power Ratio or relation between power of the element
                  D IG .             o ff     o ff     o ff    o ff     o ff     o ff              controlled by output 2.rEG and power of the element controlled by
               (H E A t)
                                                                                                   output 1.rEG.
                           tcr1   tc r 1   tc r 1   tc r 1   tc r 1   tcr1   tc r 1
                 100%                                                                      4.7 - PID CONTROL FOR MOTORIZED ACTUATORS WITH TIME
               1 .rE G                                                                     POSITIONING (1.rEG - 2.rEG)
             AN ALO G .                                                                    All the parameters concerning the PID control for motorised
              (H E A t)                                                                    actuators are contained in the group “]rEG”.
                    0%
                                                                                           This type of control is used to control installations that have a
                                                                                           motorised actuator with digital opening and closing controls that
           In order to obtain good stability of the process variable, in the event         remain at the point they have reached if no command is received
           of fast processes and with control by digital output, the cycle time            and which are started up when 2 outputs are configured as 1.rEG
           “tcr1” has to have a low value with a very frequent intervention of             and 2.rEG respectively and the parameter “Cont” = 3 Pt is set.
           the control output.                                                             The opening command for actuation will be supplied by the output
           In this case use of a solid state relay (SSR) is recommended for                configured as 1.rEG while the closing command will be supplied by
           driving the actuator.                                                           the output configured as 2.rEG.
           The Single Action PID control algorithm foresees the setting of the             The PID type control for motorised actuators therefore acts on the
           following parameters :                                                          outputs 1.rEG and 2.rEG depending on the active Set point “SP”
           "Pb" - Proportional Band
                            TECNOLOGIC spa - TLK 94 -OPERATING INSTRUCTIONS - Vr.01 - 01/10 - ISTR-MTLK94ENG1 - PAG. 6
Downloaded from www.Manualslib.com manuals search engine
           and the result of the PID control algorithm with two degrees of          1) Program and activate the desired Set Point.
           liberty for the instrument.                                              2) Program par. "Cont" =Pid or =3 Pt if the instrument drives a
           The control system used does not foresee a retroaction for finding       motorized actuator with time positioning.
           the current position of the actuator.                                    3) Program par. "Func" according to the process to be controlled
           If the actuator is not fitted with safety stop contacts that interrupt   through output 1.rEG.
           the actuator at the end of its run it is necessary to equip the          4) Program an output as 2.rEG if the instrument controls a plant
           installation with these contacts (SQo, SQc) as shown in the              with double action or a motorized actuator with time positioning.
           diagram                                                                  5) Set the parameter "Auto" as:
                                                                                    = 1 - if FAST autotuning is desired automatically, each time the
                                                  TLK 94                            instrument is switched on, on the condition that the process value
                                                                                    is lower (with “Func” =HEAt) than [SP- |SP/2|] or higher (with
                                 1 .rE G                   2 .rE G                  “Func” =CooL) than [SP+ |SP/2|].
                                                                                    = 2 - if FAST autotuning is desired automatically, the next time the
                                                                                    instrument is switched on, on the condition that the process value
                                                                                    is lower (with “Func” =HEAt) than [SP- |SP/2|] or higher (with
                                                                                    “Func” =CooL) than [SP+ |SP/2|], and once the tuning is finished,
              S u p p ly           S Q o                     S Q c
                                                                                    the par. “Auto” is automatically swapped to the OFF state
                                                                                    = 3 - if manual FAST autotuning is desired, by selecting par. “tunE”
                                                                                    in the main menu or by key “U” correctly programming as “USrb” =
                                  O P E N              M             C LO S E       tunE. The Autotuning will start at the condition that the process
                                                                                    value is lower (with “Func” =HEAt) than [SP- |SP/5|] or higher (with
                                                                                    “Func” =CooL) than [SP+ |SP/5|].
           The PID control algorithm for motorised actuators with time              = 4 - if it’s desired to activate the FAST autotuning automatically at
           positioning foresees the setting of the following parameters:            the end of programmed Soft-Start cycle or each time the Set Point
           “Pb” - Proportional band                                                 is changed. The Autotuning will start at the condition that the
           “Int” - Integral time                                                    process value is lower (with “Func” =HEAt) than [SP- |SP/5|] or
           “rS” - manual reset (only if “Int =0)                                    higher (with “Func” =CooL) than [SP+ |SP/5|].
           “dEr” - Derivative time                                                  = - 1 - if the OSCILLATING autotuning is to be started automatically
           “FuOC” - Fuzzy Overshoot Control                                         each time the instrument is turned on.
           “tcor” - time of actuator run.                                           = - 2 - if the          OSCILLATING autotuning is to be started
           This is the time, expressed in seconds that is needed for the            automatically when the instrument is turned on the next time and,
           actuator to pass from the “completely open” position to “completely      once tuning has been completed, the parameter “Auto"=OFF is set
           closed” position.                                                        automatically.
           “SHrI” - Minimum control value.                                          = - 3 - if OSCILLATING autotuning is started up manually, by
           It is the value that the control must have reached (in %) before it      selecting par. “tunE” in the main menu or by key “U” correctly
           has an effect on the output. It is needed to prevent the control from    programming as “USrb” = tunE.
           intervening too frequently.                                              = - 4 - if OSCILLATING autotuning is to be started automatically
           “PoSI” - Switch on position.                                             each time the Set Point is changed.
           This is the position that the actuator must reach when the               Note : the Autotuning Fast type is particularly rapid and has no
           instrument is switched on. It can have the following values :            effect on the control as it calculates the parameters during the Set
           nO = the actuator remains where it is,                                   Point reaching phase.
           oPEn = the actuator goes to the “completely open” position,              In order to correctly perform the Autotuning Fast type it’s necessary
           cLoS = the actuator goes to the “completely closed” position.            that at the start of the cycle there is a certain difference between
           If the options "OPEn" or "CloS" are programmed, when it is turned        the process and the Set Point and for this reason the instrument
           on the device with activate the output 1.rEG (if "oPEn") or 2.rEG (if    activates the Autotuning Fast type only when :
           "cLoS") for the time set on parameter "tcor" after which control         - For “Auto” = 1 or 2: the process value is lower (with “Func”
           begins.                                                                  =HEAt) than [SP- |SP/2|] or higher (with “Func” =CooL) than [SP+
           In the event of an error in measurement, the outputs are activated       |SP/2|].
           so that the valve moves to the position fixed by the parameter           - For “Auto” = 3 or 4 : the process value is lower (with “Func”
           “PoSI”.                                                                  =HEAt) than [SP- |SP/5|] or higher (with “Func” =CooL) than [SP+
                                                                                    |SP/5|].
           4.8 - AUTOTUNING AND SELFTUNING FUNCTIONS                                The Autotuning Fast type is not advisable when the Set Point is
           All the parameters referring to the AUTO-TUNING and                      next to the initial reading or when the measured variable changes
           SELF-TUNING functions are contained in the group “]rEG”.                 irregularly during the tuning cycle (for reasons due to the process
           The AUTO-TUNING and SELF-TUNING functions permit the                     the variable goes up or down).
           automatic tuning of the PID controller.                                  In this cases we advice the Autotuning oscillatory type that
           The AUTO-TUNING function (FAST or OSCILLATING type)                      activates some ON-OFF control cycles permitting the oscillation of
           permits the calculation of the PID parameters by means of a tuning       the process value around the Se Point value and afterward the
           cycle and, at the end of this operation, the parameters are stored       control swap to the PID type with those values calculated by the
           into the instrument’s memory and remain constant during control.         Autotuning.
           The SELF-TUNING function (rule based "TUNE-IN") instead allows           6) Exit from the parameter programming.
           control monitoring and the continuous calculation of the parameters      7) Connect the instrument to the controlled plant.
           during control.                                                          8) Start up autotuning turning off and on the instrument if “Auto" = 1
           All functions automatically calculate the following parameters :         or 2, by selecting “tunE” in the main menu (or by correctly
           "Pb" - Proportional Band                                                 programming key “U” ) if “Auto" = 3, or by varying the Set value if
           "tcr1" - Cycle time of the output 1.rEG
                                                                                    “Auto" = 4.
                                                                                    At this point, the Autotuning function is started up and is marked by
           "Int" - Integral Time
                                                                                    the turning on of the led TUN.
           "dEr" - Derivative Time
                                                                                    The regulator starts up a series of operations on the connected
           “FuOC” - Fuzzy Overshoot Control                                         system in order to calculate the most suitable PID regulation
           and, for the Double Action PID control, also :                           parameters.
           “tcr 2” - Cycle time of the output 2.rEG                                 If, at the FAST Auto-tuning start, the condition for the lower or
           "Prat" - Ratio P 2.rEG/ P 1.rEG                                          higher process value is not found the display will show “ErAt” and
           To activate the AUTO-TUNING function proceed as follows :
                           TECNOLOGIC spa - TLK 94 -OPERATING INSTRUCTIONS - Vr.01 - 01/10 - ISTR-MTLK94ENG1 - PAG. 7
Downloaded from www.Manualslib.com manuals search engine
           the instrument will be swapped to normal control conditions               The limitation function is deactivated by setting the parameters =
           according to the previously programmed parameters.                        InF and if “OPLO” is not active in manual control mode.
           To make the error “ErAt” disappear, press key P.
           The autotuning cycle is limited to a maximum of 12 hours.                 4.11 - SPLIT RANGE FUNCTION
           If the process has not ended in 12 hours the instrument will show         The use of this function is only possible if the PID control is dual
           "noAt" .                                                                  function and can be used to delay or bring forward the intervention
           Instead, if a probe error should occur, the instrument will interrupt     of the actuators commanded by the instrument.
           the cycle being carried out.                                              Using this function it is therefore possible to optimise the
           The values calculated by Autotuning will be memorized                     intervention of the two actuators in such a way that their actions do
           automatically by the instrument at the end of the correct completion      not overlap or so that they overlap so that they obtain the mix of the
           of the autotuning cycle in the parameters related to PID regulation.      two actions of the actuators.
           Note : The instrument is already programmed in our factory to             Basically, this means setting two power offsets (one for direct
           carry out auto-tuning at every instrument switch on ("Auto" = 1).         action and one for reverse action) that set the beginning of the
           To activate the SELF-TUNING function proceed as follows                   intervention of the actuator commanded by the output.
           1) Program and activate the desired Set Point.                            The parameters that can be set for this function contained in the
           2) Program par. "Cont" =Pid.                                              block “]rEG”, are:
           3) Program par. "Func" according to the process to be controlled          “thr1” : Power threshold at which output 1.rEG begins to operate.
           through output 1.rEG.                                                     “thr2” : Power threshold at which output 2.rEG begins to operate.
           4) Program an output as 2.rEG if the instrument controls a                Basically, if one wishes to bring forward the reverse action (1.rEG)
           dual-action plant                                                         and delay the direct action (2.rEG) it is necessary to set positive
           5) Program par. "SELF" = yES                                              values on parameter “thr1” and negative values on parameter
           6) Exit from the parameter programming.                                   “thr2”.
           7) Connect the instrument to the controlled plant.                        In this way, the area within which the two outputs are not activated
           8) Activate Self-tuning selecting par. “tunE” in the main menu (or        at the same time is increased.
           by correctly programming key “U”).                                                          PV
           When the Self-tuning function is active, the led TUN is permanently
           lit up and all the PID parameters ("Pb", "Int", "dEr", etc.) are no                                                                        Pb
           longer visualized.                                                                          SP
                                                                                                                                                      Pb
           To stop the Auto-tuning cycle or deactivate the Self-tuning function
           select one of the control types : "rEG", "OPLO" or "OFF" from the
           menu “SEL”. If the instrument is switched off during Auto-tuning or                     100%
                                                                                                                                                     time
           with the Self-tuning function activated, these functions will remain         1rEG       thr1
                                                                                      (Heating)
           activated the next time it is switched on.                                                  0%
                                                                                        2rEG        thr2
           4.9 - CONTROL POWER LIMITATION                                             (Cooling)
                                                                                                  -100%
           Using this function, it is possible to limit the output control power     Vice versa if one wishes to extend the reverse action (1.rEG) and
           (separately for both control outputs) within a minimum limit and a        bring forward the direct action (2.rEG) it is necessary to set nega-
           maximum limit .                                                           tive values on parameter “thr1” and positive values on parameter
           It is only possible to use these limits if the PID control is single or   “thr2”.
           dual action and it may be useful to overcome some mechanical              In this way, the area within which the two outputs are activated at
           problems of the actuators such as valves that do not open until the       the same time is increased.
           output has reached at least 20% and/or are already completely
           closed when the power has reached 80%.                                                      PV
           The PID control of the instrument normally works producing power
           between 0 and 100 % in the case of single-action PID and –100                                                                              Pb
                                                                                                       SP
           (C) and 100 (H) % in the case of dual-action PID.                                                                                          Pb
           The function is therefore deactivated by setting “ro1.L” =0 “ro2.L” =
           0 and “ro1.H” =100, “ro2.H” = 100.
           By setting different values the power is lowered to within the limits                                                                    time
                                                                                                   100%
           set in order to use the actuator’s dynamics to the maximum.                  1rEG       thr2
           The parameters that can be set for this function, contained in the         (Heating)
                                                                                                       0%
           “]rEG” block are:                                                            2rEG       thr1
           “ro1.L” - minimum power in output from 1.rEG (H)                           (Cooling)
                                                                                                  -100%
           “ro1.H” - maximum power in output from 1.rEG (H)
           “ro2.L” - minimum power in output from 2.rEG (C)                          The split range function is deactivated by setting the respective
           “ro2.H” - maximum power in output from 2.rEG (C)                          parameters =0.
           The limitation is not active under the “OPLO” manual control mode.                     PV
           4.10 - LIMITATION OF THE CONTROL POWER VARIATION                                                                                           Pb
           SPEED                                                                                 SP
                                                                                                                                                      Pb
           This function makes it possible to limit the variation speed of the
           control power in output (separately for both control outputs).
           It is only possible to use this function if the PID control is single or
                                                                                                                                                    time
           dual action and can be useful for overcoming some problems with                     100%
           the actuators that may need a slow progressive variation in power.          1rEG
                                                                                     (Heating)
           The parameters that can be set for this function, contained in the                    0%
                   ]
           block “ rEG”, are:                                                          2rEG
                                                                                     (Cooling)
           “OPS1” - variation speed of the output power from 1.rEG (H)                       -100%
           expressed in [% / sec].
                                                                                    Note : In order to simplify the explanation of the example graphs a
           “OPS2” - variation speed of the output power from 2.rEG (C)
                                                                                    dual action control that is only proportional (and therefore with “dEr”
           expressed in [% / sec].
                                                                                    and “Int” = OFF) with “Prat” = 1.0 and “rS” = 0.0 was considered.
                           TECNOLOGIC spa - TLK 94 -OPERATING INSTRUCTIONS - Vr.01 - 01/10 - ISTR-MTLK94ENG1 - PAG. 8
Downloaded from www.Manualslib.com manuals search engine
           4.12 - REACHING OF THE SET POINT AT CONTROLLED                                      “SSt” - Soft-Start time (expressed in hh.mm)
           SPEED AND AUTOMATIC SWITCHING BETWEEN TWO SET                                       “HSEt” - End Soft Start cycle threshold
           POINTS (RAMPS AND DWELL TIME)                                                       If both parameters are programmed with values other than OFF,
           All the parameters referring to the ramps functioning are contained                 when switched on the instrument gives an output power as
           in the group “]rEG”.                                                                programmed on par. “St.P” for the time programmed on par. “SSt”
           It is possible to reach the set point in a predetermined time (in any               or when is reached the absolute value programmed at par. “HSEt”.
           case longer than the time the plant would naturally need). This                     Practically, the instrument works in manual condition and switches
           could be useful in those processes (heating or chemical                             to automatic control at the elapsing of time “SSt” or when is
           treatments, etc.) where the set point has to be reached gradually,                  reached the absolute value programmed at par. “HSEt”.
           in a predetermined time.                                                            To disable the Soft-Start function simply program par. “SSt” = OFF.
           Once the instrument has reached the first Set Point (SP1) it is pos-                Whenever, a measurement errors occurs during the Soft-Start
           sible to have automatic switching to the second Set Point (SP2) af-                 execution, the function is interrupted and the instrument gives an
           ter a set time, thus obtaining a simple automatic process cycle.                    output power as programmed on par. “OPE”.
           These functions are available for all the programmable controls                     If the measurement is restored, the Soft-Start is still deactivated.
           (PID single and double action, ON/OFF and Neutral Zone                              If it’s desired to activate the Autotuning with Soft-Start set par.
           ON/OFF).                                                                            “Auto”=4 / -4
           The function is determined by the following parameters :                            The Autotuning will start automatically at the end of programmed
           "SLor" - Gradient of first ramp expressed in unit/minute                            Soft-Start cycle (see. par. 4.8).
           "SLoF" - Gradient of second ramp expressed in unit/minute.
           "dur.t" - Dwell time of Set Point “SP1” before automatic switching                  4.14 - ALARMS OUTPUTS FUNCTIONS (AL1, AL2, AL3, AL4)
           to Set Point “SP2” (expressed in hrs. and min.).                                    The alarms depend on the process value (AL1, AL2, AL3, AL4) and
           The functions are deactivated when the relative parameters are =                    before setting them to work, it is necessary to know which output
           InF.                                                                                the alarm has to correspond to.
           If is desired only one ramp (ex. to reach “SP1”) it is enough to                    First of all it is necessary to configure in the groups of parameters
           program on the par. "SLor" the desired value.                                       “]Out ”, the parameters relative to the outputs required as alarm
           The ramp "SLor" it will always active at power on and when the                      (“O1F”, “O2F”, “O3F”, “O4F”, “O5F”, “O6F”) programming the
           Active Set Point value is changed.                                                  parameter relating to the desired output as follows :
                                                                                               = ALno if the alarm output has to be ON when the alarm is active,
              SV
            [U n it ]
                                                                                               while it is OFF when the alarm is not active
                                                                                               = ALnc if the alarm output has to be ON when the alarm is not
             SP1                                                         SLor                  active, while it is OFF when the alarm is active
                         SLor                                                       SP1
                                                                                               Note: In all the examples that follow is made reference to the alarm
                                                                                               AL1. Naturally the operation of the other alarms results analogous.
                                                                                               Have now access at the group “]AL1”, and program on par.
                                                                                               “OAL1” , to which output the alarm signal has to be sent.
                                                          change
                                                        S P 1 V a lu e
                                                                             t im e [m in .]   The alarm functioning is instead defined by parameters :
                                                                                               "AL1t " - ALARM TYPE
           If it is desired an automatic cycle from the power on instead it is                 "Ab1" - ALARM CONFIGURATION
           necessary to program the par. "nSP" = 2, to program the two Set                     “AL1” - ALARM THRESHOLD
           Point values "SP1" and "SP2" and naturally to program the par.
                                                                                               “AL1L” - LOW ALARM THRESHOLD (for band alarm) OR
           "SLor", "dur.t" and "SLoF" with the desired values.
                                                                                               MINIMUM SET OF AL1 ALARM THRESHOLD (for low or high
           In this case at the end of the cycle all the ramps won't be more
                                                                                               alarm)
           active.
                                                                                               “AL1H” - HIGH ALARM THRESHOLD (for band alarm) OR
               SV                                                                              MAXIMUM SET OF AL1 ALARM THRESHOLD (for low or high
            [ U n it]
                                       d u r .t                                                alarm)
             SP1
                                                            SLoF                               “HAL1” - ALARM HYSTERESIS
                        SLor                                                                   “AL1d” - ALARM ACTIVATION DELAY (in sec.)
                                                                                    SP2
                                                                                               "AL1i" - ALARM BEHAVIOUR IN THE EVENT OF
                                                                                               MEASUREMENT ERROR
                                              AUTO                       tim e [m in .]
                                                                                               "AL1t" - ALARM TYPE : the alarm output can behave in six
                                             ch an ge
                                               Set                                             different ways.
           Examples with starts from values lower than SP and with                             LoAb = ABSOLUTE LOW ALARM: The alarm is activated when
           decreasing of SP.                                                                   the process value goes below the alarm threshold set on parameter
           Note: In case of PID control, if Auto-tuning is desired whilst the                  "AL1” and will be deactivated when it goes above the value
           ramp function is active, this will not be carried out until the tuning              [AL1+HAL1].
           cycle has been completed. It is therefore recommended that                          With this mode is possible to program the minimum and the
           Auto-tuning be started avoiding activating the ramp function and,                   maximum set of “AL1” by “AL1L” and “AL1H” parameters.
           once the tuning is finished, deactivate Auto-tuning (“Auto” = OFF),                 HiAb = ABSOLUTE HIGH ALARM: The alarm is activated when the
           program the desired ramp and, if it automatic tuning is desired,                    process value goes higher than the alarm threshold set on
           enable the Self-tuning function.                                                    parameter "AL1" and will be deactivated when it goes below the
                                                                                               value [AL1 - HAL1].
                                                                                               With this mode is possible to program the minimum and the
           4.13 - SOFT-START FUNCTION
                                                                                               maximum set of “AL1” by “AL1L” and “AL1H” parameters.
           All the parameters referring to the Soft -Start functioning are
                                                                                                 PV                                        PV
           contained in the group “]rEG”.
           The Soft-Start function only works through PID control and allows                                                              AL1
           the limitation of control power when the instrument is switched on,                                                     HAL1
                                                                                                                                                                            HAL1
           for a programmable period of time.                                                    AL1
           This is useful when the actuator, driven by the instrument, may be
           damaged excess power supplied when the application is not yet in                                  ON         ON                            ON         ON
                                                                                                                                   time                                     time
           the normal rating. (ex. for certain heating elements).                               OUT                                       OUT
           The function depends on the following parameters :                                   AL1    off        off        off          AL1   off        off        off
            “St.P” - Soft-Start power                                                                        LoAb                                     HiAb
                           TECNOLOGIC spa - TLK 94 -OPERATING INSTRUCTIONS - Vr.01 - 01/10 - ISTR-MTLK94ENG1 - PAG. 9
Downloaded from www.Manualslib.com manuals search engine
           LodE = DEVIATION LOW ALARM: The alarm is activated when                                                    sec.) and the alarm will be activated only after the elapsing of that
           the process value goes below the value [SP1 + AL1] and will be                                             time.
           deactivated when it goes above the value [SP1 + AL1 + HAL1].                                               ALARM LATCH: : the alarm output may behave in two different
           With this mode is possible to program the minimum and the                                                  ways depending on the value added to par. “Ab1”.
           maximum set of “AL1” by “AL1L” and “AL1H” parameters.                                                      + 0 = ALARM NOT LATCHED: The alarm remains active in alarm
           HidE = DEVIATION HIGH ALARM: The alarm is activated when the                                               conditions only.
           process value goes above the value [SP1 + AL1] and will be                                                 + 4 = ALARM LATCHED: The alarm is active in alarm conditions
           deactivated when it goes below the value [SP1 + AL1 - HAL1].                                               and remains active even when these conditions no longer exist,
           With this mode is possible to program the minimum and the                                                  until the correctly programmed key “U”, (“USrb”=Aac) has been
           maximum set of “AL1” by “AL1L” and “AL1H” parameters.                                                      pushed.
                                                                                                                          P V
              PV                                                        PV
             SP
                                                                                                              HAL1      A L1
                                                                       AL1
            -AL1
                                                               HAL1    SP                                                                                                            tim e
                                                                                                                                             O N
                                                                                                                          +0    o ff                          o ff
                                 ON            ON                                    ON          ON
             OUT                                               time    OUT                                    time
                                                                                                                         A b1                         O N
             AL1          off           off            off             AL1     off        off           off               +4    o ff
                                  LodE                                               HidE                             exemple with absolute high alarm
           LHAb = ABSOLUTE BAND ALARM: The alarm is activated when
           the process value goes under the alarm threshold set on parameter                                          ALARM AKNOWLEDGEMENT: : the alarm output may behave in
           "AL1L" or goes higher than the alarm threshold set on parameter                                            two different ways depending on the value added to par. “Ab1”.
           "AL1H" and will be deactivated when it goes below the value [AL1H                                          + 0 = ALARM NOT AKNOWLEDGED: The alarm always remains
           - HAL1] or when it goes above the value [AL1L + HAL1].                                                     active in alarm conditions.
           LHdE = DEVIATION BAND ALARM: The alarm is activated when                                                   + 8 = ALARM AKNOWLEDGED: The alarm is active in alarm
           the process value goes below the value [SP1 + AL1L] or goes                                                conditions and can be deactivated by key “U” if properly
           above than the value [SP1 + AL1H] and will be deactivated when it                                          programmed (“USrb”=ASi), and also if alarm conditions still exist.
           goes below the value [SP1 + AL1H - HAL1] or when it goes above                                             ALARM BEHAVIOUR AT SET POINT CHANGE (DEVIATION
           the value [SP1 + AL1L + HAL1].                                                                             ALARMS ONLY): the alarm output may behave in two different
               PV                                                        PV                                           ways, depending on the value added to par. “Ab1”.
             AL1H
                                                                HAL1                                           HAL1
                                                                                                                      +0 = NORMAL BEHAVIOUR: The alarm is always activated when
                                                                        AL1H                                          there are alarm conditions.
                                                                       SP
                                                                HAL1    AL1L                                   HAL1
                                                                                                                      +16 = ALARM NOT ACTIVATED AT SET POINT CHANGE: If,
             AL1L                                                                                                     when Set Point change, the instrument is in alarm condition, the
                                                                                                                      alarm is not activated. It will be activated only when the process
                                                                                                                      value is in non-alarm conditions and then back in alarm conditions.
                                  ON            ON              time                 ON          ON            time
             OUT                                                       OUT                                            "AL1i" - ALARM ACTIVATION IN CASE OF MEASUREMENT
             AL1           off           off             off           AL1     off         off          off           ERROR: This allows one to establish how the alarm have behave
                                                                                                                      in the event of a measurement error (yES=alarm active; no=alarm
                                   LHAb                                               LHdE                            deactivated).
           "Ab1" - ALARM CONFIGURATION: This parameter can assume a
           value between 0 and 31.                                                                                    4.15 - HEATER BREAK ALARM FUNCTION (HB)
           The number to be set, which will correspond to the function                                                All the parameters referring to the Heater Break alarm function are
           desired, is obtained by adding the values reported in the following                                        contained in the group “]Hb”.
           descriptions :                                                                                             The Heater Break alarm function (Breakage of the heating element)
           ALARM BEHAVIOUR AT SWITCH ON: the alarm output may                                                         is only available when the instrument is equipped with the input
           behave in two different ways, depending on the value added to par.                                         (TAHB) to measure the current and if use a digital output to control
           “Ab1”.                                                                                                     the load.
           +0 = NORMAL BEHAVIOUR: The alarm is always activated when                                                  This input accepts signals coming from current transformers (TA)
           there are alarm conditions.                                                                                with max. output 50 mA.
           +1 = ALARM NOT ACTIVATED AT SWITCH ON: If, when switched                                                   The first operation to be carried out in order to obtain a correct
           on, the instrument is in alarm condition, the alarm is not activated.                                      current measurement, is to set the current that the instrument has
           It will be activated only when the process value is in non-alarm                                           to measure at the end of scale of the input TA (50 mA) on par.
           conditions and then back in alarm conditions.                                                              “IFS”.
                   P V
                                                                                                                                                   TLK 94
               A L1
                                                                                                                                           5b 6b             o u t 1 .rE G
                                                                                                              tim e
                                 O N                                           O N
                    + 0                               o ff                                       o ff
                                                                                                                                                                         KM
                   A b1                                                        O N
                    + 1                        o ff                                              o ff                  EH                             TA                        AC
                                                                                                                                                                              P ow er
           exemple with absolute low alarm                                                                                                                                    S u p p ly
           ALARM DELAY: the alarm output may behave in two different                                                       Load
           ways depending on the value added to par. “Ab1”.                                                           It is necessary to establish to which output the alarm has to
           +0 = ALARM NOT DELAYED: The alarm is immediately activated                                                 correspond.
           when the alarm condition occurs.                                                                           To do this it is necessary to set the parameter relative to the output
           +2 = ALARM DELAYED: When the alarm condition occurs, delay                                                 to be used (“O1F”, “O2F”, “O3F”, “O4F”, “O5F”, “O6F”) in the
           counting begins, as programmed on par. “AL1d” (expressed in                                                groups “]Out”, programming the parameter as :
                                       TECNOLOGIC spa - TLK 94 -OPERATING INSTRUCTIONS - Vr.01 - 01/10 - ISTR-MTLK94ENG1 - PAG. 10
Downloaded from www.Manualslib.com manuals search engine
           = ALno if the alarm output has to be active when the alarm is             To restore normal functioning after the alarm, select the control
           active while it is deactivated when the alarm is not active.              mode “OFF” and then re-program the automatic control (“rEG”)
           = ALnc if the alarm output has to be active when the alarm is not         after checking the correct functioning of probe and drive.
           active while it is deactivated when the alarm is active.                  To exclude the Loop Break alarm, set “OLbA” = OFF.
           Enter group “]Hb” and program which output the alarm signal has
           to address on parameter “OHb.                                             4.17 - FUNCTIONING OF KEY “U”
           The functioning mode of the alarm is instead defined on par.              The function of key “U” can be set through par. “USrb” contained
           “HbF” which can be set in the following way :                             in the group ““]PAn”.
           = 1 : The alarm is active when, with output 1rEG active, the current      The parameter can be programmed as :
           measured by the input TAHB is lower than the value programmed             = noF : no function
           on par. "IHbL" .                                                          = tunE : Pushing the key for 1 sec. at least, it is possible to
           = 2 : The alarm is active when, with output 1rEG not active, the cur-     activate/deactivate Auto-tuning or Self-tuning
           rent measured by the input TAHB is higher than the value pro-             = OPLO : Pushing the key for 1 sec. at least, it is possible to swap
           grammed on par. "IHbH" .                                                  from automatic control (rEG) to manual one (OPLO) and vice
           = 3 : The alarm is active when, with output 1rEG active, the current      versa.
           measured by the input TAHB is lower than the value programmed             = Aac : Pushing the key for 1 sec. at least, it is possible to
           on par. "IHbL" or with output 1rEG not active, the current meas-          acknowledge the alarm. (see par. 4.14)
           ured by the input TAHB is higher than the value programmed on             = ASi : Pushing the key for 1 sec. at least, it is possible to
           par. "IHbH".                                                              acknowledge an active alarm (see par. 4.14)
           = 4 : The alarm is active when the current measured by the input           = CHSP : Pushing the key for 1 sec. at least, it is possible to select
           TAHB is lower than the value programmed on par. "IHbL" or the             one of the 4 pre-programmed Set Points on rotation.
           measured current is higher than the value programmed on par.              = OFF : Pushing the key for 1 sec. at least, it is possible to swap
           "IHbH", independently by the state of the output 1.rEG.                   from automatic control (rEG) to OFF control (OFF) and vice versa.
           On par. “IHbL” the value of the current normally absorbed by the
           load when output 1.rEG is active has to be set, while on par. “IHbH”      4.18 - DIGITAL INPUT
           the current normally absorbed by the load when output 1.rEG is not        The instrument is equipped with 2 digital inputs whose function can
           active.                                                                   be set by the parameter "diF" contained in the group “]InP”.
           The programming of these parameters has to be carried out while           The parameter can be programmed as:
           also considering the fluctuations of the net voltage to avoid             = noF : the input does not carry out any function
           undesired alarms.                                                         = AaC : By closing the contact connected to the digital input, it is
           With regards to the hysteresis of the HB alarm, this is automatically     possible to reset a memorised alarm (see par. 4.14)
           calculated by the instrument as 1% of the programmed thresholds.          = ASi: By closing the contact connected to the digital input, it is
           During functioning it is possible to visualize the current measured       possible to silence an active alarm (see par. 4.14)
           by the input TAHB when output 1rEG is activated, by pushing the           = HoLd: By closing the contact connected to the digital input the
           “DOWN” key and the current measured when output 1.rEG is deac-            measurement taken at that moment is blocked (N.B.: not the
           tivated, by pushing the “DOWN” and “U” keys at the same time.             reading on the display, therefore the indication may stabilise itself
           To exclude the Heater Break alarm it is enough to set “OHb” =             with a delay that is proportional to the measuring filter). With the
           OFF.                                                                      hold function turned on, the instrument carries out control
           Note : The HB current measurement is valid if the output 1rEG is          according to the memorised measurement. By opening the contact,
           activated (or deactivated) for 264 ms. at least.                          the instrument starts normal measurement acquisition once more.
           This means that, if the cycle time (“tcr1”) is = 1 sec, the HB alarm is   = OFF : When the instrument is in “rEG” status, by closing the
           able to intervene only when the output power is higher than 26,4%.        contact connected to the digital input, the instrument is placed in
                                                                                     OFF status. By reopening the contact, the instrument returns to the
           4.16 - LOOP BREAK ALARM FUNCTION                                          automatic control status “rEG”.
           All the parameters referring to the Loop Break alarm function are         = CHSP : by closing and reopening the contact connected to the
           contained in the group “]LbA”.                                            digital input, it is possible to select one of the 4 memorised set
           The Loop Break alarm is available on all the instruments, which           points in rotation.
           intervenes when, for any reason (short-circuit of a thermocouple,         = SP1.4 : The following combination of the connected contacts to
           thermocouple inversion, load interruption), the loop control is           the two digital entries allows the activation of one of the 4
           interrupted.                                                              memorized set points.
           First of all, it is necessary to establish to which output the alarm              DIG IN1                 DIG IN2             SET POINT
           has to correspond.                                                                   off                    off                  SP1
           To do this it is necessary to set the parameter relative to the output               on                     off                  SP2
           to be used (“O1F”, “O2F”, “O3F”, “O4F”, “O5F”, “O6F”) in the                         off                    on                   SP3
           groups “]Out ”, programming the parameter as :                                       on                     on                   SP4
           = ALno if the alarm output has to be ON when the alarm is active          The function can be activated using “nSP” = 4 , also, when it is acti-
           while it is OFF when the alarm is not active.                             vated, it disables the selection of the active set by the parameter
           = ALnc if the alarm output has to be ON when the alarm is not             “SPAt” and by the key U.
           active while it is OFF when the alarm is active.                          = HE.Co : by closing the contact connected to the digital input it is
           Enter group “]LbA” and program which output the alarm signal              possible to select as active the set point SP2 in “CooL” mode. Reo-
           has to be addressed to on par. “OLbA” .                                   pening the contact is select as active the set point SP1 in “HEAt”
           The Loop Break alarm is activated if the output power remains at          mode. This function is possible only when “nSP” = 2.
           the 100% of the value for the time programmed on par. "LbAt"
           (expressed in sec.).                                                      4.19 - RS 485 SERIAL INTERFACE
           To avoid false alarms, the value of this parameter has to be set          The instrument can be equipped with a RS 485 serial
           considering the time the plant takes to reach the Set point when          communication interface, by means of which it is possible to
           the measured value is a long distance from it (for example at the         connect the regulator with a net to which other instruments
           plant start-up).                                                          (regulators of PLC) are connected, all depending typically on a
           On alarm intervention, the instrument visualizes the message              personal computer used as plant supervisor. Using a personal
           “LbA” and behaves as in the case of a measurement error giving a          computer it is possible to acquire all the function information and to
           power output as programmed on par. “OPE” (programmable in                 program all the instrument’s configuration parameters. The
           the group “]InP”) .                                                       software protocol adopted for TLK94 is a MODBUS RTU type,
                          TECNOLOGIC spa - TLK 94 -OPERATING INSTRUCTIONS - Vr.01 - 01/10 - ISTR-MTLK94ENG1 - PAG. 11
Downloaded from www.Manualslib.com manuals search engine
           widely used in several PLC and supervision programs available on Instrument supplied from the device
           the market (protocol manual is available on request).
           The interface circuit allows the connection of up to 32 instruments
           on the same line.
           To maintain the line in rest conditions a 120 Ohm resistance (Rt)
           must be connected to the end of the line.
           The instrument is equipped with two terminals called A and B which
           have to be connected with all the namesake terminals of the net.
           For the wiring operation it is advisable to adopt a screened cable
           wired as in the drawing.
               HOST
              (PC/PLC)
                                               shield
                  A
                                                                                 Rt
                  B                                                          120 ohm
                GND
                                                                                                             SUPPLY
                                                                                                             ADAPTER
              RS485
              Interface
                             A   B   GND   A   B   GND         A   B   GND                        AC SUPPLY            12 VDC
                            3a 2a 1a     3a 2a 1a               3a 2a 1a
                                                                                 P.A.: For the instruments equipped with RS485 serial
                                                                                 communication, it’s indispensable that the parameter “PACS” is
                           TLK94 n.1    TLK94 n.2              TLK94 n.N         programmed = LorE.
           If the instrument is equipped with a serial interface, the parameters For additional info, please have a look at the A01 instruction
           to be programmed are the following, all present in the parameters manual.
           group “]SEr” :
           "Add" : Address of the station. Set a different number for each 5 - PROGRAMMABLE PARAMETERS TABLE
           station, from 1 to 255.
           "baud" : Transmission speed (baud-rate), programmable from Here following are described all the parameters available on the
           1200 to 38400 baud. All the stations have to have the same instrument. Some of them could be not present or because they
           transmission speed.                                                   are depending on the type of instrument or because they are
           "PACS" : Programming access. If programmed as "LoCL" this automatically disabled as unnecessary.
           means that the instrument is only programmable from the
                                                                                         ]
           keyboard, if programmed as "LorE" it is programmable both from Group “ SP” (parameters relative to the Set Point)
           the keyboards and serial line.                                           Par.            Description                Range         Def. Note
           If an attempt is made to enter the programming from the keyboard 1 nSP Numero Set point                               1÷4          1
           whilst a communication through the serial port is in progress the                 programmabili
           instrument will visualise "buSy" to indicate the busy state.           2 SPAt Set point Attivo                     1 ÷ nSP         1
                                                                                  3 SP1 Set Point 1                      SPLL ÷ SPHL          0
           4.20 - PARAMETERS CONFIGURATION BY “ A01”                              4 SP2 Set Point 2                      SPLL ÷ SPHL          0
           The instrument is equipped with a connector that allows the trans- 5 SP3 Set Point 3                          SPLL ÷ SPHL          0
           fer from and toward the instrument of the functioning parameters 6 SP4 Set Point 4                            SPLL ÷ SPHL          0
           through the device TECNOLOGIC A01 with 5 poles connector.              7 SPLL Set Point minimo               -1999 ÷ SPHL -1999
           This device it’s mainly useable for the serial programming of the
                                                                                  8 SPHL Set Point massimo               SPLL ÷ 9999 9999
           instruments which need to have the same parameters configuration                ]
           or to keep a copy of the programming of an instrument and allow its   Gruppo  “   InP”  (parametri relativi agli  ingressi)
           rapid retransmission. To use the device A01 it’s necessary that the      Par.            Descrizione                Range         Def. Note
           device or instrument are being supplied.                               9  HCFG    Input  type                    tc  / rtd  / I /  tc
           Instrument supplied and device not supplied                                                                      UoLt / SEr
                                                                                  10 SEnS Probe type:                             tc :        J
                                                                                             J=thermocoupled J           J/ CrAL/ S/ b/
                                                                                             CrAL=thermocoupled K E/ L/ n/ r/ t/ C/
                                                                                             S=thermocoupled S              Ir.J / Ir.CA
                                                                                             b=thermocoupled B                   rtd :
                                                                                             E=thermocoupled E           Pt1 / Ptc / ntc
                                  SUPPLY
                                                                                             n=thermocoupled N                     I:
                                                                                             r=thermocoupled R              0.20 / 4.20
                                                                                             t=thermocoupled T                 UoLt :
                                                                                             C=thermocoupled C            0.50 / 0.60 /
                                                                                             Ir.J=IR Sen. IRS J           12.60 / 0.5 /
                                                                                             Ir.CA=IR Sen. IRS K            1.5 / 0.10 /
                                                                                             Pt1=thermores. Pt100               2.10
                                                                                             0.50= 0..50 mV
                                                                                             0.60= 0..60 mV
                                                                                             12.60= 12..60 mV
                                                                                             Ptc= PTC KTY81-121
                                                                                             ntc= NTC 103-AT2
                                                                                             0.20= 0..20 mA
                                                                                             4.20= 4..20 mA
                                                                                             0.1= 0..1 V
                                                                                             0.5=0..5 V
                                                                                             1.5= 1..5 V
                                                                                             0.10= 0..10 V
                                                                                             2.10= 2..10 V
                          TECNOLOGIC spa - TLK 94 -OPERATING INSTRUCTIONS - Vr.01 - 01/10 - ISTR-MTLK94ENG1 - PAG. 12
Downloaded from www.Manualslib.com manuals search engine
            11 rEFL Reflection      coefficient 0.10 ÷ 1.00       1.00           29 Ao2F Functioning of output 2 1.rEG / 2.rEG         OFF
                    for IRS sensors                                                         if analogue type:          r.inP / r.Err
            12 SSC Low scale limit in case -1999 ÷ FSC             0                        see “Ao1F”                r.SP / r.SEr
                    of input with V / I                                                                                    OFF
                    signals                                                      30 Ao2L Minimum reference for -1999 ÷ Ao2H             0
            13 FSC High scale limit in case SSC ÷ 9999             0                        analogical output 2 for
                    of input with V / I                                                     signal retransmission
                    signals                                                      31 Ao2H Maximum reference for Ao2L ÷ 9999              0
            14 dP Number of decimal               tc/rtd :         0                        analogical output 2 for
                    figures                         0/1                                     signal retransmission
                                                UoLt / I / SEr:                  32 O3F Functioning of output 3: 1.rEG / 2.rEG         OFF
                                                   0÷3                                      see “O1F”                 ALno / ALnc
            15 Unit Temperature unit of           tc/rtd :         °C                                                   On / OFF
                    measurement                   °C / °F                        33 O4F Functioning of output 4: 1.rEG / 2.rEG         OFF
            16 FiL Input digital filter          0FF÷ 20.0         0.2                      see “O1F”                 ALno / ALnc
                                                    sec.                                                                On / OFF
                                                                                 34 O5F Functioning of output 5: 1.rEG / 2.rEG         OFF
           17 OFSt Measuring Offset              -1999 ÷ 9999       0                       see “O1F”                 ALno / ALnc
           18 rot Rotation             of    the 0.000 ÷ 2.000    1.000                                                 On / OFF
                      measuring straight line                                    35 O6F Functioning of output 6: 1.rEG / 2.rEG          On
           19 InE “OPE” functioning in OUr / Or / Ur              OUr                       see “O1F”                 ALno / ALnc
                      case of measuring error                                                                           On / OFF
                      OUr       = Over and                                       Group “ ] AL1” (parameters relative to alarm AL1)
                      under-range                                                   Par.           Description            Range        Def.    Note
                      Or = Over-range only                                       36 OAL1 Output where alarm            Out1 / Out2     Out2
                      Ur = Under-range only
                                                                                            AL1 is addressed          Out3 / Out4 /
           20 OPE Output power in case of -100 ÷ 100               0                                                  Out5 / Out6 /
                      measuring error                   %                                                                   OFF
           21 diF Digital input s function:       noF / AaC /     noF            37 AL1t Alarm AL1 type:               LoAb / HiAb     LoAb
                      noF = No Function           ASi / HoLd /                              LoAb= Absolute Low        LHAb / LodE
                      Aac= Reset Alarms          OFF / CHSP /                               HiAb= Absolute High       HidE / LHdE
                      latch                      SP1.4 /HE.Co                               LHAb= Absolute Band
                      ASi= Aknowledged                                                      LodE= Deviation Low
                      Alarms                                                                HidE= Deviation High
                      HoLd = Hold Measure                                                   LHdE= Deviation Band
                      OFF= Control OFF
                                                                                 38 Ab1 Alarm AL1 functioning:             0 ÷ 15        0
                      CHSP = Sel. Set Point                                                 +1 = not activated at
                      SP1.4 = Sel. SP1,2,3,4
                                                                                            power on
                      HE.Co = Sel. Heat-                                                    +2 = delayed
                      SP1/Cool -SP2
                                                                                            +4 = latch
           Group “ ] Out” (parameters relative to the outputs)                              +8 = aknowledged
              Par.            Description            Range         Def.   Note   39 AL1 Alarm AL1 threshold            AL1L÷ AL1H        0
           22 O1F Func. digital output 1 :       1.rEG / 2.rEG    1.rEG          40 AL1L Low threshold band -1999 ÷ AL1H               -1999
                      1.rEG= Control output 1 ALno / ALnc                                   alarm AL1 or Minimum
                      2.rEG= Control output 2 On / OFF                                      set alarm AL1 for high
                      ALno= Alarm Out nor-                                                  or low alarm
                      mally opened                                               41 AL1H High threshold band AL1L ÷ 9999               9999
                      ALnc= Alarm Out nor-                                                  alarm AL1 or Maximum
                      mally closed                                                          set alarm AL1 for high
                      On = Output on                                                        or low alarm
                      OFF= Output off                                            42 HAL1 Alarm AL1 hysteresis          OFF ÷ 9999        1
           23 Aor1 Beginning of output 1            0 / no_0       0
                                                                                 43 AL1d Activation delay of          OFF ÷ 9999        OFF
                      scale if analogical type
                                                                                            alarm AL1                       sec.
           24 Ao1F Functioning of output 1 1.rEG / 2.rEG          1.rEG
                                                                                 44 AL1i Alarm AL1 activation in         no / yES       no
                      if analogue type:           r.inP / r.Err
                                                                                            case of measuring error
                      1.rEG= Control output 1 r.SP / r.SEr
                      2.rEG= Control output 2         OFF                        Group “ ] AL2” (parameters relative to alarm AL2)
                      r.inP= measur. retrans.                                       Par.           Description            Range        Def.    Note
                      r.Err=error [SP-PV] retr.                                  45 OAL2 Output where alarm           Out1 / Out2      OFF
                      r.SP=Set Point retr.                                                  AL2 is addressed          Out3 / Out4 /
                      r.SEr=out by ser. com.                                                                          Out5 / Out6 /
                      OFF=no funct.                                                                                        OFF
           25 Ao1L Minimum reference for -1999 ÷ Ao1H              0             46 AL2t Alarm AL2 type:              LoAb / HiAb      LoAb
                      analogical output 1 for                                               see “AL1t”                LHAb / LodE
                      signal retransmission                                                                           HidE / LHdE
           26 Ao1H Maximum reference for Ao1L ÷ 9999               0             47 Ab2 Alarm AL2 functioning:            0 ÷ 15        0
                      analogical output 1 for                                               see “Ab1”
                      signal retransmission                                      48 AL2 Alarm AL2 threshold           AL2L÷ AL2H         0
           27 O2F Functioning of output 2 1.rEG / 2.rEG           OFF            49 AL2L Low threshold band -1999 ÷ AL2H               -1999
                      if digital type:            ALno / ALnc                               alarm AL2 or Minimum
                      see “O1F”                    On / OFF                                 set alarm AL2 for high
           28 Aor2 Beginning of output 2            0 / no_0       0                        or low alarm
                      scale if analogical type
                          TECNOLOGIC spa - TLK 94 -OPERATING INSTRUCTIONS - Vr.01 - 01/10 - ISTR-MTLK94ENG1 - PAG. 13
Downloaded from www.Manualslib.com manuals search engine
           50 AL2H High threshold band AL2L ÷ 9999 9999                                                             Out5 / Out6 /
                      alarm AL2 or Maximum                                                                              OFF
                      set alarm AL2 for high                                  75 IFS High scale limit for input 0.0 ÷ 100.0 100.0
                      or low alarm                                                       TA HB
           51 HAL2 Alarm AL2 hysteresis         OFF ÷ 9999      1             76 HbF HB Alarm function:              1/2/3/4           1
           52 AL2d Activation delay of          OFF ÷ 9999    OFF                        1= Min. 1.rEG on
                      alarm AL2                     sec.                                 2=Max. 1.rEG off
           53 AL2i Alarm AL2 activation in        no / yES     no                        3= Min. 1.rEG on and
                      case of measuring error                                            Max. 1.rEG off
           Group “ ] AL3” (parameters relative to alarm AL3)                             4= Max and Min.
              Par.          Description            Range      Def.     Note   77 IHbL Low alarm HB threshold 0.0 ÷ IFS                0.0
           54 OAL3 Output where alarm            Out1 / Out2 OFF                         (with Out 1.rEG ON)
                      AL3 is addressed          Out3 / Out4 /                 78 IHbH High          alarm      HB IHbL ÷ IFS 100.0
                                                Out5 / Out6 /                            threshold (with Out
                                                    OFF                                  1.rEG OFF)
           55 AL3t Alarm AL3 type:              LoAb / HiAb LoAb              Group “ ] rEG” (parameters relative to control)
                      see “AL1t”                LHAb / LodE                       Par.          Description             Range         Def. Note
                                                HidE / LHdE                    79 Cont Control type:                 Pid / On.FA       Pid
           56 Ab3 Alarm AL3 functioning:           0 ÷ 15       0                         Pid= PID                   On.FS / nr
                      see “Ab1”                                                           On.FA= ON/OFF asym.             3 Pt
           57 AL3 Alarm AL3 threshold           AL3L÷ AL3H      0                         On.FS= ON/OFF sym.
           58 AL3L Low threshold band -1999 ÷ AL3H -1999                                  nr= Neutral Zone
                      alarm AL3 or Minimum                                                3Pt= PID mot. act.
                      set alarm AL3 for high                                   80 Func Functioning mode              HEAt / CooL HEAt
                      or low alarm                                                        output 1.rEG
           59 AL3H High threshold band AL3L ÷ 9999 9999                        81 HSEt Hysteresis of ON/OFF            0 ÷ 9999         1
                      alarm AL3 or Maximum                                                control (or end Soft
                      set alarm AL3 for high                                              Start cycle threshold)
                      or low alarm                                             82 Auto Autotuning enable            -4 / -3 / -2 / -1   1
           60 HAL3 Alarm AL3 hysteresis         OFF ÷ 9999      1                         FAST (positive values),         0/
           61 AL3d Activation delay of          OFF ÷ 9999    OFF                         OSCILLATING                 1/2/3/4
                      alarm AL3                     sec.                                  (negative values)
           62 AL3i Alarm AL3 activation in        no / yES     no                         OFF = Not active
                      case of measuring error                                             1 = Start each power on
                                                                                          2= Start at first power
           Group “ ] AL4” (parameters relative to alarm AL4)
                                                                                          on
              Par.          Description            Range      Def.     Note               3= Start manually
           63 OAL4 Output where alarm            Out1 / Out2 OFF                          4= Start after Soft Start
                      AL4 is addressed          Out3 / Out4 /                             or Set change
                                                Out5 / Out6 /                  83 SELF Selftuning enable               no / yES         no
                                                    OFF
                                                                               84   Pb Proportional band               0 ÷ 9999         50
           64 AL4t Alarm AL4 type:              LoAb / HiAb LoAb
                                                                               85    Int Integral time               OFF ÷ 9999        200
                      see “AL1t”                LHAb / LodE
                                                                                                                          sec.
                                                HidE / LHdE
                                                                               86 dEr Derivative time                OFF÷ 9999          50
           65 Ab4 Alarm AL4 functioning:           0 ÷ 15       0
                                                                                                                          sec.
                      see “Ab1”
                                                                               87 FuOc Fuzzy overshoot control 0.00 ÷ 2.00             0.5
           66 AL4 Alarm AL4 threshold           AL4L÷ AL4H      0
                                                                               88 tcr1 Cycle time of output          0.1 ÷ 130.0      20.0
           67 AL4L Low threshold band -1999 ÷ AL4H -1999
                                                                                          1.rEG                           sec.
                      alarm AL4 or Minimum
                      set alarm AL4 for high                                   89 Prat Power ratio 2rEG/1rEG 0.01 ÷ 99.99 1.00
                      or low alarm                                             90 tcr2 Cycle time of 2.rEG           0.1 ÷ 130.0      10.0
           68 AL4H High threshold band AL4L ÷ 9999 9999                                                                   sec.
                      alarm AL4 or Maximum                                     91    rS   Manual reset              -100.0÷100.0    0.0
                      set alarm AL4 for high                                                                              %
                      or low alarm                                             92    tcor Time for motorised        4 ÷ 1000 sec.   4
           69 HAL4 Alarm AL4 hysteresis         OFF ÷ 9999      1                         actuator run
           70 AL4d Activation delay of          OFF ÷ 9999    OFF              93   SHrI Minimum value for          0.0 ÷ 10.0 %    0.0
                      alarm AL4                     sec.                                  motorised actuator
           71 AL4i Alarm AL4 activation in        no / yES     no                         control
                      case of measuring error                                  94   PoSI Switch on position for        no /         no
           Group “ ] LbA” (parameters relative to Loop Break Alarm)                       motorised actuator      cLoS / oPEn
              Par.          Description            Range      Def.     Note    95   SLor Gradient of first ramp : 0.00 ÷ 99.99      InF
           72 OLbA Output where alarm            Out1 / Out2 OFF                          InF= Ramp not active         / InF
                      LbA is addressed          Out3 / Out4 /                                                       unit/min.
                                                Out5 / Out6 /                  96    dur.t Duration time between 0.00 ÷ 99.59       InF
                                                    OFF                                    two ramps                   / InF
           73 LbAt Time necessary to acti- OFF ÷ 9999         OFF                          InF= Time not active      hrs.-min.
                      vate alarm LbA                sec.                       97   SLoF Gradient of second       0.00 ÷ 99.99      InF
           Group “ ] Hb” (parameters relative to Heater Break Alarm)                       ramp:                      / InF
              Par.          Description            Range      Def.     Note                InF= Ramp not active     unit / min.
           74 OHb Output where alarm HB Out1 / Out2 OFF                        98   ro1.L Minimum       power   in 0 ÷ ro1.H        0
                      is addressed              Out3 / Out4 /                              output from 1.rEG             %
                          TECNOLOGIC spa - TLK 94 -OPERATING INSTRUCTIONS - Vr.01 - 01/10 - ISTR-MTLK94ENG1 - PAG. 14
Downloaded from www.Manualslib.com manuals search engine
             99 ro1.H Maximum power from            ro1.L ÷ 100    100                     LorE = Yes (Local and
                      output from 1.rEG                  %                                 remote progr.)
            100 ro2.L Minimum       power   in       0 ÷ ro2.H     0
                      output from 2.rEG                  %                     6 - PROBLEMS, MAINTENANCE AND GUARANTEE
            101 ro2.H Maximum power from            ro2.L ÷ 100    100
                      output from 2r.EG                  %                    6.1 - ERROR SIGNALLING
            102 OPS1 Power variation speed          1 ÷ 50 / InF   InF           Error            Reason                       Action
                      in output from 1.rEG            % / sec.
                                                                                 ----    Probe interrupted           Verify      the      correct
            103 OPS2 Power variation speed          1 ÷ 50 / InF   InF
                                                                                 uuuu    The measured variable       connection between probe
                      in output from 2.rEG            % / sec.
                                                                                         is under the probe’s        and instrument and then
            104 thr1 Split Range Power             -100 ÷ 100 %    0                                                 verify      the      correct
                      threshold      of output                                           limits (under-range)
                                                                                 oooo    The measured variable       functioning of the probe
                      1.rEG
            105 thr2 Split Range Power             -100 ÷ 100 %    0                     is over the probe’s
                      threshold      of output                                           limits (over-range)
                      2.rEG                                                      ErAt    FAST Autotuning not         Push key “P” in order to
            106 St.P Soft-Start power            -100 ÷ 100 %      0                     possible because the        make the error message
            107 SSt Soft-Start time                  OFF /        OFF                    process value is too        disappear. Once the error
                                                   0.1÷7.59                              higher or too lower         has been found, try to
                                                      / InF                                                          repeat the auto-tuning.
                                                    hrs.-min.                    noAt     Auto-tuning         not    Check the functioning of
           Group “ ] PAn” (parameters relative to the user interface)                     finished    within   12    probe and actuator and try
              Par.            Description            Range        Def. Note               hours                      to repeat the auto-tuning.
           108 USrb Functioning of key “U” : noF / tunE /         noF            LbA      Loop             control   Check the working of
                       noF = No Function         OPLO / Aac /                             interrupted                probe and actuator and
                       tune= Start Autotuning ASi / CHSP /                                (Loop break alarm)         swap the instrument to
                       or Selftuning                  OFF                                                            (rEG) control
                       OPLO= Manual Control                                      ErEP      Possible anomaly of       Push key “P”
                       (open loop)                                                         the EEPROM memory
                       Aac= Reset        Alarms                               In error conditions, the instrument provides an output power as
                       latch                                                  programmed on par “OPE” and activates the desired alarms, if the
                       ASi=        Aknowledged                                relative parameters “ALni” have been programmed = yES.
                       Alarms
                       OFF= Control OFF                                       6.2 - CLEANING
           109 diSP Variable visualized on OFF / Pou / SP.F                   We recommend cleaning of the instrument with a slightly wet cloth
                       the display SV:           SP.F / SP.o /                using water and not abrasive cleaners or solvents which may
                       OFF= Display OFF           AL1 / AL2 /                 damage the instrument.
                       Pou= Control Power          AL3 / AL4
                       SP.F= Active Set Value                                 6.3 - GUARANTEE AND REPAIRS
                       SP.o = Operative Set                                   The instrument is under warranty against manufacturing flaws or
                       value                                                  faulty material, that are found within 12 months from delivery date.
                       AL1 = AL1 threshold                                    The guarantee is limited to repairs or to the replacement of the
                       AL2 = AL2 threshold                                    instrument.
                       AL3 = AL3 threshold                                    The eventual opening of the housing, the violation of the instrument
                       AL4 = AL4 threshold                                    or the improper use and installation of the product will bring about
           110 Edit Fast progr. Active Set SE / AE /              SAE         the immediate withdrawal of the warranty’s effects.
                       and alarms:                SAE / SAnE                  In the event of a faulty instrument, either within the period of
                       SE= Active Set can be                                  warranty, or further to its expiry, please contact our sales
                       modified     while    the                              department to obtain authorisation for sending the instrument to
                       alarm thresholds can-                                  our company.
                       not be modified                                        The faulty product must be shipped to TECNOLOGIC with a
                       AE= Active Set cannot                                  detailed description of the faults found, without any fees or charge
                       be modified while the                                  for Tecnologic, except in the event of alternative agreements.
                       alarm thresholds can
                       be modified                                             7 - TECHNICAL DATA
                       SAE= Active Set and
                       alarm thresholds can
                                                                              7.1 - ELECTRICAL DATA
                       be modified
                                                                              Power supply: 24 VAC/VDC, 100... 240 VAC +/- 10%
                       SAnE= Active Set and
                                                                              Frequency AC: 50/60 Hz
                       alarm thresholds can-
                                                                              Power consumption: 10 VA approx.
                       not be modified
                                                                              Input/s: 1 input for temperature probes: tc J,K,S,B,C,E,L,N, R,T; in-
           Group “ ] SEr” (parameters relative to the serial communication)   frared sensors TECNOLOGIC IRS J and K range A ; RTD Pt 100
              Par.            Description            Range        Def. Note   IEC; PTC KTY 81-121 (990 Ω @ 25 °C); NTC 103AT-2 (10KΩ @
           111 Add Station address in case          0 … 255        1          25 °C) or mV signals 0...50 mV, 0...60 mV, 12 ...60 mV or
                       of serial communication                                normalized signals 0/4...20 mA, 0/1...5 V , 0/2...10 V.
           112 baud Transmission          speed 1200 / 2400 / 9600            1 input for current transformer (50 mA max.)
                       (Baud rate)               9600 / 19.2 /                2 digital inputs for free voltage contact
                                                       38.4                   Impedance normalized signals input: 0/4..20 mA: 51 Ω;
           113 PACS Access at the                 LoCL / LorE LorE            mV and V: 1 M Ω
                       programming through                                    Output/s: Up to 6 digital outputs. OUT1: SPST-NO (6 A-AC1, 3 A-
                       serial port:                                           AC3 / 250 VAC), OUT2,3,4,5:SPST-NO (4 A-AC1, 2 A-AC3 / 250
                       LoCL = No (Local only)                                 VAC),or in tension to drive SSR (12 VDC / 20 mA).
                          TECNOLOGIC spa - TLK 94 -OPERATING INSTRUCTIONS - Vr.01 - 01/10 - ISTR-MTLK94ENG1 - PAG. 15
Downloaded from www.Manualslib.com manuals search engine
           Up to 2 analogue outputs: 0/4 ..20 mA (Load Max. 300 Ω) or 0/2                                          PANEL + GASKET
           ..10 V.                                                                                                     MAX. 8 mm
           Auxiliary supply output / OUT6: 12 VDC / 20 mA Max.                                                                                       BRACKETS
           Electrical life for relay outputs: 100000 operat.
           Installation category: II
           Measurement category: I
           Protection class against electric shock: Class II for Front panel
           Insulation: Reinforced insulation between the low voltage section
           (supply and relay outputs) and the front panel; Reinforced
           insulation between the low voltage section (supply and relay
           outputs) and the extra low voltage section (inputs, analogue
           outputs, SSR outputs); analogue and SSR outputs optoisolated
           respect to the input. 50 V insulation between RS485 and extra low
           voltage section.
           7.2 - MECHANICAL DATA
           Housing: Self-extinguishing plastic, UL 94 V0
           Dimensions: 48 x 96 mm DIN, depth 98 mm
           Weight: 260 g approx.
           Mounting: Flush in panel in 45 x 92 mm hole
           Connections: 2 x 1 mm 2 screw terminals block
           Degree of front panel protection : IP 54 mounted in panel with 7.4 - FUNCTIONAL FEATURES
           gasket                                                         Control: ON/OFF, single and double action PID, PID for motorized
           Pollution situation: 2                                         actuators with time positioning
           Operating temperature: 0 ... 50 °C                             Measurement range: according to the used probe (see range table)
           Operating humidity: 30 ... 95 RH% without condensation         Display resolution: according to the probe used 1/0,1/0,01/0,001
           Storage temperature: -10 ... +60 °C                            Overall accuracy: +/- (0,2 % fs + 1 digit); PTC/NTC: +/- (0,5 % fs +
                                                                          1 digit)
           7.3 - MECHANICAL DIMENSIONS, PANEL CUT-OUT AND Max. cold junction compensation drift (in tc) : 0,04 °C/°C with
           MOUNTING [mm]                                                  operating temperature 0 ... 50 °C after warm-up of 20 min.
                         48           10                                  Sampling rate: 130 ms.
                                                        97,5
                                                                          Serial Interface : RS485 insulated
                                                                          Communication protocol: MODBUS RTU (JBUS)
                                                                          Baud rate: Programmable from 1200 ... 38400 baud
                       Out1 Out2 Out3 Out4 Out5
                                                                          Display: Display: 4 digit, 1 Red (PV) h 10mm and 1 green (SV), h
                  PV
                                                        TUN
                                                                          7,5 mm
                                                                          Compliance: ECC directive EMC 2004/108/CE (EN 61326), ECC
                  SV
                                                        SET
                                                                          directive LV 2006/95/CE (EN 61010-1).
                                                                        89,5
            96
                       Out6
                                                                                               7.5 - MEASURING RANGE TABLE
                                                                                                       INPUT          “dP” = 0                   “dP”= 1, 2, 3
                                                                                                       tc J                 -160 ... 1000 °C    -160.0 ... 999.9 °C
                                                                                                   “HCFG” = tc              - 256 ... 1832 °F   -199.9 ... 999.9 °F
                                                                                                    “SEnS” = J
                                               TLK 94                                                  tc K                 -100 ... 1370 °C    -100.0 ... 999.9 °C
                                                                                                   “HCFG” = tc              - 148 ... 2498 °F   -148.0 ... 999.9 °F
                                                                                                  “SEnS” = CrAl
                                                                               min. 10 mm              tc S                   0 ... 1760 °C      0.0 ... 999.9 °C
                                                                                                   “HCFG” = tc                32 ... 3200 °F     32.0 ... 999.9 °F
                                                                                                   “SEnS” = S
                                                                                                       tc B                  72 ... 1820 °C     72.0 ... 999.9 °C
                                                                   45
                                                                                                   “HCFG” = tc               162 ... 3308 °F    162.0 ... 999.9 °F
                                                                                                   “SEnS” = b
                                                                                                        tc E                  -150 ... 750 °C   -150.0 ... 750.0 °C
                                                                                                   “HCFG” = tc               -252 ... 1382 °F   -199.9 ... 999.9 °F
                                                              92
                                                                                                   “SEnS” = E
                                                                                                        tc L                  -150 ... 900 °C   -150.0 ... 900.0 °C
                                                                                                   “HCFG” = tc               -252 ... 1652 °F   -199.9 ... 999.9 °F
                                                                                                   “SEnS” = L
                                                                                                       tc N                  -250 ... 1300 °C   -199.9 ... 999.9 °C
                                                                                                   “HCFG” = tc               -418 ... 2372 °F   -199.9 ... 999.9 °F
                                                                                                   “SEnS” = n
                                  min. 20 mm
                                                                                                       tc R                  -50 ... 1760 °C    -50.0 ... 999.9 °C
                                                                                                   “HCFG” = tc               -58 ... 3200 °F    -58.0 ... 999.9 °F
                                                                                                    “SEnS” = r
                                                                                                        tc T                 -250 ... 400 °C    -199.9 ... 400.0 °C
                                                                                RECOMMENDED        “HCFG” = tc               -418 ... 752 °F    -199.9 ... 752.0 °F
                                                                                PANEL CUTOUT        “SEnS” = t
                                                                                                       tc C                   0 ... 2320 °C      0.0 ... 999.9 °C
                                                                                                   “HCFG” = tc                32 ... 4208 °F     32.0 ... 999.9 °F
                                                                                                   “SEnS” = C
                                                                                                  IRS range “A”               -46 ... 785 °C    -46.0 ... 785.0 °C
                                                                                                   “HCFG” = tc               -50 ... 1445 °F    -50.8 ... 999.9 °F
                                                                                                “SEnS”= Ir.J - Ir.CA
                                     TECNOLOGIC spa - TLK 94 -OPERATING INSTRUCTIONS - Vr.01 - 01/10 - ISTR-MTLK94ENG1 - PAG. 16
Downloaded from www.Manualslib.com manuals search engine
                 Pt100 (IEC)            -200 ... 850 °C    -199.9 ... 850.0 °C   - = (No OUT4)
                “HCFG” = rtd           -328 ... 1562 °F    -199.9 ... 999.9 °F
                “SEnS” = Pt1                                                     f : OUTPUT OUT5
               PTC (KTY81-121)          -55 ... 150 °C     -55.0 ... 150.0 °C    R = OUT5 Relay
                “HCFG” = rtd            -67 ... 302 °F      -67.0 ...302.0 °F    O = OUT5 VDC for SSR
                “SEnS” = Ptc
                NTC (103-AT2)           -50 ... 110 °C     -50.0 ... 110.0 °C    - = (No OUT5)
                “HCFG” = rtd            -58 ... 230 °F     -58.0 ... 230.0 °F
                “SEnS” = ntc                                                     g    :   COMMUNICATION         INTERFACE       AND      CURRENT
                  0..20 mA                                  -199.9 ... 999.9     TRANSFORMER INPUT
                 “HCFG” = I             -1999 ... 9999      -19.99 ... 99.99     S = RS 485 Serial interface
                “SEnS” = 0.20                                                    H = Current Trasformer input
                                                            -1.999 ... 9.999
                                                                                 T =RS 485 Serial interface + Current Trasformer input
                  4..20 mA                                  -199.9 ... 999.9     - = (No RS485, No TA in)
                 “HCFG” = I             -1999 ... 9999      -19.99 ... 99.99
                “SEnS” = 4.20
                                                            -1.999 ... 9.999     h, i, j : INTERNAL CODES
                  0 ... 50 mV                               -199.9 ... 999.9
                “HCFG” = UoLt                                                    kk, ll : SPECIAL CODES
                                        -1999 ... 9999      -19.99 ... 99.99
                 “SEnS” = 0.50
                                                            -1.999 ... 9.999
                                                                                 m : SPECIAL VERSION
                   0 ... 60 mV                              -199.9 ... 999.9
                “HCFG” = UoLt           -1999 ... 9999      -19.99 ... 99.99     P.A. : The outputs OUT 4, 5 must be the same type (Relay or VDC
                 “SEnS” = 0.60                                                   for SSR)
                                                            -1.999 ... 9.999
                  12 ... 60 mV                              -199.9 ... 999.9
                “HCFG” = UoLt
                                                                                 TLK 94 PASSWORD = 381
                                        -1999 ... 9999      -19.99 ... 99.99
                “SEnS” = 12.60
                                                            -1.999 ... 9.999
                   0 ... 5 V                                -199.9 ... 999.9
                “HCFG” = UoLt           -1999 ... 9999      -19.99 ... 99.99
                 “SEnS” = 0.5
                                                            -1.999 ... 9.999
                   1 ... 5 V                                -199.9 ... 999.9
                “HCFG” = UoLt           -1999 ... 9999      -19.99 ... 99.99
                 “SEnS” = 1.5
                                                            -1.999 ... 9.999
                   0 ... 10 V                               -199.9 ... 999.9
                “HCFG” = UoLt           -1999 ... 9999      -19.99 ... 99.99
                 “SEnS” = 0.10
                                                            -1.999 ... 9.999
                   2 ... 10 V                               -199.9 ... 999.9
                “HCFG” = UoLt           -1999 ... 9999      -19.99 ... 99.99
                 “SEnS” = 2.10
                                                            -1.999 ... 9.999
           7.6 - INSTRUMENT ORDERING CODE
           TLK94 a b c d e f g h i j kk ll m
           a : POWER SUPPLY
           L = 24 VAC/VDC
           H = 100 ... 240 VAC
           b : OUTPUT OUT1
           R = OUT1 Relay
           O = OUT1 VDC for SSR
           I = OUT1 analog. 0/4 ..20 mA
           V = OUT1 analog. 0/2 .. 10 V
           c : OUTPUT OUT2
           R = OUT2 Relay
           O = OUT2 VDC for SSR
           I = OUT1 analog. 0/4 ..20 mA
           V = OUT1 analog. 0/2 .. 10 V
           - = (No OUT2)
           d : OUTPUT OUT3
           R = OUT3 Relay
           O = OUT3 VDC for SSR
           - = (No OUT3)
           e : OUTPUT OUT4
           R = OUT4 Relay
           O = OUT4 VDC for SSR
                          TECNOLOGIC spa - TLK 94 -OPERATING INSTRUCTIONS - Vr.01 - 01/10 - ISTR-MTLK94ENG1 - PAG. 17
Downloaded from www.Manualslib.com manuals search engine