DATASHEET
EtherNet/IP™ to PROFINET®
                                                                          Gateway for dual subnets
                                                                                       PLX32-EIP-PND
The EtherNet/IP to PROFINET device gateway offers bi-directional data
transfers between a PROFINET Controller and EtherNet/IP networks. The
PLX32-EIP-PND gateway is a stand-alone DIN-rail mounted unit that provides
two Ethernet ports, with each port using a different subnet.
The onboard SD Card slot (SD card optional) is used for storing configuration
files that can be used for recovery, transferring the configuration to another
gateway, or general configuration backup. The EtherNet/IP Driver uses Class 1
I/O connections or Class 3 Message instructions. The PROFINET driver
operates as a PROFINET Class A device.
Features
   ODVA Approved
   PROFINET v2 certification with PROFINET Class A compliance
   EtherNet/IP and PROFINET certifications ensure the device is compatible with their respective network
   Field-tested with multiple PROFINET controllers from multiple vendors
   Remotely view and diagnose EtherNet/IP and PROFINET networks
   Embedded EDS AOP provided to allow for seamless integration to Studio 5000 and RSLogix 5000
   Using EtherNet/IP I/O connections, no ladder programming is required
   Multiple I/O connections to allow for increased throughput
   Video setup tutorial provided on www.prosoft-technology.com
   Secure module configuration via module switch (v1.04 and greater) 
   Up to 10,000 16-bit registers can be used to exchange large amounts of data
EtherNet/IP™ Specifications
Specification                 Description
Number of Class 3 Server      5
Connections
Supported PLC Types           PLC2, PLC5, SLC, CLX, CMPLX, MICROLX
Supported Message Types       PCCC and CIP
Class 3 Client Connections    Connected: 2
                              Unconnected: 1
Number of Class 1 I/O         8                                                         Where Automation
Connections
I/O connection sizes in/out   496/496 bytes
                                                                                        Connects™
Max RPI time                  5 ms per connection
CIP Services Supported        0x4C - CIP Data Table Read
                              0x4D - CIP Data Table Write                               Global Distribution
Command List                  Support for 100 commands per Client, each
                                                                                        ProSoft Technology® products are
                              configurable for command type, IP address, register
                                                                                        distributed and supported worldwide
                              to/from addressing and word/bit count.
                                                                                        through a network of over 500
Command Sets                  PLC-2/PLC-3/PLC5 Basic Command Set
                                                                                        distributors in over 50 countries.
                              PLC5 Binary Command Set
                                                                                        Our knowledgeable distributors are
                              PLC5 ASCII Command Set
                                                                                        familiar with your application needs.
                              SLC500 Command Set
                                                                                        For a complete list of distributors,
                                                                                        go to our website at:
PROFINET Specifications                                                                 www.prosoft-technology.com
Specification                 Description
Driver Type                   Class A Device
PROFINET I/O Data             1440 bytes IN, 1440 bytes OUT
                                                                                        Ordering Information
Exchange Types                Cyclic Real-time (RT) and Acyclic Data
                                                                                        To order this product, please use the
Hardware Specifications                                                                 following:
Specification                 Description
Power Supply                  24 VDC nominal                                            EtherNet/IP™ to
                              10 to 36 VDC allowed
                              Positive, Negative, GND Terminals                         PROFINET® Device
Current Load                  24 VDC nominal @ 300 mA                                   Gateway for dual subnets
                              10 to 36 VDC @ 610 mA maximum
Operating Temperature         -25°C to 70°C (-13°F to 158°F)                            PLX32-EIP-PND
Storage Temperature           -40°C to 80°C (-40°F to 176°F)
Relative Humidity             5% to 95% RH with no condensation
                                                                                        To place an order, please contact
Shock                         IEC 60068-2-27; 15G @ 11ms, 3-Axis (Operational)          your local ProSoft Technology
                              IEC 60068-2-27; 30G @ 18ms, 3-Axis (Non-Operation)        distributor. For a list of ProSoft
Vibration                     IEC 60068-2-6; 5G @ 10Hz to 150Hz                         Technology distributors near you,
Dimensions                    5.38 x 1.99 x 4.38 in                                     go to:
(H x W x D)                   13.67 x 5.05 x 11.13 cm                                   www.prosoft-technology.com
Ethernet Ports (2)            10/100Mbit full- and half-duplex RJ45 Connector           and select Where to Buy from the
                              Electrical Isolation 1500 Vrms at 50 Hz to 60 Hz for 60   menu.
                              seconds, applied as specified in section 5.3.2 of IEC
                              60950: 1991
                              Ethernet Broadcast Storm Resiliency = less than or
                              equal to 5000 [ARP] frames-per-second and less than
                              or equal to 5 minutes duration
Shipped With Each Unit        2.5 mm screwdriver
                              J180 Power Connector
Agency Approvals and Certifications
Please visit our website: www.prosoft-technology.com
                                                                                        Copyright © 2022 ProSoft Technology, Inc.
                                                                                        All Rights Reserved. 7/22/2022
                                                                                        For Public Use.
                                                                                        Specifications subject to change without notice.