MORLEY LITE
FIRE ALARM CONTROL
Honeywell Morley Lite is a Compact, High Performance, Feature
enriched Fire Alarm Control Panel designed to meet the Fire Detection
Addressability.
Honeywell Morley-Lite Fire Detection Control Panel series is ideally
suited for Small to Medium Sized Buildings, Residential Complexes,
Banks, Healthcare, Restaurants, Retail Stores etc. Morley Lite panels
communicates via LiteSpeedTM protocol with Morley Lite detectors and
devices.
Morley Lite Panel is built with Combination of quick installation, enhanced
feature set and advanced programming which allows installer to meet
demands of the end user with flexibility in configuration. Equipped with
configurable remote monitoring inputs, programmable relays, delay
setting for alarm verification, software isolation of class B circuit and NAC
outputs, mapping of NAC to specific class B circuits, password protections
etc.
End users get clear visible indications, easy to operate functions
to activate the control buttons, customizable class B circuit text via text
inserts to meet building naming conventions. Reliable and trouble free
system built as per latest safety standards of industry which ensures
system is safe and protected. Internal memory lock feature to restrict
changes to fire panel configuration by any intruder without key lock.
FEATURES
Display: 16 X 4 Char LCD Screen.
Control Keys: Silence Buzzer, Silence/Resound Alarm, Reset, Evaluate, Accept delay. Indicators: Fault, NAC
Fault, Earth Fault, Fire, Power, System Fault.
USER INTERFACE
• 16* 4 Char LCD display, Aesthetically • Staged Delay configuration for alarm
designed front facia • Fire, Fault, Configurable Relay verification
• Individual Class B Circuit Isolation • Circuit wise NAC configuratio n • Engineering Mute Configuration
• Battery Charging/Battery Internal
• Customizable text inserts • NAC Enable/Disable facility
Resistance Monitoring
• Programmable input for remote reset/ • Monitored NAC and Class B Circuit for Open/
• Aux output facility
evacuate/alert/fire Short/Faults
• PC tool for advanced configuration • On board memory lock switch to prevent
• Event Logging needs/ Event exploring unauthorized panel configuration changes.
• Configurable delays to output, with timer to fire
• Lamp Test Facility • One Man walk test facility
indication
• Upto 1000m cable connectivity per circuit, • Latching/Non-Latching configuration for fault for
• Detectors/MCPs in same circuit
Typically 20 Detectors per Class B Circuit+ 5 easy debugging
MCP's
• Data/Time/Password configuration • Earth Fault Monitoring • Mechanical Keylock
• Separate configuration/user memories/system
• Certified for Safety standard IEC
fault, sound/ resound feature like EN 54-4 standard • CE certificate
62368-1:2018
MORLEY LITE FIRE ALARM CONTROL
WIRING DIAGRAM
EOL
2, 4, 6 & 8 Mechanical Specifications
Class B Dimensions (H X W X D) 360 X 422 X 122.8 mm (Front Facia), 360 X 380 X 92.3 mm
Detection (Back Box)
Circuits
EOL
Weight 5.8 Kg Approx. (No Battery Fitted)
Construction Powder coated Cold Rolled STEEL 1.2mm thick
Programmable Cable Entry 15 X 20mm Knockout
Input 1
Operating Temperature 0 to 49°C
**Programmable
Input 2 Relative Humidity 5% to 95% Non-Condensing
Sounder Electrical Specifications
EOL
Circuit 1 Operating Voltage 230V-AC +/- 20% Output current 2A maximum, Alarm Load
1A Maximum
Sounder
Circuit 2 EOL
Standby Batteries Minimum capacity 2 x 12 V 2.8Ah,
Maximum capacity 2 x 12 V 7 Ah
Auxiliary +24 Vdc
Power output 0 Vdc Detection Circuits 2, 4, 6, 8 Class B Circuit, Max 2mA per Detect or Circuit
Approved Detectors Honeywell Morley Lite Series
Fire Relay
Programmable Inputs Configurable (Alarm, Reset, Evacuate)
output
Programmable Input Extended closing contact
Fault Relay
output Trigger External Outputs Sounder Outputs:
• 2 monitored outputs
• 0.5 Amps per circuit
Auxiliary Output:
Programmable • 18.5 to +28.5 Vdc, 0.5 Amp. (max)
Relay output
Circuit diagram*
* Number of Programmable input might vary based on panel model, minimum 1 would be supported in all variants
check installation manual for all details
** Each panel would have minimum 1 programmable input. 2 programmable inputs are made available on special
request with prior confirmation.
COMPATIBLE DEVICES
Order Codes Description
HML/PSE Morley Lite Photo-Electric Smoke Detector
HML/PTSE Morley Lite Photo-Electric Smoke & Heat Detector
HML/RHSE Morley Lite Heat Detector
B/401 Plug-in detector base
MORLEY LITE FIRE ALARM CONTROL
ORDERING PART CODES
Order Codes Description
HML/100/2A Morley Lite 2 Circuit Class B Fire Alarm Control Panel
HML/100/4A Morley Lite 4 Circuit Class B Fire Alarm Control Panel
HML/100/6A Morley Lite 6 Circuit Class B Fire Alarm Control Panel
HML/100/8A Morley Lite 8 Circuit Class B Fire Alarm Control Panel
MCP2A/R470FF/01 System Sensor MCP Red W/O Back Box
MCP2A/R470SF/01 System Sensor MCP Red with Back Box
W1A-R470SF-K013-01 System Sensor WCP Red, Flexible Element
W1A-R470SG-K013-81 System Sensor Intrinsic WCP Red, Glass Element
SYS/HS System Sensor Horn cum Strobe, Wall, Red, Standard Candela
SYS/HS/C System Sensor Horn cum Strobe, Ceiling, Red, Standard Candela
SYS/ST System Sensor Strobe, Wall, Red, Multi Candela
SYS/ST/C System Sensor Strobe, Ceiling Mount, Red, Multi Candela
MHR/1 System Sensor Red Mini Horn, Red, UL certified
For more information,
https://honeywellbuildings.in
Call: 1-800-103-0339
Email: HBT-Indiabuildings@honeywell.com
Honeywell HBT India Buildings MORLEY LITE
Unitech Trade Center, 5th Floor, Sector-43, FIRE ALARM CONTROL
Block C, Sushant Lok Phase - I,
Gurgaon - 122 002