Bulletin 510 Rev.C Bulletin 510 Rev.
Model DDX Deluge Valves 4" (100 mm), 6" (150 mm) and 165 mm Sizes
Features
1. Differential-type, lightweight, dependable construction. 2. Easily trimmed for releasing by: Manual pull stations Wet pilot sprinklers Dry pilot actuators Solenoid valves 3. Drop in seat & clapper assembly simplifies maintenance. 4. Bronze seat with O-ring seals resists corrosion and leakage. 5. Pressure-actuated clapper facing provides dependable seal. 6. Reset externally. Cover removal is not required. 7. Grooved inlet and outlet connections. 8. Drain valve to drain standing water column. 9. Valve latches in open position. No pressure-operated relief valve is required. 10. Pressure rating of 250 psi (17,2 bar). Listings & Approvals
(Only when used with Reliables Trim Sets.) 1. Listed by Underwriters Laboratories, Inc. and UL certified for Canada (cULus). 2. Certified by Factory Mutual Approvals (FM).
The Reliable Model DDX Deluge Valve is a hydraulically operated, differential-type valve used to control the water supply to a deluge or preaction system. Deluge systems use open sprinklers or nozzles as discharge outlets in the fire area, while preaction systems use closed sprinklers or nozzles. Both systems use separate detection devices to control the operation of the Deluge Valve. Three simple trim arrangements allow for actuation of the Reliable Model DDX Deluge Valve by utilizing manual, hydraulic, pneumatic, or electrical devices. These devices include break glass stations, wet pilot sprinklers, dry pilot sprinklers, thermal detectors, and smoke detectors. The Reliable Model DDX Deluge Valve can be reset externally, without cover removal. This i s accomplished by pushing in and turning the external reset knob at the rear of the Deluge Valve (see Fig. 2).
Valve Operation The Reliable Model DDX Deluge Valve is shown in both closed and open positions in Fig. 3. In the closed position, the supply pressure acts on the underside of the clapper and also on the push rod through the push rod chambers inlet restriction. The resultant force due to the supply pressure acting on the push rod is multiplied by the mechanical advantage of the lever and is more than sufficient to hold the clapper closed against normal supply pressure surges.
Fig. 2
TheReliable AutomaticSprinkler Co., Inc., 525 North MacQuesten Parkway, Mount Vernon, New York10552
When a fire is detected, a releasing device vents the push rod chamber to atmosphere through the chambers outlet. Since the pressure cannot be replenished through the inlet restriction as rapidly as it is vented, the push rod chamber pressure falls instantaneously. When the push rod chamber pressure approaches approximately one-third of the supply pressure, the upward force of the supply pressure acting beneath the clapper overcomes the lever-applied force thereby opening the clapper. Once the clapper has opened, the lever acts as a latch, preventing the clapper from returning to the closed position. Water from the supply flows through the Deluge Valve into the system piping. Water also flows through the Deluge Valves alarm outlet to the alarm devices. After system shutdown, resetting the Model DDX Deluge Valve is quite simple. Doing so only requires pushing in and turning the reset knob at the rear of the valve (see Fig.2). The external reset feature of the Model DDX Deluge Valve provides a means for simple, economical system testing, which is one essential facet of a good maintenance program. The external reset feature does not, however, eliminate another important facet of good maintenance, namely, periodic cleaning and inspection of the internal valve parts. In the event that water builds up inside the valve due to condensate from the air supply system, or water left inside from valve system testing, a drain is available for venting. After closing the main supply valve, a small valve over the drain cup can be opened slightly until the water inside the valve body and the main pipe column has drained. Whenever ambient temperature conditions are high, the water temperature in the Model DDX Deluge Valves pushrod chamber could possibly increase, thereby increasing the pressure in the chamber to values
exceeding the rated pressure of the system. In an indoor installation where standard room temperatures are exceeded, a pressure relief kit may be needed. Pressure relief kit, P/N 6503050001, can be installed into the pushrod chambers releasing line to limit the pressure to 175 psi (12,1 bar). Reliable Model DDX Deluge Valves with associated trim sizes 4" (100 mm), 6" (150mm) and 165mm, are rated for use at a minimum water supply pressure of 20 psi (1,4 bar) and a maximum water supply pressure of 250 psi (17,2 bar). Water supplied to the inlet of the valve and to the push rod chamber must be maintained between 40F (4C) and 140F (60C). Detection and Actuation In general, the Reliable Model DDX Deluge Valve can be released by any Reliable UL Listed or FM Approved device that opens sufficiently to vent the push rod chamber in response to a fire. The releasing device is simply connected to the push rod chambers outlet. When the releasing device operates and vents the push rod chamber, the Deluge Valve opens. Typical releasing devices include hydraulic manual emergency stations, M odel F1-FTR Fixed Temperature Detectors on wet pilot lines, dry pilot actuators, and solenoid valves. Model F1-FTR Detectors perform both Deluge Valve releasing and fire detection functions with wet pilot lines. The use of a solenoid valve for Deluge Valve releasing enables various types of electrical fire detection devices to be used. Typical detection devices include electrical emergency pull stations, thermal detectors, and ionization or photoelectric smoke detectors. Electrical detection and releasing equipment used in Supertrol Electrical Systems is described in Bulletins 707 and 708, for both deluge and preaction systems.
Fig. 3
2.
Model DDX-LP Dry Pipe Valve Description
1. Rated working pressure: Valve & System - 250 psi (17.2 bar). 2. Factory tested to a hydrostatic pressure of 500 psi (34,5 bar). (Valve only) 3. End and trim connections: ANSI/AWWA C606 grooved inlet and outlet
Groove Dimensions Valve Size 4" (100 mm) 165 mm 6" (150 mm) Outlet Diameter 4.500" (114 mm) 6.500" (165 mm) 6.625" (168 mm) Groove Diameter 4.334" (110 mm) 6.330" (161 mm) 6.455" (164 mm) " (10 mm)
3 8
Groove Width
Outlet Face to Groove " (16 mm)
5 8
The Dry Pilot Trim (see Fig. 5) is used when dry pilot sprinklers are used as the fire detection means. This trim set includes the Model LP Dry Pilot Line Actuator, air and water pressure gauges, low air pressure switch (for Dry Pilot Line), air pressure relief valve, connections for the air supply and pilot sprinkler lines, a two-inch main drain, alarm test, push rod chamber connections, push rod chamber pressure gauge, and the Model B Hydraulic Manual Emergency Station. Table A provides the recommended air pressure when the dry pilot trim set is used as the actuation means.
Table A
Water Pressure psi (bar) Maximum 20 (1,4 ) 50 (3,4) 75 (5,2) 100 (6,9) 125 (8,6) 150 (10,3) 175 (12,1) 200 (13,8) 225 (15,5) 250 (17,2) Pneumatic Pressure to be Pumped into Sprinkler System, psi (bar) Not Less Than 10 (0,7) 12 (0,8) 13 (0,9) 15 (1,0) 16 (1,1) 17 (1,2) 18 (1,2) 19 (1,3) 21 (1,5) 22 (1,5) Not More Than 14 (0,9) 16 (1,1) 17 (1,2) 19 (1,3) 20 (1,4) 21 (1,4) 22 (1,5) 23 (1,6) 25 (1,7) 26 (1,8)
Threaded openings Per ANSI B 2.1 Valve Exterior's Color:
Valve Size 4" (100 mm) 6" (150 mm) 165 mm Color Black Red
4. Face to face dimensions: 4" (100 mm) 14" (355 mm) 6" (150 mm) & 165 mm 16" (406 mm) 5. Shipping weight:
Valve Size 4" (100 mm) 6" (150 mm) & 165 mm Weight 64 lb. (29 kg) 95 lb. (43 kg)
Note: During system set-up, a higher pneumatic pressure may be required in order to properly set the Model LP Dry Valve Actuator.
6. Friction loss (Expressed in equivalent length of Schedule 40 pipe, based on Hazen & Williams formula with C = 120 and a flow velocity of 15ft/sec (4.6 m/sec)):
Valve Size 4" (100 mm) 6" (150 mm) & 165 mm Equivalent Length 14' (4.27 m) 29.4' (9 m)
7. Installation position: Vertical
Trim Descriptions The trims for the Reliable Model DDX Deluge Valve are arranged for rapid, easy, and compact attachment, and serve as connection points to Reliable Model C Mechanical Alarms and other devices. The available Model DDX Deluge Valve trim sets are:
Wet Pilot Trim Dry Pilot Trim Electric Actuation Trim,
The Electric Actuation Trim (see Fig. 6) is used when electric detection and releasing are desired. This trim set includes a solenoid valve (175 psi (12,1 bar) or 250 psi (17, 2 bar) rated), two-inch main drain, alarm test supply pressure gauge, push rod chamber supply connections, push rod chamber pressure gauge, and the Model B Hydraulic Manual Emergency Station are also included. Detailed description of electrical operation can be found in Bulletins 707 and 708. The Model B Hydraulic Manual Emergency Station is a standard item in all trim sets. However, the Model A Hydraulic Manual Emergency Station, described in Bulletin 506, is also available as an option. All Model DDX Deluge Valves are listed by Underwriters Laboratories, Inc, and certified by UL for Canada (cULus) and certified by Factory Mutual A p p r o v a l s , o n l y wh e n u s e d w i t h t h e v a l v e manufacturers trim sets.
The Wet Pilot Trim (see Fig. 4) is used when wet pilot sprinklers or hydraulic manual emergency pull boxes are used for detection and releasing. This trim set provides a two-inch main drain, alarm test, supply pressure gauge, push rod chamber pressure gauge, push rod chamber supply connections, Model B Hydraulic Manual Emergency Station, and a connection for releasing devices. 3.
Fig. 4
4.
Fig. 5
5.
Fig. 6
6.
Ordering Information Specify:
Valve Model & Size 4" (100 mm) Model DDX Deluge Valve (P/N 6103040026), 6" (150 mm) Model DDX Deluge Valve (P/N 6103060024), 165mm Model DDX Deluge Valve (P/N 6103060028)
Trim Wet Pilot Trim, Dry Pilot Trim, or Electric Actuation Trim. Each trim set is available in individual parts, in time-saving, segmentally assembled kit forms, or fully assembled to the Model DDX Deluge Valve with or without a control valve). The Electric Actuation trim is available with a 175 psi (12,1 bar) or 250 psi (17,2 bar) rated solenoid valve.
Wet Pilot Line Deluge Trim Part Numbers Trim Configurations Fully Assembled to DDX Valve w/ Control Valve Fully Assembled to DDX Valve w/o Control Valve Segmentally Assembled (DDX Valve Sold Separately) Individual Parts (DDX Valve Sold Separately) For 4" (100 mm) Valve 6505040200 6505040201 For 6" (150 mm) Valve 6505060200 6505060201 6503001003 6503001002 For 165 mm Valve Not Available 6505065201
Dry Pilot Line Deluge Trim Part Numbers Trim Configurations UL/FM Approved Pressure Switch ULC Approved Pressure Switch For 4" (100 mm) Valve 6505040205 6505040206 For 6" (150 mm) Valve 6505060205 6505060206 6503001108 6503001107 6505060208 6505060209 6503001110 6503001109 For 165 mm Valve Not Available 6505065206
{ { { {
Fully Assembled to DDX Valve w/ Control Valve Fully Assembled to DDX Valve w/o Control Valve Segmentally Assembled (DDX Valve Sold Separately) Individual Parts (DDX Valve Sold Separately) Fully Assembled to DDX Valve w/Control Valve Fully Assembled to DDX Valve w/o Control Valve Segmentally Assembled (DDX Valve Sold Separately) Individual Parts (DDX Valve Sold Separately)
6505040208 6505040209
Not Available 6505065207
Electric Actuation Deluge Trim Part Numbers Trim Configurations 175 psi (12,1 bar) Rated Solenoid Valve 250 psi (17,2 bar) Rated Solenoid Valve Fully Assembled to DDX Valve w/ Control Valve Fully Assembled to DDX Valve w/o Control Valve Segmentally Assembled (DDX Valve Sold Separately) Individual Parts (DDX Valve Sold Separately) Fully Assembled to DDX Valve w/ Control Valve Fully Assembled to DDX Valve w/o Control Valve Segmentally Assembled (DDX Valve Sold Separately) Individual Parts (DDX Valve Sold Separately) For 4" (100 mm) Valve 6505040205 6505040206 For 6" (150 mm) Valve 6505060205 6505060206 6503001108 6503001107 6505060215 6505060216 6503001508 6503001506 For 165 mm Valve Not Available 6505065206
6505040215 6505040216
Not Available 6505065216
Note: For metric installations, a 2" NPT x R2. ISO 7/1 x Close Nipple (Reliable P/N 98543401) is sold separately as an adapter for the single drain outlet of the trims.
Additional equipment Air compressors, electric detection, actuation equipment, and mechanical sprinkler alarms must be ordered separately. These devices are described in Bulletin 707.
7.
Installation Dimensions in Inches (mm) Valve A
1 4
B
3
C
1 2
F 22 4 (578) 233 4 (603)
3
G 30 4 (781) 313 4 (806)
3
H 8 (216)
1 2
J 13 4 (349) 133 4 (349)
3
K 5 (140) 5 12 (140)
1 2
L 8 12 (216) 8 12 (216)
N 2 (64)
1 2
P 6 (159) 83 4 (222)
1 4
Q 12 (305) 12 12 (318)
R 11 14 (286) 12 14 (311)
5 6 4 4" (100mm) (133) (171) 6" 1 73 4 (150mm) 6 4 (159) (197) & 165mm
9 14 29 (241) (356) (737) 10 12 16 30 (267) (406) (767)
8 12 (216)
13 12 (343)
3 14 (83)
The equipment presented in this bulletin is to be installed in accordance with the latest pertinent Standards of the National Fire Protection Association, Factory Mutual Research Corporation, or other similar organizations and also with the provisions of governmental codes or ordinances whenever applicable. Products manufactured and distributed by Reliable have been protecting life and property for over 80 years, and are installed and serviced by the most highly qualified and reputable sprinkler contractors located throughout the United States, Canada and foreign countries.
Manufactured by The Reliable Automatic Sprinkler Co., Inc. (800) 4311588 (800) 8486051 (914) 6683470
www.reliablesprinkler.com
Sales Offices Sales Fax Corporate Offices Internet Address
Revisions indicate updated or new data.
EG. Printed in U.S.A. 2/06 P/N 9999970269