0% found this document useful (0 votes)
185 views3 pages

Datasheet Rectiverter 6

The document describes a Rectiverter power module that combines AC and DC power sources and provides both AC power for loads up to 6 kVA and DC power for battery charging up to 0.6 kW. It has a modular design and can provide backup power during mains outages from the battery. It is intended for use in marine and offshore applications.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
185 views3 pages

Datasheet Rectiverter 6

The document describes a Rectiverter power module that combines AC and DC power sources and provides both AC power for loads up to 6 kVA and DC power for battery charging up to 0.6 kW. It has a modular design and can provide backup power during mains outages from the battery. It is intended for use in marine and offshore applications.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 3

Rectiverter 6 kVA,

Marine UPS 1ph MB


The Rectiverter power module combines both AC and DC
feed into one common unit. Simultaneously it provides AC
backup power for 230 VAC or 115 VAC loads, and 48 VDC
power for battery charging.

AC and DC output limits can be set according to the


attached load, where the limitation for AC load is set to max
6 kVA with possibility to set recharge values for battery
banks up to max 0,6 kW

Rectiverter 6 kVA, Marine UPS 1ph MB


Up to 6 kVA AC & up to 0,6 kW 48 VDC output for battery charging
Doc CIER0418.DS3 – rev1

MODULAR ARCHITECTURE APPLICATIONS KEY FEATURES


RECTIVERTER MODULE MARINE  230 OR 115 VAC INPUT/OUTPUT
The 3 port converter simultaneously  DUAL A & B AC FEED
provides power for AC loads and battery  Communication onboard ships
charging. During mains outage the  Dynamic positioning  SINGLE PHASE INPUT/OUTPUT
Rectiverter 48/1200 HE feeds AC loads  Propulsion control  MAX 6 KVA AC OUTPUT
using energy stored in the battery.  Navigation  2 POLE AC DISTRIBUTION
 Ship identification  GROUND FAULT ALARM (RCR)
The modular architecture, industry-leading  Drilling systems
 BUILT IN MANUAL BYPASS SWITCH
efficiency, compact size, innovative design  Computer room
and comprehensive monitoring and control  BUILT IN TRANSFER TECHNOLOGY
 Public address and alarm
features provide significant benefits over  150% OVERLOAD CAPABILITY, 15S
the current industry standard.
 600% QUICK TRIP CURRENT, 20MS
OFFSHORE AND PROCESS INDUSTRY
 HOT PLUGGABLE
 Safety and Automation Systems  SMARTPACK 2 CONTROLLER
(SAS)
 DNV & ABS APPROVAL
 GLOBAL COMPLIANCE
 PATENTED HE TECHNOLOGY

Rectiverter Module

Eltek — Gråterudveien 8, PB 2340 Strømsø, 3003 Drammen, Norway Phone: +47 32 20 32 00 Eltek © 2016 – www.eltek.com
Rectiverter 6kVA Marine UPS
Doc CIER0418.DS3 – rev1
FRONT VIEW WITHOUT DOOR
MODEL 6 KVA / 3 KVA
Part number CIER0418.002/001
INPUT DATA
Voltage range AC 185-275 / 95-140 V
Voltage range DC 40-58 V
Maximum current AC 29 A
Frequency 47-53 / 57-63 Hz
Power factor > 0.99
OUTPUT DATA
Adjustable range AC 200-240 / 100-127 V
Adjustable range DC 43-58 V
Max output power AC 6,0 / 3,0 kVA
Max output power DC 0,6 / 0,3 kW
Power factor 0,8
Frequency 50Hz, 60 Hz
OTHER SPECIFICATIONS
Manual bypass switch 63 A
Dual single phase input A and B feed
AC Distribution, 2 pole breaker 12pc 6A C char.
Battery breaker, 2 pole 125 A ( Remote trip)
Ground fault alarm RCR
Rectiverter 6 kVA single phase marine UPS without door
Specifications are subject to change without notice

SINGLE LINE Specifications are subject to change without notice

Eltek — Gråterudveien 8, PB 2340 Strømsø, 3003 Drammen, Norway Phone: +47 32 20 32 00 Eltek © 2016 – www.eltek.com
Rectiverter 6kVA Marine UPS
Doc CIER0418.DS3 – rev1

Models / ordering information 6 KVA, 230 V 3KVA, 115 V


Part number CIER0418.002 CIER0418.001
AC OUTPUT DATA
Voltage (default) / (adjustable range)1) 230 VAC / 200 - 240 VAC 115 VAC / 100 - 127 VAC
Frequency (default inverter mode) 50Hz, 60Hz or last synced 50/60Hz (adaptive)
Frequency (set-able inverter mode) 50Hz, 60Hz or last synced 50/60Hz (adaptive)
Power maximum (continuous / overload (<15s) ) 4800 W (6000 VA) / 8000 VA 2400 W (3000VA) / 4000 VA
Current maximum (continuous / overload (<15s) ) 26ARMS / 34,8ARMS
Current (maximum) Quick trip (20ms) 120A (6 x nominal)
Hold up (Voltage dips) (before switching to battery) > 5 ms @ 4800W load > 5 ms @ 2400W load
THD < 1.5 % at resistive load
Fuse in L and N, Hot pluggable
Output features AC Distribution: 12x6 A, C characteristics 2 pole breaker
Ground fault alarm relay on AC output (Residual Current Relay)
DC OUTPUT FOR BATTERY CHARGING
Voltage (default) / (adjustable range) 53.5 VDC / 43 - 58 VDC
Power (maximum @nominal input) 600 W 300 W
Current (maximum @VOUT ≤ 48 VDC) 12,5 A 6,25 A
Hold up time, maximum output power >10ms; VOUT > 41 VDC
Short circuit proof, Over voltage Shutdown
Output features
1x 125 A, C characteristics 2 pole battery breaker with 24V external ESD trip
Extended battery kit PN: 350055 Additional 1*125 A, 2 pole battery breaker with battery looms
INPUT DATA
AC Mains Input Voltage (single phase) 185 - 275 VAC, 95 - 140 VAC
3)
AC Current (at nominal output voltage) 29 ARMS
Frequency (default: sync range) 47-53 & 57-63 Hz
Frequency (set-able: sync range) 47-53 Hz, 57-63 Hz or both (adaptive)
Power Factor / THD > 0.99 at 50% load or more / < 3.5%
DC Voltage nominal / extended range (no overload)2) 45 - 58 VDC / 40 - 45 VDC
DC Current (maximum) 128 A / 180A during overload (15s) 64 A / 90A during overload (15s)
Fuse in L and N, Hot pluggable, Varistor, Hot pluggable
Input features
Dual single phase input; A and B feed (changeover device controlled by feed A)

OTHER SPECIFICATION
Efficiency >96% (mains mode (AC/AC and AC/DC)), >94% (inverter mode (DC/AC))
Manual bypass switch 63 A (make before break)
Colour RAL 7035
Protection Class IP 33
Battery backup time (at maximum AC power) 30-60 min
Operating temperature -10 to +45°C (+14 to +113°F), humidity 5 - 95% RH non-condensing
Storage temperature -40 to +85°C (-40 to +185°F), humidity 0 - 99% RH non-condensing
Dimensions[WxDxH] / Weight 600 x 600 x 900mm (23,7 x 23,7 x 35,5”) / 70 kg (155 lbs)
DESIGN STANDARDS
Electrical safety EN 60950-1, EN 62040-1
ETSI EN 300 386 V.1.6.1, FCC CFR 47 Part 15
EMC
EN 61000-6-1/-2/-3/-4
ETSI EN 300 019: 2-1 (Class 1.2), 2-2 (Class 2.3) & 2-3 (Class 3.2)
Environment
RoHS (2011/65/EU) and WEEE (2002/96/EC) compliant
DNV-OS-D202, Ch.2 Sec. 4 (DNV 2.4)
o Temperature Cl. B
Approvals o Humidity Cl. B
o Vibration Cl. A
EMC Class A (pending approvals in next version EMC Class B & ABS)
1) Output voltage ranges configured in factory and have individual keying in top chassis 3) If DC voltage is pulled below 43V the input current may increase above this level
2) 40 - 45 VDC: reduced performance - no power boost and increased voltage THD on AC output.