Three Phase HT Smart Meter
Three Phase HT Smart Meter
TECHNICAL SPECIFICATION
Document Title Technical Specification of HT Consumer Smart Energy Meter
Document No. MMG-SMART - 005
Page 1 of 39
CONTENTS
1.0 SCOPE
7.0 TESTS
11.0 GUARANTEE
12.0 PACKING
13.0 SAMPLE
14.0 TRAINING
1 SCOPE This specification covers the technical requirements of design, manufacturing, testing at
meter manufacturer's works ,packing, forwarding, supply and unloading at store/site of
Three Phase Four Wire, HT (CT and VT operated) AC Static Smart Meters of accuracy
class 0.5s (here after referred as meters) complete with all accessories for efficient and
trouble free operation with communication module (NIC) compatible with 4G and fall back
to 2G technology.
It is not the intent to specify completely herein all the details of tech design and
construction of material. However, the material shall conform in all respects to high
standards of engineering, design and workmanship and shall be capable of
performing in continuous commercial operation in manner acceptable to the
TPCODL, who will interpret the meanings of drawings and specification and shall
have the power to reject any work or material which, in his judgment is not in
accordance therewith. The offered material shall be complete with all components
necessary for their effective and trouble free operation. Such components shall be
deemed to be within the scope of Bidder's supply irrespective of whether those are
specifically brought out in this specification and/or the commercial order or not.
2 APPLICABLE a. IS 16444 part 2: A.C. Static Transformer operated watt hour and VAR-
STANDARDS 2017 hour meters, class 0.2s, 0.5s & 1.0S (Smart Meters)
b. IS15959 Part3: Data exchange for electricity meter reading, tariff and
2017 load control
c. IS 14697 A.C. Static Transformer operated watt hour and VAR-
hour meters, class 0.2s, 0.5s & 1.0S
d. IEC 60687 AC Static Watthour Meters for active energy (class 0.2s
(1992-06) and 0.5s)
e. IS 9000 Basic Environmental testing procedure for electrical and
electronic items.
f. IS 12346: 1999 Testing Equipment For Ac Electrical Energy Meters
g. IS 11000 Fire Hazard Testing
h. IEC 62052 Part Electricity metering equipment (AC) - General
11 : 2003 requirements , tests and test conditions – metering
equipment
i. IEC 62053 Part Electricity metering equipment (a.c.) - Particular
22: 2003 Requirements - Part 22: Static meters for active energy
(classes 0,2 S and 0,5 S)
j. IS 15707: 2006 Testing Evaluation installation and maintenance of AC
Electricity Meters- Code of practice.
k. IEC 60068 Environmental testing.
l. CBIP–TR Specification for A.C. Static Electrical Energy Meters
No.325 (latest amendment)
m. CEA Regulation Installation and operation of meters
(2019)
n. IS 60529 Degree of protection provided by enclosure
o. IEC 62056-61 Electricity metering- Object Identification system (OBIS)
p. ASTM D648 Standard Test Method for Deflection Temperature of
Plastics Under Flexural Load in the Edgewise Position
q. IS 11731-1 Methods of test for determination of the flammability of
solid electrical insulating materials when exposed to an
igniting source, Part 1: Horizontal specimen method
r. IS 11731-2 Methods of Test for Determination of Flammability of
Solid Electrical Insulating Materials When Exposed to An
Igniting Source, Part 2: Vertical Specimen Method
s. ISO 75 Part Determination of temperature of deflection under load
1&2
TPCODL TP CENTRAL ODISHA DISTRIBUTION LIMITED
TECHNICAL SPECIFICATION
Document Title Technical Specification of HT Consumer Smart Energy Meter
Document No. MMG-SMART-005
Page 3 of 39
Current
4.10 Influence of heating Temperature rise at any point of the external surface
of the meter shall not exceed by more than 20K with
an ambient temperature at 450 C.
4.11 Rated Impulse 6 kV (shall be applied ten times with one polarity and
withstand then repeated with the other polarity and minimum
voltage time between each impulse to be 3 sec)
4.12 AC withstand
4 kV
Voltage for 1 min
4.13 Minimum Insulation
resistance at test
voltage 500+/- 50 V
dc
a)Between frame &
current ,voltage a) 5 M ohm
circuits as well as
auxiliary circuits
connected together:
b)Between each
current (or voltage b) 50 M ohm.
circuit) & each
and every other
circuit:
4.14 Mechanical Meter shall be in compliance with clause 12.3 of IS
requirements 14697& IS16444 part 2
4.15 Resistance to heat The terminal block and Meter case shall ensure safety
and fire against the spread of fire. They shall not be ignited by
thermal overload of live parts in contact with them as
per clause 6.8 of IS 14697. Fire retardant material
shall be used.
4.16 Protection against Degree of protection: IP 51 as per IS 12063/60529,
penetration of dust but Without suction in the meter. Meter shall comply
and water. with clause 6.9 and 12.5 of IS 14697
4.17 Resistance against Meter shall be in compliance with clause 12.6 of IS
Climatic influence. 14697.
4.18 Electromagnetic Meter shall be in compliance with clause CBIP report
Compatibility (EMC) 325 and IS
4.19 Accuracy Meter shall be in compliance with clause 11 of
requirements IS14697 & IS16444 part-2
4.20 Power factor range Zero lag to Zero lead. Meter shall be programed at
default Lag only configuration i.e. Lead to be treated
as unity for kVA & kVAh calculations’
4.21 Energy
Fundamental energy +Energy due to Harmonics
measurement
4.22 Connection The connection diagram for the system shall be
Diagram provided on terminal cover.
4.23 Self-Diagnostic The meter shall have logging with date and time in
feature memory for un satisfactory / non-functioning of
1. Real Time Clock
2. RTC battery
3. Non Volatile Memory
4. Status of NIC (installed/ discovered/ normal)/
Signal Strength
TPCODL TP CENTRAL ODISHA DISTRIBUTION LIMITED
TECHNICAL SPECIFICATION
Document Title Technical Specification of HT Consumer Smart Energy Meter
Document No. MMG-SMART-005
Page 5 of 39
4.24 Initial start-up of Meter shall be fully functional within 5 sec after
meter reference voltage is applied to the meter terminals (as
per clause 11.4.1 of IS 14697).
4.25 Alternate mode of In case of meter power failure, reading/data should be
supply to the meters retrieved with the help of battery or other power
source.
4.26 Internal diameter of 5 mm ( minimum )
the terminal holes:
Depth of the 20 mm (minimum)
terminal holes:
4.27 Clearance between 10 mm ( minimum)
adjacent terminals
4.28 Display Backlit LCD, Scrolling, 10 seconds for each
parameter minimum 8 digits for reading LCD display
4.29 Security feature Programmable facility to restrict the access to the
information recorded at different security level such
as read communication, write communication,
firmware selection from remote etc.
4.31 Software and The bidder shall supply software required for local
communication HHU & remote (AMI) connectivity including required
compatibility training to use the software free of cost. If this
software can be used in a device readily available in
market and can connect to meter through optical port
or other communication port without any security
checks or with MR securities which OEM will provide;
then, OEM can provide only software, else the device
on which this software will run is also to be provided
along with technical specification of this device.
4.32 Calibration Meters shall be software calibrated at factory and
modifications in calibration shall not be possible at
site by any means. There shall be provision for
firmware update to change payment mode from
Prepaid to Postpaid and vice versa; similarly for
metering mode from Import only to Export-Import
(NET mode) and vice versa, through proper
authentication process remotely over the air (OTA).
The change should be recorded as Transaction
Event. Billing should be done at that time of firmware
upgrade so that readings at which this upgrade has
happened are logged in meter and system.
4.33 Usage Application Indoor
4.34 Ultrasonic welding / Meter cover and body should be continuous and
Chemical Bonding seamless ultrasonically welded with an overlapping of
5 mm (min.) or should be seamlessly chemically
bonded, so that meter should not open without
leaving clear mark.
TPCODL TP CENTRAL ODISHA DISTRIBUTION LIMITED
TECHNICAL SPECIFICATION
Document Title Technical Specification of HT Consumer Smart Energy Meter
Document No. MMG-SMART-005
Page 6 of 39
4.3.2 It should be the responsibility of the bidder to ensure integration of meter into HES
of TPCODL. For cellular fallback, the Module should have backward compatibility.
The fall back provision shall be taken through optical port with external modem by
TPCODL. Meter should be capable for sending all data from 4G NIC and optical
port.
4.3.3 It shall be possible to reconfigure the meters for RTC, TOD slots reprogramming,
DIP (Demand Integration period), billing date , display parameters etc. through
proper authentication process locally through MRI and remotely over the air
(OTA). Meter data should remain intact with timings. And billing should be done
whenever any above mentioned attribute is changed. The change should be
recorded as upgrade event.
4.3.4 Necessary keys if required for performing this reconfiguration operation should
also be provided along with supply of meter lot & training to TPCODL staff on how
to use it free of cost. Bidder to provide this support on a later stage also on the
request of TPCODL without any cost implication.
4.3.6 Bidder to ensure integration of meter data with head end for data transfer as
mentioned in specification.
4.3.7 Meter should be supplied to TPCODL along with integrated NIC card. NIC card
should be plug in type with proper sealing arrangement.
4.3.8 The bidder shall supply software required for local (MRI) & remote (AMI)
connectivity including required training to use the software free of cost. Bidder
shall provide the communication protocol / APIs for communication with meter
through local (MRI) / remote (AMI) as and when required by TPCODL free of cost
during life time of meter. The bidder should provide DLMS compliance for
Communication with the meter at Optical port and at HES.
4.3.9 Bidder should also provide software for changing/upgrading meter firmware in
mass and should support integration of this software with HES. Bidder should also
provide base computer software (BCS) for viewing the data downloaded through
TPCODL TP CENTRAL ODISHA DISTRIBUTION LIMITED
TECHNICAL SPECIFICATION
Document Title Technical Specification of HT Consumer Smart Energy Meter
Document No. MMG-SMART-005
Page 8 of 39
4.3.10 For purpose of exercising control, like outage management, the meter should
send abnormalities at the consumers' end like Power failure (Last Gasp) instantly,
Power Restoration (First Breath) as event. Additional exceptional events should
also be communicated to HES by meter immediately after the occurrence. It
should also indicate the restoration of the same event.
4.3.11 List of events to be reported should be configurable over the air(OTA).The meter
should have "Last Gasp" and “First Breath” feature to facilitate sending alerts to
the HES during fully powered off / On condition.
4.3.12 If there are 2 requests given for communication one from HES and other from
local device, request from local device should supersede.
4.3.13 Last mile mesh network must support auto-registration and self-healing feature to
continue operation using easiest possible available route in case of failure of any
communication device in the mesh. Self-registrations in first communication.
4.3.14 Meter Serial no will be used for tagging of all data of the meters in all database ( at
HES / MDM/ DCU level etc). However, it will be the responsibility of the Bidder
to establish the complete communication solution involving all the meters in the
system. Also, the Bidder must ensure that, the mode of communication used for
4G shall be consistent with the Government of India stipulations. Bidder should
come out with it requirements for integration of meter with HES and MDMS clearly
during tender submission.
4.3.15 The Bidder's supplied meter with third party communication module should have
suitable hand-shaking features to allow a third-party MDMS( procured by
TPCODL) to configure, command, read and control smart meters installed at site.
The Bidder shall extend all necessary assistance in developing the adaptor
software through a third-party for facilitating the above.
4.3.16 Integration of meter software’s with HES / MDMS for seamless transfer of data will
also be in scope of bidder till the expiry of warranty of the meters. It is desired
meter firmware up gradation/selection should be available over the air. Meter
should be able to change to prepaid mode if required with firmware upgrade. The
required firmware and any required support for integration with HES shall be
provided free of cost till the useful life of the meter.
4.3.17 Communication of the meter at optical port /OTA (NAN/WAN) should be as per IS
15959 (Part-2):2016. The optical port should be with proper lockable mechanism
4.3.19 Meter once powered up with NIC card should be self-detected by 4G network and
its basic name plate details & current readings are transferred to HES.
4.3.20 The required OBIS codes will be finalized with successful bidder. The bidder can
offer desired codes from Blue Book ensuing the codes reserved or standardized
by Bureau of Indian standards. The reserved codes in BIS are to be used/utilized
as per guidelines of BIS and remaining codes from blue book can be used for
TPCODL TP CENTRAL ODISHA DISTRIBUTION LIMITED
TECHNICAL SPECIFICATION
Document Title Technical Specification of HT Consumer Smart Energy Meter
Document No. MMG-SMART-005
Page 9 of 39
4.3.21 Meter display should have provision for showing if NIC card if : 1. Installed, 2.
Getting Network, 3. Latched with HES, 4. Communicating with HES
4.3.22 If any tamper occurs in power off situation, it should be pushed as soon as the
meter is powered on.
4.3.23 Bidder to provide facility for Up-gradation / Modification of Firmware
4.3.24 Following parameters may be updated multiple times during life cycle of meters
over the air :
Post Paid to Prepaid mode and vice versa
Import mode to export Mode and vice versa.
Accordingly Display parameters shall be updated remotely.
b. AC magnetic induction: >10 milli Tesla ( if produced with circular metal core
with square cross section as specified in CBIP latest report with 2800 AT)
c. Permanent Magnet: Immune up to 0.5T and Event logging >0.5T.
Component
SNo Requirement Makes and Origin
Function
USA: Analog
Devices, Cyrus
The Measurement/ computing Logic, Atmel, Phillips,
Measurement/c chips used in the meter should be Free scale
1
omputing chips with the Surface mount type along semiconductor,
with the ASICs Texas Instruments,
South Africa:
SAMES, Japan: NEC
USA: Atmel,
The memory chips should not be National,
affected by the external parameters Semiconductors,
Memory
2 like sparking, high voltage spikes or Texas Instruments,
chips/NVM
electrostatic discharges. The life of Phillips, Microchip,
NVM shall be 15 years. Japan: Hitachi or
Oki, Swiss: STMicro
The display modules should be well
protected from the external UV
radiations. The display visibility
should be sufficient to read the
Taiwan: Holtek,
meter mounted between height of
Singapore: Bonafied,
0.5m and 2m. The construction of
Display Technologies, Korea:
3 the modules should be such that
modules Advantek, China:
the displayed quantity should not
Xiamen, Truly
disturbed with the life of display.
semiconductor
Should be with Green LED
background. It should be trans-
reflective STN type industrial grade
with extended temperature range.
Optical port should be used to
USA: National,
transfer the meter data to meter
Semiconductors,
reading instrument. The mechanical
Holland / Korea:
4 Optical port construction of the port should be
Phillips, Taiwan:
such to facilitate the data transfer
MAXIM, Everlight,
easily. It should be magnetic
Japan: Hitachi
locking type
TPCODL TP CENTRAL ODISHA DISTRIBUTION LIMITED
TECHNICAL SPECIFICATION
Document Title Technical Specification of HT Consumer Smart Energy Meter
Document No. MMG-SMART-005
Page 11 of 39
5.1.3 Meter base shall be opaque with virgin polycarbonate LEXAN 500R or equivalent
(i.e. chart of Lexan 500R compared with the alternative material) on prior approval
from the TPCODL. (If different material offered the bidders should submit material
data sheet in technical bid )
5.1.4 Meter cover shall be transparent with virgin polycarbonate LEXAN 143R/943A or
equivalent (i.e. chart of Lexan 500R compared with the alternative material) on
prior approval from the TPCODL. (If different material offered the bidders should
submit material data sheet in technical bid )
5.1.5 Meter cover & base shall be provided with continuous and seamless Ultrasonic
welding such that it cannot be opened without breaking the enclosure. Front cover
& base shall be such that it is not possible to cut & open the meter without
certainly damaging the meter body and by no means shall an attempt to
reassemble would not leave physical evidence. The damage evidences should
be visible externally& should be traceable in such a way that attempts can be
proved in court of law.
5.1.6 The meter body shall be sealed in such a way that opening of meter base and
cover is possible only after breaking the seal(s).
5.1.7 During meter manufacturing the meter seal fixing should be tightened such that
the seal body should be close to meter body.
5.1.8 Unidirectional screws to be used on meter covers where ever required.
5.1.9 The Meter body shall be such that the liquid or chemical shall not reach the
electronic parts (in installed condition), if liquid is injected from any side of meter
body such as meter terminals, push button, display, NIC card casing etc.
TPCODL TP CENTRAL ODISHA DISTRIBUTION LIMITED
TECHNICAL SPECIFICATION
Document Title Technical Specification of HT Consumer Smart Energy Meter
Document No. MMG-SMART-005
Page 12 of 39
Necessary protection and water tight sealing to be provided at terminals and Push
buttons etc.
5.2 Terminals, 5.2.1 Even after any attempts the terminal block should get disengaged, opened or
Terminal Block loosen from any side. Any attempt to disengage the terminal block should
certainly damage the meter body with physical evidences. The damage
evidences should be visible externally& should be traceable in such a way that
attempts can be proved in court of law.
5.2.2 Terminals may be grouped in terminal block having adequate insulating
properties and mechanical strength. In order to satisfy such requirements when
choosing insulating virgin materials for the terminal block adequate testing of
materials shall be taken into account.
5.2.3 Terminal block and terminal cover shall be of a material which complies with the
requirements of IS11731 (part 1) method FH1. The material of which the terminal
block is made shall be capable of passing the Heat Deflection temperature test
given in ISO 75 for temperature of 135°C and pressure of 1.8 MPa as mentioned
in IS 14697. Tested as per ISO 75-2/A or ASTM D648.
5.2.4 The terminal block shall be of opaque with virgin polycarbonate LEXAN500R or
equivalent (complying with above requirement) on prior approval from the
TPCODL. (The bidders should submit material data sheet in technical bid )
5.2.5 The terminal block, the terminal cover and the meter case shall ensure
reasonable safety against the spread of fire. They shall not be ignited by thermal
overload of live parts in contact with them. The material and plating details of
terminals screw shall be submitted by the bidder.
5.2.6 The manner of fixing the conductors to the terminals shall ensure adequate and
durable contact such that there is no risk of loosening or undue heating. Terminal
& screw should not be damaged during regular opening and tightening.
5.2.7 Temperature sensor to be provided for sensing the temperature and meter
should be programmed in such way that on reaching the threshold value set (as
per tamper table no. 1) the event/alert should go to HES.
5.2.8 Internal diameter of the terminal holes shall be minimum 5 mm; minimum
clearance between adjacent terminals shall be 10 mm. Minimum Depth of the
terminal holes shall be of 20 mm.
5.2.9 Minimum two number of terminal screws to be provided per terminal wire.
5.2.10 Terminal block shall be such that the risk of corrosion resulting from contact with
any other metal part is minimized. Electrical connections shall be so designed
that contact pressure is not transmitted through insulating material.
5.2.11 Meter terminal should have 10 terminals arrangement. The terminals should have
center to center distance of min. 11.5mm. Terminal configuration shall be R-Cin,
R volt, R-Cout, Y-Cin, Y volt, Y-Cout, B-Cin, B-volt, B-Cout, Neutral.
5.3 Terminal Cover 5.3.1 Terminal cover shall be short type and transparent with virgin polycarbonate
LEXAN 143R/943A or equivalent on prior approval from the TPCODL (the bidders
should submit the relevant material data sheet in technical bid).
5.3.2 Appropriate space shall be available for incoming /outgoing cables without
damaging/stressing terminal cover (terminal cover design shall be as per the
TPCODL approval). After sealing the cover, terminals shall not be accessible
TPCODL TP CENTRAL ODISHA DISTRIBUTION LIMITED
TECHNICAL SPECIFICATION
Document Title Technical Specification of HT Consumer Smart Energy Meter
Document No. MMG-SMART-005
Page 13 of 39
without breaking the seals. Terminal cover should be of short type 20-25 mm
length. The system connection diagram shall be provided on the terminal cover.
5.3.3 The terminal cover design should be such that the sealing screw locking provision
on cover should have min dimension of 3mmx3mm. (Excluding seal lock hole)
5.3.4 The terminal cover should open on the top side, during connection of the cables.
The side opening of terminal cover is not acceptable due to additional opening
space requirement.
5.4 Sealing of meter, 5.4.1 The system connection diagram shall be provided on the terminal cover. Reliable
terminal cover and sealing arrangement shall be provided to make the meter tamper evident and to
NIC cover avoid fiddling or tampering by unauthorized persons.
5.4.2 For this, one no. Polycarbonate seal and three no. Hologram seal with unique
serial numbers (on Left, Right & Top side) shall be provided by the bidder. One
no polycarbonate seal shall be provided by the TPCODL. This seal shall be fix on
right hand side of meter.
5.4.3 All the seals with unique serial numbers shall be fixed on meter body by the bidder
at his works before calling for inspection.
5.4.4 Two sealing provision shall be provided at meter terminal cover, such that terminal
shall not be accessible without breaking the seals. All the seals shall be provided
on front side only and as per the TPCODL specification. Rear side sealing
arrangement shall not be accepted. Bidder shall provide seals be as per CEA
regulation (2006). Only patented seals to be used as per CEA requirements.
5.4.5 The bidder shall provide TPCODL(MMG store and MTL) the soft record of
polycarbonate seal and hologram seal serial number and NIC card serial number
used against each meter serial number along with its position
(RHS/LHS/Top/Meter body/ NIC Cover) in tabular form for every lot of meter.
5.4.6 Plug in type NIC card cover should have proper sealing arrangement and should
be sealed with manufacturer’s polycarbonate seal.
5.5 TOD Feature The meter shall be capable of measuring Cumulative Energy (kWh & kVAh)both for
IMPORT and IMPORT – EXPORT mode, wherever applicable and MD (kW & kVA) with
time of day (TOD) registers having 8 zones & 02 seasons (no. of zones & time slot shall
be programmable by MRI/ Over the air with adequate security level and in one to one
/broadcast mode over the air). Current TOD (during tender) to be given is as below:
Slots Time Slot Jan-Dec
Off-peak 2200-0600 Register 1
Normal 0600-2200 Register 2
# The bidder to ask TPCODL for latest TOD timing slots before manufacturing of
every lot.
5.6 MD Integration The MD integration period shall be 15 minutes, as applicable (integration period-
programmable by MRI/HHU at site and also through HES with adequate security level).
The MD resetting shall be automatic at the 1st of the month i.e. 0000 hours of 1st day of
the month. Manual MD reset button shall not be available. Last 12 MD values shall be
stored in the memory. MD shall be recorded and displayed with minimum three digits
before decimal and minimum three digits after decimal points. MD integration shall be of
sliding Type at an interval of 10 min.
5.7 Parameters in All these parameters shall be downloaded locally or remotely and interpreted in
Meter/HES PC/Laptop. All the parameters shall be recorded and memorized in its Non Volatile
Memory (NVM). The corresponding Non Volatile Memory shall have a minimum retention
time of 15 years. It is to be ensured that any data which is pushed / pulled from meter
TPCODL TP CENTRAL ODISHA DISTRIBUTION LIMITED
TECHNICAL SPECIFICATION
Document Title Technical Specification of HT Consumer Smart Energy Meter
Document No. MMG-SMART-005
Page 14 of 39
must have Meter Sr. No. as one of the parameters.Time-sync with RTC and over-writes
on drift threshold. Clarity on event logged in memory and server time-stamps matching.
‘Fail’ to be log in memory in the following conditions:
a) RTC fail
b) NVM memory fail
c) Battery fail
5.7.1 Load survey (for Meter serial number and NIC serial number shall be recorded and communicated for all
pre-paid, post- profiles of data. The meter shall be capable of recording 15 minutes average of the
paid & NET meter following parameters for at least last 45 days
mode) a) Voltage for each phase
b) Current of each phase
c) Average PF
d) Average kWh
e) Average kVAh (lag only, for import only)
f) kVArh(Lagging)
g) kVArh(Leading)
h) Demand (KW)
i) Demand(KVA)
j) Temperature near terminal block (˚C)
k) THD Voltage phase wise
l) THD Current phase wise
Meter shall be capable of recording daily Energy and Demand 00:00 to 24:00 Hrs
kWh/kVAh, kW/kVA for 45 days. Midnight energy value of cumulative KWh, KVAh along
with H1 KW and KVA along with daily consumption kWh should be available in meter
memory for last 45 days.
Load survey data should be at least with 5 decimal place
5.7.2 Instantaneous Meter serial number and NIC serial number shall be recorded and communicated for all
Parameters profiles of data. Meter shall be capable for following Instantaneous Parameters in Memory
and should be available in HES.
Meter Sr.No.
NIC Sr. No.
Meter Type 3P HT
Meter date & Time DD MM YYYY HH MM SS
Voltage –R 000.000V
Voltage –Y 000.000V
Voltage –B 000.000V
Line Current –R 00.000A
Line Current –Y 00.000A
Line Current –B 00.000A
Active Current –R 00.000A
Active Current –Y 00.000A
Active Current –B 00.000A
Reactive Current-R 00.000A
Reactive Current-Y 00.000A
Reactive Current-B 00.000A
Power factor-R 0.000
Power factor-Y 0.000
Power factor-B 0.000
Average Power factor 0.000
Instantaneous Frequency 00.000Hz
Instantaneous Load Active ,Reactive Lag/Lead,
Apparent
Present Cumulative Energy Active ,Reactive Lag/Lead,
Apparent
TPCODL TP CENTRAL ODISHA DISTRIBUTION LIMITED
TECHNICAL SPECIFICATION
Document Title Technical Specification of HT Consumer Smart Energy Meter
Document No. MMG-SMART-005
Page 15 of 39
# if any additional key is required to see this value, it should be provided without any
additional cost to TPCODL .
5.7.4 Billing Parameters 1) Meter serial number and NIC serial number shall be recorded and communicated for
all profiles of data. All these below mentioned data should be available for Import
Mode and Export-Import Mode, as applicable.
2) Cumulative kWh, kVAh (lag only for import mode), kVArh lead, lag (all import and
export) and TOD1 kWh,TOD2 kWh, TOD1 kVAh (lag only for import mode),TOD2
kVAh (lag only for import mode), For present and last 12 Resets (reset date for all
resets/history, time zone register wise).
3) Maximum Demand Absolute Active Load and Absolute Apparent load and TOD1
kW,TOD2 kW, TOD1 kVA (lag only for import mode),TOD2 kVA (lag only for import
mode), for present and last 12 Resets ( reset date for all resets/history, time zone
register wise) along with date and time stamp.
4) Consumption (Reading date, Current Month & 12 History, time zone register wise)
kWh and kVAh.
Cumulative energy parameters kWh, kVAh (lag only for import mode), kVArh lead, lag (all
import and export) and TOD1 kWh, TOD2 kWh, , TOD1 kVAh (lag only for import mode),
TOD2 kVAh (lag only for import mode) . The meter shall be capable of measuring
Cumulative Energy (kWh & kVAh) both for IMPORT and IMPORT – EXPORT mode,
wherever applicable.
5.9.3 Phase indication : Individual phases should be displayed on LCD display of meter
and shall glow with minimum operating voltage (as defined in 4.05 of GTR)
6.0 NAME PLATE Meters shall have a name plate clearly visible and effectively secured against removal.
AND MARKING The name plate data should be laser printed. The base color of Name plate shall be blue
(Pantone 2727C) indelibly and distinctly marked with all essential particulars as per
relevant standards along with the following:
i.Manufacturer's name
ii.Type designation
iii.Number of phases and wires
iv. Serial number (Meter serial number shall be laser printed on name plate
instead on sticker).
v.Month and Year of manufacture (MM/YYYY)
vi.Unit of measurement
vii.Reference voltage ,frequency
viii.Ref. temperature if different from 27 deg. C
ix.Rated basic and maximum Current
x.Meter constant (imp/kWh, Imp/kVArh)
xi.‘BIS’ Mark
xii.Class index of meter
TPCODL TP CENTRAL ODISHA DISTRIBUTION LIMITED
TECHNICAL SPECIFICATION
Document Title Technical Specification of HT Consumer Smart Energy Meter
Document No. MMG-SMART-005
Page 19 of 39
xiii."Property of TPCODL ”
xiv.Purchase Order No. & date
xv.Guarantee period.
xvi.Rated frequency
xvii.Sign of double square
xviii.Country of manufacture.
xix.Firmware version for meter
xx.Category
xxi.Communication Tech for WAN and NAN( with carrier frequency)
xxii.Communication Technology is IHD supported (with carrier frequency).
However the following shall be printed in bar code on the meter nameplate(shall be laser
printed on name plate instead of any sticker). All data shall be laser printed on meter along
with Sr.NO and date of manufacturing. No sticker to be used to avoid loss of data in event
of fire. Content Format for bar code: TPCODL MMYY XXXXXXXXX (9-digit Serial no.)
The PCB Serial number should be printed on the PCB instead of sticker.
Bidder should ensure that each NIC provided in meters are having laser printed Sr.
No., MFG date, ‘Property of TPCODL’ marked, PO date and no. (same as that of
meter PO)
7.0 TESTS All routine, acceptance & type tests shall be carried out on the meter and meter body
separately in accordance with the relevant IS/IEC. All routine/acceptance tests shall be
witnessed by the TPCODL /his authorized representative. All the components shall also
be type tested as per the relevant standards. Following tests shall be necessarily
conducted in addition to the tests specified in IS/IEC from CPRI/ERDA.
7.1 TYPE TEST 1) All type-tests defined in IS 16444 (Part-2) and IS 15959 (Part-3):2016
2) Test against abnormal magnetic influence as per CBIP TR 325.
3) Test for Material used for Terminal Block and meter body as per relevant standards.
4) IP test for IP 51 as per IS 60529
5) Bidder/BA must submit valid BIS license for manufacturing smart energy meters as
per IS 16444 and IS 15959 (Part-3) with all requisite inclusions.
7.2 ROUTINE TEST 1) AC High Voltage test (Clause no. 12.7.6.3 of IS 14697)
2) Insulation test (Table 18 of Clause no. 12.7.6 of IS 14697)
3) Test on limits of error (Clause no. 11 of IS 14697)
4) Test of starting current (Clause no. 12.13 of IS 14697)
5) Test of no load condition (Clause no. 12.12 of IS 14697)
6) Communication check of NIC (Table27 of IS 15959 (Part 3); Clause no. 9.5 & 10 of IS
16444 Part -2)
7.3 ACCEPTANCE 1) AC High Voltage test (Clause no. 12.7.6.3 of IS 14697)
TEST 2) Insulation test (Table 18 of Clause no. 12.7.6 of IS 14697)
3) Test on limits of error (Clause no. 11 of IS 14697) with following loads:
120% Imax Ib (5A) 0.1 Ib 0.02 Ib 0.05Ib 0.01Ib
Imax (10A)
UPF, 0.8 UPF, 0.8 UPF, UPF, UPF, UPF UPF
lead and lead and 0.8 lead 0.8 lead 0.8 lead
0.5 lag 0.5 lag and 0.5 and 0.5 and 0.5
lag lag lag
12.0 PACKING 1. Bidder shall ensure that all material covered under this specification shall be prepared
for rail/road transport (local equipment) and be packed in such a manner as to protect
it from damage in transit. The material used for packing shall be environmentally
friendly. Packing and transportation shall be as per IS 15707:206 clauses 9.1 and 9.2.
2. Individual meter should be packed in separate box. Routine test report (with
manufacturing company logo) of the individual meter shall be kept inside each card
board carton of the meter.
3. On back side of routine test certificate (RTC) the bidder shall print a picture of the
meter with its small details like for consumer to know about meter or display
parameters sheet.
4. The soft copy of the routine test certificate of each meter to be provided with each lot
to TPCODL, MMG lan at Bhubaneswar.
5. The routine test certificate shall contain results & all tests of clause no. 7.2.
TPCODL TP CENTRAL ODISHA DISTRIBUTION LIMITED
TECHNICAL SPECIFICATION
Document Title Technical Specification of HT Consumer Smart Energy Meter
Document No. MMG-SMART-005
Page 21 of 39
6. Bar code containing information of meter Sr. No should be pasted on the outer most
box in which single / group of meters are transported
14.0 TRAINING Suitable training to be arranged for TPCODL representatives, for operation and handling
of every software and hardware regarding communication between meter & HHU, meter
& HES, without any cost implications towards TPCODL.
15.0 QUALITY The bidder shall submit with the offer Quality assurance plan indicating the various stages
CONTROL of inspection, the tests and checks which will be carried out on the material of construction,
components during manufacture and bought out items and fully assembled component
and equipment after finishing. As part of the plan, a schedule for stage and final inspection
within the parameters of the delivery schedule shall be furnished.
Quality should be ensured at the following stages:
At PCB manufacturing stage, each board shall be subjected to computerized bare
board testing.
At insertion stage, all components should undergo computerized testing for
conforming to design parameter and orientation.
Complete assembled and soldered PCB should undergo functional testing using
Automatic Test Equipment (ATEs).
Prior to final testing and calibration, sample meters shall be subjected to aging test
(i.e. meters will be kept in ovens for 24 hours at 55 Deg. C temperature and
atmospheric humidity under real-life condition at its full load current. After 24 hours
meter should work satisfactorily.
TPCODL's engineer(s) or its nominated representative(s) shall have free access to the
bidder’s/manufacturer’s works to carry out inspections.
16.0 MINIMUM Bidder shall have adequate in house testing facilities for carrying out all routine tests &
TESTING acceptance tests as per relevant International / Indian standards. The bidder shall have
FACILITIES duly calibrated Reference Standard meter of Class 0.1 accuracy or better.
17.0 MANUFACTURING The successful bidder will have to submit the bar chart for various manufacturing activities
ACTIVITIES clearly elaborating each stage, with quantity. This bar chart shall be in line with the Quality
assurance plan submitted with the offer.
18.0 SPARES, 1. Bidder to be provide free of cost 02 nos. of jig (irrespective of order lot) for retrieving
ACCESSORIES data from memory of meter with every new design of meter in which previous jig is
AND TOOLS supplied cannot be used. Jig should be such that NVM can be push fit on this jig and
data can be retrieve from this NVM.
2. Five (5) nos. of optical cord against each 100 meter lot on pro-rata basis for retrieving
the data of meter through optical port should be provided, if design of optical port is
changed from those of previously supplied meters.
19.0 DRAWINGS AND Following drawings & Documents shall be prepared based on TPCODL specifications
DOCUMENTS and statutory requirements and shall be submitted with the bid:
a) Completely filled-in Technical Parameters.
b) General arrangement drawing of the meter
c) Terminal Block dimensional drawing
d) Mounting arrangement drawings.
e) General description of the equipment and all components with makes and technical
requirement
f) Type Test Certificates
g) Experience List
After the award of the contract, soft copies of following drawings, drawn to scale,
describing the equipment in detail shall be forwarded for approval:
S. No. Description For For Review Final
Approval Information Submission
TPCODL TP CENTRAL ODISHA DISTRIBUTION LIMITED
TECHNICAL SPECIFICATION
Document Title Technical Specification of HT Consumer Smart Energy Meter
Document No. MMG-SMART-005
Page 22 of 39
1 Technical Parameters
2 General Arrangement
drawings
3 Terminal block Dimensional
drawings
4 Mounting arrangement
drawing.
5 Manual/Catalogues √
6 Transport/ Shipping
dimension drawing
7 QA &QC Plan
8 Routine, Acceptance and
Type Test Certificates
Bidder shall subsequently provide soft copy of all the drawings, GTP, data-sheet of
dis-connector switch, data-sheet/ comparative analysis (of material of terminal
block, terminal cover, terminal screw, meter body, meter base), Test certificates
and integration documents with HES for the final approval of TPCODL, before mass
manufacturing. All the documents & drawings shall be in English language.
TPCODL TP CENTRAL ODISHA DISTRIBUTION LIMITED
TECHNICAL SPECIFICATION
Document Title Technical Specification of HT Consumer Smart Energy Meter
Document No. MMG-SMART-005
Page 23 of 39
Note: Load Profile parameters are required to be field programmable, a TPCODL specific OBIS code will be
used for this purpose and on changing capture objects LS data will be reset.
S. No. Profile for Power Fail events OBIS Code OBIS Source
Power Fail event profile 0.0.99.98.2.255 IS15959-Part3
1 Real Time Clock – Date and Time 0.0.1.0.0.255 IS15959-Part3
2 Event Code ( power fail events ) 0.0.96.11.2.255 IS15959-Part3
TPCODL TP CENTRAL ODISHA DISTRIBUTION LIMITED
TECHNICAL SPECIFICATION
Document Title Technical Specification of HT Consumer Smart Energy Meter
Document No. MMG-SMART-005
Page 28 of 39
S. No. Profile for Non Rollover events OBIS Code OBIS Source
Non Rollover event profile 0.0.99.98.5.255 IS15959-Part3
1 Real Time Clock – Date and Time 0.0.1.0.0.255 IS15959-Part3
2 Event Code ( non-rollover events ) 0.0.96.11.5.255 IS15959-Part3
S. No. Profile forTPCODL Specific events compartments OBIS Code OBIS Source
TPCODL Specific events compartments profile 0.0.99.98.128.255 TPCODL Specific
1 Real Time Clock – Date and Time 0.0.1.0.0.255 IS15959-Part3
2 Event Code ( Non Standard events ) 0.0.96.11.128.255 TPCODL Specific
3 Current - IR 1.0.31.7.0.255 IS15959-Part3
4 Current - IY 1.0.51.7.0.255 IS15959-Part3
5 Current - IB 1.0.71.7.0.255 IS15959-Part3
6 Voltage - VRN 1.0.32.7.0.255 IS15959-Part3
7 Voltage - VYN 1.0.52.7.0.255 IS15959-Part3
TPCODL TP CENTRAL ODISHA DISTRIBUTION LIMITED
TECHNICAL SPECIFICATION
Document Title Technical Specification of HT Consumer Smart Energy Meter
Document No. MMG-SMART-005
Page 29 of 39
S. No. Profile for Digital Input events Compartments OBIS Code OBIS Source
Digital Input event Profile 0.0.99.98.130.255 TPCODL Specific
1 Real Time Clock – Date and Time 0.0.1.0.0.255 IS15959-Part2
2 Event Code (Digital Input events ) 0.0.96.11.129.255 TPCODL Specific
Note: Accuracy check profile is used by windows based HHU to check meter accuracy in field.
Note:- TOU (Time ZON) timing can programmed by using activity calendar for times zone (0.0.13.0.0.255)
The same OBIS code shall be used for reading the configured TOU timings.
3. Three phase default display parameter shall be configured as Post-paid & shall be programmable through
HES (OTA) for following combinations.
a. Post-paid with TOD
b. Net mode (Import/export)
4. Meter serial number shall be alpha numeric and with 9 digits. Alphabetic part detail shall be shared by
TPCODL
5. Communication LCD indicator-Meter display shall have indication in context to NIC. The blinking
should be slow when NIC is detected; blinking should be fast when NIC had searched the network and it
should be stable when it is successfully latched to the HES.
6. Billing shall be done at following programming events and programing can be done OTA.
a. Metering mode change
b. Communication driven MD reset
c. Time zone activation
d. Demand integration period change
e. Display parameter configuration
f. Firmware upgrade
g. Kvah configuration Lag or Lag+lead (OBIS code 1.0.128.5.131.255,event ID 192, value 0= Lag+Lead &
value 1 = Lag only )
8. Default MD integration period is 15 minute (sliding interval time 5 minute) & it can be configured to 30/15
minute
9. Default load survey integration period is 15 minute & can be configured to 30/15 minute. The load survey
data shall be recorded for 45 days with 15 minute IP & 90 days with 30 minute IP
10. KVAH calculation shall be lag only by default it shall be configurable to lag + lead/lag only
OBIS code 1.0.128.5.131.255, event ID 192, (value 0= Lag+Lead & value 1 = Lag only) shall be used for
KVAH energy configuration
11. All DATE should be in DDMMYYYY format.
Event Push data (This data shall be push when any event
S. No. OBIS Code OBIS Source
(Tamper, First breath, last gasp etc) is occurred)
1 Device ID 0.0.96.1.2.255 IS 15959 part-3
2 Event Push SM(Smart Meter) to HES 0.4.25.9.0.255 IS 15959 part-3
3 Real Time Clock – Date and Time 0.0.1.0.0.255 IS 15959 part-3
4 Event Status Word 1 0.0.94.91.18.255 IS 15959 part-3
5 Meter serial number 0.0.96.1.0.255 IS 15959 part-3
Note- This data shall be pushed to HES only
TPCODL TP CENTRAL ODISHA DISTRIBUTION LIMITED
TECHNICAL SPECIFICATION
Document Title Technical Specification of HT Consumer Smart Energy Meter
Document No. MMG-SMART-005
Page 33 of 39
Daily survey profile (Mid night) push data (This data shall be
S. No. OBIS Code OBIS Source
pushed at every midnight)
1 Device ID 0.0.96.1.2.255 IS 15959 part-3
2 Mid Night (daily) push SM(Smart Meter) to HES 0.6.25.9.0.255 TPCODL Specific
3 Real Time Clock - Date and Time 0.0.1.0.0.255 IS15959-Part-3
Daily survey profile (All daily survey profile parameters which are
4 mentioned in daily profile – 1.0.99.2.0.255) 1.0.99.2.0.255 IS 15959 part-3
Note- This data shall be pushed to HES only
S. No. Billing Push Data (This data shall be pushed at every month end) OBIS Code OBIS Source
1 Device ID 0.0.96.1.2.255 IS 15959 part-3
2 Billing Push SM(Smart Meter) to HES 0.99.25.9.0.255 TPCODL Specific
3 Real Time Clock - Date and Time 0.0.1.0.0.255 IS15959-Part-3
Daily survey profile (All daily survey profile parameters which are
4 mentioned in daily profile – 1.0.98.1.0.255) 1.0.98.1.0.255 IS 15959 part-3
Note- This data shall be pushed to HES only
TPCODL TP CENTRAL ODISHA DISTRIBUTION LIMITED
TECHNICAL SPECIFICATION
Document Title Technical Specification of HT Consumer Smart Energy Meter
Document No. MMG-SMART-005
Page 34 of 39
S. No. Block Load Profile (90 days with 30 min IP and 45 days with 15 OBIS Code OBIS Source
minute IP) Profile
Block Load 1.0.99.1.0.255 IS15959-Part-3
1 RTC 0.0.1.0.0.255 IS15959-Part-3
2 Average Current - IR 1.0.31.27.0.255 IS15959-Part-3
3 Average Current - IY 1.0.51.27.0.255 IS15959-Part-3
4 Average Current - IB 1.0.71.27.0.255 IS15959-Part-3
5 Average Voltage - VRN 1.0.32.27.0.255 IS15959-Part-3
6 Average Voltage - VYN 1.0.52.27.0.255 IS15959-Part-3
7 Average Voltage - VBN 1.0.72.27.0.255 IS15959-Part-3
8 Block Energy – kWh- Import/Forwarded 1.0.1.29.0.255 IS15959-Part-3
9 Block Energy – kWh-Export 1.0.2.29.0.255 IS15959-Part-3
10 Block energy. kvarh-Q1/Lag 1.0.5.29.0.255 IS15959-Part-3
11 Block energy. kvarh-Q2\Lead 1.0.6.29.0.255 IS15959-Part-3
12 Block energy. kvarh-Q3\Lag 1.0.7.29.0.255 IS15959-Part-3
13 Block energy. kvarh-Q4/Lead 1.0.8.29.0.255 IS15959-Part-3
14 Block Energy – kVAh- Import/Forwarded 1.0.9.29.0.255 IS15959-Part-3
15 Block Energy – kVAh-Export 1.0.10.29.0.255 IS15959-Part-3
16 %THDV R- Phase Average 1.0.32.128.124.25 TPCODL
17 %THDV Y- Phase Average 5
1.0.52.128.124.25 TPCODL
18 %THDV B- Phase Average 5
1.0.72.128.124.25 TPCODL
19 %THDI R- Phase Average 5
1.0.31.128.124.25 TPCODL
20 %THDI Y- Phase Average 5
1.0.51.128.124.25 TPCODL
21 %THDI B- Phase Average 5
1.0.71.128.124.25 TPCODL
22 Average Temperature 5
0.0.96.9.129.255 TPCODL
23 Signal strength (CSQ value) 0.1.96.12.5.255 TPCODL
24 Meter Serial number 0.0.96.1.0.255 IS15959-Part-3
Note-1: Block energies data shall be with 3 decimal place
Note-2: Demand KW ,KVA & Signed Power factor shall be derived at HES/MDMS & BCS end
Note-3: Block load profile parameters shall be field programmable by TPCODL specific OBIS code. On changing capture
object LS data will be reset
Note-4: This data shall be read by through BCS , HES/MDM
S.
Daily Load Profile ( 45days data ) OBIS Code OBIS Source
No.
Daily Survey Profile 1.0.99.2.0.255 IS 15959 part-3
1 Real Time Clock – Date & Time 0.0.1.0.0.255 IS 15959 part-3
TPCODL TP CENTRAL ODISHA DISTRIBUTION LIMITED
TECHNICAL SPECIFICATION
Document Title Technical Specification of HT Consumer Smart Energy Meter
Document No. MMG-SMART-005
Page 37 of 39
S. No. Profile for Voltage(e=0), Current(e=1) & Other events(e=4) event OBIS Code OBIS Source
Voltage related events Profile 0.0.99.98.e.255 IS15959-Part-3
1 Real Time Clock – Date and Time 0.0.1.0.0.255 IS15959-Part-3
2 Event Code ( voltage events ) 0.0.96.11.e.255 IS15959-Part-3
3 Current - IR 1.0.31.7.0.255 IS15959-Part-3
4 Current - IY 1.0.51.7.0.255 IS15959-Part-3
5 Current - IB 1.0.71.7.0.255 IS15959-Part-3
6 Voltage - VRN 1.0.32.7.0.255 IS15959-Part-3
7 Voltage - VYN 1.0.52.7.0.255 IS15959-Part-3
8 Voltage - VBN 1.0.72.7.0.255 IS15959-Part-3
9 Signed R Phase Pf 1.0.33.7.0.255 IS15959-Part-3
10 Signed Y Phase Pf 1.0.53.7.0.255 IS15959-Part-3
11 Signed B Phase Pf 1.0.73.7.0.255 IS15959-Part-3
12 KWH Import/Forwarded 1.0.1.8.0.255 IS15959-Part-3
13 KWH Export 1.0.2.8.0.255 IS15959-Part-3
14 Cumulative tamper count 0.0.94.91.0.255 IS15959-Part-3
15 KVAH Import/Forwarded 1.0.9.8.0.255 IS15959-Part-3
16 KVAH Export 1.0.10.8.0.255 IS15959-Part-3
17 R Phase active Current 1.0.31.7.128.255 TPCODL
18 Y Phase active Current 1.0.51.7.128.255 TPCODL
19 B Phase active Current 1.0.71.7.128.255 TPCODL
20 Total PF 1.0.13.7.0.255 IS15959-Part-3
21 Meter Serial number 0.0.96.1.0.255 IS15959-Part-3
Note- This data shall be read by BCS & HES
S. No. Profile for TPCODL Temperature compartments OBIS Code OBIS Source
TPCODL events compartments profile 0.0.99.98.128.255 TPCODL
1 Real Time Clock – Date and Time 0.0.1.0.0.255 IS15959-Part-3
2 Event Code ( Non Standard events ) 0.0.96.11.128.255 TPCODL
3 Current – IR 1.0.31.7.0.255 IS15959-Part-3
4 Current – IY 1.0.51.7.0.255 IS15959-Part-3
5 Current – IB 1.0.71.7.0.255 IS15959-Part-3
6 Voltage – VRN 1.0.32.7.0.255 IS15959-Part-3
7 Voltage – VYN 1.0.52.7.0.255 IS15959-Part-3
8 Voltage – VBN 1.0.72.7.0.255 IS15959-Part-3
9 R Phase Pf 1.0.33.7.0.255 IS15959-Part-3
10 Y Phase Pf 1.0.53.7.0.255 IS15959-Part-3
11 B Phase Pf 1.0.73.7.0.255 IS15959-Part-3
12 KWH Import/Forwarded 1.0.1.8.0.255 IS15959-Part-3
13 KWH Export 1.0.2.8.0.255 IS15959-Part-3
14 Cumulative tamper count 0.0.94.91.0.255 IS15959-Part-3 A1
15 KVAH Import/Forwarded 1.0.9.8.0.255 IS15959-Part-3
16 KVAH Export/Forwarded 1.0.10.8.0.255 IS15959-Part-3
17 R Phase active Current 1.0.31.7.128.255 TPCODL
18 Y Phase active Current 1.0.51.7.128.255 TPCODL
19 B Phase active Current 1.0.71.7.128.255 TPCODL
20 Total PF 1.0.13.7.0.255 IS15959-Part-3
21 Temperature 0.0.96.9.128.255 TPCODL
22 Meter Serial number 0.0.96.1.0.255 IS15959-Part-3
Note- This data shall be read through BCS & HES
Three phase HT Meter common Display list for all combinations Annexure-C
1. Forward mode
2. Net meter mode
S.No Display list Auto Push Mode of metering
1 LCD Check Scroll
YES Button
YES
2 Meter Serial number YES YES
3 Date(DD:MM:YY) YES YES
4 Time (HH:MM:SS) YES YES
5 Cumulative kWh(Import/Forwarded) YES YES
6 Cumulative kVAh(Import/Forwarded) YES YES
7 Cumulative kWh-Export YES YES Applicable for “net meter”
8 Cumulative kVAh-Export YES YES mode
9 Cumulative kVArh Lag (Q1) YES YES
10 Cumulative kVArh Lead (Q4) YES YES
11 Cumulative kVArh Lead (Q2) YES YES Applicable for “net meter”
12 Cumulative kVArh Lag (Q3) YES YES mode
13 Current Month MD – kW (Import/Forwarded) with YES YES
14 Date & Time
Current Month MD - kVA(Import/Forwarded) with YES YES
15 Date & Time
Current Month TOD - kW (Import/Forwarded)- TZ1 - YES
16 Current Month TOD - kW (Import/Forwarded)- TZ2 - YES
17 Current Month TOD - kVA (Import/Forwarded)- TZ1 - YES
18 Current Month TOD - kVA (Import/Forwarded)- TZ2 - YES
19 Current Month MD – kW(Export) with Date & Time YES YES Applicable for “net meter”
20 Current Month MD – kVA(Export) with Date & Time YES YES mode
21 Cumulative TOD KWH -TZ1 YES YES
22 Cumulative TOD KWH -TZ2 YES YES
23 Cumulative TOD KVAH -TZ1 YES YES
24 Cumulative TOD KVAH -TZ2 YES YES
25 Last Month (history 1) kWh (Import/Forwarded) YES YES
26 Last Month (history 1) kVAh (Import/Forwarded) YES YES
27 Last Month (history 1) kWh (Export) YES YES Applicable for “net meter”
28 Last Month (history 1) kVAh (Export) YES YES mode
29 Last Month (history 1) Cumulative TOD kWh TZ1 YES YES
30 Last Month (history 1) Cumulative TOD kWh TZ2 YES YES
31 Last Month (history 1) Cumulative TOD kVAh TZ1 YES YES
32 Last Month (history 1) Cumulative TOD kVAh TZ2 YES YES
33 Last Month (history 1) MD kW (Import/Forwarded) YES YES
34 Last Month (history 1) MD kVA(Import/Forwarded) YES YES
TPCODL TP CENTRAL ODISHA DISTRIBUTION LIMITED
TECHNICAL SPECIFICATION
Document Title Technical Specification of HT Consumer Smart Energy Meter
Document No. MMG-SMART-005
Page 43 of 39
35 Last Month (history 1) MD kW (Export) with Date & YES YES Applicable for “net meter”
36 TimeMonth (history 1) MD kVA(Export) with Date &
Last YES YES mode
TimeMonth (history 1) MD kW(Import/Forwarded)
Last
37 TZ1
- YES
Last Month (history 1) MD kW(Import/Forwarded)
38 TZ2
- YES
Last Month (history 1) MD kVA(Import/Forwarded)
39 TZ1
- YES
Last Month (history 1) MD kVA(Import/Forwarded)
40 TZ2
- YES
41 Last Month (history 1) Power Factor YES YES
42 R Phase Voltages (Vr) YES YES
43 Y Phase Voltages (Vy) YES YES
44 B Phase Voltages (Vb) YES YES
45 R Phase Current (Ir) YES YES
TPCODL TP CENTRAL ODISHA DISTRIBUTION LIMITED
TECHNICAL SPECIFICATION
Document Title Technical Specification of HT Consumer Smart Energy Meter
Document No. MMG-SMART-005
46 Y Phase Current (Iy) YES YES Page 44 of 39
47 B Phase Current (Ib) YES YES
48 Signed R phase Power Factor YES YES
49 Signed Y phase Power Factor YES YES
50 Signed B phase Power Factor YES YES
51 Instant Signed Three phase Power Factor YES YES
52 Instant Signed Active Power (kW) YES YES
53 Instant Apparent Power (kVA) YES YES
54 Voltage Sequence (R-Y-B). YES YES
55 Current Sequence (R-Y-B) YES YES
56 High Resolution kWh (Import/Forwarded) YES YES
57 High Resolution kVAh (Import/Forwarded) YES YES
58 High Resolution kWh -Export YES YES Applicable for “net meter”
59 High Resolution kVAh -Export YES YES mode
60 High Resolution kVArh Lag \Q1 YES YES
61 High Resolution kVArh Lead\Q4 YES YES
62 High Resolution kVArh Lead \Q2 YES YES Applicable for “net meter”
63 High Resolution kVArh Lag \Q3 YES YES mode
64 Magnetic Tamper count -- YES
65 Latest Magnetic tamper occurrence date -- YES
66 Latest Magnetic tamper occurrence Time -- YES
67 ESD Tamper count -- YES
68 Latest ESD tamper occurrence date -- YES
69 Latest ESD tamper occurrence time -- YES
70 2nd Last Month (history 2) kWh -- YES
71 (Import/Forwarded)
2nd Last Month (history 2) kVAh -- YES
72 (Import/Forwarded)
2nd Last Month (history 2) MD kW -- YES
73 (Import/Forwarded)
2 nd
Last Month (history 2) MD kVA -- YES
74 (Import/Forwarded)
2 nd
Last Month (history 2 Average PF -- YES
75 2nd Last Month (history 2) kWh (Export) -- YES
76 2nd Last Month (history 2) kVAh (Export) -- YES Applicable for “net meter”
77 2nd Last Month (history 2) MD kW (Export) with -- YES mode
78 Date-Time
2nd Last Month (history 2) MD kVA (Export)with -- YES
79 Date-Time MD-KW
Cumulative -- YES
80 Cumulative MD-KVA -- YES
81 Self-diagnostic check -- YES
82 Rising Demand in KW with elapsed time -- YES
83 Rising Demand in KVA with elapsed time -- YES
84 Cover Open tamper count -- YES
85 Cover Open occurrence date of very first event -- YES
86 Cover Open occurrence time of very first event -- YES
87 Current month power On duration -- YES
88 RTC Status -- YES
89 RTC Battery Status -- YES
90 NVM (Memory) Status -- YES
91 Signal strength (CSQ value) -- YES
92 NIC card status -- YES
93 Meter display firmware version number -- YES
94 Meter PT Ratio -- YES
95 Meter CT Ratio -- YES