Tanta University   Electrical Power and Machines Department
Faculty of Engineering
                            Fourth Year- Second Term
                                   2020-2021
                           Power System Protection
                                 Section # 5
                                  Sheet #3
                                   Eng. Eatmad Nahas
                                 Generator Protection
                 Internal                                     External (System)
        Stator                 Rotor
                            (DC System)
                                                          1- loss of Prim-mover
                                                          2- Over excitation
Phase       earth
Fault       Fault       Electrical        Mechanical      3- Unbalance current
                                                          4- Over voltage
                       OC      SC         • Bearing
                                          • Symmetrical
          Generator Protection
1- 87 Differential
2- 50/51 Overcurrent
3- 46 Unbalance/ negative sequence OCR
4- 51V voltage control OCR
5- 32 Power directional relay
6- 27 H under voltage relay
7- 59 G Over voltage relay
8- 81 O/U Over/Under frequency
9- 24 Over excitation
                            87 G - Differential Protection
1- Principle of operation
a- Healthy
             I1                                      I2
             i1
                                   G                      i2
                                    R   IR=i2 - i1
                        Differential Protection
1- Principle of operation
b- Internal fault
          I1                                    I2
                              G                      i2
          i1
                               R   IR=i2 + i1
                            Differential Protection
1- Principle of operation
c- External fault
           I1                                       I2
           i1
                                  G                      i2
                                   R   IR=i2 - i1
                            Differential Protection
2- Characteristics
                                                  ➢ Iomin = (0.1-0.2 ) INCT G-M-B.B- Cable
              ❑ IR> = Iomin Trip             IR
                                                  ➢ Iomin = (0.15-0.4 ) INCT XFMR
              ❑ IR< Iomin   No op.
                                                              Trip
                                         Iomin
                     G                    IPu
                                          ISet
                                                     No operation
                     R                                                              Status
                                                        Sheet (3)
1. Three 21,875 kVA, 13.8 kV generators with Xd =13.9% are connected to individual buses, from which various loads are
supplied. These buses are connected to another bus through 0.25 Ω reactors as shown in Figure 1. The generators are all
ungrounded. In this system:
    (a) Calculate a three-phase fault at the terminals of one of the generators.
    (b) Choose a current transformer ratio for differential relays to protect the generators. If the generator differential relays have a
minimum pickup of 0.14 A, how many times pickup does the three-phase fault provide?
    (c) Calculate a single-phase-to-ground fault at the terminals of one Of the generators.
    (d) Will this ground fault operate the generator differential relays? If so, how many times pickup will the ground fault
provide?
                                   Sheet (3)
      (a) Calculate a three-phase fault at the terminals of one of the generators.
❑PU calculation:
                                                         𝑆𝑏        100 ∗ 1000
    𝑆𝑏 = 100 𝑀𝑉𝐴 ,       𝑉𝑏 = 13.8 𝑘𝑉 ,           𝐼𝑏 =         =                = 4183𝐴
                                                         3𝑉𝑏         3 ∗ 13.8
                                         𝑆𝑏,𝑛𝑒𝑤
                           𝑋𝑔 = 𝑋𝑔,𝑜𝑙𝑑 ∗        = 0.635 𝑝𝑢
                                         𝑆𝑏,𝑜𝑙𝑑
                                            𝑉𝑏2
                Reactor impedance , 𝑍𝑏 =          , 𝑋𝑟𝑒𝑎𝑐𝑡𝑜𝑟 = 0.1313 𝑝𝑢
                                            𝑆𝑏
     Three – Phase fault
       + ve seq. impedance
                 𝑉𝑡ℎ
            𝐼𝑓 =
                 𝑍𝑡ℎ
Vg   X1g             X
Vg   X1g             X       Xsystem
Vg    X1g            X                 Vs
                𝑰𝒇
                        Three – Phase fault
                                  𝑉𝑡ℎ          + ve seq. impedance
                             𝐼𝑓 =
                                  𝑍𝑡ℎ
        𝑅𝑎 𝑅𝑏                                  X1g             X
𝑅1 =
     𝑅𝑎 + 𝑅𝑏 + 𝑅𝑐                              X1g             X             Xsys
                                               X1g                 X
          𝑋𝑒𝑞1 ∗ 𝑋
𝑋1 =
                                                                   𝑰𝒇
       𝑋𝑒𝑞1 + 𝑋 + 𝑋1𝑔                                  Vth
𝑍𝑡ℎ = ((𝑋1 +𝑋𝑠𝑦𝑠 )/ /(𝑋2 )) + 𝑋3 )
                                               Xeq1
                                                                        X1
             𝑍𝑡ℎ = j0.2307 pu             X2                                  Xsys
                                                              X3
                                                 X1g                    X
               𝐼𝑓 = 4.332 𝑝𝑢
                                                                    𝑰𝒇
                                                        Vth
               𝐼𝑓 = 18127 𝐴
                                                   Sheet (3)
 (b) Choose a current transformer ratio for differential relays to protect the generators. If the generator differential
relays have a minimum pickup of 0.14 A, how many times pickup does the three-phase fault provide?
                                           𝑆g        21.875 ∗ 1000
                                 𝐼𝑓.𝑙 =          =                       = 915𝐴
                                           3𝑉g            3 ∗ 13.8
                                                  CTR 1000/5
                                         For secondary side of CT
                                                      5
                                      𝐼𝑓 = 18127 ∗       = 90.635 𝐴
                                                    1000
                                                𝐼𝑓
                                                    = 647.39
                                              𝐼𝑜𝑚𝑖𝑛
                                                  Sheet (3)
(c ) Calculate a single-phase-to-ground fault at the terminals of one Of the generators.
                                    𝑍𝑡ℎ,1 = 𝑍𝑡ℎ,2 = 𝑍𝑡ℎ = j0.2307 pu
                            𝑍𝑡ℎ,0 = 𝑋 + 3𝑍𝑜 = 𝑗0.1313 + 3 ∗ (11 + 𝑗4.73)
                                     Zero seq. impedance
                        isolated
                                     X1g           X
                                                                              isolated
                                     X1g           X                 Xsys
                                      X1g              X
                                             𝑰𝒇                3Zo
                                                      Sheet (3)
(c ) Calculate a single-phase-to-ground fault at the terminals of one Of the generators.
 𝑍𝑡ℎ,1 = 𝑍𝑡ℎ,2 = 𝑍𝑡ℎ = j0.2307 pu,            𝑍𝑡ℎ,0
                                                               1
                                    𝐼𝑓 = 3 𝐼𝑜 = 3 ∗                       = 0.083𝑝𝑢
                                                      2 ∗ j0.2307 + 𝑍𝑡ℎ,0
                                                      𝐼𝑓𝑎𝑐𝑡 = 347 A
 ❑ For secondary side of CT:
                 5                                             𝐼𝑓
 𝐼𝑓 = 347 ∗           = 1.736 𝐴 > 𝐼𝑜𝑚𝑖𝑛 ,                             = 12
               1000                                           𝐼𝑜𝑚𝑖𝑛
                                                        The relay will trip
                                                       Equivalent Circuit
                            𝒁𝒕𝒉,𝟏                            𝒁𝒕𝒉,𝟐                    𝒁𝒕𝒉,𝒐
                    Vg                                  𝑰𝒐
                                              Sheet (3)
2. The unit generator shown in figure 2 has the following capacitance to ground values in microfarads per phase:
        Generator surge capacitors                             0.25
        Generator to transformer leads                         0.004
        Power transformer low voltage windings                0.03
    Station service transformer high voltage windings      0.004
   Voltage transformer windings                            0.0005
The ground resistor R has a 64.14 kW rating at 138 volts.
▪ Determine the fault current magnitude for a single line to ground fault between the generator and the power
   transformer.
▪ Determine the three phase fault current magnitude for a fault between the generator and the power transformer.
▪ Choose a CT ratio for the generator differential protection .
▪ Compare the fault currents of parts a and b with the generator relay pick up value of 0.15 amp.
▪ How much voltage is available to operate an overvoltage relay 59G when connected across the grounding resistor?
▪ What is the multiple of pick up if 59G minimum operating value is 5.4 volt?
▪ How much current flows through the resistor?
▪ Select a CT and suggested over-current pick up values for the 50/51 relay.
Sheet (3)
                                        Sheet (3)
❑PU calculation:
Choose : 𝑆𝑏 = 160 𝑀𝑉𝐴 ,         𝑉𝑏1 = 18 𝑘𝑉 ,              𝑉𝑏2 = 345 𝑘𝑉,
For Generator :    𝑋1𝑔 = 0.21 𝑝𝑢
For MT :          𝑋1𝑡𝑟 = 0.15 𝑝𝑢
                                  𝑆𝑏,𝑛𝑒𝑤       𝑉𝑏,𝑜𝑙𝑑 2              160
For System :      𝑋1,2 = 𝑋𝑜𝑙𝑑 ∗            ∗              = 0.04 ∗         = 0.064 𝑝𝑢
                                  𝑆𝑏,𝑜𝑙𝑑       𝑉𝑏,𝑛𝑒𝑤 2              100
                                160
                  𝑋𝑜 = 0.12 ∗         = 192 𝑝𝑢
                                100
                                      Sheet (3)
❑Equivalent circuit 3-ph fault
 𝑋𝑡ℎ = (𝑋𝑔1 //𝑋𝐶 )// (𝑋𝑡𝑟 + 𝑋𝑠𝑦𝑠 )
                                              X1g        Xtr   Xsys
          𝐶𝑒𝑞 =  𝐶 = 0.2885 μ 𝐹
                1                                   𝑋𝐶
          𝑋𝐶 =     = −𝑗11033 Ω       Eg                               E
               𝑗ω𝐶
For PU:
                   2
                  𝑉𝑏1
           𝑍𝑏 =         = 2.025 Ω
                  𝑆𝑏
            𝑋𝐶 = − j5448 pu
   Note: We can neglect Xc W.r.t Xg
                                               Sheet (3)
                                                       X1g              Xtr       Xsys
 ❑Equivalent circuit 3-ph fault
                                                             𝑋𝐶
                                              Eg                                          E
𝑋𝑡ℎ = (𝑋𝑔1 )// (𝑋𝑡𝑟 + 𝑋𝑠𝑦𝑠 ) = 0.106 𝑝𝑢
                  𝑉𝑡ℎ
             𝐼𝑓 =     = 9.433 𝑝𝑢
                  𝑋𝑡ℎ                                      X1g            Xtr      Xsys
            𝑆𝑏        160 ∗ 1000
     𝐼𝑏 =         =                = 5132 𝐴
            3𝑉𝑏          3 ∗ 18
                                                                  Vth
                  𝐼𝑓 = 48410 𝐴
                      Fault current represent Generator and system contribution
                                     Sheet (3)
❑Equivalent circuit 3-ph fault
                        X1g                      Xtr            Xsys
                              𝑋𝐶
               Eg                                                      E
                                   For Generator contribution
                                      𝑋𝑡𝑟 + 𝑋𝑠𝑦𝑠
                      𝐼𝑓 = 48410 ∗
                                   𝑋𝑡𝑟 + 𝑋𝑠𝑦𝑠 + 𝑋𝑔1
                                              Sheet (3)
                                                            Xgo          Xtro
❑Equivalent circuit L-G fault
         𝑍𝑡ℎ,1 = 𝑍𝑡ℎ,2 = 𝑍𝑡ℎ                                      𝑋𝐶
                                                                                                  Xsyso
                                       3Rg
Zero sequence impedance:
For grounding resistance :
                              𝑉2
                         𝑃=
                               𝑅
                      𝑅 = 0.296 Ω                                      𝑍𝑡ℎ𝑜 = 3𝑅𝑔 + Xgo // -jXc
By referring to primary side of Distribution transformer:
                                 2                                                           ∘
                         18000                                         𝑍𝑡ℎ𝑜 = 2245∠ − 24.33 𝑝𝑢
             𝑅𝑔 = 𝑅 ∗              = 1663Ω
                          240
                  1663
PU value : 𝑅𝑔 =           = 821 𝑝𝑢
                  2.025
                                         Sheet (3)
❑Equivalent circuit L-G fault
                                                         Equivalent Circuit
                                        𝒁𝒕𝒉,𝟏                  𝒁𝒕𝒉,𝟐          𝒁𝒕𝒉,𝒐
    𝑍𝑡ℎ,1 = 𝑍𝑡ℎ,2 = 𝑍𝑡ℎ
                          ∘       Vg                      𝑰𝒐
 𝑍𝑡ℎ𝑜 = 2245∠ − 24.33 𝑝𝑢
                                   𝑉𝑡ℎ          3
                          𝐼𝑓 = 3 ∗     =
                                   𝑍𝑡ℎ 𝑍𝑡ℎ,1 + 𝑍𝑡ℎ,2 + 𝑍𝑡ℎ𝑜
                                                 ∘
                      𝐼𝑓 = 1.336 ∗ 10`3 ∠24.33 pu
                                            ∘
                      𝐼𝑓 = 6.858∠24.33 A
                                               Sheet (3)
• Choose a CT ratio for the generator differential protection .
• Compare the fault currents of parts a and b with the generator relay pick up value of 0.15 amp.
                                          𝑆g
                                 𝐼𝑓.𝑙 =         = 5132 𝐴
                                          3𝑉g
                                       CTR 6000/5
                               For secondary side of CT
                                                  5
                                                                                Correct operation as 87
                          𝐼𝑓−3𝑝ℎ = 48410 ∗
                                                6000
                                                       >> 0.15 A                 G is mainly for phase
                                                                                fault not ground faults
                                                  5
                          𝐼𝑓−𝑆𝑙−𝐺 = 6.858 ∗
                                                6000
                                                       << 0.15 A
                                                   Sheet (3)
 ▪   How much voltage is available to operate an overvoltage relay 59G when connected across the grounding resistor?
 ▪   What is the multiple of pick up if 59G minimum operating value is 5.4 volt?
 ▪   How much current flows through the resistor?
                                                                                 Xgo                 Xtro
     𝐼𝑓−𝑆𝑙−𝐺 = 6.858∠24.33 ∘ = 6.249+j2.82 A
                                                                                                                       Xsyso
                        𝐼𝑓𝑅 = 6.249 𝐴                                    3Rg       𝑋𝐶
                             18000
             𝐼𝑓𝑅   = 6.249 ∗       = 468 𝐴
                              240
                   𝑉𝑅 = 𝐼𝑓𝑅 ∗ 𝑅 = 138.6 𝑉
This is the voltage that seen by 59G (Vomin=5.4 V)
The relay 59G will trip (138.6/5.4=25.5)
                                                     Sheet (3)                   6.24 A
▪   How much current flows through the resistor?
▪   Select a CT and suggested over-current pick up values for the 50/51 relay.
                                                                                             𝐼𝑓𝑅        59 G
                                                                                                    R
                                        18000
                   𝐼𝑓𝑅50/51   = 6.249 ∗       = 468 𝐴
                                         240                                                468.6
                                        18000
                                𝐷𝑇 =            =75                                       50/51 G
                                         240
                        CTR = 75/1………… 375 /5                                             6.24 A
                                   CTR: 400/5
         1.5 < 𝐼𝑝𝑢 < 2 𝐼𝑢𝑛𝑏𝑎𝑙𝑎𝑛𝑐𝑒 20% 𝑢𝑛𝑏𝑎𝑙𝑎𝑛𝑐𝑒
         20% * 5A=1A,                          𝑰𝒑𝒖 =2 A