LOCKOUT RELAY SWITCH
B-MR type
B-MR
LOCKOUT RELAY SWITCH
B-MR type (Solenoid type)
Description
Lockout relay is used to control and protection such as power generation and distribution
equipment.
It's possible to judge the state of the Lockout Relay from the target color.
The operation time realized shorter by adopting a solenoid coil. Quick response protects other
instruments from malfunction.
Features
1. High Speed Operation
Operation time becomes less than 16ms including bounce.
~Operation time~
NC Contact : Less than 8ms, NO Contact : Less than 8ms
2. Compact size
The mechanical portion of solenoid type is smaller than BA-6 Coil type.
3. Wide variation of coil
There are 10 types of coils, each type differs operation time and also preparing BA-6 Coil type
various operation voltage.
A-G : High speed operation type (NC contact operation time will be less than 8ms.)
H-J : Normal operation type (NC contact operation time will be less than 30ms.)
~Remarks~
*Operation time is varied depending on the handle type.
*NC contact operation time will be 30ms.
*Operation time differs from handle type and circuit voltage.
1
B-MR type LOCKOUT RELAY SWITCH
Product coding
B - MR- 2001 - B - LP B
① ② ③ ④ ⑤ ⑥
No. Item Detail Remark
B : B type cam switch (Normal contact)
① Basic type
BH : BH type cam switch (Normal contact)
-
② Operation type MR : Manual reset -
③ Contact arrangement Please contact us separately -
Coil code A B C D E F G
A-G : High speed
Operation voltage ( V) DC24 DC100/110 DC125 DC200/220 AC100/110 AC200/220 DC48
operation type
④ Coil
Coil code H I J H-J : Normal operation
type
Operation voltage ( V) DC125 AC DC100/110 AC DC200/220
• •
Refer to page 6 for the handle shape.
⑤ Handle shape
Operation time varies depending on handle shape. -
Black : B
⑥ Handle color
Blue green : BG
-
Ratings and Specifications
No. Item Rating / Specification
① Operation time Refer to page 3 for the operation time chart.
② Rated insulation voltage (Ui) 600V
③ Conventional free air thermal current (Ith) 20A
④ Contact resistance 50mΩ or less <initial value>
⑤ Insulation resistance 1,000MΩ or more
⑥ Power frequency withstand voltage AC2,500V, 1 min.
⑦ Rated impulse withstand voltage (Uimp) ±6kV, 5 times for each pole (1.2/50μs)
⑧ Conditional short-circuit current 1,000A (cosθ=1)
⑨ Shock 6 directions, 3times for each direction, durabilitiy : 500m/s², malfunction : 100m/s²
Resonance : 10Hz~55Hz, 0.05mm (half-amplitude)
⑩ Vibration 55Hz~150Hz, 0.01mm (half-amplitude)
Durability : 16.7Hz, 1.5mm (half-amplitude)
⑪ Mechanical durability 10,000 operations
⑫ Electrical durability 10,000 operations
⑬ Rated connecting wire 2mm²
⑭ Maximum connecting wire 5.5mm²
⑮ Number of wires simultaneously connectable 2
*No. ⑤ ~ ⑦ : Adapted to "all live parts - grounded metal" and "between the live parts mutual"
2
LOCKOUT RELAY SWITCH
Coil rating
No. Item Detail
① Coil code A B C D E F G H I J
② Operation voltage (V) DC24 DC100/110 DC125 DC200/220 AC100/110 AC200/220 DC48 DC125 AC DC100/110 AC DC200/220
• •
③ Coil resistance (Ω) 3.3 16.5 27 60 16.5 60 13 75 60 240
④ Current on operation (A) 7.3 6/6.6 4.6 3.3/3.6 6/6.6 3.3/3.6 3.7 1.7 1.7/1.8 0.8/0.9
Operation voltage MAX DC28 DC143 DC140 DC286 AC143 AC286 DC56 DC140 AC DC143 AC DC286
• •
⑤
range ( V ) MIN DC20 DC80 DC100 DC160 AC80 AC160 DC40 DC100 AC DC80 AC DC160
• •
⑥ Minimum operation voltage (V) DC20 DC40 DC50 DC80 AC50 AC90 DC40 DC100 AC DC80 AC DC160
• •
Handle
10 8 8 8 14 14 10
①
Make T1
contact Handle
⑦ 12 10 10 10 16 16 12 30
operation time ②
(ms or less)
Handle
T2 16 16 16 16 18 18 16
①②
Break contact
⑧ operation time T3 8 28
(ms or less)
Continuous application limit to
⑨ 10 Impossible of continuous application 10 10
coil (s or less)
〜Remarks〜
*Please refer to the below time chart.
*Operation time differs from handle type and circuit voltage.
Time Chart
At rated voltage
Coil input
Make (a)
contact
T1 Bounce
T2
Break (b)
contact
T3
Handle
LDP LD HDP HD LFP LF
Handle ①
HFP HF LS LE HE
Handle ② LP HP MP HR HSP USP
※ T1:Make contact operation time without bounce T2:Make contact operation time including bounce
T3:Break contact operation time
3
B-MR type LOCKOUT RELAY SWITCH
Circuit and Notch code
Ex.) Diagram (Max.20 contacts/10 units)
(LOCK)
ex. ) (43) (44) A
(41) (42)
B
max. 10 units
(11) (12)
(9) (10)
(7) (8) 45°
1 unit (5) (6)
Coil input (3)
(4) Coil Notch
terminal (1), (3) (1)
(2)
Target color
B A
(LOCK) : A position( Lock)
: B position
It turns A to B automatically after tripping.
Operation method
Coil input(Tripping) makes lockout from A to B position automatically.
By manual rotation from B to A position makes lock at A position.
Ex.) Application example
Order contacts(Specified by user.)
Protective relay contact Contact for coil attached with main body
(Not included in order contacts)
(1)
(5) (7) (9) (11)
(2)
Coil
(4)
(6) (8) (10) (12)
(3)
Reset operation on existence of external signal to coil is prohibited.
Caution This may cause severe malfunction. (Ex. Coil burnout)
4
LOCKOUT RELAY SWITCH
Shape and Size
B-MR type
50 45°
(2)
40
50
58
55
95
55
(5)
7
A 37
L 15 55 50
55
2-φ6
30
φ13
Mounting hole
BH-MR type
50
45°
55
(2)
40
60
58
55
95
55
(5)
A 37
L 50
15 55
30
φ13
2-φ6
Mounting hole
Size (No. of units)
Unit No. 2 3 4 5 6 7 8 9 10
A (mm) 57 70 83 96 109 122 135 148 161
L (mm) 94 107 120 133 146 159 172 185 198
*Coil circuit is not included in unit number.
5
B-MR type LOCKOUT RELAY SWITCH
Handle shape
Handle ① (Small)
Code LDP LD HDP HD LFP LF
Rose shape (large) Rose shape (large) Rose shape (small) Rose shape (small) Octagonal shape (large) Octagonal shape (large)
with one point with one point with one point
Shape
50
50
58
42
42
58
55 55 55
(size) 45 45 55
47 47 40 40 30 30
Code HFP HF LS * LE HE LF
Octagonal shape Octagonal shape (small) Knob shape Egg shape (large) Egg shape (small)
(small) with one point
Shape
15
48
48
48
(size)
60
19 47
32
45 45 55
φ2 25
25 25 6 30
*The shaft for the LS handle is 13mm shorter than the standard shaft.
Therefore, other types of handles cannot be replaced with the LS handle ( knob shape ).
Handle ② (Large)
Code LP HP MP HR HSP USP
Stick shape (large) Stick shape (small) Pistol shape (large) Pistol shape (small) Beak shape (large) Beak shape (small)
18
21
10
13
11
25
12
17
Shape 60 45
(size) 88 57
50
60
57
75
58 39
44
51
φ2 φ2
8 2
15 13
*Handle shapes are divided into handle ① and handle ② because operation time varies depending on handle shape.
Standard
• IEC 60947-5-1 : 2003 (eqv.EN 60947-5-1 : 2004) Low voltage switchgear and controlgear-Part5-1 : Control circuit devices and
switching elements-Electromechanical control circuit devices.
• IEC 60947-1 : 2007 (eqv.EN 60947-1 : 2007) Low voltage switchgear and controlgear-Part1 : General rules.
• JIS C 8201-5-1 (2007) Low voltage switchgear and controlgear-Part5-1 : Control circuit devices and switching elements-
Electromechanical control circuit devices.
• JIS C 8201-1 (2007) Low voltage switchgear and controlgear-Part1 : General rules
• NECA C 4522 (2002) Cam operated control switches.
• NECA C 4520 (2002) General rules for control switches (Quasi-applied standard).
• B402 Digital type protective relay and protective relay device.
6
Ensuring Quality Assurance for Control Devices
www.fujidk.co.jp/english/
Head Office Kusatsu Factory
585, Higashihachiman-cho, Oike-dori Tominokoji Nishi-iru, Nakagyo-ku, 3-4-1, Nomura, Kusatsu, Shiga 525-8521, Japan
Kyoto 604-0954, Japan Phone: +81-77-562-1215 Fax: +81-77-562-1213
Phone: +81-75-221-7978 Fax: +81-75-251-0425
Minami-Kusatsu Factory
Engineering & Sales Department, Sales Team 2-5-5, Noji-higashi, Kusatsu, Shiga 525-0058, Japan
3-4-1, Nomura, Kusatsu, Shiga 525-8521, Japan Phone: +81-77-565-8253 Fax: +81-77-565-8254
Phone: +81-77-562-1215 Fax: +81-77-562-1213
Shin-Asahi Factory
Tokyo Office 905-1, Aza-Nishigawara, Ota, Shin-Asahi-cho, Takashima, Shiga 520-1512, Japan
Shibakoen denki Bldg., 1-1-12, Shibakoen, Minato-ku, Tokyo 105-0011, Japan Phone: +81-740-25-6338 Fax: +81-740-25-6339
Phone: +81-3-5401-3379 Fax: +81-3-5401-3047
PRECAUTIONS FOR USE
• Use products within the correct voltage and current.
• Check connections carefully, as a faulty connection may lead to accidents.
• Check for no abnormal conditions such as wire break, etc. before using the products.
• Fasten screws by the torque complying the standard.
• Use products under no stress condition to wires.
• Avoid the excessive shock and vibration.
• Use under the conditions of no organic solvent or oil.
• Avoid using products in abnormal environments such as high temperature, high humidity, dust or corrosive gases.
• Check carefully specification when used for special purpose.
NP BMR2006-10