BACtalk® Field-Level Gateway
for Modbus
Features and highlights
• Interoperable
BACnet-compliant on MS/TP LAN
at up to 76.8 Kbps.
• Versatile
Supports 100 analog and 100
binary values to integrate Modbus
device data with a BACnet system.
• Reliable
AZ60 processor, with all program
data backed up in nonvolatile flash
memory.
• Economical
Simple, low cost solution for
field-level integration of Modbus
devices.
• Flexible
Offers user-configurable poll
delay, response timeout and
unreliable threshold for increased
compatibility with other Modbus
devices.
The Alerton ® FLG-MODBUS is a field-level gateway that resides on
a BACnet MS/TP network and connects to Modbus over EIA-232 or
EIA-485, translating Modbus data to BACnet AVs and BVs. EIA-232 can
interface to a single Modbus device; EIA-485 can interface to up to 10
Modbus devices (with a valid address between 1–247). The FLG-MODBUS
appears to the BACnet system as a single BACnet device instance.
The FLG-MODBUS offers a point capacity of 100 BACnet AVs and 100
BVs—an ideal point count for most Modbus applications such as chillers
and VFDs. A single FLG-MODBUS supports up to 10 Modbus devices on
a multi-drop Modbus EIA-485 network. A DB-9 connector supports a point-
to-point connection to a Modbus device over Modbus EIA-232.
High baud rates of 4800, 9600, 19200, 38400, 76800 and 115200
baud provide fast transactions. User-configurable poll delay, response
timeout and unreliable threshold enable users to futher customize the
FLG-MODBUS operation. Enhanced diagnostics facilitate
troubleshooting.
The FLG-MODBUS features an AZ60 processor. All configuration data
is backed up in nonvolatile flash memory. An MS/TP header provides for
connection of an Alerton FST-100 with an AC-2680 cable, which is helpful
for troubleshooting and field service.
6670 185th Avenue Northeast, Redmond, WA 98052 USA • Tel: 425.869.8400 • Fax: 425.869.8445 • www.alerton.com
2 of 2 LTBT-FLGMDBS Rev. 0003
© Honeywell International Inc. All rights reserved. Alerton is a registered trademark of Honeywell.
BACtalk® Field-Level Gateway
Technical data
for Modbus
• Power 24 VAC @ 5 VA. Utilizes a half-wave rectifier, which allows a single
transformer to power multiple devices. One leg of 24 VAC connects to earth 3 9/32" (83mm)
(panel) ground. 1 15/32" (37mm)
• Processor and Memory Motorola AZ60 processor with on-board flash 7/32" (5mm)
memory. Flash memory provides nonvolatile program and data storage, 24VAC
GND
and allows for encrypted updates to the program for future product FLG-MODBUS
ASSEMBLED IN USA
POWER STATUS
enhancements. POWER: 24 VAC @ 24VAC - 1
0.5A MAX GND - 2
CLASS 2 CIRCUITS
ONLY
USE COPPER
CONDUCTORS ONLY STATUS
•
FOR INDOOR USE ONLY
LBL-FLG-MB-A
SUITABLE FOR PLENUM MOUNTING
Max. Dimensions 4.75” (120mm)H x 3.25” (83mm)W x 1.13” TUX/MODBUS
STATUS
MODBUS STATUS
SW2 = MS/TP MAC ADDR
EIA-232 / 485
(DB-9)
(28mm)D.
VALUE EIA-232
MODBUS
SW2 ON CONFIG.
1 1
2 2 JUMPER
3 4 1 2 3
8
4 23/32" (120mm)
4
5
6
16
32
4 5/16" (109mm)
•
7 64 EIA-232
EIA-485 DB
Terminations Removable header-type screw terminals for BACnet MS/TP MS/TP
MS/TP STATUS
SW3 MODBUS SETTINGS
SWITCH NUMBER
and Modbus EIA-485 accept 14–24 AWG wire. Male DB-9 connector for
OFF ON
STATUS 1 RTU ASCII
2 NO PARITY PARITY
SW3 3 ODD PARITY EVEN PARITY
4 9600 BAUD 4800 BAUD
Modbus EIA-232.
5 STANDARD 1 STOP BIT
6 (NOT USED)
+
7 (NOT USED) MODBUS
-
(B) + - 3
EIA-485
(W) - - 4
•
OPEN ENERGY
+
MANAGEMENT
Environmental 0–158 deg. F (-17–70 deg. C). 0–95% RH, non-
EQUIPMENT 5K05
OPTION (B) + - 5
MS/TP MS/TP
(W) - - 6
+ -
MS/TP
condensing.
-
• Modbus Communications Either EIA-232 (serial cable) to single
1/2" (12mm)
Modbus device or multi-drop EIA-485 (twisted pair) to up to 10 Modbus
devices. Network options configurable for ASCII/RTU, 4800, 9600, 19200,
38400, 76800 and 115200 baud, even/odd/no parity, and stop bit options for
compatibility with various Modbus implementations.
• BACnet Communications BACnet MS/TP LAN with auto-detection of
MS/TP communications rate up to 76.8 Kbps.
• Software Support for 100 BACnet AVs and 100 BACnet BVs, each
mapped to a Modbus data point through a string written to the description
property of the AV or BV object.
• Ratings
Listed Underwriters Laboratory for Open Energy Management Equipment
(PAZX) under the UL Standard for Safety 916; listing includes U.S. and
Canadian certification
Suitable for plenum mounting
EMC Directive 89/336/EEC (European CE Mark)
FCC Part 15, Subpart J, Class A
Ordering information
Item number Description
FLG-MODBUS BACtalk field level gateway for
Modbus
Specifications subject to change without notice
6670 185th Avenue Northeast, Redmond, WA 98052 USA • Tel: 425.869.8400 • Fax: 425.869.8445 • www.alerton.com
2 of 2 LTBT-FLGMDBS Rev. 0003